Contactors and Contactor Assemblies

SIRIUS Contactors for Switching Motors


3RT1 contactors
Contac tors and Contactor Assemblies

Technical data

Contactor Sizes S00 to S12

Auxiliary circuit
Ratings of the auxiliary contacts acc. to IEC 60 947-5-1/
EN 60 947-5-1 (VDE 0660 Part 200)
The data is valid for integrated auxiliary contacts and contacts
in the auxiliary switch blocks for contactor sizes S00 to S12
Rated insulation voltage Ui (pollution degree 3) V 690
For laterally mountable 3RH19 21-.EA . . and 3RH19 21-.KA . .
auxiliary switch blocks V max. 500

Conventional thermal current Ith =


rated operational current Ie/AC-12 A 10

Load ratings with AC


Rated operational current Ie/AC-15/AC-14
at rated operational voltage Ue 24 V A 6
110 V A 6
125 V A 6
220 V A 6
230 V A 6
380 V A 3
400 V A 3
500 V A 2
660 V 2) A 1
690 V 2) A 1

Load ratings with DC


Rated operational current Ie/DC-12
at rated operational voltage Ue 24 V A 10
60 V A 6
110 V A 3
125 V A 2
220 V A 1
440 V A 0.3
600 V 2) A 0.15

Rated operational current Ie/DC-13


at rated operational voltage Ue 24 V A 10 1)
60 V A 2
110 V A 1
125 V A 0.9
220 V A 0.3
440 V A 0.14
600 V 2) A 0.1

Contact reliability at 17 V, 1 mA Frequency of contact faults < 10–8


acc. to IEC 60 947-5-4 i.e. less than 1 fault per 100 million operating cycles
Endurance of the auxiliary contacts
It is assumed that the operating mechanisms are switched ran- 30
NSB00472
domly, i. e. not synchronized with the phase angle of the supply
Basic unit
system.
Million operating cycles (10 6 )

10
The contact endurance is mainly dependent on the breaking Basic unit
5
current. 4 with snap-
3 on block
The characteristic curves apply to: 2
Integrated auxiliary contacts for 3RT10 DC-13 DC-13
1 220 V 110 V
3RH19 11 or 3RH19 21 auxiliary switch blocks for contactor AC-15/AC-14
0,5
sizes S00 to S12.
DC-13
24 V
0,1
0,05

1)
0,01
0,01 0,03 0,05 0,1 0,3 0,5 1 2 3 5 6 7 10 Ia (A)
I e -DC-13 I e -DC-13 I e -AC-15 I e -DC-13
220 V 110 V < 230 V 24 V

Legend:
Ia = Breaking current
Ie = Rated operational current

1) DC-13: Snap-on auxiliary switch blocks 2) With laterally mountable auxiliary switch blocks,
for size S00: 6 A. making/breaking capacity only up to 500 V.

Siemens NS K · 2002 3/85


Contactors and Contactor Assemblies
Contactors for Switching Motors SIRIUS
3RT1 contactors

Technical data

Endurance of the main contacts


The characteristic curves show Size S00
the contact endurance of the Operating cycles at
contactors when used to switch

230 V

500 V

690 V

400 V
resistive and inductive three- Contactor type 3RT1015 3RT1016, 3RT1017
phase loads (AC-1/AC-3), (3 kW) (4 kW, 5,5 kW)
10 7
depending on the breaking cur- 10 7 8 6 8 NSB00473a
rent and the rated operational 8 6 6
4
voltage. It is assumed that the 6 4 4
operating mechanisms are 4 2
switched randomly, i.e. not syn- 2 2
chronized with the phase angle 2 10 6
10 6 8 10 6
of the supply system.
10 6 8 6 8
The rated operational current Ie 8 6 6
4
for the AC-4 utilization category 6 4 4
(breaking six times the rated 4 2
operational current) is designed 2 2
for a contact endurance of at 2 10 5
5
least 200 000 operating cycles. 10 8 10 5
10 5 8 6 8
If a shorter endurance is suffi- 8 6
4 6
cient, the rated operational cur- 6 4 4
rent Ie/AC-4 can be increased. 4 2
For mixed operation, i.e. nor- 2 2
mal switching (breaking the 2 10 4
rated operational current 10 4 8 10 4
according to the AC-3 utiliza- 2 3 4 5 6 8 10 20 I a (A) 40 50 60 80
tion category) in combination 7 9 12 I e (A)
with intermittent inching (break-
ing several times the rated 3 4 5,5 PN (kW)
operational current according
to the AC-4 utilization cate-
gory), the contact endurance
can be calculated approxi-
mately from the following equa-
tion:
A Size S0
X = --------------------------------------------------------
C A
1 + ---------- ---- – 1 Operating cycles at
100  B 
230 V

500 V

690 V

400 V

Contactor type 3RT1023 3RT1024 3RT1025 3RT1026


Where: (4 kW) (5,5 kW) (7,5 kW) (11 kW)
X Contact endurance for mixed opera- 10 7
10 7 8 6 8 NSB00474a
tion in operating cycles 6
8 4 6
A Contact endurance for normal ope- 6 4 4
ration (Ia = Ie) in operating cycles
4 2
B Contact endurance for inching (Ia =
2 2
multiple of Ie) in operating cycles
2 10 6
C Inching operations as a percentage 10 6 8 10 6
of total switching operations 10 6 8 6 8
8 6 6
4
6 4 4
4 2
2 2
2 10 5
5
10 8 10 5
10 5 8 6 8
8 6 6
4
6 4 4
4 2
Legend: 2 2
PN = Ratings of 2 10 4
4
three-phase motors with 10 8 10 4
squirrel-cage rotor at 400 V 3 4 5 6 8 10 20 30 40 50 60 80 100 Ia(A)
Ia = Breaking current 9 12 17 25 Ie(A)
Ie = Rated operational current
4 11 PN(kW)

3/86 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Switching Motors
3RT1 contactors

Technical data

Endurance of the main contacts


Size S2 Size S3
Operating cycles at Operating cycles at

230 V

500 V

690 V

400 V
230 V

500 V

690 V

400 V

Contactor type 3RT1034 3RT1035 3RT1036 Contactor type 3RT1044 3RT1045 3RT1046
(15 kW) (18.5 kW) (22 kW) (30 kW) (37 kW) (45 kW)
10 7 10 7
10 7 8 6 8 NSB00475a 10 7 8 6 8 NSB00476a
8 6 4 6 8 6 4 6
6 4 4 6 4 4
4 2 4 2
2 2 2 2
2 6 6
6 10 2 10
6 6 6
6
10 10 8 10 10 8
6
10 8 8 6 10 8 8 6
8 6 6 4 8 6 6 4
6 4 4 6 4 4
4 2 4 2
2 2 2 2
2 5 2 5
5 10 5 5 10
5
10 8 10 10 8 10
5
10 5
8 6 8 10 8 6 8
8 6 4 6 8 6 4 6
6 4 4 6 4 4
4 2 4 2
2 2 2 2
2 10
4 2 10
4
10 4 8 10 4 10 4 8 10 4
10 20 30 40 50 60 80 100 Ia(A) 200 300 400 10 20 30 40 50 60 80 100 Ia (A) 200 300 400 600
32 40 50 Ie (A) 65 80 95 Ie (A)
15 18,5 22 PN (kW) 30 37 45 PN (kW)

Sizes S6 to S12
Operating cycles at
230 V

500 V

690 V

400 V

Contactor 3RT1054 3RT1055 3RT1056 3RT1064 3RT1065 3RT1066 3RT1075 3RT1076


type (55 kW) (75 kW) (90 kW) (110 kW) (132 kW) (160 kW) (200 kW) (250 kW)
10 7
10 7 8 6 8 NSB01141
8 6 4 6
6 4 4
4 2
2 2
2 6
6 10 6
6
10 8 10
10 8 6 8
8 6 4 6
6 4 4
4 2
2 2
2 5
5 10 5
5
10 8 10
10 8 6 8
8 6 4 6
6 4 4
4 2
2 2
2 10
4
10 4 8 10 4
10 20 30 40 50 60 80 100 200 300 400 600 8001000 Ia(A) 2000 3000

55 90 132 200 PN (kW)


75 110 160 250
3RT12 vacuum contactors
Sizes S10 and S12
Operating cycles at
230 V

500 V

690 V

400 V

Contactor type 3RT1264 3RT1265 3RT1266 3RT1275 3RT1276


(110 kW) (132 kW) (160 kW) (200 kW) (250 kW)
7 10 7
10 8 6 8 NSB01142
8 6 4 6
6 4 4
4 2
2 2
2 6
6 10
10 8 6
6 10
10 8 6 8
8 6 4 6
6 4 4
4 2
2 2
2 5
5 10
5
10 8 10 5
10 8 6 8
8 6 4 6
6 4 4
4 2
2 2
Legend:
2 10
4 PN = Ratings of
10 4 8 10 4 three-phase motors with
40 50 60 80 100 200 300 400 600 800 1000 Ia(A) 2000 3000 squirrel-cage rotor at 400 V
Ia = Breaking current
110 160 250 PN (kW)
132 200 Ie = Rated operational current

Siemens NS K · 2002 3/87


Contactors and Contactor Assemblies
Contactors for Switching Motors SIRIUS
3RT1. 1. contactors

Technical data

Contactor Size S00


Type 3RT1. 1.
General data
Permissible mounting position AC and DC operation 360° 22,5° 22,5°
The contactors are designed for operation

NSB00478
on a vertical mounting surface.

Upright mounting position:

NSB00477
AC operation Special design required.
Positions 13 to 16 of the Order No. must be changed to -1AA0.
Additional charge.
DC operation Standard design

Mechanical Basic units Oper. 30 million


endurance Basic unit with snap-on auxiliary switch block cycles 10 million
Solid-state compatible aux. switch block 5 million
Electrical endurance See page 3/86

Rated insulation voltage Ui (pollution degree 3) V 690

Rated impulse withstand voltage Uimp kV 6

Safe isolation between coil and main contacts V 400


(acc. to DIN VDE 0106 Part 101 and A1 [draft 2/89])

Positively driven operation 3RT10 1 ., 3RT13 1 . Yes, both in the basic unit and auxiliary switch block and between
There is positively driven operation if the NC and (removable aux. switch block) the basic unit and mounted auxiliary switch block acc. to ZH 1/457,
NO contacts cannot be closed at the same time IEC 60 947-4-1, Annex H (draft 17B/996/DC)
The 3RH19 11- .NF. . solid-state compatible 3RT10 1 ., 3RT13 1 . Yes, both in the basic unit and auxiliary switch block and between
auxiliary switch blocks have no positively driven (permanent aux. switch block) the basic unit and mounted auxiliary switch block acc. to ZH 1/457,
contacts IEC 60 947-4-1, Annex H (draft 17B/996/DC), Swiss regulations
(SUVA)

Permissible ambient temperature in operation °C –25 ... +60


when stored °C –55 ... +80

Degree of protection acc. to IEC 60 947-1 and DIN 40 050 IP 20, coil system IP 40

Shock resistance Rectangular pulse AC operation g/ms 7/5 and 4.2/10


DC operation g/ms 7/5 and 4.2/10
Sine pulse AC operation g/ms 9.8/5 and 5.9/10
DC operation g/ms 9.8/5 and 5.9/10

Conductor cross-sections See page 3/91


Short-circuit protection of contactors without overload relays For short-circuit protection and contactors with overload relays, see
Part 4.
For short-circuit protection of fuseless load feeders, see Part 5.
Main circuit
Fuse links, utilization category gL/gG
NH Type 3NA, DIAZED Type 5SB, NEOZED Type 5SE
– acc. to IEC 60 947-4-1/EN 60 947-4-1 Type of coord. "1" 1) A 35
Type of coord. "2" 1) A 20
Weld-free 2) A 10
or miniature circuit-breaker (up to 230 V) with C-characteristic A 10
(short-circuit current 1 kA, type of coordination "1" 1)

Auxiliary circuit
Fuse links, utilization category gL/gG A 10
DIAZED Type 5SB, NEOZED Type 5SE (weld-free protection at Ik ≥ 1 kA)
or miniature circuit-breaker (up to 230 V) with C-characteristic A 6
(short-circuit current Ik < 400 A)

1) According to excerpt from IEC 60 947-4-1 Type of coordination "2": 2) Test conditions acc. to IEC 60 947-4-1.
(VDE 0660 Part 102): No damage can be tolerated to the overload
Type of coordination "1": relay, but contact welding on the contactor is
Destruction of the contactor and the overload permitted if the contacts can be easily separa-
relay is permissible. The contactor and/or over- ted.
load relay must be replaced if necessary.

3/88 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Switching Motors
3RT1. 1. contactors

Technical data

Contactor Size S00


Type 3RT1. 1.
Control circuit
Coil voltage tolerance AC at 50 Hz: 0.8 ... 1.1 × Us
at 60 Hz: 0.85 ... 1.1 × Us
DC up to +50 °C:0.8 ... 1.1 × Us
at +60 °C: 0.85 ... 1.1 × Us

Power consumption of the coils (with coil in cold state and 1.0 × Us) Standard design For USA and Canada
AC operation Hz 50/60 50 60
closing VA 27 /24.3 26.4 31.7
p.f. 0.8 / 0.75 0.81 0.77
closed VA 4.4 / 3.4 4.7 5.1
p.f. 0.27/ 0.27 0.26 0.27
DC operation closing = closed W 3.3

Permissible residual current of the electronics (with 0 signal) The 3RT19 16-1GA00 additional load
AC operation mA < 3 mA x 230
----------- 
V
module is recommended for higher residual
 Us  currents, see accessories

< 10 mA x --------- 
24 V
DC operation mA
 Us 
Operating times 1)
Break-time = opening time + arcing time
AC operation closing time ms 8 ... 35
at 0.8 ... 1.1 × Us opening time ms 4 ... 30
DC operation closing time ms 25 ... 100
at 0.85 ... 1.1 × Us opening time ms 7 ... 10
Arcing time ms 10 ... 15

Operating times at 1.0 × Us 1)


AC operation closing time ms 10 ... 25
opening time ms 5 ... 30
DC operation closing time ms 30 ... 50
opening time ms 7 ... 9

Contactor Size S00 S00 S00


Type 3RT10 15 3RT10 16 3RT10 17
Main circuit
Load ratings with AC
AC-1 utilization category, switching resistive load
Rated operational currents Ie at 40 °C up to 690 V A 18 22 22
at 60 °C up to 690 V A 16 0 20
Ratings at 230 V kW 6.3 7.5 7.5
of three-phase loads 2) 400 V kW 11 13 13
p.f. = 0.95 (at 60 °C) 500 V kW 13.8 17 17
690 V kW 19 22 22
Minimum conductor cross-section with Ie load at 40 °C mm2 2.5 2.5 2.5
60 °C mm2 2.5 2.5 2.5

AC-2 and AC-3 utilization categories


Rated operational currents Ie up to 400 V A 7 9 12
500 V A 5 6.5 9
690 V A 4 5.2 6.3
Ratings of slipring or squirrel-cage at 230 V kW 2.2 3 3
motors at 50 Hz and 60 Hz 400 V kW 3 4 5.5
500 V kW 3.5 4.5 5.5
690 V kW 4 5.5 5.5
Thermal loading capacity 10 s current 3) A 56 72 96
Power loss per conducting path at Ie/AC-3 W 0.42 0.7 1.24

1) The opening times of the NO contacts and the 2) Industrial furnaces and electric heaters with 3) Acc. to VDE 0660 Part 102.
closing times of the NC contacts increase if the resistance heating, for example (higher For rated values for various
contactor coils are protected against voltage current input allowed for during heating up). starting conditions, see Part 4.
peaks (suppression diode 6 to 10 times, diode
assemblies 2 to 6 times, varistor +2 to 5 ms).

Siemens NS K · 2002 3/89


Contactors and Contactor Assemblies
Contactors for Switching Motors SIRIUS
3RT1. 1. contactors

Technical data

Contactor Size S00 S00 S00


Type 3RT10 15 3RT1. 16 3RT1. 17
Main circuit
Load ratings with AC
AC-4 utilization category (at Ia = 6 × Ie) 1)
Rated operational current Ie up to 400 V A 6.5 8.5 8.5
Ratings of squirrel-cage motors at 400 V kW 3 4 4
at 50 Hz and 60 Hz
For a contact endurance of approx. 200 000 operating cycles:
Rated operational currents Ie up to 400 V A 2.6 4.1 4.1
690 V A 1.8 3.3 3.3
Ratings of squirrel-cage motors at 230 V kW 0.67 1.1 1.1
at 50 Hz and 60 Hz 400 V kW 1.15 2 2
500 V kW 1.45 2 2
690 V kW 1.15 2.5 2.5
AC-5a utilization category, switching gas discharge lamps
per main conducting path at 230 V
Rating Rated operational
per lamp current per lamp (A)
uncorrected
L 18 W 0.37 units 30 43 43
L 36 W 0.43 units 26 37 37
L 58 W 0.67 units 16 23 23
lead-lag
L 18 W 0.11 units 100 144 144
L 36 W 0.21 units 54 76 76
L 58 W 0.32 units 35 50 50

Switching gas discharge lamps with correction, electronic ballast


per main conducting path at 230 V
Rating Capacitor Rated operational
per lamp (µF) current per lamp (A)
Parallel correction
L 18 W 4.5 0.11 units 16 22 22
L 36 W 4.5 0.21 units 16 22 22
L 58 W 7 0.32 units 10 14 14
With electronic ballast,
single lamp
L 18 W 6.8 0.10 units 44 63 63
L 36 W 6.8 0.18 units 25 35 35
L 58 W 10 0.27 units 16 23 23
With electronic ballast,
twin lamp
L 18 W 10 0.18 units 25 35 35
L 36 W 10 0.35 units 13 18 18
L 58 W no.: 22 0.52 units 8 12 12

AC-5b utilization category, switching incandescent lamps


per main conducting path at 230/220 V kW 1.2 1.6 1.6

AC-6a utilization category, switching three-phase transformers


with inrush n 30 20 30 20 30 20
Rated operational current Ie up to 400 V A 2.4 3.6 3.3 5.1 5.1 7.2
Ratings of three-phase transformers at 230 V kVA 1.0 1.4 1.3 2 2 2.9
with an inrush of n = 30 or 20. 400 V kVA 1.6 2.5 2.3 3.5 3.5 5
The ratings must be re-calculated 500 V kVA 2.2 3.3 3,1 4.6 4.6 6.2
for other inrush factors x: 690 V kVA 2.9 4.3 4 6 6 8.6
30
Px = Pn 30 ⋅ ------
x

1) The data applies to 3RT15 16 and 3RT15 17


(2 NO + 2 NC) only up to a rated operational
voltage 400 V.

3/90 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Switching Motors
3RT1. 1. contactors

Technical data

Contactor Size S00 S00 S00


Type 3RT10 15 3RT10 16 3RT10 17
Main circuit
Load ratings with DC
DC-1 utilization category,
switching resistive load (L/R ≤ 1 ms)
Rated operational current Ie (at 60 °C)
Number of conducting paths connected in series 1 2 3 1 2 3 1 2 3
up to 24 V A 15 15 15 20 20 20 20 20 20
60 V A 15 15 15 20 20 20 20 20 20
110 V A 1.5 8.4 15 2.1 12 20 2.1 12 20
220 V A 0.6 1.2 15 0.8 1.6 20 0.8 1.6 20
440 V A 0.42 1.6 0.9 0.6 0.8 1.3 0.6 0.8 1.3
600 V A 0.42 0.5 0.7 0.6 0.7 1 0.6 0.7 1

DC-3 and DC-5 utilization categories,


shunt and series motors (L/R ≤ 15 ms)
Rated operational current Ie (at 60 °C)
Number of conducting paths connected in series 1 2 3 1 2 3 1 2 3
up to 24 V A 15 15 15 20 20 20 20 20 20
60 V A 0.35 3.5 15 0.5 5 20 0.5 5 20
110 V A 0.1 0.25 15 0.15 0.35 20 0.15 0.35 20
220 V A – – 1.2 – – 1.5 – – 1.5
440 V A – – 0.14 – – 0.2 – – 0.2
600 V A – – 0.14 – – 0.2 – – 0.2
Operating frequency
Operating frequency z in operating cycles per hour AC/DC operation
Contactors without overload relays No-load operating 1/h 10 000
frequency
Dependence of the operating frequency z’ Rated operation
on the operational current I’ and the operational for AC-1 1/h 1 000
voltage U’: for AC-2 1/h 750
for AC-3 1/h 750
z’ = z ⋅ ---- ⋅ ----------  1/h
Ie 400 V 1,5
for AC-4 1/h 250
I′  U ′ 

Contactors with overload relays (mean value) 1/h 15


Conductor cross-sections
Screw connections Main and auxiliary conductors:
(1 or 2 conductor Solid mm2 2 × (0.5 ... 1.5); 2 × (0.75 ... 2.5) acc. to IEC 60 947;
connections possible) max. 2 × (1 ... 4)
For screwdriver Finely stranded with end sleeve mm2 2 × (0.5 ... 1.5); 2 × (0.75 ... 2.5)
size 2 and Pozidriv 2
AWG conductor connections, solid or stranded AWG 2 × (20 ... 16); 2 × (18 ... 14); 1 × 12
– Terminal screws M3
– Tightening torque Nm 0.8 ... 1.2 (7 ... 10.3 lb.in)

Cage Clamp connections Main and auxiliary conductors; coil terminals:


(1 or 2 conductor Solid mm2 2 × (0.25 ... 2.5)
connections possible) Finely stranded with end sleeve mm2 2 × (0.25 ... 1.5)
Finely stranded without end sleeve mm2 2 × (0.25 ... 2.5)
AWG conductor connections, solid or stranded AWG 2 × (24 ... 14)

For tool for opening the Cage Clamp connection, see accessories on page 3/52.
An "insulation stop" must be used for conductor cross-sections ≤ 1 mm2, see accessories on page 3/52.
Max. outer diameter of conductor insulation: 3.6 mm.
For information about Cage Clamp connections, see page 4.

Siemens NS K · 2002 3/91


Contactors and Contactor Assemblies
Contactors for Switching Motors SIRIUS
3RT10 2. contactors

Technical data

Contactor Size S0
Type 3RT10 2.
General data
Permissible mounting position AC and DC operation 360° 22,5° 22,5°
The contactors are designed for operation

NSB00478
on a vertical mounting surface.

NSB00477
Upright mounting position:

AC operation Standard design


DC operation Special design required; also applies to
3RT10 2 . - . K . 40 coupling relays
Positions 13 to 16 of the Order No. must be changed to -1AA0.
In the case of 3RT10 2 . -3K . 44-0LA0 contactors with extended coil
voltage tolerance, positions 13 to 16 of the Order No. are changed
to -1LA0. Additional charge
Mechanical Basic units Oper. 10 million
endurance Basic unit with snap-on auxiliary switch block cycles 10 million
Solid-state compatible aux. switch block 5 million
Electrical endurance See page 3/86
Rated insulation voltage Ui (pollution degree 3) V 690
Rated impulse withstand voltage Uimp kV 6
Safe isolation between coil and main contacts V 400
(acc. to DIN VDE 0106 Part 101 and A1 [draft 2/89])
Positively driven operation 3RT10 2 ., 3RT13 2 . Yes, between main contacts and auxiliary NC contacts and within
There is positively driven operation if the NC and (removable aux. switch block) the auxiliary switch blocks acc. to ZH 1/457, IEC 60 947-4-1, Annex
NO contacts cannot be closed at the same time H (draft 17B/996/DC)
Positively driven operation for contactors with solid-state 3RT10 2 ., 3RT13 2 .
compatible auxiliary switch block according to Swiss (permanent aux. switch block) Yes, between main contacts and auxiliary NC contacts and within
regulations (SUVA) on request. the auxiliary switch blocks acc. to ZH 1/457, IEC 60 947-4-1, Annex
H (draft 17B/996/DC), Swiss regulations (SUVA)
Permissible ambient temperature in operation °C –25 ... +60
when stored °C –55 ... +80
Degree of protection acc. to IEC 60 947-1 and DIN 40 050 IP 20, coil system IP 20
Shock resistance Rectangular pulse AC operation g/ms 8.2/5 and 4.9/10
DC operation g/ms 10/5 and 7.5/10
Sine pulse AC operation g/ms 12.5/5 and 7.8/10
DC operation g/ms 15/5 and 10/10
Conductor cross-sections See page 3/95

Contactor Size S0 S0
Type 3RT10 23, 3RT10 24, RT10 25 3RT10 26
Short-circuit protection of contactors without overload For short-circuit protection of contactors with overload relays, see
Part 4.
For short-circuit protection of weld-free contactors, see Part 5.
(overload and short-circuit protection only with 3RV10 circuit-
breaker).
For short-circuit protection of fuseless load feeders, see Part 5.
Main circuit
Fuse links, utilization category gL/gG
NH Type 3NA, DIAZED Type 5SB, NEOZED Type 5SE
With fuse links
– acc. to IEC 60 947-4-1/EN 60 947-4-1 Type of coord. "1" 1) A 63 100
Type of coord. "2" 1) A 25 35
Weld-free 2) A 10 16
or miniature circuit-breaker with C-characteristic A 25 32
(short-circuit current 3 kA, type of coordination "1") 1)
Auxiliary circuit
Fuse links, utilization category gL/gG A 10 10
DIAZED Type 5SB, NEOZED Type 5SE (weld-free protection at Ik ≥ 1 kA)
or miniature circuit-breaker with C-characteristic A 10 10
(short-circuit current Ik < 400 A)

1) According to excerpt from Type of coordination "2": 2) Test conditions acc. to IEC 60 947-4-1.
IEC 60 947-4-1 (VDE 0660 Part 102): No damage can be tolerated to the overload relay, For 3RT11 weld-free contactors, see Part 5
Type of coordination "1": but contact welding on the contactor is permitted if (overload and short-circuit protection only with
Destruction of the contactor and the overload the contacts can be easily separated. 3RV10 circuit-breaker).
relay is permissible. The contactor and/or over-
load relay must be replaced if necessary.

3/92 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Switching Motors
3RT10 2. contactors

Technical data

Contactor Size S0
Type 3RT10 2.
Control circuit
Coil voltage tolerance AC/DC 0.8 ... 1.1 × Us

Power consumption of the coils (with coil in cold state and 1.0 × Us) Standard design For USA and Canada
AC operation Hz 50 50/60 50 60
closing VA 61 64 /63 61 69
p.f. 0.82 0.72/ 0.74 0.82 0.76
closed VA 7.8 8.4 / 6.8 7.8 7.5
p.f. 0.24 0.24/ 0.28 0.24 0.28
DC operation closing = closed W 5.4

Permissible residual current of the electronics


(with 0 signal)
< 6 mA x ------------ 
230 V
AC operation mA
 Us 
DC operation mA < 16 mA x
24
--------- 
V
 Us 
Operating times at 0.8 ... 1.1 × Us 1)
Break-time = opening time + arcing time
AC operation closing time ms 8 ... 44
opening time ms 4 ... 20
DC operation closing time ms 50 ... 170
opening time ms 13.5 ... 15.5
Arcing time ms 10

Operating times at 1.0 × Us 1)


AC operation closing time ms 10 ... 17
opening time ms 4 ... 20
DC operation closing time ms 55 ... 85
opening time ms 14 ... 15.5

Contactor Size S0 S0 S0 S0
Type 3RT10 23, 3RT10 23, 3RT10 25 3RT10 26
3RT10 23 3RT10 24
Main circuit
Load ratings with AC
AC-1 utilization category, switching resistive load
Rated operational currents Ie at 40 °C up to 690 V A 40
at 60 °C up to 690 V A 35
Ratings at 230 V kW 13.3
of three-phase loads 2) 400 V kW 23
p.f. = 0.95 (at 60 °C) 500 V kW 29
690 V kW 40
Minimum conductor cross-section with Ie load at 40 °C mm2 10
60 °C mm2 10
AC-2 and AC-3 utilization categories
Rated operational currents Ie up to 400 V A 9 12 17 25
500 V A 6.5 12 17 18
690 V A 5.2 9 13 13
Ratings of slipring or squirrel-cage at 110 V kW 1.1 1.5 2.2 3
motors at 50 Hz and 60 Hz 230 V kW 3 3 4 5.5
400 V kW 4 5.5 7.5 11
500 V kW 4.5 7.5 10 11
660/690 V kW 5.5 7.5 11 11
Thermal loading capacity 10 s current 3) A 80 110 150 200
Power loss per conducting path at Ie/AC-3 W 0.4 0.5 0.9 1.6

1) The opening times of the NO contacts and the 2) Industrial furnaces and electric heaters with 3) Acc. to VDE 0660 Part 102.
closing times of the NC contacts increase if the resistance heating, for example (higher current For rated values for various starting conditions,
contactor coils are protected against voltage input allowed for during heating up). see Part 4.
peaks (varistor +2 ms to 5 ms, diode assem-
blies: 2 to 6 times).

Siemens NS K · 2002 3/93


Contactors and Contactor Assemblies
Contactors for Switching Motors SIRIUS
3RT10 2. contactors

Technical data

Contactor Size S0 S0 S0 S0
Type 3RT10 23 3RT10 23 3RT10 25 3RT10 26
Main circuit
Load ratings with AC
AC-4 utilization category (at Ia = 6 × Ie)
Rated operational current Ie up to 400 V A 8.5 12.5 15.5 15.5
Ratings of squirrel-cage motors at 400 V kW 4 5.5 7.5 7.5
at 50 Hz and 60 Hz
For a contact endurance of approx. 200 000 operating cycles:
Rated operational currents Ie up to 400 V A 4.1 5.5 7.7 9
690 V A 3.3 5.5 7.7 9
Ratings of squirrel-cage motors at 110 V kW 0.5 0.73 1 1.2
at 50 Hz and 60 Hz 230 V kW 1.1 1.5 2 2.5
400 V kW 2 2.6 3.5 4.4
500 V kW 2 3.3 4.6 5.6
690 V kW 2.5 4.6 6 7.7
AC-5a utilization category, switching gas discharge lamps
per main conducting path at 230 V 1)
Rating Rated operational
per lamp current per lamp (A)
uncorrected
L 18 W 0.37 units 95
L 36 W 0.43 units 81
L 58 W 0.67 units 52
lead-lag
L 18 W 0.11 units 318
L 36 W 0.21 units 166
L 58 W 0.32 units 109
Switching gas discharge lamps with correction, electronic ballast
per main conducting path at 230 V
Rating Capacitor Rated operational
per lamp (µF) current per lamp (A)
Parallel correction
L 18 W 4.5 0.11 units 37 61
L 36 W 4.5 0.21 units 37 61
L 58 W 7 0.32 units 23 39
With electronic ballast,
single lamp
L 18 W 6.8 0.10 units 105 105
L 36 W 6.8 0.18 units 58 97
L 58 W 10 0.27 units 38 64
With electronic ballast,
twin lamp
L 18 W 10 0.18 units 58 97
L 36 W 10 0.35 units 30 50
L 58 W 22 0.52 units 20 33
AC-5b utilization category, switching incandescent lamps
per main conducting path at 230/220 V kW 3 4

AC-6a utilization category, switching three-phase transformers


with inrush n 30 20 30 20
Rated operational current Ie up to 400 V A 7.6 11.4 13.5 20,2
Ratings of three-phase transformers at 230 V kVA 3 4.5 5.4 8
with an inrush of n = 30 or 20. 400 V kVA 5.2 7.9 9.3 13.9
The ratings must be re-calculated 500 V kVA 6.6 9.9 11.7 15.5
for other inrush factors x: 690 V kVA 9.1 13.6 15.5 15.5
30
Px = Pn 30 ⋅ ------
x

AC-6b utilization category, switching low-inductance


(low-loss, metallized-dielectric) three-phase capacitors
Rated operational currents Ie up to 400 V A 5.8 10.8
Ratings of single capacitors at 230 V kvar 2.5 4
or of capacitor banks (minimum inductance between 400 V kvar 4 7.5
parallel capacitors 6 µH) at 50 Hz, 60 Hz and 500 V kvar 4 7.5
690 V kvar 4 7.5

1) Ie/AC-1 = 35 A (60 °C) and with the correspon-


ding minimum conductor cross-section 10 mm2.

3/94 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Switching Motors
3RT10 2. contactors

Technical data

Contactor Size S0 S0
Type 3RT10 23, 3RT10 24, 3RT10 25 3RT10 26
Main circuit
Load ratings with DC
DC-1 utilization category,
switching resistive load (L/R ≤ 1 ms)
Rated operational current Ie (at 60 °C)
Number of conducting paths connected in series 1 2 3
up to 24 V A 35 35 35
60 V A 20 35 35
110 V A 4.5 35 35
220 V A 1 5 35
440 V A 0.4 1 2.9
600 V A 0.25 0.8 1.4

DC-3 and DC-5 utilization categories,


shunt and series motors (L/R ≤ 15 ms)
Rated operational current Ie (at 60 °C)
Number of conducting paths connected in series 1 2 3
up to 24 V A 20 35 35
60 V A 5 35 35
110 V A 2.5 15 35
220 V A 1 3 10
440 V A 0.09 0.27 0.6
600 V A 0.06 0.16 0.6
Operating frequency
Operating frequency z in operating cycles per hour AC DC AC DC
Contactors without overload relays No-load operating 1/h 5000 1500 5000 1500
frequency
Dependence of the operating frequency z’ AC/DC AC/DC
on the operational current I’ and the operational for AC-1 1/h 1 000 1 000
voltage U’: for AC-2 1/h 1 000 750
for AC-3 1/h 1 000 750
z’ = z ⋅ ---- ⋅ ----------  1/h
Ie 400 V 1.5
for AC-4 1/h 300 250
I′  U ′ 

Contactors with overload relays (mean value) 1/h 15 15


Conductor cross-sections
Screw connections Main conductor:
(1 or 2 conductor
Solid mm2 2 × (1 ... 2.5); 2 × (2.5 ... 6)
connections possible)
Finely stranded with end sleeve mm2 2 × (1 ... 2.5); 2 × (2.5 ... 6) acc. to IEC 60 947; max. 1 × 10
AWG conductor connections, – solid AWG 2 × (16 ... 12)
– solid or stranded AWG 2 × (14 ... 10)
– stranded AWG 1×8
– Terminal screws M4 (Pozidriv size 2)
– Tightening torque Nm 2.0 ... 2.5 (18 ... 22 lb.in)
Auxiliary conductor:
Solid mm2 2 × (0.5 ... 1.5); 2 × (0.75 ... 2.5) acc. to IEC 60 947;
max. 2 × (0.75 ... 4)
Finely stranded with end sleeve mm2 2 × (0.5 ... 1.5); 2 × (0.75 ... 2.5)
AWG conductor connections, solid or stranded AWG 2 × (20 ... 16); 2 × (18 ... 14); 1 × 12
– Terminal screws M3
– Tightening torque Nm 0.8 ... 1.2 (7 ... 10.3 lb.in)
Cage Clamp connections Auxiliary conductor:
(1 or 2 conductor Solid mm2 2 × (0.25 ... 2.5)
connections possible) Finely stranded with end sleeve mm2 2 × (0.25 ... 1.5)
Finely stranded without end sleeve mm2 2 × (0.25 ... 2.5)
AWG conductor connections, solid or stranded AWG 2 × (24 ... 14)
For tool for opening the Cage Clamp connection, see accessories on page 3/52.
An "insulation stop" must be used for conductor cross-sections ≤ 1 mm2, see accessories on page 3/52.
Max. outer diameter of conductor insulation: 3.6 mm.
For information about Cage Clamp connections, see page 4.

Siemens NS K · 2002 3/95