Beruflich Dokumente
Kultur Dokumente
[Document subtitle]
[Draw your reader in with an engaging abstract. It is typically a short summary of the document.
When you’re ready to add your content, just click here and start typing.]
GROUP-6
Contents
1. PRINCIPLE OF OPERATION……………………………………………………………………………………………….. 1
The time axis is roughly divided into the range of fast-front overvoltage’s (mainly lightning
overvoltage’s) in the microsecond range, slow-front overvoltage’s (mainly switching
overvoltage’s) in the millisecond range3, temporary overvoltage’s in the second range – which are
commonly cited by the abbreviation "TOV" – and finally the temporally unlimited highest
continuous system operation voltage. The voltage or overvoltage, which can be reached without
the use of arresters, is a value of several p.u. If instead, one considers the curve of the withstand
voltage of equipment insulation, (here equipment means electrical devices such as power
transformers) one notices that starting in the range of switching overvoltages1, and especially for
lightning overvoltage’s, the equipment insulation cannot withstand the occurring dielectric
stresses. At this point, the arresters intervene. While in operation, it is certain that the voltage that
occurs at the terminal of the device – while maintaining an adequate safety margin – will stay
below the withstand voltage. Arresters' effect, therefore, involves lightning and switching
overvoltages2. However, arresters cannot and are not expected to limit temporary overvoltages.
They must instead be designed to withstand the continuous system operation voltage without
sustaining damage. This is shown in Figure 1 by the dotted part of the arrester curve on the right,
in which the arrester – like any other device in the system – must demonstrate sufficient
operational stability over and above likely voltage stress.
Even though a great number of arresters which are gapped arresters with resistors made of silicon-
carbide (SiC), are still in use, the arresters installed today are almost all metal-oxide (MO)
arresters without gaps, which means arresters with resistors made of metal-oxide (metal-oxide or
MO resistors). The distinctive feature of an MO resistor is its extremely non-linear voltage-
current or U-I-characteristic, rendering unnecessary the disconnection of the resistors from the
line through serial spark-gaps, as is found in the arresters with SiC resistors. The currents passing
through the arrester within the range of possibly applied power-frequency voltages are so small
that the arrester almost behaves like an insulator. If, however, surge currents in the kilo ampere
range are injected into the arrester, such as is the case when lightning or switching overvoltage’s
occur, then the resulting voltage across its terminals will remain low enough to protect the
insulation of the associated device from the effects of overvoltage.
Table E.1 typically needed arrester data in order to make a proper selection of surge arrestor
If no further information is given and no special requests are made:
1. For the given transformer of 500 KV the highest system voltage is indicated by Us ,in this case
for 500 KV transformer assuming 500±10×1% this will give as a tap range of
100
500kv 5kv
100
For the given tape range of 10 the maximum tap will be
10 5kv 50kv
From this the highest system voltage will be
500kv 50kv 550kv
Us = 550 kV= Um
2. Rated Voltage (Ur)
A simplified guideline to select a minimum value of the arrester rated voltage (Ur).
In each case, choose the next higher standard rating as given in the manufacturer's catalogue
Fault System Voltage (Um) / Min. Rated Voltage (Ur /
System Earthing
Duration kV kV)
Effective ≤1s ≤ 100 kV ≥ 0.80 x Um
Effective ≤1s ≥ 123 kV ≥ 0.72 x Um
Non-effective ≤ 10 s ≤ 170 kV ≥ 0.91 x Um
Non-effective ≤2h ≤ 170 kV ≥ 1.11 x Um
Non-effective >2h ≤ 170 kV ≥ 1.25 x Um
Table E.2 a simplified guideline to select a minimum value of the arrester rated voltage (Ur)
Uc = 336 kV
1.5 kA 2.5 kA 5 kA 10 kA 20 kA
Table E.4: Guide values for line discharge classes depending on system voltage
So according to the table we can select line discharge class of 4.In practice, however, one
frequently tends to select the next higher line discharge class, so according to the table we can
select line discharge class of 5
6. Protective Levels
The lightning impulse protective level of an arrester is the maximum residual voltage at
nominal discharge current. It is applicable to the protection of equipment from fast-front
over voltages.
Manufacturers guaranteed data sheet gives:
Lightning impulse protective level (at 20 kA, 8/20 μs): 1051 kV
The switching impulse protective level is the maximum residual voltage at the specified
switching impulse currents. It is applicable to the protection of equipment from slow-front
over voltages.
Manufacturers guaranteed data sheet gives:
Switching impulse protective level (at 2 kA, 30/60 μs): 849 kV
Selecting a Housing (composite hollow core insulator* - "tube design" – in order to fulfill the
seismic requirements)
Minimal requirements:
1. lightning impulse withstand voltage =
1.3 * lightning impulse protective level = 1.3 ⋅1051 kV = 1366 kV
2. switching impulse withstand voltage =
1.25 *switching impulse protective level = 1.25 ⋅849 kV = 1061 kV
3. creepage distance: 25 mm/kV *550 kV (43.3 mm/kV* 317 kV) = 13750 mm
4. Permissible head load dynamic (SSL): The specified short-term load SSL is the greatest force
perpendicular to the longitudinal axis of an arrester, allowed to be applied during service for
short periods and for relatively rare events (for example, short-circuit current loads or extreme
wind gusts) without causing any mechanical damage to the arrester.it is given in terms of force
(in N) or bending moment (in Nm)
Installation Outdoor
Energy capability
a) line discharge class (IEC) 5