Nomenclature
CS B - 0300 - L Q M
Large Air-Cooled Condensing Units Available in Standard, Oversize, and Title 24 Model Configurations
Models
n CS Series Units are new, more efficiently sized units that have a reduced footprint,
more standard features and provide increased options for sizing large jobs.
n CP Series Parallel Units are two compressors piped together to provide one refrigeration circuit.
n CD Series Dual Units are two compressors piped independently for a separate circuit operation.
10°F SaturatedTemperature
Ambient Suction
15°F Temperature 20°F
(SST) 95°F 25°F
-5°F105°F* 95°F 0°F
30°F
105°F 95°F 5°F
35°F
105°F 95°F 10°F40°F
105°F 95°F 15°F105°F45°F 95°F 20°F 105°F 95°F 25°F105°F 95°F 30°F105°F
5°F 95°F 105°FElectrical
AmbientUnit
Unit
Specifications
Temperature
95°F 105°F Compressor Cond R-448A
95°F
Compressor
105°F
Cond
95°F 105°F*
105°F
Capacity (MBH)
Capacity
Capacity (MBH)
(MBH)
95°F
95°F 105°F
105°F 95°F
95°F 105°F
105°F 95°F
95°F 105°F 105°F 95°F 95°F
105°F 105°F
95°F 105°F 95°F (MBH)
Capacity
Capacity
105°F 95°F 105°F
CSD-0100-MT S 58.2 55.3 65.0 61.8 72.3 68.8 80.2 76.3 90.2 85.8 101.1 95.2 111.8 (MBH)
105.4 124.5 118.4
.8 80.2 CSD-0100-MT
76.3 CSD-0101-MT
90.2 Voltage
85.83DB3R12ME
101.1 S
95.2 111.8
58.2 208-230/3/60
105.4
55.3 (TFC)
65.0
124.5 61.8
118.4 72.3
136.7 460/3/60
68.8 (TFD)
130.1 82.3
80.2
149.8 78.4
76.3142.5 92.8 575/3/60
90.2 N/A88.4
85.8 (TFE)
N/A
101.1 95.2 111.8 105.4 124.5 118.4
O 59.7 56.9 66.7 63.5 74.2 70.7 104.2 98.4 115.4 109.1 128.8 123.0
.7 82.3 78.4 CSD-0102-MT
CSD-0101-MT
92.8 88.43DB3R12ME
104.2 98.4
O Comp
115.4
59.7 Cond
109.1
56.9 66.7
128.8 MOPD 123.0 Comp
63.5 74.2
141.9 Cond
70.7
135.6 MCA82.3 78.4149.1Comp
156.0 MOPD 92.8 N/ACond
88.4 N/A
104.2 98.4 115.4 109.1 128.8 123.0
Unit Compressor Cond
T 59.3 56.4 MCA
66.3 63.0 73.8 70.2 81.8 77.8 92.1 87.5 MCA
103.1 MOPD
97.1 114.0 107.5 126.9 120.8
.2 81.8 77.8 CSD-0150-MT
CSD-0102-MT
92.1 87.5 103.1 97.1
T RLA
114.0
59.3 FLA
107.5
56.4 66.3
126.9 63.0
120.8 RLA
73.8
139.4 FLA
70.2
132.7 107.8
81.8
152.8 100.0 RLA
77.8145.4121.7 FLA
92.1 N/A112.4
87.5 N/A
103.1 97.1 114.0 107.5 126.9 120.8
CSD-0100-MT S
S 74.9 67.5
5.4 84.6
62.9 77.8
100 96.2 88.4
2.5 29.0 45 2.5 135.3
24.3 125.0
40 148.7 138.2 164.3 147.9
.4 107.8 100.0 CSD-0151-MT
CSD-0150-MT
121.7 112.43DS3R17ME
135.3 125.0
S
O 148.7
74.9
76.0 138.2
67.5
68.6 84.6
164.3
86.9 77.8
147.9
79.3 96.2
179.4
98.0 88.4
161.5 110.2
90.2 107.8
187.0 102.2
100.0171.5124.5
121.7 N/A114.2
112.4 N/A
135.3
139.1 125.0
128.5 148.7
153.2 138.2
141.3 164.3
168.2 147.9
156.5
CSD-0101-MT 3DB3R12ME O 43.6 10.8 68.3 110 20 5.0 31.5 50 16.5 5.0 26.8 40
.2 110.2 102.2 CSD-0152-MT
CSD-0151-MT
124.5 114.23DS3R17ME
139.1 128.5
O
T 153.2
76.0
77.6 141.3
68.6
70.0 86.9
168.2
88.7 79.3
156.5
80.9 98.0
186.1
100.0 90.2
169.4
92.0 110.2
198.0
112.4 102.2
104.2 182.0124.5
127.0 N/A114.2
116.5 N/A
139.1
141.8 128.5
131.1 153.2
156.2 141.3
144.2 168.2
171.6 156.5
159.6
CSD-0102-MT T 5.4 62.9 100 2.5 29.0 45 2.5 24.3 40
.0 112.4 104.2 CSD-0200-MT
CSD-0152-MT
127.0 116.5 141.8 131.1
T
S 156.2
77.6
89.6 144.2
70.0
80.0 88.7
171.6
103.0 80.9
159.6 115.8
92.1 100.0
189.8 104.6
92.0
172.8 130.7
112.4
202.0 118.2
104.2185.6146.8
127.0 N/A132.8
116.5 N/A
141.8
162.5 131.1
147.2 156.2
180.6 144.2
162.2 171.6
201.6 159.6
181.5
CSD-0150-MT S 10.8 88.4 150 5.0 42.8 70 5.0 35.7 60
4.6 130.7 118.2 CSD-0201-MT
CSD-0200-MT
146.8 132.8 162.5
4DBNR20ME 147.2
S
O 180.6
89.6
91.6 162.2
80.0
81.9 103.0
201.6
104.7 92.1
181.5
94.5 115.8
220.7
118.9 104.6
200.6
107.6 130.7
235.6
133.2 118.2
120.7 216.3146.8
150.1 N/A132.8
136.0 N/A
162.5
168.2 147.2
151.2 180.6
185.7 162.2
168.6 201.6
207.9 181.5
187.1
CSD-0151-MT 3DS3R17ME O 59.6 10.8 88.4 150 29.0 5.0 42.8 70 23.6 5.0 35.7 60
7.6 133.2 120.7 CSD-0202-MT
CSD-0201-MT
150.1 136.04DBNR20ME
168.2 151.2
O
T 185.7
91.6
93.5 168.6
81.9
83.5 104.7
207.9
106.7 94.5
187.1 121.3
96.4 118.9
229.5 109.7
107.6
208.7 135.9
133.2
245.0 123.1
120.7225.0153.1
150.1 N/A138.7
136.0 N/A
168.2
171.6 151.2
154.2 185.7
189.4 168.6
171.9 207.9
212.1 187.1
190.9
CSD-0152-MT T 10.8 88.4 150 5.0 42.8 70 5.0 35.7 60
9.7 135.9 123.1 CSD-0250-MT
CSD-0202-MT
153.1 138.7 171.6 154.2
T
S 189.4
93.5
104.4 171.9
83.5
95.4 106.7
212.1 108.3
117.6 96.4
190.9 132.7
121.3
234.1 122.0
109.7
212.8 149.3
135.9
249.9 137.3
123.1229.5167.5
153.1 N/A152.3
138.7 N/A
171.6
185.0 154.2
169.9 189.4
205.1 171.9
186.7 212.1
226.1 190.9
203.5
CSD-0200-MT S 10.8 104.0 175 5.0 51.6 80 5.0 45.5 70
2.0 149.3 137.3 CSD-0251-MT
CSD-0250-MT
167.5 152.3 185.0
4DHNR22ME 169.9
S
O 104.4
205.1
107.3 186.7
95.4
98.2 117.6
226.1 110.9
121.4 108.3
203.5 137.5
132.7
247.6 126.6
122.0
222.9 153.9
149.3
265.0 141.6
137.3243.0171.6
167.5 N/A157.8
152.3 N/A
185.0
192.1 169.9
175.1 205.1
214.0 186.7
195.0 226.1
236.8 203.5
217.8
CSD-0201-MT 4DBNR20ME O 72.1 10.8 104.0 175 36.1 5.0 51.6 80 31.4 5.0 45.5 70
6.6 153.9 141.6 CSD-0252-MT
CSD-0251-MT
171.6 157.84DHNR22ME
192.1 175.1
O
T 107.3
214.0
106.5 195.0
98.2
97.3 121.4
236.8 110.4
120.0 110.9
217.8 135.3
137.5
263.0 124.5
126.6
239.7 152.3
153.9
282.0 140.0
141.6260.0170.8
171.6 N/A155.4
157.8 N/A
192.1
188.7 175.1
173.3 214.0
209.2 195.0
190.4 236.8
230.6 217.8
207.6
CSD-0202-MT T 10.8 104.0 175 5.0 51.6 80 5.0 45.5 70
4.5 152.3 140.0 CSD-0300-MT
CSD-0252-MT
170.8 155.4 188.7 173.3
T
S 106.5
209.2
120.8 190.4
97.3
110.5 120.0
230.6 126.5
138.6 110.4
207.6 156.7
135.3
252.6 144.0
124.5
227.3 177.8
152.3
270.3 161.7
140.0247.9199.1
170.8 N/A180.7
155.4 N/A
188.7
219.7 173.3
199.2 209.2
241.3 190.4
218.6 230.6
264.0 207.6
237.6
CSD-0250-MT S 10.8 116.4 200 5.0 57.8 100 5.0 49.1 80
4.0 177.8 161.7 CSD-0301-MT
CSD-0300-MT
199.1
CSD-0251-MT 180.7 219.7
4DJNR28ME
4DHNR22ME 199.2
S
O
O 120.8
241.3
122.2
82.1 110.5
218.6
112.0
16.2 138.6
264.0
142.1
121.8 126.5
237.6
129.8
200 156.7
290.2
161.1
41.1 144.0
261.2
148.3
7.5 177.8
305.0
181.8
60.3 161.7
165.6
100 278.0199.1
204.2
34.4 N/A180.7
185.7
7.5 N/A
219.7
226.1
51.6 199.2
207.4
80 241.3
249.3 218.6
230.8 264.0
276.5 237.6
250.9
8.3 181.8 165.6 CSD-0302-MT
CSD-0301-MT
204.2
CSD-0252-MT 185.74DJNR28ME
226.1 207.4
O
T
T 122.2
249.3
122.0 112.0
230.8
111.6
10.8 142.1
276.5 127.7
140.0
116.4 129.8
250.9 158.2
200 161.1
302.4 145.5
148.3
274.4
5.0 181.8
321.0 163.3
179.6
57.8 165.6
100 295.0201.1
204.2 N/A182.5
185.7
5.0 N/A
226.1
221.9
49.1 207.4
201.2
80 249.3
243.7 230.8
220.8 276.5
266.6 250.9
239.9
5.5 179.6 163.3 CSD-0350-MT
CSD-0302-MT
201.1
CSD-0300-MT 182.5 221.9 201.2
T
S 122.0
243.7
148.1 220.8
111.6
136.9
10.8 140.0
266.6
169.1
145.6 127.7
239.9
154.9
250 158.2
293.1
190.2 145.5
263.8
176.0
5.0 179.6
308.1
212.9
72.4 163.3
197.0
125 280.8201.1
237.4 N/A182.5
219.3
5.0 N/A
221.9
263.5
61.4 201.2
243.1
100 243.7
288.5 220.8
265.8 266.6
314.8 239.9
283.3
6.0 212.9 197.0 CSD-0351-MT
CSD-0350-MT
237.4
CSD-0301-MT 219.3 263.5
6DHNR35ME
4DJNR28ME 243.1
S
O 148.1
288.5
155.5
105.4 136.9
265.8
142.8
16.2 169.1
314.8 162.3
176.4
151.0 154.9
283.3 197.3
250 190.2
342.3 185.3
52.7 176.0
308.0
7.5 212.9
378.0 208.7
224.3
74.9 197.0
125 350.0251.7
237.4
44.1 N/A234.0
219.3
7.5 N/A
263.5
281.4
63.9 243.1
259.0
100 288.5
310.6 265.8
285.6 314.8
341.7 283.3
314.0
5.3 224.3 208.7 CSD-0352-MT
CSD-0351-MT
251.7
CSD-0302-MT 234.06DHNR35ME
281.4 259.0
O
T 155.5
310.6
151.1 142.8
285.6
139.6
10.8 176.4
341.7 158.0
172.5
145.6 162.3
314.0 194.0
250 197.3
371.3 179.5
185.3
344.1
5.0 224.3
396.0 200.9
217.2
72.4 208.7
125 366.0242.1
251.7 N/A223.7
234.0
5.0 N/A
281.4
268.7
61.4 259.0
247.9
100 310.6
294.3 285.6
271.2 341.7
321.1 314.0
289.0
9.5 217.2 200.9 CSD-0400-MT
CSD-0352-MT
242.1
CSD-0350-MT 223.7 268.7 247.9
T
S 151.1
294.3
180.2 139.6
271.2
166.4
16.2 172.5
321.1 189.7
205.4
175.6 158.0
289.0 231.0
300 194.0
349.1 215.2
179.5
314.2
7.5 217.2
385.6 243.1
261.2
87.2 200.9
150 357.0294.1
242.1 N/A270.7
223.7
7.5 N/A
268.7
323.4
62.5 247.9
300.3
100 294.3
357.6 271.2
331.7 321.1
393.8 289.0
354.4
5.2 261.2 243.1 CSD-0401-MT*
CSD-0400-MT
294.1 270.76DJNR40ME
323.4 300.3
S 180.2
357.6 166.4
331.7 205.4
393.8 194.7
189.7
354.4 237.3
231.0
427.8 219.4
215.2
385.0 266.4
261.2
452.9 248.7
243.1
CSD-0351-MT 6DHNR35ME
6DJNR40ME O 184.3
125.1 170.5
21.6 208.4
181.0 300 62.6 10.0 89.7 150 420.2298.0
294.1
43.1 N/A277.9
270.7
10.0 N/A
323.4
332.0
65.0 300.3
306.4
100 357.6
368.4 331.7
339.8 393.8
403.2 354.4
375.2
9.4 266.4 248.7 CSD-0401-MT*
298.0
CSD-0352-MT 277.9 332.0 306.4
O
T 184.3
368.4 170.5
339.8
16.2 208.4
403.2
175.6 194.7
375.2
300 237.3
443.9 219.4
409.1
7.5 266.4
471.0
87.2 248.7
150 437.0298.0 N/A277.9
7.5 N/A
332.0
62.5 306.4
100 368.4 339.8 403.2 375.2
CSD-0400-MT S 16.2 197.8 300 7.5 98.3 150 7.5 73.9 125
6DJNR40ME 142.9 71.4 52.1
Electrical
CSD-0401-MT*Specifications O R-448A 21.6 203.2 300 10.0 100.8 150 10.0 76.4 125
Electrical Specifications
Voltage
R-448A208-230/3/60 (TFC) 460/3/60 (TFD) 575/3/60 (TFE)
/3/60 (TFD) 575/3/60
Voltage (TFE) Comp 208-230/3/60
Cond (TFC) Comp 460/3/60
Cond (TFD) Comp 575/3/60
Cond (TFE)
nd Unit
Comp CondCompressor Cond Comp Cond MCA MOPD Comp Cond MCA MOPD Comp Cond MCA MOPD
MCA MOPD Unit Compressor
MCA MOPD
Cond RLA FLA MCA MOPD RLA FLA MCA MOPD RLA FLA MCA MOPD
A RLA
CSD-0100-MT FLA S RLA FLA
5.4 62.9 100 RLA FLA
2.5 29.0 45 RLA FLA
2.5 24.3 40
5 29.0 45 CSD-0101-MT
CSD-0100-MT 2.5 3DB3R12ME 24.3 40O
S 43.6 5.4
10.8 62.9
68.3 100
110 20 2.5
5.0 29.0
31.5 45
50 16.5 2.5
5.0 24.3
26.8 40
0 31.5 50 CSD-0102-MT
CSD-0101-MT
16.5 5.0 3DB3R12ME 26.8 40O
T 43.6 10.8
5.4 68.3
62.9 110
100 20 5.0
2.5 31.5
29.0 50
45 16.5 5.0
2.5 26.8
24.3 40
5 29.0 45 CSD-0150-MT
CSD-0102-MT 2.5 24.3 40ST 5.4
10.8 62.9
88.4 100
150 2.5
5.0 29.0
42.8 45
70 2.5
5.0 24.3
35.7 40
60
0 42.8 70 CSD-0151-MT
CSD-0150-MT 5.0 3DS3R17ME 35.7 60O
S 59.6 10.8 88.4 150 29.0 5.0 42.8 70 23.6 5.0 35.7 60
0 42.8 70 CSD-0152-MT
CSD-0151-MT
23.6 5.0 3DS3R17ME 35.7 60O
T 59.6 10.8 88.4 150 29.0 5.0 42.8 70 23.6 5.0 35.7 60
0 42.8 70 CSD-0200-MT
CSD-0152-MT 5.0 35.7 60ST 10.8 88.4
104.0 150
175 5.0 42.8
51.6 70
80 5.0 35.7
45.5 60
70
0 51.6 80 CSD-0201-MT
CSD-0200-MT 5.04DBNR20ME 45.5 70O
S 72.1 10.8 104.0 175 36.1 5.0 51.6 80 31.4 5.0 45.5 70
0 51.6 80 CSD-0202-MT
CSD-0201-MT
31.4 5.0 4DBNR20ME 45.5 70O
T 72.1 10.8 104.0 175 36.1 5.0 51.6 80 31.4 5.0 45.5 70
0 51.6 80 CSD-0250-MT
CSD-0202-MT 5.0 45.5 70ST 10.8 104.0
116.4 175
200 5.0 51.6
57.8 80
100 5.0 45.5
49.1 70
80
0 57.8 100 CSD-0251-MT
CSD-0250-MT 5.04DHNR22ME 49.1 80O
S 82.1 10.8
16.2 116.4
121.8 200 41.1 5.0
7.5 57.8
60.3 100 34.4 5.0
7.5 49.1
51.6 80
5 60.3 100 CSD-0252-MT
CSD-0251-MT
34.4 7.5 4DHNR22ME 51.6 80O
T 82.1 16.2
10.8 121.8
116.4 200 41.1 7.5
5.0 60.3
57.8 100 34.4 7.5
5.0 51.6
49.1 80
0 57.8 100 CSD-0300-MT
CSD-0252-MT 5.0 49.1 80ST 10.8 116.4
145.6 200
250 5.0 57.8
72.4 100
125 5.0 49.1
61.4 80
100
0 72.4 125 CSD-0301-MT
CSD-0300-MT 5.0 4DJNR28ME 61.4 100S
O 105.4 10.8
16.2 145.6
151.0 250 52.7 5.0
7.5 72.4
74.9 125 44.1 5.0
7.5 61.4
63.9 100
5 74.9 125 CSD-0302-MT
CSD-0301-MT
44.1 7.5 4DJNR28ME 63.9 100O
T 105.4 16.2
10.8 151.0
145.6 250 52.7 7.5
5.0 74.9
72.4 125 44.1 7.5
5.0 63.9
61.4 100
0 72.4 125 CSD-0350-MT
CSD-0302-MT 5.0 61.4 100ST 10.8
16.2 145.6
175.6 250
300 5.0
7.5 72.4
87.2 125
150 5.0
7.5 61.4
62.5 100
5 87.2 150 CSD-0351-MT
CSD-0350-MT 7.56DHNR35ME 62.5 100S
O 125.1 16.2
21.6 175.6
181.0 300 62.6 7.5
10.0 87.2
89.7 150 43.1 7.5
10.0 62.5
65.0 100
.0 89.7 150 CSD-0352-MT
CSD-0351-MT
43.1 10.06DHNR35ME 65.0 100O
T 125.1 21.6
16.2 181.0
175.6 300 62.6 10.0
7.5 89.7
87.2 150 43.1 10.0
7.5 65.0
62.5 100
5 87.2 150 CSD-0400-MT
CSD-0352-MT 7.5 62.5 100ST 16.2 175.6
197.8 300 7.5 87.2
98.3 150 197.5 62.5
73.9 100
125
5 98.3 150 CSD-0401-MT*
CSD-0400-MT 7.5 6DJNR40ME73.9 125S 142.9 16.2 197.8 71.4 7.5 98.3 52.1 7.5 73.9
52.1 6DJNR40ME O 142.9 21.6 203.2 300 71.4 10.0 100.8 150 52.1 10.0 76.4 125
.0 100.8 150 CSD-0401-MT*10.0 76.4 125O 21.6 203.2 300 10.0 100.8 150 10.0 76.4 125
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser 4. The capacity and electrical data could be referred for R-449A.
and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 6. * SST = -5˚F, ambient temperature = 105˚F, head cooling fan is required.
2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condenser.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser 4. The capacity and electrical data could be referred for R-507.
and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
4
10 LARGE AIR-COOLED COMMERCIAL CONDENSING UNITS
Specifications subject to change without notice.
4
CS Single Systems
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, 4. The capacity and electrical data could be referred for R-407F.
condenser and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA = 1.25x(RLAcomp)+FLAcond+Control Circuit Amps 6. * SST = -5°F, ambient temperature = 105°F, head cooling fan is required.
2) MOP = 2.25x(RLAcomp)+FLAcond+Control Circuit Amps
4
LARGE AIR-COOLED COMMERCIAL CONDENSING UNITS 11
Specifications subject to change without notice.
4
CS Single Systems
Notes:
1. S - Standard, O - Oversized, T - Title 24 compliant , * - Title 24 compliant
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser and control circuit amps.
The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation
1) MCA=1.25x(RLAcomp)+FLAcond+Control Circuit Amps 2) MOP=2.25x(RLAcomp)+FLAcond+Control Circuit Amps
3. Condening unit capacities based on LAVF condensers
4. The capacity and electrical data could be referred for R-449A.
5. Capacity rating is based on mid-point temperature.
6. * SST = -5°F, ambient temperature = 105°F, head cooling fan is required
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser 4. The capacity and electrical data could be referred for R-449A.
and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 6. * SST = -5°F, ambient temperature = 105°F, head cooling fan is required.
2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, 4. The capacity and electrical data could be referred for R-507.
condenser and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
21 1) MCA = 1.25x(RLAcomp)+FLAcond+Control Circuit Amps 6. Head cooling fan 21
is required for all low temperature applications.
2) MOP = 2.25x(RLAcomp)+FLAcond+Control Circuit Amps
21
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser 4. The capacity and electrical data could be referred for R-407F.
and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 6. Demand cooling is required for all low temperature applications, in addition to head cooling fan.
2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
21 21
CS Single Systems
21
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, 4. The capacity and electrical data could be referred for R-449A.
condenser and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA = 1.25x(RLAcomp)+FLAcond+Control Circuit Amps 6. Demand cooling is required for all low temperature applications,
2) MOP = 2.25x(RLAcomp)+FLAcond+Control Circuit Amps in addition to head cooling fan.
21 21
CS Single Systems
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser 4. The capacity and electrical data could be referred for R-507.
and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
6 6
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 6. Head cooling fan is required for all low temperature applications.
2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, 4. The capacity and electrical data could be referred for R-407F.
condenser and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
6 6
1) MCA = 1.25x(RLAcomp)+FLAcond+Control Circuit Amps 6. Liquid injection is required for all low temperature applications, in addition to
2) MOP = 2.25x(RLAcomp)+FLAcond+Control Circuit Amps head cooling fan.
6
LARGE AIR-COOLED COMMERCIAL CONDENSING UNITS 17
Specifications subject to change without notice.
CS Single Systems
Notes:
1. S - Standard, O - Oversized, T - Title 24 compliant , * - Title 24 compliant
6
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser and control circuit amps.
The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation
1) MCA=1.25x(RLAcomp)+FLAcond+Control Circuit Amps 2) MOP=2.25x(RLAcomp)+FLAcond+Control Circuit Amps
3. Condening unit capacities based on LAVF condensers
4. The capacity and electrical data could be referred for R-449A.
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser 4. The capacity and electrical data could be referred for R-449A.
and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
6
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 6 applications, in addition to head cooling fan.
6. Liquid injection is required for all low temperature
2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, 4. The capacity and electrical data could be referred for R-507.
condenser and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
6 1) MCA = 1.25x(RLAcomp)+FLAcond+Control Circuit Amps 6
6. Head cooling fan is required for all low temperature applications.
2) MOP = 2.25x(RLAcomp)+FLAcond+Control Circuit Amps
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser 4. The capacity and electrical data could be referred for R-407F.
and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 6. Liquid injection is required for all low temperature applications, in addition to head cooling fan.
2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
6 6
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, 4. The capacity and electrical data could be referred for R-449A.
condenser and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA = 1.25x(RLAcomp)+FLAcond+Control Circuit Amps 6. Liquid injection is required for all low temperature applications, in addition to
2) MOP = 2.25x(RLAcomp)+FLAcond+Control Circuit Amps head cooling fan.
6 6
Model CSD-0300LxM
Compressor RLA 43.6
Condenser Fans + 5.4 Example calculation has details for
Control* + 3.0 the calculation of the MCA shown
in the electrical table above. The
25% Compressor RLA + 10.9 Calculated MCA includes the
MCA 62.9 addition of 12.0 amps to power
evaporator fans to show how to
Evaporator Fan RLA + 12.0 recalculate values for MCA and
Calculated MCA 74.9 MOPD for the addition of electrical
loads that would be in operation at
Compressor RLA + 43.6 the same time as the compressor
Calculaed MOP 118.5
and condenser.
MOPD** 110
*Control circuit amps are: 208-230/3/60 3.0A, 460/3/60 1.5A, 575/3/60 1.2A
**Round MOP down to next Standard MOPD Size shown below. The MOPD must be larger than
the calculated MCA.
Standard MOPD Sizes : 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150,
175, 200, 225, 250, 300, 350, 400, 450, 500
Alternate Calculation for Electric Defrost: If 1.25 X defrost amps plus Control Transformer
exceeds calculated MCA use this value and round up to next standard breaker size for MOPD.
Use the MOPD calculated for defrost if it exceeds what is calculated using the compressor
information.
Notes
Notes: Notes:
mpliant , * - Title 24 compliant 1. S - Standard,
1. S - Standard, O - Oversized, T - Title 24 compliant , * - Title O
24-compliant
Oversized, T - Title 24 compliant , * - Title 24 compliant
and maximum overcurrent protection device (MOPD) covers compressor,
2. Calculation condensercircuit
of minimum and control circuit 2.
amps (MCA) amps.
andCalculation
maximumofovercurrent
minimum circuit ampsdevice
protection (MCA)(MOPD)
and maximum overcurrent protection
covers compressor, condenserdevice (MOPD)
and control covers
circuit compressor, condenser and control circuit amps.
amps.
mps are not considered in MCA and MOPD calculation The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation
CP Parallel Systems
Notes:
Notes:
1. S - Standard, O - Oversized, T - Title 24 compliant , * - Title 24 compliant
1. S - Standard, O - Oversized, T - Title 24 compliant , * - Title 24 compliant
CP Parallel Systems
Notes: Notes:
4 compliant 1. S - Standard, O1. S - Standard,
- Oversized, T -O - Oversized,
Title T - Title
24 compliant , * - 24
Titlecompliant , * - Title 24 compliant
24 compliant
rcurrent protection device (MOPD) covers compressor, condenser and control
2. Calculation of circuit
2. Calculation
minimum amps.
circuitof minimum
amps (MCA)circuit amps (MCA)
and maximum and maximum
overcurrent overcurrent
protection protection
device (MOPD) device
covers (MOPD) covers
compressor, compressor,
condenser condenser
and control circuit and control circuit amps.
amps.
red in MCA and MOPD calculation The evaporator fans and electric defrost amps are not considered in MCAconsidered
The evaporator fans and electric defrost amps are not and MOPDincalculation
MCA and MOPD calculation
CP Parallel Systems
2. S
1.
28
Calculation
- Standard,
LARGE AIR-COOLED COMMERCIAL CONDENSING UNITS
1. S - Standard, O - Oversized, T - Title 24 compliant , * - Title 24 compliant
Notes:
of O
minimum circuitT amps
- Oversized, - Title (MCA) and maximum
24 compliant , * - Titleovercurrent
24 compliantprotection device (MOPD) covers compressor, condenser and control circuit amps.
2. The evaporator fans andcircuit
electric defrost ampsandare not considered in MCA and MOPD calculation
ondenser and control circuit
Calculation
amps.
Specifications subject to change without notice.
of minimum amps
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control
The
(MCA) maximum
evaporator fans and electric defrost amps are not considered
overcurrent
Circuit Amps
protection
in MCA
device (MOPD) covers compressor, condenser and control circuit amps.
2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control
and MOPD calculation Circuit Amps
+Control Circuit Amps 3. Condening unit capacities based on LAVF condensers
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
4. The
3. capacity
Condening and
unit electricalbased
capacities data couldon LAVFbe referred for R-407F.
condensers
5. The
4. Capacity rating
capacity andis electrical
based on datamid-point
couldtemperature.
be referred for R-407F.
6. Capacity
5. * SST = -5°F, ambient
rating is basedtemperature
on mid-point = 105°F, head cooling fan is required
temperature.
6. * SST = -5°F, ambient temperature = 105°F, head cooling fan is required
CP Parallel Systems
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser 9
4. The capacity and electrical data could be referred for R-507.
and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, 9
4. The capacity and electrical data could be referred for R-407F.
condenser and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA = 1.25x(RLAcomp)+FLAcond+Control Circuit Amps 6. * SST = -5°F, ambient temperature = 105°F, head cooling fan is required.
2) MOP = 2.25x(RLAcomp)+FLAcond+Control Circuit Amps
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser 4. The capacity and electrical data could be referred for R-449A.
and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
9
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 6. * SST = -5°F, ambient temperature = 105°F, head cooling fan is required.
2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
CPD Performance Data - Low Temperature R-404A - Total Capacity CPD Performance Data - Low Temperature R-404A - Total Capacity
e (SST) -40°F -35°F -30°F
Saturated Suction Temperature
-25°F (SST) -20°F -15°F
-40°F -10°F
-35°F Electrical
-5°F
-30°F Specifications
0°F
-25°F R-404A
-20°F
95°FCPD Series
105°F Air-Cooled
95°F 105°F Condensing
95°F Voltage Unit105°F 95°F 105°F
105°FTemperature
Ambient 95°F 95°F
95°F
208-230/3/60 105°F
105°F 95°F
95°F 105°F 105°F 95°F
460/3/60 95°F 105°F105°F 95°F
95°F 105°F105°F
575/3/60 95°F 105°F
mpressor Cond Unit Capacity (MBH) Unit Compressor
Comp Cond Unit Unit Capacity
Capacity (MBH)
(MBH) Comp Cond Comp Cond
S 81.8 73.2 96.6 Unit
87.0 111.2 Compressor
CPD-0300-LS*
100.6 126.4 Cond
114.6 142.2 Cond 129.0 FLA
S MCA
158.8
81.8 MOPD
144.273.2 176.8 96.6 160.6 MCA
87.0 196.2111.2 MOPD
178.2
100.6 RLAN/A
126.4 FLA
N/A114.6 MCA142.2 MOPD129.0
KNF63KE 2 - 4DKNF63KERLA RLA FLA
O 85.9 77.3 101.6 CPD-0300-LS*
92.1 117.2 CPD 106.7Performance
CPD-0301-LS 133.5 121.7
S Data150.6 - Low10.8 Temperature
137.4 O 168.7
85.9
132.1 175 R-404A - 5Total 65.6
154.177.3 188.5
101.6 172.092.1 Capacity
209.9
117.2 191.6
106.7
90 N/A
133.5 N/A
5121.7 53.3
150.6 137.4
70
S 96.8 83.3 114.6 CPD-0301-LS
100.5 132.9 2 CPD-0440-LS
-117.9
4DKNF63KE 152.0 135.8 52.6
171.8 154.4 S 192.6
96.8 173.683.3 26.3
214.4
114.6 193.7
100.5 237.4
132.9 214.8
117.9 20.9
N/A
152.0 N/A135.8 171.8 154.4
JNF76KE Saturated Suction Temperature (SST) -40°F 2O- 4DJNF76KE -35°F
16.2 137.5
-30°F
175
-25°F
7.5 68.1
-20°F
90
-15°F
7.5 55.8
-10°F
70
O 98.9 85.7 117.2 CPD-0440-LS
103.2 136.2 CPD-0441-LS*
121.2 155.9 139.6
S 176.6 158.8
16.2 O 198.3
98.9
163.8 178.9
22585.7 221.4117.2 200.0103.2 245.8
7.5 136.2 222.3
81.3 121.2 N/A
110 155.9 N/A 139.6 74.1
7.5 176.6 100 158.8
S 118.3 Ambient Temperature
103.1 138.8 CPD-0441-LS*
122.6 161.3 2 - 4DJNF76KE
CPD-0540-LS*
143.9 95°F
185.8 105°F
166.8 95°F
64.3
212.1 105°F
191.2 95°F 105°F 95°F
32.1 105°F 95°F 105°F 95°F
29.1 105°F 95°F 105°F
HNF93KE 2O- 6DHNF93KE 21.6S 239.8
118.3
169.2 216.7
103.1 268.9
225 138.8 243.3122.6 299.0
10.0 161.3 270.7
83.8 143.9 N/A
110 185.8 10.0
N/A166.8 76.6
212.1 100 191.2
O 121.0 Unit
106.0 Compressor
141.9 CPD-0540-LS*
126.0 165.2 Cond Unit
CPD-0541-LS*
148.0 Capacity
190.6 (MBH)
171.8 217.9 197.3 O 247.1
121.0 224.2
106.0 277.8141.9 252.4126.0 309.9165.2 281.7 Unit
148.0 N/A Capacity
190.6 N/A (MBH)
171.8 84.7
217.9 110 197.3
S 16.2 200.8 250 7.5 99.8 125 7.5
S 134.5 CPD-0300-LS*
116.8 157.5 CPD-0541-LS* 2 - S6DHNF93KE 81.8 73.2 96.6
80.7 87.0 111.2 100.6 126.4
40.4 114.6 142.2 129.0 158.8
33.8 144.2 176.8 160.6
2 - 138.9
4DKNF63KE 182.4 CPD-0600-LS
162.3 209.0 187.1
O 237.5 213.2
21.6S 267.8
134.5
206.2 240.8
116.8 299.9
250 157.5 269.8138.9 333.8
10.0 182.4 300.2
102.3 162.3 N/A
125 209.0 10.0
N/A187.1 87.2
237.5 110 213.2
JNF11ME O 138.7 CPD-0301-LS
121.1 162.6 CPD-0600-LS
143.9 188.5 O
CPD-0601-LS
168.3 85.9
216.5 77.3 101.6
2S- 6DJNF11ME
194.4 246.8 92.1
222.2
21.6 O 117.2
279.3
138.7
239.9
106.7
251.9
121.1
300
133.5
314.3
162.6 121.7
283.5
143.9
10.0
150.6
351.6
188.5
119.2
137.4
317.0
168.3
150
168.7
N/A
216.5 154.1
N/A194.4
10.0
188.5
246.8
99.6
172.0
222.2
125
T 137.2 CPD-0440-LS
119.1 160.7 CPD-0601-LS
2 -141.7
4DJNF76KE
S
186.0 2 CPD-0602-LS
-165.5
6DJNF11ME
96.8
213.2 83.3
190.8
O
114.6
242.3
95.7
100.5
217.5
32.4T
132.9
137.2 117.9
273.2
250.7 119.1 152.0
245.6
300 160.7 135.8
305.9
47.9 141.7 171.8
275.2
15.0 186.0 154.4
340.5
124.2 165.5 192.6
306.2
150 213.2 173.6
N/A
39.3 N/A190.8 214.4
15.0 242.3 193.7
104.6 217.5
125
CPD-0441-LS* O 98.9 85.7 117.2 103.2 136.2 121.2 155.9 139.6 176.6 158.8 198.3 178.9 221.4 200.0
CPD-0602-LS T 21.6 239.9 300 10.0 119.2 150 10.0 99.6 125
CPD-0540-LS* S 118.3 103.1 138.8 122.6 161.3 143.9 185.8 166.8 212.1 191.2 239.8 216.7 268.9 243.3
2 - 6DHNF93KE
CPD-0541-LS*
CPD-0600-LS
O
S
121.0
134.5
Electrical
106.0
116.8
Specifications
141.9
157.5
126.0
138.9
165.2
182.4
R-404A
148.0
162.3
190.6
209.0
171.8
187.1
217.9
237.5
197.3
213.2
247.1
267.8
Electrical
224.2
240.8
Specifica
277.8
299.9
252.4
269.8
208-230/3/60 Notes: 460/3/60 Voltage 575/3/60 208-230/3/60 460/3/60
CPD-0601-LS 1. S2- -Standard,
6DJNF11ME O - Oversized,O T - Title 138.7 121.1 , * - 162.6
24 compliant Title 143.9
24 compliant 188.5 168.3 216.5 194.4 246.8 222.2 279.3 251.9 314.3 283.5 57
Comp CPD-0602-LS Comp Cond
T 137.2 119.1 Comp
160.7 Cond
141.7 Comp 165.5
186.0 213.2 190.8 Comp 217.5
242.3 Cond 273.2 245.6 Comp 275.2
305.9 Cond
mpressor Cond Cond FLA MCA 2. MOPD of minimum circuitUnit
Calculation amps MCA
(MCA) MOPD
and Compressor
maximum overcurrentCond MCAdevice
protection MOPD
Cond FLA covers
(MOPD) MCAcompressor,
MOPD condenser and control circuit MCA amps. MOPD
RLA RLA FLA RLA FLA RLA RLA FLA RLA FLA
S 10.8 132.1 The evaporator
175 fans and electric
CPD-0300-LS*
5 defrost
65.6 amps are
90 not considered in MCA
5S and MOPD
53.3 calculation
7010.8 132.1 175 5 65.6 90 5
KNF63KE 52.6 26.3 2 - 4DKNF63KE 20.9 52.6 26.3 Circuit Amps 20.9
137.5 1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 7.5O2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control
O
S
16.2
16.2 163.8
175
3. Condening
225 unit capacities
CPD-0301-LS
7.5
based on81.3
CPD-0440-LS
7.5
68.1 90
LAVF condensers
110 7.5S
55.8
74.1
70
100
16.2
16.2
Electrical
137.5
163.8
175
225
Specifications 7.5
7.5
R-404A
68.1
81.3
90
110
7.5
7.5
JNF76KE 64.3 4.Voltage
The capacity 32.1
and electrical data could 2 - 4DJNF76KE
be referred 29.1 64.3 32.1 29.1
O 21.6 169.2 225 CPD-0441-LS*
10.0 83.8 110 for R-507.
208-230/3/60 10.0O 76.6 100460/3/60 169.2
21.6 225 575/3/60
10.0 83.8 110 10.0
S 16.2 200.85. Capacity
250 rating is basedCond on mid-point
CPD-0540-LS*
7.5 Comp temperature.
99.8 125 7.5S Comp
84.7 Cond
11016.2 MCA 200.8 MOPD 250 Comp Cond7.5 99.8 MOPD 125 7.5
HNF93KE 80.7 Unit Compressor
6. Head250 cooling fan 40.4is required Cond FLA
2 - 6DHNF93KE MCA
33.8 MOPD 80.7 40.4 FLA MCA 33.8
O 21.6 206.2 10.0for allRLA
CPD-0541-LS* low
102.3temperature
125 applications. 10.0 O RLA
87.2 FLA
11021.6 206.2 250 RLA 10.0 102.3 125 10.0
S CPD-0300-LS*
21.6 239.9 2 - 4DKNF63KE
300 S
CPD-0600-LS
10.0 119.2 10.8
150 132.1 175
10.0S 99.6 521.6 65.6
125 239.9 90300 5 10.0 53.3 119.2 70150 10.0
52.6 26.3 20.9
JNF11ME O 95.7 CPD-0301-LS
32.4 250.7 300 47.9 O
CPD-0601-LS
15.0 124.2 16.2
2150 137.5
- 6DJNF11ME39.3 175
15.0O 104.6
95.7 7.5
12532.4 68.1 250.7 90300 47.9 7.515.0 55.8 124.2 70150 39.3 15.0
T CPD-0440-LS
21.6 239.9 2 - 4DJNF76KE
300 S
CPD-0602-LS
10.0 119.2 16.2
150 163.8 225
10.0T 99.6 7.5
12521.6 81.3 239.9 110300 29.1 7.510.0 74.1 119.2 100150 10.0
64.3 32.1
CPD-0441-LS* O 21.6 169.2 225 10.0 83.8 110 10.0 76.6 100
CPD-0540-LS* S 16.2 200.8 250 7.5 99.8 125 7.5 84.7 110
2 - 6DHNF93KE 80.7 40.4 33.8
CPD-0541-LS* Notes:O 21.6 206.2 250 10.0 102.3 125 10.0 87.2 110
T - Title 24 compliant , * - Title 24CPD-0600-LS
compliant 1. S S - Standard, O - Oversized,21.6 T - 239.9 300
Title 24 compliant 10.0
, * - Title 24 compliant 119.2 150 10.0 99.6 125
CPD-0601-LS 2 - 6DJNF11ME
uit amps (MCA) and maximum overcurrent protection device (MOPD) covers2.compressor, O
Calculation of 95.7
condenser
minimumand32.4
circuit 250.7
control
amps circuit
(MCA) 300
amps. 47.9 15.0 124.2 150 39.3 15.0 104.6 125
and maximum overcurrent protection device (MOPD) covers compressor, condenser and control circuit amps.
ctric defrost amps are not considered CPD-0602-LS
in MCA and MOPD calculation The T evaporator fans and 21.6electric239.9
defrost amps 300are not considered 10.0
in MCA119.2
and MOPD150 calculation 10.0 99.6 125
RLAcomp+FLAcond+Control Circuit Amps 2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control 1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control
Circuit Amps Circuit Amps 2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
ased on LAVF condensers 3. Condening unit capacities based on LAVF condensers
ata could be referred for R-507. Notes: 4. The capacity and electrical data could be referred for R-507.
mid-point temperature. 1. S - Standard, O - Oversized, T - Title 24 compliant
5. Capacity , * -rating
Title is
24based
compliant
on mid-point temperature.
2. Calculation of minimum circuit amps (MCA)
for all low temperature applications. 6. and
Head maximum
cooling fanovercurrent
is required protection
for all lowdevice (MOPD)applications.
temperature covers compressor, condenser and control circuit amps.
The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
3. Condening unit capacities based on LAVF condensers
4. The capacity and electrical data could be referred for R-507.
5. Capacity rating is based on mid-point temperature.
6. Head cooling fan is required for all low temperature applications.
26
26 1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on26LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, 4. The capacity and electrical data could be referred for R-507.
condenser and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA = 1.25x(RLAcomp)+FLAcond+Control Circuit Amps 6. Head cooling fan is required for all low temperature applications.
2) MOP = 2.25x(RLAcomp)+FLAcond+Control Circuit Amps
26
LARGE AIR-COOLED COMMERCIAL CONDENSING UNITS 33
Specifications subject to change without notice.
CP Parallel Systems
26
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser 4. The capacity and electrical data could be referred for R-407F.
and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 6. Demand cooling is required for all low temperature applications, in addition to head cooling fan.
2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
26
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, 4. The capacity and electrical data could be referred for R-449A.
condenser and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA = 1.25x(RLAcomp)+FLAcond+Control Circuit Amps 6. Demand cooling is required for all low temperature applications, in addition to head cooling fan.
2) MOP = 2.25x(RLAcomp)+FLAcond+Control Circuit Amps
Notes:
1. S - Standard, O - Oversized, T - Title 24 compliant , * - Title 24 compliant
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser and control circuit amps.
The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
3. Condening unit capacities based on LAVF condensers
4. The capacity and electrical data could be referred for R-507.
5. Capacity rating is based on mid-point temperature.
6. Head cooling fan is required for all low temperature applications.
11
11 11
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser 4. The capacity and electrical data could be referred for R-507.
and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 6. Head cooling is required for all low temperature applications.
2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
Notes:
1. S - Standard, O - Oversized, T - Title 24 compliant , * - Title 24 compliant
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser and control circuit amps.
The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
3. Condening unit capacities based on LAVF condensers
4. The capacity and electrical data could be referred for R-407F.
5. Capacity rating is based on mid-point temperature.
6. Liquid injection is required for all low temperature applications, in addition to head cooling fan.
11
11 11
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, 4. The capacity and electrical data could be referred for R-407F.
condenser and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA = 1.25x(RLAcomp)+FLAcond+Control Circuit Amps 6. Liquid injection is required for all low temperature applications, in addition to head cooling fan.
2) MOP = 2.25x(RLAcomp)+FLAcond+Control Circuit Amps
Notes:
1. S - Standard, O - Oversized, T - Title 24 compliant , * - Title 24 compliant
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser and control circuit amps.
The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
3. Condening unit capacities based on LAVF condensers
4. The capacity and electrical data could be referred for R-449A.
5. Capacity rating is based on mid-point temperature.
6. Liquid injection is required for all low temperature applications, in addition to head cooling fan.
11
Notes:
1. S - Standard, O - Oversized, T - Title 24 compliant , * - Title 24 compliant
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser and control circuit amps.
The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
3. Condening unit capacities based on LAVF condensers
4. The capacity and electrical data could be referred for R-507.
5. Capacity rating is based on mid-point temperature.
6. Head cooling fan is required for all low temperature applications.
11
Notes:
1. S - Standard, O - Oversized, T - Title 24 compliant , * - Title 24 compliant
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser and control circuit amps.
The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
3. Condening unit capacities based on LAVF condensers
4. The capacity and electrical data could be referred for R-407F.
5. Capacity rating is based on mid-point temperature.
6. Liquid injection is required for all low temperature applications, in addition to head cooling fan.
11
11 11
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser 4. The capacity and electrical data could be referred for R-407F.
and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 6. Liquid injection is required for all low temperature applications, in addition to head cooling fan.
2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
Notes:
1. S - Standard, O - Oversized, T - Title 24 compliant , * - Title 24 compliant
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser and control circuit amps.
The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
3. Condening unit capacities based on LAVF condensers
4. The capacity and electrical data could be referred for R-449A.
5. Capacity rating is based on mid-point temperature.
6. Liquid injection is required for all low temperature applications, in addition to head cooling fan.
11
11 11
1. S - Standard, O - Oversized, T - Title 24 compliant, * - Title 24 compliant. 3. Condensing unit capacities based on LAVF condensers.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, 4. The capacity and electrical data could be referred for R-449A.
condenser and control circuit amps. The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation: 5. Capacity rating is based on mid-point temperature.
1) MCA = 1.25x(RLAcomp)+FLAcond+Control Circuit Amps 6. Liquid injection is required for all low temperature applications, in addition to head cooling fan.
2) MOP = 2.25x(RLAcomp)+FLAcond+Control Circuit Amps
Model CPD-0440LxM
Compressor 1 RLA 22.3
Compressor 2 RLA + 22.3 Example calculation has details for
Condenser Fans + 5.4 the calculation of the MCA shown
Control* + 3.0 in the electrical table above. The
25% Compressor RLA + 5.6 Calculated MCA includes the
MCA 58.6 addition of 12.0 amps to power
evaporator fans to show how to
Evaporator Fan RLA + 12.0 recalculate values for MCA and
Calculated MCA 70.6 MOPD for the addition of electrical
loads that would be in operation at
Compressor RLA 1 + 22.3 the same time as the compressor
Calculaed MOP 92.9 and condenser.
MOPD** 90
*Control circuit amps are: 208-230/3/60 3.0A, 460/3/60 1.5A, 575/3/60 1.2A
**Round MOP down to next Standard MOPD Size shown below. The MOPD must be larger than
the calculated MCA.
Standard MOPD Sizes : 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150,
175, 200, 225, 250, 300, 350, 400, 450, 500
Alternate Calculation for Electric Defrost: If 1.25 X defrost amps plus Control Transformer
exceeds calculated MCA use this value and round up to next standard breaker size for MOPD.
Use the MOPD calculated for defrost if it exceeds what is calculated using the compressor
information.
Notes
Notes:
44
Notes:
LARGE AIR-COOLED COMMERCIAL CONDENSING UNITS
1. S - Standard, O - Oversized, T - Title 24 compliant , * - Title 24 compliant
1. S - Standard, O - Oversized, T - Title 24 compliant , * - Title 24 compliant
condenser and control circuit
2. Calculation
amps. of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser and control circuit amps.
2. Calculation of minimum circuit amps (MCA) and maximum overcurrent protection device (MOPD) covers compressor, condenser and control circuit amps.
The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation
d+Control Circuit Amps Specifications subject to change without notice.
The evaporator fans and electric defrost amps are not considered in MCA and MOPD calculation
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
1) MCA=1.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps 2) MOP=2.25x(RLAcomp)+RLAcomp+FLAcond+Control Circuit Amps
3. Condening unit capacities based on LAVF condensers
3. Condening unit capacities based on LAVF condensers
4. The capacity and electrical data could be referred for R-507.
4. The capacity and electrical data could be referred for R-507.
5. Capacity rating is based on mid-point temperature.
5. Capacity rating is based on mid-point temperature.
CD Dual Systems
29
CD Dual Systems