FirePro
FPC-5 Thermal Actuation Module.
User Guide on interfacing the Bimetallic
sensor (or LHD cable) with the condensed
aerosol fire extinguishing units.
Issue February 2015
Version 1.00
Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015
This document has been prepared by the FirePro® Technical Department.
FirePro®
Condensed Aerosol Fire Extinguishing Systems
Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015
INDEX
1. Overview .............................................................................................. 4
2. Interfacing Bimetallic sensor with condensed aerosol fire extinguishing units
FP-20SE, FP-40S, FP-80S. ......................................................................... 3
Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015 Page 1
1. Overview
This User Guide provides information on interfacing the FPC-5 module with the
bimetallic sensor (or LHD cable) with the condensed aerosol fire extinguishing units.
The rated temperatures for Bimetallic sensor and LHD cable are listed below:
Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015 Page 2
Interfacing the Bimetallic
sensor with the condensed
aerosol fire extinguishing
units
FP-20SE, FP-40S,FP-80S
Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015 Page 3
4 3 2 1
Step by step procedure connecting the bimetallic sensor to the condensed aerosol fire extinguishing unit.
D D
BAP1
Electrical BAP2
housing
C C
B B
Step 1 Step 2 Step 3 Step 4 Step 5
Applicable to Unscrew the cap of Pass the wires of the Pass through BAP1 the Screw the BAP1 on to
models: the electrical housing. condensed aerosol unit wires of the condensed the BAP2.
FP-20SE through BAP2. aerosol unit.
FP-40S Screw the BAP2 on the
FP-80S condensed aerosol
unit.
A A
4 3 2 1
4 3 2 1
Step by step procedure connecting the bimetallic sensor to the condensed aerosol fire extinguishing unit.
BAP5a
D D
BAP1
C C
B B
Take the 2 wires of Take the CR2 battery Carefully twist the wires Pass the wires of the Screw and secure the
the condensed and insert it into the of the condensed bimetallic sensor bimetallic sensor on
aerosol unit and battery holder of the aerosol unit and push through BAP5a. BAP5a.
connect them to the electronic board. the electronic board
terminal on the inside PAB1. Connect the wires of Push BAP5a on the
underside of the the bimetallic sensor to BAP1 and by turning
electronic board. the terminal at the top it by a 1/4 turn, close
of the electronic board. and secure the
device.
A A
4 3 2 1
4 3 2 1
Connecting the LHD cable to the condensed aerosol fire extinguishing unit.
Linear Heat
Detector Cable
D D
Gland
BAP5b
BAP5b
BAP1
C C
B B
4 3 2 1
4 3 2 1
Bimetallic & LHD sensors components.
Screws
Gland
BAP5a
BAP5b
Electronic board
C C
BAP2
BAP2
BAP5b
BAP5b
B B
Electrical
Interface Electrical
Interface
A A
4 3 2 1
4 3 2 1
Optional: Terminating the LHD cable.
C C
B B
A A
4 3 2 1
Interfacing the Bimetallic
sensor with the condensed
aerosol fire extinguishing
units
FP-100S, FP-200S,
FP-500S
Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015 Page 9
4 3 2 1
Bimetallic & LHD sensors components.
Screws
Gland
BAP5b BAP5a
C C
BAP2
BAP2
BAP4
BAP4
B B
Electrical
housing Electrical
housing
A A
4 3 2 1
Interfacing the Bimetallic
sensor with the condensed
aerosol fire extinguishing
units
FP-1200/S, FP-2000/S,
FP-3000/S, FP-5700/S
Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015 Page 11
4 3 2 1
Bimetallic & LHD sensors components.
D D
Gland
BAP5b
Linear Heat
Detector Cable
C C
4 3 2 1
Notes:
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015 Page 13
FirePro®
Condensed Aerosol Fire Extinguishing Systems
Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015