Technical data
Auxiliary circuit
Ratings of the auxiliary contacts acc. to IEC 60 947-5-1/
EN 60 947-5-1 (VDE 0660 Part 200)
The data is valid for integrated auxiliary contacts and contacts
in the auxiliary switch blocks for contactor sizes S00 to S12
Rated insulation voltage Ui (pollution degree 3) V 690
For laterally mountable 3RH19 21-.EA . . and 3RH19 21-.KA . .
auxiliary switch blocks V max. 500
10
The contact endurance is mainly dependent on the breaking Basic unit
5
current. 4 with snap-
3 on block
The characteristic curves apply to: 2
Integrated auxiliary contacts for 3RT10 DC-13 DC-13
1 220 V 110 V
3RH19 11 or 3RH19 21 auxiliary switch blocks for contactor AC-15/AC-14
0,5
sizes S00 to S12.
DC-13
24 V
0,1
0,05
1)
0,01
0,01 0,03 0,05 0,1 0,3 0,5 1 2 3 5 6 7 10 Ia (A)
I e -DC-13 I e -DC-13 I e -AC-15 I e -DC-13
220 V 110 V < 230 V 24 V
Legend:
Ia = Breaking current
Ie = Rated operational current
1) DC-13: Snap-on auxiliary switch blocks 2) With laterally mountable auxiliary switch blocks,
for size S00: 6 A. making/breaking capacity only up to 500 V.
Technical data
230 V
500 V
690 V
400 V
resistive and inductive three- Contactor type 3RT1015 3RT1016, 3RT1017
phase loads (AC-1/AC-3), (3 kW) (4 kW, 5,5 kW)
10 7
depending on the breaking cur- 10 7 8 6 8 NSB00473a
rent and the rated operational 8 6 6
4
voltage. It is assumed that the 6 4 4
operating mechanisms are 4 2
switched randomly, i.e. not syn- 2 2
chronized with the phase angle 2 10 6
10 6 8 10 6
of the supply system.
10 6 8 6 8
The rated operational current Ie 8 6 6
4
for the AC-4 utilization category 6 4 4
(breaking six times the rated 4 2
operational current) is designed 2 2
for a contact endurance of at 2 10 5
5
least 200 000 operating cycles. 10 8 10 5
10 5 8 6 8
If a shorter endurance is suffi- 8 6
4 6
cient, the rated operational cur- 6 4 4
rent Ie/AC-4 can be increased. 4 2
For mixed operation, i.e. nor- 2 2
mal switching (breaking the 2 10 4
rated operational current 10 4 8 10 4
according to the AC-3 utiliza- 2 3 4 5 6 8 10 20 I a (A) 40 50 60 80
tion category) in combination 7 9 12 I e (A)
with intermittent inching (break-
ing several times the rated 3 4 5,5 PN (kW)
operational current according
to the AC-4 utilization cate-
gory), the contact endurance
can be calculated approxi-
mately from the following equa-
tion:
A Size S0
X = --------------------------------------------------------
C A
1 + ---------- ---- – 1 Operating cycles at
100 B
230 V
500 V
690 V
400 V
Technical data
230 V
500 V
690 V
400 V
230 V
500 V
690 V
400 V
Contactor type 3RT1034 3RT1035 3RT1036 Contactor type 3RT1044 3RT1045 3RT1046
(15 kW) (18.5 kW) (22 kW) (30 kW) (37 kW) (45 kW)
10 7 10 7
10 7 8 6 8 NSB00475a 10 7 8 6 8 NSB00476a
8 6 4 6 8 6 4 6
6 4 4 6 4 4
4 2 4 2
2 2 2 2
2 6 6
6 10 2 10
6 6 6
6
10 10 8 10 10 8
6
10 8 8 6 10 8 8 6
8 6 6 4 8 6 6 4
6 4 4 6 4 4
4 2 4 2
2 2 2 2
2 5 2 5
5 10 5 5 10
5
10 8 10 10 8 10
5
10 5
8 6 8 10 8 6 8
8 6 4 6 8 6 4 6
6 4 4 6 4 4
4 2 4 2
2 2 2 2
2 10
4 2 10
4
10 4 8 10 4 10 4 8 10 4
10 20 30 40 50 60 80 100 Ia(A) 200 300 400 10 20 30 40 50 60 80 100 Ia (A) 200 300 400 600
32 40 50 Ie (A) 65 80 95 Ie (A)
15 18,5 22 PN (kW) 30 37 45 PN (kW)
Sizes S6 to S12
Operating cycles at
230 V
500 V
690 V
400 V
500 V
690 V
400 V
Technical data
NSB00478
on a vertical mounting surface.
NSB00477
AC operation Special design required.
Positions 13 to 16 of the Order No. must be changed to -1AA0.
Additional charge.
DC operation Standard design
Positively driven operation 3RT10 1 ., 3RT13 1 . Yes, both in the basic unit and auxiliary switch block and between
There is positively driven operation if the NC and (removable aux. switch block) the basic unit and mounted auxiliary switch block acc. to ZH 1/457,
NO contacts cannot be closed at the same time IEC 60 947-4-1, Annex H (draft 17B/996/DC)
The 3RH19 11- .NF. . solid-state compatible 3RT10 1 ., 3RT13 1 . Yes, both in the basic unit and auxiliary switch block and between
auxiliary switch blocks have no positively driven (permanent aux. switch block) the basic unit and mounted auxiliary switch block acc. to ZH 1/457,
contacts IEC 60 947-4-1, Annex H (draft 17B/996/DC), Swiss regulations
(SUVA)
Degree of protection acc. to IEC 60 947-1 and DIN 40 050 IP 20, coil system IP 40
Auxiliary circuit
Fuse links, utilization category gL/gG A 10
DIAZED Type 5SB, NEOZED Type 5SE (weld-free protection at Ik ≥ 1 kA)
or miniature circuit-breaker (up to 230 V) with C-characteristic A 6
(short-circuit current Ik < 400 A)
1) According to excerpt from IEC 60 947-4-1 Type of coordination "2": 2) Test conditions acc. to IEC 60 947-4-1.
(VDE 0660 Part 102): No damage can be tolerated to the overload
Type of coordination "1": relay, but contact welding on the contactor is
Destruction of the contactor and the overload permitted if the contacts can be easily separa-
relay is permissible. The contactor and/or over- ted.
load relay must be replaced if necessary.
Technical data
Power consumption of the coils (with coil in cold state and 1.0 × Us) Standard design For USA and Canada
AC operation Hz 50/60 50 60
closing VA 27 /24.3 26.4 31.7
p.f. 0.8 / 0.75 0.81 0.77
closed VA 4.4 / 3.4 4.7 5.1
p.f. 0.27/ 0.27 0.26 0.27
DC operation closing = closed W 3.3
Permissible residual current of the electronics (with 0 signal) The 3RT19 16-1GA00 additional load
AC operation mA < 3 mA x 230
-----------
V
module is recommended for higher residual
Us currents, see accessories
< 10 mA x ---------
24 V
DC operation mA
Us
Operating times 1)
Break-time = opening time + arcing time
AC operation closing time ms 8 ... 35
at 0.8 ... 1.1 × Us opening time ms 4 ... 30
DC operation closing time ms 25 ... 100
at 0.85 ... 1.1 × Us opening time ms 7 ... 10
Arcing time ms 10 ... 15
1) The opening times of the NO contacts and the 2) Industrial furnaces and electric heaters with 3) Acc. to VDE 0660 Part 102.
closing times of the NC contacts increase if the resistance heating, for example (higher For rated values for various
contactor coils are protected against voltage current input allowed for during heating up). starting conditions, see Part 4.
peaks (suppression diode 6 to 10 times, diode
assemblies 2 to 6 times, varistor +2 to 5 ms).
Technical data
Technical data
For tool for opening the Cage Clamp connection, see accessories on page 3/52.
An "insulation stop" must be used for conductor cross-sections ≤ 1 mm2, see accessories on page 3/52.
Max. outer diameter of conductor insulation: 3.6 mm.
For information about Cage Clamp connections, see page 4.
Technical data
Contactor Size S0
Type 3RT10 2.
General data
Permissible mounting position AC and DC operation 360° 22,5° 22,5°
The contactors are designed for operation
NSB00478
on a vertical mounting surface.
NSB00477
Upright mounting position:
Contactor Size S0 S0
Type 3RT10 23, 3RT10 24, RT10 25 3RT10 26
Short-circuit protection of contactors without overload For short-circuit protection of contactors with overload relays, see
Part 4.
For short-circuit protection of weld-free contactors, see Part 5.
(overload and short-circuit protection only with 3RV10 circuit-
breaker).
For short-circuit protection of fuseless load feeders, see Part 5.
Main circuit
Fuse links, utilization category gL/gG
NH Type 3NA, DIAZED Type 5SB, NEOZED Type 5SE
With fuse links
– acc. to IEC 60 947-4-1/EN 60 947-4-1 Type of coord. "1" 1) A 63 100
Type of coord. "2" 1) A 25 35
Weld-free 2) A 10 16
or miniature circuit-breaker with C-characteristic A 25 32
(short-circuit current 3 kA, type of coordination "1") 1)
Auxiliary circuit
Fuse links, utilization category gL/gG A 10 10
DIAZED Type 5SB, NEOZED Type 5SE (weld-free protection at Ik ≥ 1 kA)
or miniature circuit-breaker with C-characteristic A 10 10
(short-circuit current Ik < 400 A)
1) According to excerpt from Type of coordination "2": 2) Test conditions acc. to IEC 60 947-4-1.
IEC 60 947-4-1 (VDE 0660 Part 102): No damage can be tolerated to the overload relay, For 3RT11 weld-free contactors, see Part 5
Type of coordination "1": but contact welding on the contactor is permitted if (overload and short-circuit protection only with
Destruction of the contactor and the overload the contacts can be easily separated. 3RV10 circuit-breaker).
relay is permissible. The contactor and/or over-
load relay must be replaced if necessary.
Technical data
Contactor Size S0
Type 3RT10 2.
Control circuit
Coil voltage tolerance AC/DC 0.8 ... 1.1 × Us
Power consumption of the coils (with coil in cold state and 1.0 × Us) Standard design For USA and Canada
AC operation Hz 50 50/60 50 60
closing VA 61 64 /63 61 69
p.f. 0.82 0.72/ 0.74 0.82 0.76
closed VA 7.8 8.4 / 6.8 7.8 7.5
p.f. 0.24 0.24/ 0.28 0.24 0.28
DC operation closing = closed W 5.4
Contactor Size S0 S0 S0 S0
Type 3RT10 23, 3RT10 23, 3RT10 25 3RT10 26
3RT10 23 3RT10 24
Main circuit
Load ratings with AC
AC-1 utilization category, switching resistive load
Rated operational currents Ie at 40 °C up to 690 V A 40
at 60 °C up to 690 V A 35
Ratings at 230 V kW 13.3
of three-phase loads 2) 400 V kW 23
p.f. = 0.95 (at 60 °C) 500 V kW 29
690 V kW 40
Minimum conductor cross-section with Ie load at 40 °C mm2 10
60 °C mm2 10
AC-2 and AC-3 utilization categories
Rated operational currents Ie up to 400 V A 9 12 17 25
500 V A 6.5 12 17 18
690 V A 5.2 9 13 13
Ratings of slipring or squirrel-cage at 110 V kW 1.1 1.5 2.2 3
motors at 50 Hz and 60 Hz 230 V kW 3 3 4 5.5
400 V kW 4 5.5 7.5 11
500 V kW 4.5 7.5 10 11
660/690 V kW 5.5 7.5 11 11
Thermal loading capacity 10 s current 3) A 80 110 150 200
Power loss per conducting path at Ie/AC-3 W 0.4 0.5 0.9 1.6
1) The opening times of the NO contacts and the 2) Industrial furnaces and electric heaters with 3) Acc. to VDE 0660 Part 102.
closing times of the NC contacts increase if the resistance heating, for example (higher current For rated values for various starting conditions,
contactor coils are protected against voltage input allowed for during heating up). see Part 4.
peaks (varistor +2 ms to 5 ms, diode assem-
blies: 2 to 6 times).
Technical data
Contactor Size S0 S0 S0 S0
Type 3RT10 23 3RT10 23 3RT10 25 3RT10 26
Main circuit
Load ratings with AC
AC-4 utilization category (at Ia = 6 × Ie)
Rated operational current Ie up to 400 V A 8.5 12.5 15.5 15.5
Ratings of squirrel-cage motors at 400 V kW 4 5.5 7.5 7.5
at 50 Hz and 60 Hz
For a contact endurance of approx. 200 000 operating cycles:
Rated operational currents Ie up to 400 V A 4.1 5.5 7.7 9
690 V A 3.3 5.5 7.7 9
Ratings of squirrel-cage motors at 110 V kW 0.5 0.73 1 1.2
at 50 Hz and 60 Hz 230 V kW 1.1 1.5 2 2.5
400 V kW 2 2.6 3.5 4.4
500 V kW 2 3.3 4.6 5.6
690 V kW 2.5 4.6 6 7.7
AC-5a utilization category, switching gas discharge lamps
per main conducting path at 230 V 1)
Rating Rated operational
per lamp current per lamp (A)
uncorrected
L 18 W 0.37 units 95
L 36 W 0.43 units 81
L 58 W 0.67 units 52
lead-lag
L 18 W 0.11 units 318
L 36 W 0.21 units 166
L 58 W 0.32 units 109
Switching gas discharge lamps with correction, electronic ballast
per main conducting path at 230 V
Rating Capacitor Rated operational
per lamp (µF) current per lamp (A)
Parallel correction
L 18 W 4.5 0.11 units 37 61
L 36 W 4.5 0.21 units 37 61
L 58 W 7 0.32 units 23 39
With electronic ballast,
single lamp
L 18 W 6.8 0.10 units 105 105
L 36 W 6.8 0.18 units 58 97
L 58 W 10 0.27 units 38 64
With electronic ballast,
twin lamp
L 18 W 10 0.18 units 58 97
L 36 W 10 0.35 units 30 50
L 58 W 22 0.52 units 20 33
AC-5b utilization category, switching incandescent lamps
per main conducting path at 230/220 V kW 3 4
Technical data
Contactor Size S0 S0
Type 3RT10 23, 3RT10 24, 3RT10 25 3RT10 26
Main circuit
Load ratings with DC
DC-1 utilization category,
switching resistive load (L/R ≤ 1 ms)
Rated operational current Ie (at 60 °C)
Number of conducting paths connected in series 1 2 3
up to 24 V A 35 35 35
60 V A 20 35 35
110 V A 4.5 35 35
220 V A 1 5 35
440 V A 0.4 1 2.9
600 V A 0.25 0.8 1.4