Sie sind auf Seite 1von 6

IEEE TRANSACTIONS ON SMART GRID, VOL. 4, NO.

1, MARCH 2013 353

Advanced Power Distribution System Configuration


for Smart Grid
Jae-Chul Kim, Member, IEEE, Sung-Min Cho, Member, IEEE, and Hee-Sang Shin

Abstract—Power distribution systems should meet demands TABLE I


such as high reliability, efficiency, and penetration of renewable CAPACITY LIMITS OF DG [2]
energy generators (REGs) in a smart grid. In general, power dis-
tribution systems are radial in nature. One-way power flow is the
advantage of a radial system. However, the introduction of REGs
causes bidirectional power flow. Furthermore, there are limits
to improvements in reliability and efficiency in a radial system.
Therefore, the upgrading of primary feeders from a radial to a
loop configuration has been considered in the Korea Smart Distri-
bution Project. An advanced power distribution system (APDS),
in which primary feeders operate in a loop configuration, has been
explored in this paper. First, the design scheme of a conventional
power distribution system configuration that adopts distribution
automation is introduced. Subsequently, an upgrading scheme of
loop configuration using normally opened tie switches and a tie
switch selection algorithm for loss minimization are described.
KEPCO (Korea Electric Power Cooperation) also published a
Finally, the advantages of the upgraded configuration are reported
through case studies. It is observed that the APDS configuration DG interconnection manual in 2005. In this manual, the capacity
can integrate more REGs from the viewpoint of voltage regulation. of a DG is limited by the voltage level and line configuration.
An advanced distribution system allowing greater use of REGs Table I shows capacity limits of a DG [2].
will be a major contribution to smart grid implementation. The main goal of these DG installment limitations is to keep
Index Terms—Power distribution system configuration, renew- the distribution system voltage within a permissible range. In
able energy generation, smart distribution, voltage regulation. Korean power distribution systems, the distribution voltage is
controlled by an on-load tap changer (OLTC) through the line
drop compensation (LDC) method. In some cases, the high pen-
I. INTRODUCTION
etration of REGs may cause voltage regulation failures [3].
A fault occurrence in a feeder or lateral that is connected

C ONCERNS about global climate change have increased


the penetration of REGs, which are connected to power
distribution systems. The Korean government announced a na-
to an REG leads to its interruption. For stable reclosing oper-
ation and maintenance crew safety, the REGs must detect is-
landing operation and be disconnected within 0.5 s according to
tional objective to increase the share of REGs, which was 2.24% the KEPCO DG interconnecting manual. Furthermore, REGs
in 2006, to 11% by 2030. In general, power distribution sys- should wait 5 min to re-connect after the distribution system
tems are radial in nature. In addition, given their relatively late becomes stable [1], [2]. Therefore, the reliability of the power
development, REGs were not considered in the design phase distribution system is important for REGs as well as for cus-
of current power distribution systems. For these reasons, con- tomers.
necting distributed generation units (i.e., REGs) to the distri- For several decades, the configuration of power distribu-
bution system may cause various interconnection problems in- tion systems has been typically designed in a radial form for
cluding harmonic concerns, system overvoltage, fault coordina- easy control [4], [5]. However, some power utilities such as
tion, increased fault currents, and islanding concerns. To miti- Taipower, Florida Power Company, Hong Kong Electric Com-
gate these problems, the IEEE Std. 1547 for distributed gener- pany, and Singapore Power have adopted normally closed loop
ator (DG) interconnection was published in 2003 [1]. In Korea, configurations to serve their customers with high reliability
[6]–[9]. Loop power distribution systems have the advantages
Manuscript received November 26, 2012; accepted December 09, 2012. Date of reliability and voltage regulation. To accommodate these
of publication February 06, 2013; date of current version February 27, 2013.
strengths, an APDS including loop configuration is being
This work was supported by the Power Generation & Electricity Delivery of
the Korea Institute of Energy Technology Evaluation and Planning (KETEP) developed in the Korea Smart Distribution System Project.
grant funded by the Korea government Ministry of Knowledge Economy (No. In Korea, KEPCO has already adopted a distribution automa-
2009T100200067). Paper no. TSG-00821-2012.
tion system (DAS) with many normally opened tie switches to
S.-M. Cho (corresponding author) is with the Department of Electrical Engi-
neering, Soongsil University, Seoul 156-743, Korea (e-mail: dannyone@ssu.ac. improve reliability [10]. Therefore, without feeders or lateral
kr). extensions, the power distribution system can simply be up-
J.-C. Kim and H.-S. Shin are with the Department of Electrical Engi-
graded to an APDS through tie switch closure. However, to op-
neering, Soongsil University, Seoul 156-743, Korea (e-mail: jckim@ssu.ac.kr;
shs8828@ssu.ac.kr). erate in loop configuration, the protection system should be up-
Digital Object Identifier 10.1109/TSG.2012.2233771 graded as well. All reclosers and circuit breakers (CBs) in the

1949-3053/$31.00 © 2013 IEEE


354 IEEE TRANSACTIONS ON SMART GRID, VOL. 4, NO. 1, MARCH 2013

Fig. 2. Diagram of a conventional LDC voltage regulation method.


Fig. 1. Conventional power distribution configuration in KEPCO.

loop path should detect bi-directional fault currents. Thus, ap-


propriate tie switches are selected to upgrade the radial configu-
ration to a loop configuration with the minimum upgrading cost.
The purpose of this paper is to introduce the advantages of the
APDS, which is being studied in the Korea Smart Distribution
Project, and to propose an algorithm for appropriate tie switch
selection. In section two, the conventional power distribution
system in Korea is described. The basic scheme of an APDS and
the algorithm for tie switch selection are introduced in section
three. In section four, the advantages of the APDS are examined
through a case study.
Fig. 3. Diagram of a conventional LDC voltage regulation method.
II. CONVENTIONAL POWER DISTRIBUTION CONFIGURATION
should reduce momentary interruptions to assure continuous
A. Design Scheme Which Considers Reliability operation of REGs.
The DAS is very useful for reliability enhancement. To min-
B. Voltage Regulation Scheme
imize interruption time, KEPCO has adopted the DAS for de-
termination of fault location, fault isolation, and service restora- Power utilities are required to keep customers’ voltage pro-
tion. A conventional power distribution configuration adopting files on feeders close to the rated value under all load conditions.
the DAS is shown in Fig. 1. In urban areas, the power transformer located in the substation
In the figure, CB, RA, and GA are substation circuit breakers, with an under-load tap changer (ULTC) is the main voltage reg-
automatic reclosers, and remote-controlled switches, respec- ulation equipment. Pole-mounted voltage regulators (PVRs) are
tively. Distribution feeders are normally divided into three additionally installed in rural feeders. A ULTC controlled by the
sections. Each section has one or more normally opened tie LDC method is used to keep the voltage constant at a fictitious
switches for service restoration. For example, if a fault occurs regulation point (FRP) regardless of the magnitude or power
in section two as illustrated in Fig. 2, automatic equipment de- factor of the load. Sending currents and voltages , as
vices which experience a fault current generate a fault indicator shown in Fig. 3, are used to calculate the FRP voltage according
(FI) signal within 30 s. At the same time, RA1 is opened to clear to (1). The power distribution system operator should set up pa-
the fault. Subsequently, by considering the FI message, the rameters such as dead band, time delay, reference voltage, resis-
fault location is determined. Next, GA3 and GA4 are opened to tance , and reactance for automatic voltage regulation
isolate the fault. Finally, RA1 and GA10 or GA6 are closed for [3]–[5].
service restoration. As these processes are completed within 5
min, the DAS is very useful in improving reliability. However, (1)
because the REG interconnected in section three experiences
momentary interruptions, it should be disconnected within 0.5 where
s by an anti-islanding detection function. Furthermore, the
REGs should wait 5 min to re-connect after service restoration Fictitious regulation point (FRP) voltage.
is complete [2], [10] . Sending voltage.
In the conventional power distribution system, a service
restoration scheme using normally opened tie switches is useful Sending current.
for minimizing interruption time. However, REG operation is Resistance of a feeder from ULTC to FRP.
sensitive to momentary interruptions due to anti-islanding de-
Reactance of a feeder from ULTC to FRP.
tection. Therefore, the service restoration process in an APDS
KIM et al.: ADVANCED POWER DISTRIBUTION SYSTEM CONFIGURATION FOR SMART GRID 355

In Korean power distribution systems, a power transformer


bank has 6 to 8 feeders. The voltage of the feeders depends on
the ULTC at the power transformer. If the load imbalance be-
tween feeders exceeds an acceptable range, voltage regulation
using only ULTC may fail. Furthermore, if many REGs are con-
nected to the feeders, LDC detects sending currents that are less
than the actual values. The output of REGs depends on weather
conditions such as wind, solar radiation, and temperature, and is
therefore uncontrollable. For this reason, it becomes more diffi-
cult for the distribution system operator to predict the load bal-
ance in advance as the penetration of REGs increases. There-
fore, high penetration of REGs may cause voltage regulation
failures [3].

III. ADVANCED POWER DISTRIBUTION CONFIGURATION

A. Basic Scheme
The configuration of a conventional power distribution
system is radial because of its simplicity. However, as men-
tioned above, the upgrading of primary feeders is needed
because there are numerous problems for a radial structure to
accommodate many REGs. In Korea, primary feeders have
at least three normally opened tie switches. By closing the
Fig. 4. Flowchart of loop path selection algorithm for loss minimization.
opened tie switches, the radial distribution configuration can
be upgraded to a loop structure without installing additional
electric power lines. Fig. 3 shows the upgrading scheme of an Step 2) Carry out power flow analysis for 24 h.
ADPS, which includes a loop feeder structure as an example. Step 3) Calculate accumulated switch voltage (ASV) for all
If tie switch GA4 is closed, feeder1 and feeder2 form a loop tie switches according to (2).
structure. In this case, other tie switches should be opened to
avoid a mesh structure. Although additional electric power (2)
lines do not need to be installed, the protection devices should
be upgraded to operate the power distribution system in a
loop structure. Therefore, the optimum tie switches should be where
selected to maximize the profits of ADPS upgrading for the
Tie switch number.
loop structure.
Hours.
B. Loop Configuration Selection Algorithm for Loss
Open voltage of switch n at hour h.
Minimization
Step 4) If all ASV calculations for tie switches are com-
Load imbalance between feeders increases loss in the power pleted, calculate the total ASV according to (3) for
distribution system. In a radial structure, network reconfigura- each case.
tion is used for load imbalance alleviation, loss minimization
and others [11]. However, in a loop structure, a loop path con- (3)
necting a heavily loaded feeder and a lightly loaded feeder can
alleviate the load imbalance to minimize loss. Step 5) Select the case with the maximum total ASV for loss
The voltage drop in a heavily loaded feeder is larger than that minimization.
in lightly loaded feeders. Therefore, by considering the voltage
across the opened tie switch, we can infer which side of the
IV. CASE STUDY
tie switch is the heavily loaded feeder. If the voltage across an
opened tie switch is high, loop operation using the tie switch In this section, we compared the conventional radial structure
is more effective for loss minimization. Therefore, we present and the APDS loop structure to explore the advantages of the
a loop path selection algorithm using the voltage across open APDS from the perspective of loss reduction and voltage profile.
tie switches. The loop path selection algorithm considers a 24 h The conventional Korean power distribution system adopting
load profile because the output is for representing stable rather the DAS, which is shown in Fig. 5, is used as the test distribu-
than temporary states. A flowchart of the loop path selection tion system model [12]. In the test model, there are four feeders
algorithm for loss minimization is shown in Fig. 4. and six normally opened tie switches. There are three available
The loop path selection algorithm is as follows. cases for upgrading the primary feeder from a radial to a loop
Step 1) Generate tie switch cases for loop configuration. configuration. All test cases are summarized in Table II. Case 1
356 IEEE TRANSACTIONS ON SMART GRID, VOL. 4, NO. 1, MARCH 2013

Fig. 5. Conventional Korea power distribution system adopting DAS.

TABLE II
TEST CASES FOR CASE STUDY

Fig. 7. Losses during 24 h in the test distribution system model.

A. Loss Reduction Study


Power flow analysis was performed for loss analysis using the
cases summarized in Table II. Fig. 7 shows the losses accumu-
lated during 24 h for each case. Upgrading to case 3, in which
the loss is reduced from 6.74 to 6.42 MWh, is the best solution
for loss minimization. However, to compare loss reduction be-
tween cases, power flow analysis should be conducted for each
case. Yet if there are more tie switches, the processing time will
increase. Therefore, to compare loss reduction more efficiently,
we applied the proposed loop path selection algorithm to test the
Fig. 6. Load profile of each feeder in the test distribution system model.
power distribution system model. In the radial case, the ASVs
for each tie switch calculated by (2) are shown in Fig. 8.
involves a radial structure and cases 2, 3, and 4 involve a loop The total ASVs for each case are summarized in Table III.
structure. The total ASV is highest in case 3. Therefore, this case is the
Each feeder supports electric power of various loads for res- best loop-upgrading solution for loss minimization. This shows
idential, commercial, and industrial customers. Most load pro- that we can select a loop-upgrading path without conducting
files depend on the type of customer. Fig. 6 shows feeder load power flow analysis for each case.
profiles in the test model. Feeder 3 shows a relatively light load
throughout the day. Alternatively, feeders 1 and 2 show a heavy B. Voltage Control Study
load. The load profiles are derived from actual load patterns in Voltage regulation in the test power distribution system
Korea. model mainly depends on ULTC control by the LDC method.
KIM et al.: ADVANCED POWER DISTRIBUTION SYSTEM CONFIGURATION FOR SMART GRID 357

Fig. 8. ASV for each tie switch. Fig. 10. Maximum and minimum voltages with REGs of case 1 and case 3.

TABLE III 2) The robustness of voltage regulation in the loop structure


CALCULATED TOTAL ASV allows the APDS to accommodate more REGs than the
radial structure.
3) The proposed loop path selection algorithm gives the best
solution for loss minimization using only a power flow
analysis of the radial system.
Coordination of protection using communication technology
may permit the upgrading of primary feeders from radial to loop
configurations. We expect the APDS presented here to support
a more suitable environment for high penetration of REGs in
smart grids.

APPENDIX
The line impedance and load profiles of the test power dis-
tribution system used in the case study are listed in Tables IV
and V, respectively. All per units are based on 22.9 kV and 100
MVA. All power factors are 0.9.
Fig. 9. Maximum and minimum voltage profiles for case 1 and case 3.
TABLE IV
Maximum and minimum voltage profiles for cases 1 and 3 are LINE IMPEDANCE
compared in Fig. 9. The difference between the maximum and
minimum voltages for case 3 is narrower than that for case 1
(radial). Therefore, voltage regulation is easier in case 3.
The voltage regulation of power distribution systems in
which many REGs are interconnected may fail. Therefore, we
compared the robustness of voltage regulation between cases
1 and 3. The REGs were interconnected at line sections F2–5,
F3–6, and F4–14, respectively. Subsequently, we changed the
generation capacity from 1 to 10 MW. The maximum and
minimum voltages in the test power distribution system are
shown in Fig. 10. In case 1, undervoltage occurred because
the LDC method failed as a result of the 24 MW generated by
the REGs. In contrast, in case 3, the power distribution system
could accommodate the 30 MW generated by the REGs within
a permissible voltage range.

V. CONCLUSION
In this paper, we analyzed the advantages of an APDS loop
structure from the perspective of loss reduction and voltage reg-
ulation. In addition, we presented a loop path selection algo-
rithm for loss minimization. The results of case studies using
the test power distribution system are summarized as follows:
1) Appropriate upgrading of primary feeders from a radial to
a loop configuration reduces loss in the power distribution
system
358 IEEE TRANSACTIONS ON SMART GRID, VOL. 4, NO. 1, MARCH 2013

TABLE V [7] T. C. Yu, Principles and Design of Low Voltage Systems. Singapore:
AVERAGE LOAD AT END OF LINE SECTION Byte Power Publ., 1996, pp. 13–14.
[8] W. T. Huang, T. H. Chen, G. C. Pu, Y. F. Hsu, and T. Y. Guo, “As-
sessment of upgrading existing primary feeders from radial to nor-
mally closed loop arrangement,” in Proc. 2002 IEEE Power Eng. Soc.
Transm. Distrib. Conf., pp. 2123–2128.
[9] T. H. Chen, W. T. Huang, J. C. Gu, G. C. Pu, Y. F. Hsu, and T. Y. Guo,
“Feasibility study of upgrading primary feeders from radial and open-
loop to normally closed-loop arrangement,” IEEE Trans. Power Syst.,
vol. 19, no. 3, pp. 1308–1316, 2004.
[10] N.-G. James, Robert Wilson, Control and Automation of Electrical
Power Distribution Systems. Boca Raton, FL, USA: CRC, 2006.
[11] S. M. Cho, H. S. Shin, J. H. Park, and J. C. Kim, “Distribution system
reconfiguration considering customer and DG reliability cost,” J. Elect.
Eng. Technol., vol. 7, no. 4, Jul. 2012.
[12] H. T. Lee, “A study on the reliability analysis of loop power distribu-
tion systems with microgrid structure,” Ph.D. dissertation, Dept Electr.
Eng., Soongsil Univ., Seoul, Korea, 2009.

Jae-Chul Kim (M’84) received the B.S. degree from Soongsil University,
Korea, in 1979, and M.S. and Ph.D. degrees from Seoul National University,
Korea, in 1983 and 1987, respectively.
He has been a professor of Electrical Engineering at Soongsil University since
1988. His research interests include power system reliability, smart distribution
systems, and smart grids.

REFERENCES
[1] IEEE Standard for Interconnecting Distributed Resources With Elec-
tric Power Systems, IEEE Std. 1547-2003. Sung-Min Cho (S’08–M’13) received the B.S., M.S. and Ph.D. degrees in elec-
[2] Korea Electric Power Co., A Guide to the Distributed Generation In- trical engineering from Soongsil University, Korea, in 2003, 2008 and 2012, re-
terconnection to Distribution System 2005. spectively.
[3] J.-H. Choi and J.-C. Kim, “Advanced voltage regulation method of Currently, he is a Postdoctoral Researcher with Soongsil University. His re-
power distribution systems interconnected with dispersed storage and search interests include power system reliability, smart distribution systems, and
generation systems (Revised),” IEEE Trans. Power Del., vol. 16, no. distributed generation interconnection.
2, pp. 329–334, Apr. 2001.
[4] T. A. Short, Electric Power Distribution Handbook. Boca Raton, FL,
USA: CRC, 2004.
[5] T. Gonen, Electric Power Distribution System. New York, NY, USA: Hee-Sang Shin received the B.S. and M.S. degrees in electrical engineering
McGraw-Hill, 1986. from Soongsil University, Korea, in 2007 and 2009, respectively. Currently, he
[6] B. Pagel, “Energizing international drive,” Transm. Distrib. World, pp. is working toward the Ph.D. degree at Soongsil University Graduate School.
18–34, Apr. 2000. His research interests include smart distribution systems, and electric railways.

Das könnte Ihnen auch gefallen