Beruflich Dokumente
Kultur Dokumente
Slabs are used to furnish a flat and useful surface in reinforced concrete construction.
It is broad, flat plate, usually horizontal, with top and bottom surfaces parallel or nearly so. It
may be supported by reinforced concrete beams, by masonry or reinforced concrete walls, by
structural steel members, by directly by columns or continuously by the ground.
Concrete slabs may in some cases be carried directly by columns, without the use of
beams or girders. Such slabs are called flat plates. In some cases, to reduce the stresses due to
shear and negative bending around columns, a thickened slab region in the vicinity of column
and flared column tops are incorporated. Such construction is called flat- slab construction.
Type of Slabs
Flat plate
Flat Slab
Two Way Slab Beam supported slab
waffle slab
One Way Slab
One way slab is a slab which is supported by beams on the two opposite sides to carry the
load along one direction. In one way slab, the ratio of longer span (l) to shorter span (b) is
equal or greater than 2, i.e Longer span (l)/Shorter span (b) ≥ 2
Verandah slab is a type of one way slab, where the slab is spanning in the shorter direction
with main reinforcement and the distribution of reinforcement in the transverse direction.
When a reinforced concrete slab is supported by beams on all the four sides and the loads are
carried by the supports along both directions, it is known as two way slab. In two way slab,
the ratio of longer span (l) to shorter span (b) is less than 2 i.e Longer span (l)/Shorter span
(b) < 2
This types of slabs are mostly used in the floor of multi-storey buildings.
Flat slabs include two-way reinforced concrete slabs with capitals, drop panels, or both.
These slabs are very satisfactory for heavy loads and long spans. Although the formwork
is more expensive than for flat plates, flat slabs will require less concrete and reinforcing
than would be required for flat plates with the same loads and spans. They are particularly
economical for warehouses, parking and industrial buildings, and similar structures where
exposed drop panels or capitals are acceptable.
A two-way slab with beams is a type of floor system is obviously used where its cost is
less than the costs of flat plates or flat slabs. In other words, when the loads or spans or
both become quite large, the slab thickness and column sizes required for flat plates or
flat slabs are of such magnitude that it is more economical to use two-way slabs with
beams, despite the higher form work costs.
DIFFERENCES BETWEEN ONE WAY AND TWO WAY SLABS
For purposes of analysis and design, a unit strip of such a slab cut out at right angles
to the supporting beams, as in Figure 2, may be considered as a rectangular beam of unit
width, with a depth h equal to the thickness of the slab and a span la equal to the distance
between supported edges. This strip can then be analyzed by the methods that were used for
rectangular beams, the bending moment being computed for the strip of unit width. The load
per unit area on the slab becomes the load per unit length on the slab strip. Since all the load
on the slab must be transmitted to the two supporting beams, it follows that all the
reinforcement should be placed at right angles to these beams, with the exception of any bars
that may be placed in the other direction to control shrinkage and temperature cracking. A
one-way slab thus consists of a set of rectangular beams side by side.
The ratio of steel in a slab can be determined by dividing the sectional area of one bar
by the area of concrete between two successive bars, the latter area being the product of the
depth to the center of the bars and the distance between them, center to center. The ratio of
steel can also be determined by dividing the average area of steel per foot of width by the
effective area of concrete in a 1 ft. strip. The average area of steel per foot of width is equal to
the area of one bar times the average number of bars in a 1 ft. strip (12 divided by the spacing
in inches), and the effective area of concrete in a 1 ft. (or 12 in.) strip is equal to 12 times the
effective depth d.
https://civil-engg-world.blogspot.my/2011/04/what-is-slab.html
http://www.ce.memphis.edu/6136/PDF_notes/F_slabs.pdf
http://www.dailycivil.com/one-way-slab-vs-two-way-slab/
http://www.iamcivilengineer.com/2014/08/what-is-concrete-slab-classification-of_51.html
COLUMN
1. Short column
- If the length of column is 15 times the least dimension of its cross-section then
column will be short column. Slenderness ratio of short column is up to 80.
Slenderness ratio is the ratio between effective length of column and radius of
gyration.
2. Long column
- If the length of column is more than 15 times the least dimension of its cross-section,
then column will be categorized as long column. Slenderness ratio of long column is
more than 80.
TYPES OF COLUMNS
Columns are divided into three types according to the way they are reinforced.
1) Tied Columns
2) Spirally-Reinforced Columns
They are columns in which the longitudinal bars are arranged in a circle
surrounded by a closely spaced continuous spiral, shown in Figure 2. These
columns are usually circular or square in shape. A minimum of six bars is used for
longitudinal reinforcement.
Figure 2: Spirally-reinforced column
3) Composite Columns
Failure pattern of short column is totally different than long column patterns. Short column
directly fails at the maximum value of direct stress it can take. In result of this, column
material fails and get crushed. Long column buckles on the application of load. Bending
stress produces in result of buckling which results in column failure. Short columns of same
material and same cross section will carry more loads as compared to longer column.
-
There are two types of column loading patterns. Patterns depend on the location where load is
acting. These are:
Axially loaded columns are the one where load acts at the centroid of column cross-
section. This is also known as concentric loaded column. When the load is central to the
centre of gravity axis, it produces a direct compressive stress within the column. Axially
loaded columns are sometimes referred to as 'concentric columns'. Resistance of axial loaded
column is more against buckling than eccentric loaded column. As shown in figure below;
2. Eccentric Loaded Column
If load acts away from centroid of column cross-section then such column is known as
eccentric loaded column. This results in bending and compressive stress being applied to the
column. Resistance of eccentric loaded column against buckling is very less than
concentrically loaded column. If both types of loaded columns have same cross-section and
material, then axially loaded column will be considered as stronger.
COMPRESSION MEMBERS
Compression members, such as columns, are mainly subjected to axial forces. The principal
stress in a compression member is therefore the normal stress,
The failure of a short compression member resulting from the compression axial force looks
like,
However, when a compression member becomes longer, the role of the geometry and
stiffness (Young's modulus) becomes more and more important. For a long (slender)
column, buckling occurs way before the normal stress reaches the strength of the column
material. For example, pushing on the ends of a business card or bookmark can easily
reproduce the buckling.
For an intermediate length compression member, kneeling occurs when some areas yield
before buckling, as shown in the figure below.
The failure of a compression member has to do with the strength and stiffness of the material
and the geometry (slenderness ratio) of the member. Whether a compression member is
considered short, intermediate, or long depends on these factors.
BUCKLING
Buckling will always occur about the weakest axis unless some form of lateral
(sideways) restraint is used to prevent it. The longer or slenderer the member, the more likely
it is to buckle under compressive forces. Therefore, a long member can carry less load than a
short one of the same cross-section.
The tendency to buckle increases with the strength of the material. As the material
gets stronger, the cross-sectional area required to carry the stress decreases. This produces
slenderer struts which are more likely to buckle.
SLENDERNESS RATIO
The maximum loads a column can be allowed to support depends on the slenderness ratio and
the material from which the column is made. The slenderness ratio involves:
• the manner in which the two ends of the columns are supported or fixed.
Slenderness for the cross-sectional area of general shapes is calculated using the following
formula:
How much load a column can bear also depends on column end conditions. Column with
fixed end conditions at both ends will be stronger, then the second column of same size,
length and material but having both ends free. Ability to carry load will be different for both
columns. Effective length of a column is calculated after knowing the column end conditions.
Effective length changes with the change in column end conditions. Following are the
column end conditions.
This is the standard column end condition. Effective length in this condition is equal to the
length of column. Effective length of other end conditions can be found with reference to this
condition. In this condition, both ends of column are either pinned, pivoted or rounded. As
shown in figure below:
Le = L
Where,
Le = Effective length
L = Actual Length
This is the strongest column end condition. Both ends fixed column carries maximum load
and effective length for this condition is considered as half of total column length. Column
load bearing capacity increases with the decrease in column equivalent length. As shown in
figure below:
Le = 0.5 L
In this condition, one end of a column is stronger while the other end is very weak.
Equivalent length for this end is as following:
Le =0.7 L
This end condition makes column to bear the smallest load than all other end conditions.
Column in such condition is very weak. Equivalent length for one end fixed and other free is
as following:
Le = 2L
DESIGN CONSIDERATIONS
In practice, for a given material, the allowable stress in a compression member depends on
the slenderness ratio Leff / r and can be divided into three regions which are short,
intermediate, and long.
Short columns are dominated by the strength limit of the material. Intermediate columns are
bounded by the inelastic limit of the member. Finally, long columns are bounded by the
elastic limit (i.e. Euler's formula). These three regions are depicted on the stress/slenderness
graph below,
The short/intermediate/long classification of columns depends on both the geometry
(slenderness ratio) and the material properties (Young's modulus and yield strength). Some
common materials used for columns are listed below:
Intermediate Column
Short Column Long Column
(Inelastic Stability
Material (Strength Limit) (Elastic Stability Limit)
Limit)
Slenderness Ratio ( SR = Leff / r)
Structural Steel SR < 40 40 < SR < 150 SR > 150
Aluminum
SR < 9.5 9.5 < SR < 66 SR > 66
Alloy AA 6061 - T6
Aluminum
SR < 12 12 < SR < 55 SR > 55
Alloy AA 2014 - T6
Wood SR < 11 11 < SR < (18 ~ 30) (18 ~ 30) < SR < 50
In the table, Leff is the effective length of the column, and r is the radius of gyration of the
http://www.efunda.com/formulae/solid_mechanics/columns/intro.cfm