Sie sind auf Seite 1von 16

®

FirePro
FPC-5 Thermal Actuation Module.
User Guide on interfacing the Bimetallic
sensor (or LHD cable) with the condensed
aerosol fire extinguishing units.
Issue February 2015
Version 1.00

Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015
This document has been prepared by the FirePro® Technical Department.

FirePro®
Condensed Aerosol Fire Extinguishing Systems

Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015
INDEX
1. Overview .............................................................................................. 4
2. Interfacing Bimetallic sensor with condensed aerosol fire extinguishing units
FP-20SE, FP-40S, FP-80S. ......................................................................... 3

3. Interfacing Bimetallic sensor with condensed aerosol fire extinguishing units


FP-100S, FP-200S, FP-500S. ...................................................................... 9

4. Interfacing Bimetallic sensor with condensed aerosol fire extinguishing units


FP-1200/S, FP-2000/S, FP-3000/S, FP-5700/S. ........................................ 11

Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015 Page 1
1. Overview
This User Guide provides information on interfacing the FPC-5 module with the
bimetallic sensor (or LHD cable) with the condensed aerosol fire extinguishing units.

The rated temperatures for Bimetallic sensor and LHD cable are listed below:

Bimetallic Rated Temperatures 60°C, 70°C, 80°,100°C


LHD Rated Temperatures 68°C, 88°C, 105°C

Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015 Page 2
Interfacing the Bimetallic
sensor with the condensed
aerosol fire extinguishing
units
FP-20SE, FP-40S,FP-80S

Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015 Page 3
4 3 2 1
Step by step procedure connecting the bimetallic sensor to the condensed aerosol fire extinguishing unit.

D D

BAP1

Electrical BAP2
housing

C C

B B
Step 1 Step 2 Step 3 Step 4 Step 5

Applicable to Unscrew the cap of Pass the wires of the Pass through BAP1 the Screw the BAP1 on to
models: the electrical housing. condensed aerosol unit wires of the condensed the BAP2.
FP-20SE through BAP2. aerosol unit.
FP-40S Screw the BAP2 on the
FP-80S condensed aerosol
unit.

A A

4 3 2 1
4 3 2 1
Step by step procedure connecting the bimetallic sensor to the condensed aerosol fire extinguishing unit.

CR2 lithium Screws


Electronic
battery board Bimetallic
Sensor

BAP5a
D D

BAP1

C C

B B

Step 6 Step 7 Step 8 Step 9 Step 10

Take the 2 wires of Take the CR2 battery Carefully twist the wires Pass the wires of the Screw and secure the
the condensed and insert it into the of the condensed bimetallic sensor bimetallic sensor on
aerosol unit and battery holder of the aerosol unit and push through BAP5a. BAP5a.
connect them to the electronic board. the electronic board
terminal on the inside PAB1. Connect the wires of Push BAP5a on the
underside of the the bimetallic sensor to BAP1 and by turning
electronic board. the terminal at the top it by a 1/4 turn, close
of the electronic board. and secure the
device.

A A

4 3 2 1
4 3 2 1
Connecting the LHD cable to the condensed aerosol fire extinguishing unit.

Linear Heat
Detector Cable

D D

Gland

BAP5b

BAP5b

BAP1
C C

B B

Step 7 Step 8 Step 9 Step 10


If the Linear Heat detector cable Connect the Gland over BAP5b.
Take the Linear Heat detector Push BAP5b onto BAP1 and
is used, then follow the same
cable and pass it through the by turning it by a 1/4 turn,
procedure from step 1 to step 8.
A gland and BAP5b. close and secure the device. A

Connect the wires of the Linear


Heat detector cable to the
terminal at the top of the
electronic board.

4 3 2 1
4 3 2 1
Bimetallic & LHD sensors components.

Screws

Linear Heat Bimetallic


Detector Cable Sensor
D D

Gland

BAP5a
BAP5b
Electronic board

Electronic board CR2 lithium battery

CR2 lithium battery

C C

BAP2

BAP2

BAP5b
BAP5b

B B
Electrical
Interface Electrical
Interface

Condensed Aerosol Fire Condensed Aerosol Fire


Extinguishing Unit Extinguishing Unit

A A

4 3 2 1
4 3 2 1
Optional: Terminating the LHD cable.

MK1282 Connector Box


D D

C C

B B

A A

4 3 2 1
Interfacing the Bimetallic
sensor with the condensed
aerosol fire extinguishing
units
FP-100S, FP-200S,
FP-500S

Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015 Page 9
4 3 2 1
Bimetallic & LHD sensors components.

Screws

Linear Heat Bimetallic


Detector Cable Sensor
D D

Gland

BAP5b BAP5a

Electronic board Electronic board

CR2 lithium battery


CR2 lithium battery

C C

BAP2
BAP2

BAP4
BAP4

B B
Electrical
housing Electrical
housing

Condensed Aerosol Fire


Condensed Aerosol Fire Extinguishing Unit
Extinguishing Unit

A A

4 3 2 1
Interfacing the Bimetallic
sensor with the condensed
aerosol fire extinguishing
units
FP-1200/S, FP-2000/S,
FP-3000/S, FP-5700/S

Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015 Page 11
4 3 2 1
Bimetallic & LHD sensors components.

D D

Gland

BAP5b

Linear Heat
Detector Cable

C C

B CR2 lithium battery B


Screws
Bimetallic Electronic board
Sensor
BAP2
BAP5a BAP3 Electrical
housing

Condensed Aerosol Fire


Extinguishing Unit
A A

4 3 2 1
Notes:

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015 Page 13
FirePro®
Condensed Aerosol Fire Extinguishing Systems

FirePro Systems Limited


P O Box 54080
CY-3720 Limassol, CYPRUS
Tel: +357 25 379 999
Fax: +357 25 354 432
Web: www.firepro.info
Email: mail@firepro.info

Michaelides Loucas, FPC5 module, User Guide on interfacing the Bimetallic sensor (or LHD cable) with the condensed aerosol fire ext. units, Issue February 2015

Das könnte Ihnen auch gefallen