c Materials & Systems >> Electrical >> Recommended Lighting Levels in Buildings

Related Archtoolbox Articles

Properties of Light
Recommended Lighting Levels in Buildings Cold Formed Metal Framing

Architectural Acoustics - Acceptable Ro


Lighting in our living and workplaces is critically important for our ability to accomplish tasks efficiently and safely. In
Levels
addition, proper light levels prevent eye strain, which allows us to work comfortably for longer periods of time. This
article covers proper lighting levels and will include various lighting concepts during the conversation. If you need to Electrical Plan Symbols - Lighting
brush up on the basics of lighting, check out our Properties of Light article.
Light Fixture (Luminaire) Types

There are two main concepts that architects need to understand as they plan lighting in their buildings: Light Levels and
Light Fixture (Luminaire) Components
Lighting Power Density.
Gypsum Board (Drywall) Level of Finish

Light Levels in Buildings Commercial Lighting Control Systems

Since we are concerned mainly with accomplishing tasks in our buildings, we need to understand the Illuminance, or the Light Distribution Curves
amount of light that is hitting a surface. In an office, we might want to understand the amount of light that is hitting our
desk; however, in a gymnasium or corridor we may be more interested in the amount of light hitting the floor.

Illuminance is measured in foot candles (FC) or lux. 1 FC is the amount of light that hits a 1 square foot surface when 1 Newest Articles
lumen is shined from 1 foot away – this equates to 1 lumen per square foot. 1 lux is the amount of light that hits a 1
square meter surface when 1 lumen is shined from 1 meter away – this equates to 1 lumen per square meter. 10 lux is Health Product Declarations (HPDs): A
roughly 1 FC. Architects

Types of Frosted Glass

Tile Grout Types

Standard Pipe Dimensions

FF and FL Numbers - Floor Flatness and

We need to provide enough light to allow people to accomplish see their tasks, but not so much light that it is hard to
see the tasks – over lighting is just as bad as under lighting. Detailed tasks like drafting require more light, while general
tasks like walking can be accomplished with less light.

The most cited reference for lighting levels is the IESNA Lighting Handbook, which is published by the Illuminating
Engineering Society. The lighting levels listed below come from the Handbook as well as various other lighting
references.

Ad

Download and Play for Free

DOWNLOAD
Lighting Power Density (LPD)
Lighting power density is the amount of power used by lighting per unit of building area. In the United States, LPD is
measured in watts per square foot. Included in the watt measurement is all power consumed by light fixtures, ballasts,
controls, transformers, etc. – essentially, if the component or device is involved in lighting, it must be included in the
calculation.

Lighting power density is established by local and international codes. The values listed below for LPD come from the
2015 version of the International Energy Conservation Code (IECC 2015). Please keep in mind that certain cities or
states may have codes that require LPDs to be a certain percentage BELOW the IECC. Always make sure to check your
local codes before establishing LPD criteria for your project.

There are two ways to calculate the lighting power density. The first way is to use an LPD that applies to the full building
based on the type of building (school, museum, office, etc.) -- this method is very basic and is called the Building Area
Method. The second way is to calculate the LPD based on each specific room and is called the Space-by-Space method --
this method is much more accurate and may result in a lower LPD number, which is helpful when applying for utility
incentives.

Many utility incentive programs require the design team to improve upon the lighting power density baseline required by
local codes. For instance, a utility incentive program may require a 15% (or more) improvement over the baseline LPD in
order to receive a lower electricity rate.

Recommended Light Levels by Space


The table below provides recommended light levels from the IESNA Lighting Handbook and LPD levels from the IECC
2015. Check your local jurisdiction for other or more stringent requirements. The US General Services Administration
provides lighting levels and LPDs for US Government buildings, which can be used as a guide for other types of
buildings.

The required light levels are indicated in a range because different tasks, even in the same space, require different
amounts of light. In general, low contrast and detailed tasks require more light while high contrast and less detailed
tasks require less light.

Please keep in mind that this chart is not comprehensive. The IESNA Lighting Handbook has pages and pages of various
categories. If you have a very specific need, we recommend further research.

LIGHT
LIGHT LEVEL IECC 2015 LIGHTING POWER
ROOM TYPE LEVEL
(FOOT CANDLES) DENSITY (WATTS PER SF)
(LUX)

Bedroom -
20-30 FC 200-300 lux 0.38
Dormitory

Cafeteria - Eating 20-30 FC 200-300 lux 0.65

Classroom -
30-50 FC 300-500 lux 1.24
General

Conference Room 30-50 FC 300-500 lux 1.23

Corridor 5-10 FC 50-100 lux 0.66

Exhibit Space 30-50 FC 300-500 lux 1.45

Gymnasium -
20-30 FC 200-300 lux 0.72
Exercise / Workout

Gymnasium -
30-50 FC 300-500 lux 1.20
Sports / Games

Kitchen / Food Prep 30-75 FC 300-750 lux 1.21

Laboratory
50-75 FC 500-750 lux 1.43
(Classroom)

Laboratory
75-120 FC 750-1200 lux 1.81
(Professional)

Library - Stacks 20-50 FC 200-500 lux 1.71

Library - Reading /
30-50 FC 300-500 lux 1.06
Studying

Loading Dock 10-30 FC 100-300 lux 0.47

Lobby -
20-30 FC 200-300 lux 0.90
Office/General
LIGHT
LIGHT LEVEL IECC 2015 LIGHTING POWER
ROOM TYPE LEVEL
(FOOT CANDLES) DENSITY (WATTS PER SF)
(LUX)

Locker Room 10-30 FC 100-300 lux 0.75

Lounge /
10-30 FC 100-300 lux 0.73
Breakroom

Mechanical /
20-50 FC 200-500 lux 0.95
Electrical Room

Office - Open 30-50 FC 300-500 lux 0.98

Office - Private /
30-50 FC 300-500 lux 1.11
Closed

Parking - Interior 5-10 FC 50-100 lux 0.19

Restroom / Toilet 10-30 FC 100-300 lux 0.98

Retail Sales 20-50 FC 200-500 lux 1.59

Stairway 5-10 FC 50-100 lux 0.69

Storage Room -
5-20 FC 50-200 lux 0.63
General

Workshop 30-75 FC 300-750 lux 1.59

Ad

Sogni di Cristallo Murano's


Chandeliers. WorldWide
Shipping, Free Return.

VISIT SITE

H Help make Archtoolbox better for everyone. If you found an error or out of date information in this article (even if it
is just a minor typo), please let us know.

Subscribe to the Archtoolbox Newsletter


Receive two emails each month with industry news focusing on practice, leadership, technology, and career growth. We also include care
growth and project management tips along with the occasional helpful surprise.

Email Address First Name Last Name


Signup Now

Helpful Tools for Architects and Building Designers


Bluebeam Tools and Templates
Tool sets, hatches, line types, stamps, and templates for Bluebeam Revu.

Best Architecture Books


Our list of the top reference books for architects - these are the ones we have on our shelf.

How to Set Up Your Website Portfolio


A free guide to hosting your own website potfolio.

Archtoolbox Guide to Fee Development


A guide and toolbox of excel templates to help you develop a fee for architectural services.

About Archtoolbox Our Other Sites This website uses cookies. Display and/or use of the information containe
site constitutes acceptance of the Terms of Service and Privacy Policy.
About Archtoolbox Archlinks: Architecture News

Contact Gifts for Architects It is important that all local codes and standards are adhered to. Please c
professional architect, engineer, consultant, or agency for advice about s
Write for Archtoolbox buildings, conditions, codes, and/or regulations.
Terms and Privacy Info
Archtoolbox makes a small commission when you purchase items from co
Site Map whom we have an affiliate relationship (Amazon, GBES) after having follo
affiliate links. These commissions allow us to continue providing free info
readers.
report this ad

Copyright © Aggregate Digital LLC

Das könnte Ihnen auch gefallen