TEMPERATURE CONTROLLER OMROM E5GN

CONFIGURATION MENU (The configuration of the regulator access should Be enabled, pág. 3. Then to leave disabled.)
ACTION KEY DISPLAY
Temperature watchword
Accede to the configuration menu in-t
More than 3 seconds
Input type 2 in-t 7
(Thermocouple type “J”, -100,850ºC)
Press this key, go to the next screen d-U
Select centigrade degrees, C d-U c
Press this key, go the next screen SL-H
Scaling upper limit, 200ºC (Whit SL-H 200 (300)
Eurolock put 300º C)
Press this key, go the next screen SL-L
Scaling lower limit, 0ºC SL-L 0
Press this key, go the next screen CntL
Select the type control, CntL Pid
PID
Press this key, go the next screen S-HC
Select the type control, S-HC Stnd
Standard
Self-tuning select St
Self-tuning OFF select St oFF
Self-tuning select Ptrn
Program shape selection Ptrn off
Self-tuning select CP
Select period of control of two seconds CP 2
Press this key, go the next screen orEu
Select indirect operation orEu or-r
Press this key, go the next screen Alt1
Alarm type 1 select Alt1 1
Press this key, go the next screen Alh1
Alarm hysteresis Alh1 0.2
Press this key, go the next screen Anou
FPI02012 2 de 5
Ver.:00

Pass to Advanced Functions Anou 0


Press this key, go the next screen in-t
Exit to the configuration menu Temperature watchword
More than three seconds

SELF-TUNING

ACTION KEY DISPLAY


Temperature watchword
Self-tuning Menu select At oFF
for less than one second
Self-tuning select At* on
Wait to self-tuning concludes At oFF
Exit to self-tuning Menu Temperature watchword
for less than one second

* This symbol means that the message blinks


FPI02012 3 de 5
Ver.:00

Menu of protection (to Limit the access to the user to certain screens)

ACTINO KEY DISPLAY


Temperature watchword
Protections Menu select oAPt
+ for less than one
second
Protection mode “0” select oAPt 0 a)
Go to the next screen iCPt
Protection mode “2” select iCPt 2 b)
Go to the next screen WtPt
Protection “OFF” select WtPt oFF
Go to the next screen oAPt
Exit from the protection menu Temperature watchword
+ for less than one
second

a) With a value of 3 – The change is disabled in the watchword of temperature.


b) With a value of 1 – The access is allowed to the configuration of the regulator.
With a value of 0 – The configuration of advanced functions is allowed.
With 2 value – The access is disabled to the configuration of the regulator, with this value
it is with the one that has to be.
FPI02012 4 de 5
Ver.:00

Machine with the alarm contacts connected in series


In the pretections Menu: Put in “0” the Portection Menu to be able to enter in the Advanced
functions
Enter in the Menu of Configuration and in the last parameter that appears us (Anou) enter this
number (-169) and wait some seconds, past this time will be in the Advanced Functions.

Advance functions ( Modify alone investing the contact of Alarm)

ACTINO KEY DISPLAY


Enter to the advance functions Anou -169
Wait init
Initialize parameters init oFF
Go to the next screen mSPU
Multiple watchword points mSPU oFF
Go to the next screen SPru
Selected value of ramp to “SP” SPru M(ñ)
Go to the next screen Sb1n
Select “On/OFF” for the exit of Sb1n n-O
the alarm 1
Go to the next screen AL H 1
Alarm 1 Hysteresis AL H 1 0.2
...
...
Go to the next screens colr
13 times
Seleccionar color rojo colr
red
Go to the next screens csel
10 times
7 units visualization csel
off
Exit form the Advance functions in-t
More than 3 seconds
Exit form the configuration Temperature watchword
More than 3 seconds

In the Protection Menu put the value “2” in the Protection mode to prohibit the access to the
Configuration of Functions.
FPI02012 5 de 5
Ver.:00

Assignment of the range of correct temperature (Alarms)

ACTINO KEY DISPLAY


Temperature watchword
Go to the next screen r-S
Activate the running r-S rUn
Go to the next screen AL 1H
Upper range for the Alarm 1 AL 1H 6
Go to the next screen AL 1L
Lower range for the Alarm 1 AL 1L 6
Go to the next screen Temperature watchword