Contactors and Contactor Assemblies

SIRIUS Contactors for Switching Motors


3RT10 6. contactors
Contac tors and Contactor Assemblies

Technical data

Contactor Size S10 S10 S10


Type 3RT10 64 3RT10 65 3RT10 66
General data
Permissible mounting position 22,5° 22,5°

NSB00649
The contactors are designed for operation 90° 90°
on a vertical mounting surface.

Mechanical endurance Oper. 10 million


cycles
Electrical endurance See page 3/87

Rated insulation voltage Ui (pollution degree 3) V 1000

Rated impulse withstand voltage Uimp kV 8

Safe isolation between coil, auxiliary contacts and main contacts V 690
(acc. to DIN VDE 0106 Part 101 and A1 [draft 2/89])
Positively driven operation Yes, between main contacts and auxiliary NC contacts and within
There is positively driven operation if the NC and the auxiliary switch blocks acc. to ZH 1/457, IEC 60 947-4-1, Annex
NO contacts cannot be closed at the same time H (draft 17B/996/DC)
Permissible ambient temperature in operation °C –25 ... +60/+55 with AS-Interface
when stored °C –55 ... +80
Degree of protection acc. to IEC 60 947-1 and DIN 40 050 IP 00/open type, coil system IP 20
Shock resistance Rectangular pulse g/ms 8.5/5 and 4.2/10
Sine pulse g/ms 13.4/5 and 6.5/10

Conductor cross-sections See page 3/109


Electromagnetic compatibility (EMC) See page 3/14
Short-circuit protection
Main circuit
Fuse links, utilization category gL/gG
NH Type 3NA, DIAZED Type 5SB, NEOZED Type 5SE
– acc. to IEC 60 947-4-1/EN 60 947-4-1 Type of coord. "1" 1) A 500
Type of coord. "2" 1) A 400
Weld-free 2) A 250
Auxiliary circuit
Fuse links, utilization category gL/gG A 10
(weld-free protection at Ik ≥ 1 kA)
DIAZED Type 5SB, NEOZED Type 5SE
or miniature circuit-breaker with C-characteristic (Ik < 400 A)

Contactor Size S10


Type 3RT10 6 .
Control circuit
Coil voltage tolerance AC/DC (UC) 0.8 × Us min ... 1.1 × Us max

Power consumption of solenoid mechanism Conventional op. mechanism Solid-state op. mechanism
(with coil in cold state and rated range Us min ... Us max) Us min Us max Us min Us max
AC operation closing VA 490 590 400 530
p.f. 0.9 0.9 0.8 0.8
closed VA 5.6 6.7 4 5
p.f. 0.9 0.9 0.5 0.4
DC operation closing W 540 650 440 580
closed W 6.1 7.4 3.2 3.8
PLC control input (EN 61 131-2/Type 2) DC 24 V /≤ 30 mA
Operating times Conventional op. mechanism Solid-state op. mechanism
(Break-time = opening time + arcing time) Operation via
A1/A2 PLC input
– at 0.8 × Us min ... 1.1 × Us max closing time ms 30 ... 95 105 ... 145 45 ... 80
opening time ms 40 ... 80 80 ... 100 80 ... 100
– at Us min ... Us max closing time ms 35 ... 50 110 ... 130 50 ... 65
opening time ms 50 ... 80 80 ... 100 80 ... 100
Arcing time ms 10 ... 15 10 ... 15 10 ... 15

1) According to excerpt from Type of coordination "2": 2) Test conditions acc. to IEC 60 947-4-1.
IEC 60 947-4-1 (VDE 0660 Part 102): No damage can be tolerated to the overload relay,
Type of coordination "1": but contact welding on the contactor is permitted if
Destruction of the contactor and the overload the contacts can be easily separated.
relay is permissible. The contactor and/or over-
load relay must be replaced if necessary.

Siemens NS K · 2002 3/107


Contactors and Contactor Assemblies
Contactors for Switching Motors SIRIUS
3RT10 6. contactors
Contac tors and Contactor Assemblies

Technical data

Contactor Size S10 S10 S10


Type 3RT10 64 3RT10 65 3RT10 66
Main circuit
Load ratings with AC
AC-1 utilization category, switching resistive load
Rated operational currents Ie at 40 °C up to 690 V A 275 330
at 60 °C up to 690 V A 250 300
at 60 °C up to 1000 V A 100 150
Ratings of three-phase loads 1) at 230 V kW 94 113
p.f. = 0.95 (at 60 °C) 400 V kW 164 197
500 V kW 205 246
690 V kW 283 340
1000 V kW 164 246
Minimum conductor cross-section with Ie load at 40 °C mm2 150 185
60 °C mm2 120 185
AC-2 and AC-3 utilization categories
Rated operational currents Ie up to 500 V A 225 265 300
690 V A 225 265 280
1000 V A 68 95 95
Ratings of slipring or squirrel-cage at 230 V kW 73 85 97
motors at 50 Hz and 60 Hz 400 V kW 128 151 171
500 V kW 160 189 215
690 V kW 223 265 280
1000 V kW 90 132 132
Thermal loading capacity 10 s current 2) A 1800 2400 2400
Power loss per conducting path at Ie/AC-3/500 V W 17 18 22

AC-4 utilization category (at Ia = 6 × Ie)


Rated operational current Ie up to 400 V A 195 230 280
Ratings of squirrel-cage motors at 400 V kW 110 132 160
at 50 Hz and 60 Hz
For a contact endurance of approx. 200 000 operating cycles:
Rated operational currents Ie up to 500 V A 96 117 125
690 V A 85 105 115
1000 V A 42 57 57
Ratings of squirrel-cage motors at 230 V kW 30 37 40
at 50 Hz and 60 Hz 400 V kW 54 66 71
500 V kW 67 82 87
690 V kW 82 102 112
1000 V kW 59 80 80
AC-6a utilization category, switching three-phase transformers
with inrush n 30 20 30 20 30 20
Rated operational current Ie up to 690 V A 151 227 182 265 182 273
Ratings of three-phase transformers at 230 V kVA 60 90 72 105 72 109
with an inrush of n = 30 or 20. 400 V kVA 105 157 126 183 126 189
The ratings must be re-calculated 500 V kVA 130 196 158 229 158 236
for other inrush factors x: 690 V kVA 180 271 217 317 217 326
1000 V kVA 117 117 164 164 164 164
30
Px = Pn 30 ⋅ ------
x

AC-6b utilization category, switching low-inductance


(low-loss, metallized-dielectric) three-phase capacitors
Ambient temperature 40 °C
Rated operational currents Ie up to 500 V A 183 220
Ratings of single capacitors at 230 V kvar 73 88
or of capacitor banks (minimum inductance 400 V kvar 127 152
between parallel capacitors 6 µH) 500 V kvar 159 191
at 50 Hz, 60 Hz and 690 V kvar 127 152

1) Industrial furnaces and electric heaters 2) Acc. to VDE 0660 Part 102.
with resistance heating, for example (higher For rated values for various
current input allowed for during heating up). starting conditions, see Part 4.

3/108 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Switching Motors
3RT10 6. contactors

Technical data

Contactor Size S10 S10 S10


Type 3RT10 64 3RT10 65 3RT10 66
Main circuit
Load ratings with DC
DC-1 utilization category,
switching resistive load (L/R ≤ 1 ms)
Rated operational current Ie (at 60 °C)
Number of conducting paths connected in series 1 2 3 1 2 3
up to 24 V A 200 200 200 300 300 300
60 V A 200 200 200 300 300 300
110 V A 18 200 200 33 300 300
220 V A 3.4 20 200 3.8 300 300
440 V A 0.8 3.2 11.5 0.9 4 11
600 V A 0.5 1.6 4 0.6 2 5.2
DC-3 and DC-5 utilization categories,
shunt and series motors (L/R ≤ 15 ms)
Rated operational current Ie (at 60 °C)
Number of conducting paths connected in series 1 2 3 1 2 3
up to 24 V A 200 200 200 300 300 300
60 V A 7.5 200 200 11 300 300
110 V A 2.5 200 200 3 300 300
220 V A 0.6 2.5 200 0.6 2.5 300
440 V A 0.17 0.65 1.4 0.18 0.65 1.4
600 V A 0.12 0.37 0.75 0.125 0.37 0.75
Operating frequency
Operating frequency z in operating cycles per hour
Contactors without overload relays No-load operating 1/h 2000 2000 2000
frequency
Dependence of the operating frequency z’ on the for AC-1 1/h 750 800 750
operational current I’ and the operational voltage U’: for AC-2 1/h 250 300 250
for AC-3 1/h 500 700 500
for AC-4 1/h 130 130 130
z’ = z ⋅ ---- ⋅ ----------  1/h
Ie 400 V 1.5
I′  U ′ 

Contactors with overload relays (mean value) 1/h 60 60 60

Contactor Size S10


Type 3RT10 6.
Conductor cross-sections
Screw connections Main conductor: Front terminal Back terminal Both terminals
with 3RT19 66-4G box terminal connected connected connected
Finely stranded with end sleeve mm2 70 ... 240 120 ... 185 min. 2 × 50,
max. 2 × 185
NSB00480
NSB00479

Finely stranded without end sleeve mm2 70 ... 240 120 ... 185 min. 2 × 50,
NSB00481

max. 2 × 185
Stranded mm2 95 ... 300 120 ... 240 min. 2 × 70,
max. 2 × 240
AWG conductor connections, solid or 3/0 ... 600 kcmil 250 ... 500 kcmil min. 2 × 2/0,
stranded max. 2 × 500 kcmil
Ribbon cable (qty. × width × thickness) mm min. 6 × 9 × 0.8 min. 6 × 9 × 0.8
mm max. 20 × 24 × 0.5 max. 20 × 24 × 0.5 max. 2 × (20 × 24 × 0.5)
– Terminal screws M 12 (hexagon sok-
ket, A/F 5)
– Tightening torque Nm 20 ... 22 (180 ... 195 lb.in)

Without box terminal/busbar connection


Finely stranded with cable lug mm2 50 ... 240 If cable lugs acc. to DIN 46 234 are connec-
Stranded with cable lug mm2 70 ... 240 ted, as of a conductor cross-section of
240 mm2 and acc. to DIN 46 235 as of a con-
ductor cross-section of 185 mm2 a 3RT19 66-
4EA1 terminal cover is necessary to comply
with the phase clearance.
AWG conductor connections, solid or stranded 2/0 ... 500 kcmil
Connecting bar (max. width) mm 25
– Terminal screws M 10 × 30 (A/F 17)
– Tightening torque Nm 14 ... 24 (124 ... 210 lb.in)

Auxiliary conductor:
Solid mm2 2 × (0.5 ... 1.5); 2 × (0.75 ... 2.5) acc. to IEC 60 947;
max. 2 × (0.75 ... 4)
Finely stranded with end sleeve mm2 2 × (0.5 ... 1.5); 2 × (0.75 ... 2.5)
AWG conductor connections, solid or stranded AWG 2 × (18 ... 14)
– Terminal screws M 3 (PZ 2)
– Tightening torque Nm 0.8 ... 1.2 (7 ... 10.3 lb.in)

Siemens NS K · 2002 3/109


Contactors and Contactor Assemblies
Contactors for Switching Motors SIRIUS
3RT10 7. contactors

Technical data

Contactor Size S12 S12


Type 3RT10 75 3RT10 76
General data
Permissible mounting position 22,5° 22,5°

NSB00649
The contactors are designed for operation 90° 90°
on a vertical mounting surface.

Mechanical endurance Oper. 10 million


cycles
Electrical endurance See page 3/87
Rated insulation voltage Ui (pollution degree 3) V 1000
Rated impulse withstand voltage Uimp kV 8
Safe isolation between coil, auxiliary contacts and main contacts V 690
(acc. to DIN VDE 0106 Part 101 and A1 [draft 2/89])
Positively driven operation Yes, between main contacts and auxiliary NC contacts and within
There is positively driven operation if the NC and the auxiliary switch blocks acc. to ZH 1/457, IEC 60 947-4-1,
NO contacts cannot be closed at the same time Annex H (draft 17B/996/DC)
Permissible ambient temperature in operation °C –25 ... +60/+55 with AS-Interface
when stored °C –55 ... +80
Degree of protection acc. to IEC 60 947-1 and DIN 40 050 IP 00/open type, coil system IP 20
Shock resistance Rectangular pulse g/ms 8.5/5 and 4.2/10
Sine pulse g/ms 13.4/5 and 6.5/10
Conductor cross-sections See page 3/112
Electromagnetic compatibility (EMC) See page 3/14
Short-circuit protection
Main circuit
Fuse links, utilization category gL/gG
NH Type 3NA, DIAZED Type 5SB, NEOZED Type 5SE
– to IEC 60 947-4/EN 60 947-4-4 (VDE 0660 Part 102) Type of coord. "1" 1) A 630 630
Type of coord. "2" 1) A 500 500
Weld-free 2) A 250 315
Auxiliary circuit
Fuse links, utilization category gL/gG A 10
(weld-free protection at Ik ≥ 1 kA)
DIAZED Type 5SB, NEOZED Type 5SE
or miniature circuit-breaker with C-characteristic (Ik < 400 A)
Control circuit
Coil voltage tolerance AC/DC (UC) 0.8 × Us min ... 1.1 × Us max

Power consumption of solenoid mechanism Conventional op. mechanism Solid-state op. mechanism
(with coil in cold state and rated range Us min ... Us max) Us min Us max Us min Us max
AC operation closing VA 700 830 560 750
p.f. 0.9 0.9 0.8 0.8
closed VA 7.6 9.2 5.4 7
p.f. 0.9 0.9 0.8 0.8
DC operation closing W 770 920 600 800
closed W 8.5 10 4 5
PLC control input (EN 61 131-2/Type 2) DC 24 V/≤ 30 mA

Operating times Conventional op. mechanism Solid-state op. mechanism


(Break-time = opening time + arcing time) Operation via
A1/A2 PLC input
– at 0.8 × Us min ... 1.1 × Us max closing time ms 45 ... 100 120 ... 150 60 ... 90
opening time ms 60 ... 100 80 ... 100 80 ... 100
– at Us min ... Us max closing time ms 50 ... 70 125 ... 150 65 ... 80
opening time ms 70 ... 100 80 ... 100 80 ... 100
Arcing time ms 10 ... 15 10 ... 15 10 ... 15

1) According to excerpt from Type of coordination "2": 2) Test conditions acc. to IEC 60 947-4-1.
IEC 60 947-4-1 (VDE 0660 Part 102): No damage can be tolerated to the overload relay,
Type of coordination "1": but contact welding on the contactor is permitted if
Destruction of the contactor and the overload the contacts can be easily separated.
relay is permissible. The contactor and/or over-
load relay must be replaced if necessary.

3/110 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Switching Motors
3RT10 7. contactors

Technical data

Contactor Size S12 S12


Type 3RT10 75 3RT10 76
Main circuit
Load ratings with AC
AC-1 utilization category, switching resistive load
Rated operational currents Ie at 40 °C up to 690 V A 430 610
at 60 °C up to 690 V A 400 550 3)
at 60 °C up to 1000 V A 200 200
Ratings of three-phase loads 1) at 230 V kW 151 208
p.f. = 0.95 (at 60 °C) 400 V kW 263 362
500 V kW 329 452
690 V kW 454 624
1000 V kW 329 329
Minimum conductor cross-section with Ie load at 40 °C mm2 2 × 150 2 × 185
60 °C mm2 240 2 × 185
AC-2 and AC-3 utilization categories
Rated operational currents Ie up to 500 V A 400 500 4)
690 V A 400 450
1 000 V A 180 180
Ratings of slipring or squirrel-cage at 230 V kW 132 164
motors at 50 Hz and 60 Hz 400 V kW 231 291
500 V kW 291 363
690 V kW 400 453
1 000 V kW 250 250
Thermal loading capacity 10 s current 2) A 3200 4000
Power loss per conducting path at Ie/AC-3/500 V W 35 55
AC-4 utilization category (at Ia = 6 × Ie)
Rated operational current Ie up to 400 V A 350 430
Ratings of squirrel-cage motors at 400 V kW 200 250
at 50 Hz and 60 Hz
For a contact endurance of approx. 200 000 operating cycles:
Rated operational currents Ie up to 500 V A 150 175
690 V A 135 150
1 000 V A 80 80
Ratings of squirrel-cage motors at 230 V kW 48 56
at 50 Hz and 60 Hz 400 V kW 85 98
500 V kW 105 123
690 V kW 133 148
1 000 V kW 113 113
AC-6a utilization category, switching three-phase transformers
with inrush n 30 20 30 20
Rated operational current Ie up to 690 V A 251 377 270 404
Ratings of three-phase transformers at 230 V kVA 100 150 107 161
with an inrush of n = 30 or 20. 400 V kVA 173 261 187 280
The ratings must be re-calculated 500 V kVA 217 326 234 350
for other inrush factors x: 690 V kVA 300 450 323 483
30 1000 V kVA 311 311 311 311
Px = Pn 30 ⋅ ------
x

AC-6b utilization category, switching low-inductance


(low-loss, metallized-dielectric) three-phase capacitors
Ambient temperature 40 °C
Rated operational currents Ie up to 500 V A 287 407
Ratings of single capacitors at 230 V kvar 114 162
or of capacitor banks (minimum inductance 400 V kvar 199 282
between parallel capacitors 6 µH) 500 V kvar 248 352
at 50 Hz, 60 Hz and 690 V kvar 199 282

1) Industrial furnaces and electric heaters 2) Acc. to VDE 0660 Part 102. 3) Ambient temperature 50 °C
with resistance heating, for example (higher For rated values for various for 3RT10 76-.N contactor
current input allowed for during heating up). starting conditions, see Part 4. 4) Ambient temperature 55 °C
for 3RT10 76-.N contactor

Siemens NS K · 2002 3/111


Contactors and Contactor Assemblies
Contactors for Switching Motors SIRIUS
3RT10 7. contactors

Technical data

Contactor Size S12 S12


Type 3RT10 75 3RT10 76
Main circuit
Load ratings with DC
DC-1 utilization category,
switching resistive load (L/R ≤ 1 ms)
Rated operational current Ie (at 60 °C)
Number of conducting paths connected in series 1 2 3
up to 24 V A 400 400 400
60 V A 330 400 400
110 V A 33 400 400
220 V A 3.8 400 400
440 V A 0.9 4 11
600 V A 0.6 2 5.2
DC-3 and DC-5 utilization categories,
shunt and series motors (L/R ≤ 15 ms)
Rated operational current Ie (at 60 °C)
Number of conducting paths connected in series 1 2 3
up to 24 V A 400 400 400
60 V A 11 400 400
110 V A 3 400 400
220 V A 0.6 2.5 400
440 V A 0.18 0.65 1.4
600 V A 0.125 0.37 0.75
Operating frequency
Operating frequency z in operating cycles per hour
Contactors without overload relays No-load operating 1/h 2000 2000
frequency
Dependence of the operating frequency z’ on the for AC-1 1/h 700 500
operational current I’ and the operational voltage U’: for AC-2 1/h 200 170
for AC-3 1/h 500 420
for AC-4 1/h 130 130
z’ = z ⋅ ---- ⋅ ----------  1/h
Ie 400 V 1.5
I′  U ′ 

Contactors with overload relays (mean value) 1/h 60 60

Contactor Size S12


Type 3RT10 7.
Conductor cross-sections
Screw connections Main conductor: Front terminal Back terminal Both terminals
with 3RT19 66-4G box terminal connected connected connected
Finely stranded with end sleeve mm2 70 ... 240 120 ... 185 min. 2 × 50,
max. 2 × 185
NSB00480
NSB00479

Finely stranded without end sleeve mm2 70 ... 240 120 ... 185 min. 2 × 50,
NSB00481

max. 2 × 185
Stranded mm2 95 ... 300 120 ... 240 min. 2 × 70,
max. 2 × 240
AWG conductor connections, solid or 3/0 ... 600 kcmil 250 ... 500 kcmil min. 2 × 2/0,
stranded max. 2 × 500 kcmil
Ribbon cable (qty. × width × thickness) mm min. 6 × 9 × 0.8 min. 6 × 9 × 0.8
mm max. 20 × 24 × 0.5 max. 20 × 24 × 0.5 max. 2 × (20 × 24 × 0.5)
– Terminal screws M 12 (hexagon
socket, A/F 5)
– Tightening torque Nm 20 ... 22 (180 ... 195 lb.in)

Without box terminal/busbar connection


Finely stranded with cable lug mm2 50 ... 240 If cable lugs acc. to DIN 46 234 are connec-
Stranded with cable lug mm2 70 ... 240 ted, as of a conductor cross-section of
240 mm2 and acc. to DIN 46 235 as of a con-
ductor cross-section of 185 mm2 a 3RT19 66-
4EA1 terminal cover is necessary to comply
with the phase clearance.
AWG conductor connections, solid or stranded 2/0 ... 500 kcmil
Connecting bar (max. width) mm 25
– Terminal screws M 10 × 30 (A/F 17)
– Tightening torque Nm 14 ... 24 (124 ... 210 lb.in)

Auxiliary conductor:
Solid mm2 2 × (0.5 ... 1.5); 2 × (0.75 ... 2.5) acc. to IEC 60 947;
max. 2 × (0.75 ... 4)
Finely stranded with end sleeve mm2 2 × (0.5 ... 1.5); 2 × (0.75 ... 2.5)
AWG conductor connections, solid or stranded AWG 2 × (18 ... 14)
– Terminal screws M 3 (PZ 2)
– Tightening torque Nm 0.8 ... 1.2 (7 ... 10.3 lb.in)

3/112 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Switching Motors
3RT12 6. vacuum contactors

Technical data

Contactor Size S10 S10 S10


Type 3RT12 64 3RT12 65 3RT12 66
General data
Permissible mounting position 22,5° 22,5° 22,5° 22,5°

NSB01350
The contactors are designed for operation
on a vertical mounting surface.

Mechanical endurance Oper. 10 million


cycles
Electrical endurance See page 3/87
Rated insulation voltage Ui (pollution degree 3) V 1000
Rated impulse withstand voltage Uimp kV 8
Safe isolation between coil, auxiliary contacts and main contacts V 690
(acc. to DIN VDE 0106 Part 101 and A1 [draft 2/89])
Positively driven operation Yes, between main contacts and auxiliary NC contacts and within
There is positively driven operation if the NC and the auxiliary switch blocks acc. to ZH 1/457, IEC 60 947-4-1,
NO contacts cannot be closed at the same time Annex H (draft 17B/996/DC)
Permissible ambient temperature in operation °C –25 ... +60/+55 with AS-Interface
when stored °C –55 ... +80
Degree of protection acc. to IEC 60 947-1 and DIN 40 050 IP 00/open type, coil system IP 20
Shock resistance Rectangular pulse g/ms 8.5/5 and 4.2/10
Sine pulse g/ms 13.4/5 and 6.5/10
Conductor cross-sections See page 3/115
Electromagnetic compatibility (EMC) See page 3/14
Short-circuit protection
Main circuit
Fuse links, utilization category gL/gG
NH Type 3NA, DIAZED Type 5SB, NEOZED Type 5SE
– to IEC 60 947-4/EN 60 947-4-4 (VDE 0660Part 102) Type of coord. "1" 1) A 500
Type of coord. "2" 1) A 500
Weld-free 2) A 400
Auxiliary circuit
Fuse links, utilization category gL/gG A 10
(weld-free protection at Ik ≥ 1 kA)
DIAZED Type 5SB, NEOZED Type 5SE
or miniature circuit-breaker with C-characteristic (Ik < 400 A)
Control circuit
Coil voltage tolerance AC/DC (UC) 0.8 × Us min ... 1.1 × Us max

Power consumption of solenoid mechanism Conventional op. mechanism Solid-state op. mechanism
(with coil in cold state and rated range Us min ... Us max) Us min Us max Us min Us max
AC operation closing VA 530 630 420 570
p.f. 0.9 0.9 0.8 0.8
closed VA 6.1 7.4 4.3 5.6
p.f. 0.9 0.9 0.8 0.8
DC operation closing W 580 700 460 630
closed W 6.8 8.2 3.4 4.2
PLC control input (EN 61 131-2/Type 2) DC 24 V/≤ 30 mA

Operating times Conventional op. mechanism Solid-state op. mechanism


(Break-time = opening time + arcing time) Operation via
A1/A2 PLC input
– at 0.8 × Us min ... 1.1 × Us max closing time ms 30 ... 95 105 ... 145 45 ... 80
opening time ms 40 ... 80 80 ... 100 80 ... 100
– at Us min ... Us max closing time ms 35 ... 50 110 ... 130 50 ... 65
opening time ms 50 ... 80 80 ... 100 80 ... 100
Arcing time ms 10 ... 15 10 ... 15 10 ... 15

1) According to excerpt from Type of coordination "2": 2) Test conditions acc. to IEC 60 947-4-1.
IEC 60 947-4-1 (VDE 0660 Part 102): No damage can be tolerated to the overload relay,
Type of coordination "1": but contact welding on the contactor is permitted if
Destruction of the contactor and the overload the contacts can be easily separated.
relay is permissible. The contactor and/or over-
load relay must be replaced if necessary.

Siemens NS K · 2002 3/113


Contactors and Contactor Assemblies
Contactors for Switching Motors SIRIUS
3RT12 6. vacuum contactors

Technical data

Contactor Size S10 S10 S10


Type 3RT12 64 3RT12 65 3RT12 66
Main circuit
Load ratings with AC
AC-1 utilization category, switching resistive load
Rated operational currents Ie at 40 °C up to 1000 V A 330
at 60 °C up to 1000 V A 300
Ratings of three-phase loads 1) at 230 V kW 113
p.f. = 0.95 (at 60 °C) 400 V kW 197
500 V kW 246
690 V kW 340
1000 V kW 492
Minimum conductor cross-section with Ie load at 40 °C mm2 185
60 °C mm2 185
AC-2 and AC-3 utilization categories
Rated operational currents Ie up to 1000 V A 225 265 300
Ratings of slipring or squirrel-cage at 230 V kW 73 85 97
motors at 50 Hz and 60 Hz 400 V kW 128 151 171
500 V kW 160 189 215
690 V kW 223 265 288
1000 V kW 320 378 428
Thermal loading capacity 10 s current 2) A 1800 2120 2400
Power loss per conducting path at Ie/AC-3 W 9 12 14

AC-4 utilization category (at Ia = 6 × Ie)


Rated operational current Ie up to 690 V A 195 230 280
Ratings of squirrel-cage motors at 400 V kW 110 132 160
at 50 Hz and 60 Hz
For a contact endurance of approx. 400 000 operating cycles:
Rated operational currents Ie up to 690 V A 97 115 140
1000 V A 68 81 98
Ratings of squirrel-cage motors at 230 V kW 30 37 45
at 50 Hz and 60 Hz 400 V kW 55 65 79
500 V kW 68 81 98
690 V kW 94 112 138
1000 V kW 95 114 140
AC-6a utilization category, switching three-phase transformers
with inrush n 30 20
Rated operational current Ie up to 690 V A 185 278
Ratings of three-phase transformers at 230 V kVA 74 111
with an inrush of n = 30 or 20. 400 V kVA 128 193
The ratings must be re-calculated 500 V kVA 160 241
for other inrush factors x: 690 V kVA 221 332
1000 V kVA 320 482
30
Px = Pn 30 ⋅ ------
x

AC-6b utilization category, switching low-inductance


(low-loss, metallized-dielectric) three-phase capacitors
Ambient temperature 40 °C
Rated operational currents Ie up to 500 V A 220
Ratings of single capacitors at 230 V kvar 88
or of capacitor banks (minimum inductance 400 V kvar 152
between parallel capacitors 6 µH) 500 V kvar 191
at 50 Hz, 60 Hz and 690 V kvar 152
Operating frequency
Operating frequency z in operating cycles per hour
Contactors without overload relays No-load operating 1/h 2000 2000
frequency
Dependence of the operating frequency z’ on the for AC-1 1/h 800 750
operational current I’ and the operational voltage U’: for AC-2 1/h 300 250
for AC-3 1/h 750 750
for AC-4 1/h 250 250
z’ = z ⋅ ---- ⋅ ----------  1/h
Ie 400 V 1.5
I′  U ′ 

Contactors with overload relays (mean value) 1/h 60 60

1) Industrial furnaces and electric heaters 2) Acc. to VDE 0660 Part 102.
with resistance heating, for example (higher For rated values for various
current input allowed for during heating up). starting conditions, see Part 4.

3/114 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Switching Motors
3RT12 6. vacuum contactors

Technical data

Contactor Size S10


Type 3RT12 6.
Conductor cross-sections
Screw connections Main conductor: Front terminal Back terminal Both terminals
with 3RT19 66-4G box terminal connected connected connected
Finely stranded with end sleeve mm2 70 ... 240 120 ... 185 min. 2 × 50,
max. 2 × 185

NSB00480
NSB00479
Finely stranded without end sleeve mm2 70 ... 240 120 ... 185 min. 2 × 50,

NSB00481
max. 2 × 185
Stranded mm2 95 ... 300 120 ... 240 min. 2 × 70,
max. 2 × 240
AWG conductor connections, solid or 3/0 ... 600 kcmil 250 ... 500 kcmil min. 2 × 2/0,
stranded max. 1 × 500 kcmil
Ribbon cable (qty. × width × thickness) mm min. 6 × 9 × 0.8 min. 6 × 9 × 0.8
mm max. 20 × 24 × 0.5 max. 20 × 24 × 0.5 max. 2 × (20 × 24 ×
0.5)
– Terminal screws M 12 (hexagon
socket, A/F 5)
– Tightening torque Nm 20 ... 22 (180 ... 195 lb.in)

Without box terminal/busbar connection


Finely stranded with cable lug mm2 50 ... 240 If cable lugs acc. to DIN 46 234 are connec-
Stranded with cable lug mm2 70 ... 240 ted, as of a conductor cross-section of
240 mm2 and acc. to DIN 46 235 as of a con-
ductor cross-section of 185 mm2 a 3RT19 66-
4EA1 terminal cover is necessary to comply
with the phase clearance.
AWG conductor connections, solid or stranded 2/0 ... 500 kcmil
Connecting bar (max. width) mm 25
– Terminal screws M 10 × 30 (A/F 17)
– Tightening torque Nm 14 ... 24 (124 ... 210 lb.in)

Auxiliary conductor:
Solid mm2 2 × (0.5 ... 1.5); 2 × (0.75 ... 2.5) acc. to IEC 60 947;
max. 2 × (0.75 ... 4)
Finely stranded with end sleeve mm2 2 × (0.5 ... 1.5); 2 × (0.75 ... 2.5)
AWG conductor connections, solid or stranded AWG 2 × (18 ... 14)
– Terminal screws M 3 (PZ 2)
– Tightening torque Nm 0.8 ... 1.2 (7 ... 10.3 lb.in)

Siemens NS K · 2002 3/115


Contactors and Contactor Assemblies
Contactors for Switching Motors SIRIUS
3RT12 7. vacuum contactors

Technical data

Contactor Size S12 S12


Type 3RT12 75 3RT12 76
General data
Permissible mounting position 22,5° 22,5° 22,5° 22,5°

NSB01350
The contactors are designed for operation
on a vertical mounting surface.

Mechanical endurance Oper. 10 million


cycles
Electrical endurance See page 3/87
Rated insulation voltage Ui (pollution degree 3) V 1000
Rated impulse withstand voltage Uimp kV 8
Safe isolation between coil, auxiliary contacts and main contacts V 690
(acc. to DIN VDE 0106 Part 101 and A1 [draft 2/89])
Positively driven operation Yes, between main contacts and auxiliary NC contacts and within
There is positively driven operation if the NC and the auxiliary switch blocks acc. to ZH 1/457, IEC 60 947-4-1,
NO contacts cannot be closed at the same time Annex H (draft 17B/996/DC)
Permissible ambient temperature in operation °C –25 ... +60/+55 with AS-Interface
when stored °C –55 ... +80
Degree of protection acc. to IEC 60 947-1 and DIN 40 050 IP 00/open type, coil system IP 20
Shock resistance Rectangular pulse g/ms 8.5/5 and 4.2/10
Sine pulse g/ms 13.4/5 and 6.5/10
Conductor cross-sections See page 3/118
Electromagnetic compatibility (EMC) See page 3/14
Short-circuit protection
Main circuit
Fuse links, utilization category gL/gG
NH Type 3NA, DIAZED Type 5SB, NEOZED Type 5SE
– to IEC 60 947-4/EN 60 947-4-4 (VDE 0660Part 102) Type of coord. "1" 1) A 800
Type of coord. "2" 1) A 800
Weld-free 2) A 500
Auxiliary circuit
Fuse links, utilization category gL/gG A 10
(weld-free protection at Ik ≥ 1 kA)
DIAZED Type 5SB, NEOZED Type 5SE
or miniature circuit-breaker with C-characteristic (Ik < 400 A)
Control circuit
Coil voltage tolerance AC/DC (UC) 0.8 × Us min ... 1.1 × Us max

Power consumption of solenoid mechanism Conventional op. mechanism Solid-state op. mechanism
(with coil in cold state and rated range Us min ... Us max) Us min Us max Us min Us max
AC operation closing VA 700 830 560 750
p.f. 0.9 0.9 0.8 0.8
closed VA 7.6 9.2 5.4 7
p.f. 0.9 0.9 0.8 0.8
DC operation closing W 770 920 600 800
closed W 8.5 10 4 5
PLC control input (EN 61 131-2/Type 2) DC 24 V/≤ 30 mA

Operating times Conventional op. mechanism Solid-state op. mechanism


(Break-time = opening time + arcing time) Operation via
A1/A2 PLC input
– at 0.8 × Us min ... 1.1 × Us max closing time ms 45 ... 100 120 ... 150 60 ... 90
opening time ms 60 ... 100 80 ... 100 80 ... 100
– at Us min ... Us max closing time ms 50 ... 70 125 ... 150 65 ... 80
opening time ms 70 ... 100 80 ... 100 80 ... 100
Arcing time ms 10 ... 15 10 ... 15 10 ... 15

1) According to excerpt from Type of coordination "2": 2) Test conditions acc. to IEC 60 947-4-1.
IEC 60 947-4-1 (VDE 0660 Part 102): No damage can be tolerated to the overload relay,
Type of coordination "1": but contact welding on the contactor is permitted if
Destruction of the contactor and the overload the contacts can be easily separated.
relay is permissible. The contactor and/or over-
load relay must be replaced if necessary.

3/116 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Switching Motors
3RT12 7. vacuum contactors

Technical data

Contactor Size S12 S12


Type 3RT12 75 3RT12 76
Main circuit
Load ratings with AC
AC-1 utilization category, switching resistive load
Rated operational currents Ie at 40 °C up to 1000 V A 610
at 60 °C up to 1000 V A 550
Ratings of three-phase loads 1) at 230 V kW 208
p.f. = 0.95 (at 60 °C) 400 V kW 362
500 V kW 452
690 V kW 624
1000 V kW 905
Minimum conductor cross-section with Ie load at 40 °C mm2 2 × 185
60 °C mm2 2 × 185
AC-2 and AC-3 utilization categories
Rated operational currents Ie up to 1000 V A 400 500
Ratings of slipring or squirrel-cage at 230 V kW 132 164
motors at 50 Hz and 60 Hz 400 V kW 231 291
500 V kW 291 363
690 V kW 400 507
1000 V kW 578 728
Thermal loading capacity 10 s current 2) A 3200 4000
Power loss per conducting path at Ie/AC-3 W 21 32

AC-4 utilization category (at Ia = 6 × Ie)


Rated operational current Ie up to 690 V A 350 430
Ratings of squirrel-cage motors at 50 Hz and 60 Hz at 400 V kW 200 250

For a contact endurance of approx. 400 000 operating cycles:


Rated operational currents Ie up to 690 V A 175 215
1000 V A 123 151
Ratings of squirrel-cage motors at 230 V kW 56 70
at 50 Hz and 60 Hz 400 V kW 98 122
500 V kW 124 153
690 V kW 172 212
1000 V kW 183 217
AC-6a utilization category, switching three-phase transformers
with inrush n 30 20
Rated operational current Ie up to 690 V A 279 419
Ratings of three-phase transformers at 230 V kVA 111 167
with an inrush of n = 30 or 20. 400 V kVA 193 290
The ratings must be re-calculated 500 V kVA 241 363
for other inrush factors x: 690 V kVA 332 501
30 1000 V kVA 482 726
Px = Pn 30 ⋅ ------
x

AC-6b utilization category, switching low-inductance


(low-loss, metallized-dielectric) three-phase capacitors
Ambient temperature 40 °C
Rated operational currents Ie up to 500 V A 407
Ratings of single capacitors at 230 V kvar 162
or of capacitor banks (minimum inductance 400 V kvar 282
between parallel capacitors 6 µH) 500 V kvar 352
at 50 Hz, 60 Hz and 690 V kvar 282
Operating frequency
Operating frequency z in operating cycles per hour
Contactors without overload relays No-load operating 1/h 2000
frequency
Dependence of the operating frequency z’ on the for AC-1 1/h 700
operational current I’ and the operational voltage U’: for AC-2 1/h 250
for AC-3 1/h 750
for AC-4 1/h 250
z’ = z ⋅ ---- ⋅ ----------  1/h
Ie 400 V 1.5
I′  U ′ 

Contactors with overload relays (mean value) 1/h 60

1) Industrial furnaces and electric heaters 2) Acc. to VDE 0660 Part 102.
with resistance heating, for example (higher For rated values for various
current input allowed for during heating up). starting conditions, see Part 4.

Siemens NS K · 2002 3/117


Contactors and Contactor Assemblies
Contactors for Switching Motors SIRIUS
3RT12 7. vacuum contactors

Technical data

Contactor Size S12


Type 3RT12 7.
Conductor cross-sections
Screw connections Main conductor: Front terminal Back terminal Both terminals
with 3RT19 66-4G box terminal connected connected connected
Finely stranded with end sleeve mm2 70 ... 240 120 ... 185 min. 2 × 50,
max. 2 × 185

NSB00480
NSB00479
Finely stranded without end sleeve mm2 70 ... 240 120 ... 185 min. 2 × 50,

NSB00481
max. 2 × 185
Stranded mm2 95 ... 300 120 ... 240 min. 2 × 70,
max. 2 × 240
AWG conductor connections, solid or 3/0 ... 600 kcmil 250 ... 500 kcmil min. 2 × 2/0,
stranded max. 2 × 500 kcmil
Ribbon cable (qty. × width × thickness) mm min. 6 × 9 × 0.8 min. 6 × 9 × 0.8
mm max. 20 × 24 × 0.5 max. 20 × 24 × 0.5 max. 2 × (20 × 24 × 0.5)
– Terminal screws M 12 (hexagon
socket, A/F 5)
– Tightening torque Nm 20 ... 22 (180 ... 195 lb.in)

Without box terminal/busbar connection


Finely stranded with cable lug mm2 50 ... 240 If cable lugs acc. to DIN 46 234 are connec-
Stranded with cable lug mm2 70 ... 240 ted, as of a conductor cross-section of
240 mm2 and acc. to DIN 46 235 as of a con-
ductor cross-section of 185 mm2 a 3RT19 66-
4EA1 terminal cover is necessary to comply
with the phase clearance.
AWG conductor connections, solid or stranded 2/0 ... 500 kcmil
Connecting bar (max. width) mm 25
– Terminal screws M 10 × 30 (A/F 17)
– Tightening torque Nm 14 ... 24 (124 ... 210 lb.in)

Auxiliary conductor:
Solid mm2 2 × (0.5 ... 1.5); 2 × (0.75 ... 2.5) acc. to IEC 60 947;
max. 2 × (0.75 ... 4)
Finely stranded with end sleeve mm2 2 × (0.5 ... 1.5); 2 × (0.75 ... 2.5)
AWG conductor connections, solid or stranded AWG 2 × (18 ... 14)
– Terminal screws M 3 (PZ 2)
– Tightening torque Nm 0.8 ... 1.2 (7 ... 10.3 lb.in)

3/118 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Switching Motors
3RT10 contactors
Contac tors and Contactor Assemblies

Technical data

Contactor Size S00 S00 S00 S0 S0 S0


Type 3RT10 15 3RT10 16 3RT10 17 3RT10 23/24 3RT10 25 3RT10 26
s and u ratings of the contactors
Rated insulation voltage AC V 600 600

Continuous current, at 40 °C Free air and enclosed A 20 35

Maximum horsepower ratings


(s and u-approved values)
Ratings at 200 V hp 1½ 2 3 2/3 5 7½
of three-phase motors 230 V hp 2 3 3 3/3 5 7½
at 50/60 Hz 460 V hp 3 5 7½ 5/7½ 10 15
575 V hp 5 7½ 10 7½/10 15 20

Short-circuit protection kA 5 5 5 5 5 5
(contactor or overload relay) Fuse or circuit-breaker A 60 60 60 70 70 100
acc. to UL 489 A 50 50 50 70 70 100

NEMA/EEMAC ratings NEMA/EEMAC SIZE – 0 – 1


Conventional thermal current Free air A – 18 – 27
Enclosed A – 18 – 27
Ratings at 200 V hp – 3 – 7½
of three-phase motors 230 V hp – 3 – 7½
at 60 Hz 460 V hp – 5 – 10
575 V hp – 5 – 10

Overload relay Type 3RU11 16 3RU11 2


Setting range A 0.11 ... 12 1.8 ... 25

Contactor Size S2 S2 S2 S3 S3 S3
Type 3RT10 34 3RT10 35 3RT10 36 3RT10 44 3RT10 45 3RT10 46

Rated insulation voltage AC V 600 600

Continuous current, at 40 °C Free air and enclosed A 45 55 50 90 105

Maximum horsepower ratings


(s and u-approved values)
Ratings at 200 V hp 10 10 15 20 25 30
of three-phase motors 230 V hp 10 15 15 25 30 30
at 50/60 Hz 460 V hp 25 30 40 50 60 75
575 V hp 30 40 50 60 75 100

Short-circuit protection kA 5 5 5 10 10 10
Fuse or circuit-breaker A 125 150 200 250 300 350
acc. to UL 489 A 125 150 200 250 300 400

NEMA/EEMAC ratings NEMA/EEMAC SIZE – 2 – 3


Conventional thermal current Free air A – 45 – 90
Enclosed A – 45 – 90
Ratings at 200 V hp – 10 – 25
of three-phase motors 230 V hp – 15 – 30
at 60 Hz 460 V hp – 25 – 50
575 V hp – 25 – 50

Overload relay Type 3RU11 3 3RU11 4


Setting range A 5.5 ... 50 18 ... 100

Contactor Size S00 S0 ... S12


Screw connection and Screw connection and Screw connection and
Cage Clamp connection Cage Clamp connection Cage Clamp connection
Integrated or Single-pole and 4-pole Laterally
snap-on snap-on mountable
auxiliary switch block auxiliary switch block auxiliary switch block
s and u ratings of the auxilary contacts
Rated voltage V AC 600 600 600

Making and breaking capacity A 600, Q 600 A 600, Q 600 A 300, Q 300
Conventional thermal
current at AC 240 V A 10 10 10

Siemens NS K · 2002 3/119


Contactors and Contactor Assemblies
Contactors for Switching Motors SIRIUS
3RT10 contactors

Technical data

Contactor Size S6 S6 S6 S10 S10 S10


Type 3RT10 54 3RT10 55 3RT10 56 3RT10 64 3RT10 65 3RT10 66
s and u ratings of the contactors
Rated insulation voltage AC V 600 600

Continuous current, at 40 °C Free air and enclosed A 140 195 195 250 330 330

Maximum horsepower ratings


(s and u-approved values)
Ratings at 200 V hp 40 50 60 60 75 100
of three-phase motors 230 V hp 50 60 75 75 100 125
at 50/60 Hz 460 V hp 100 125 150 150 200 250
575 V hp 125 150 200 200 250 300

Short-circuit protection kA 10 10 10 10 18 18
CLASS RK5 fuse A 450 500 500 700 800 800
Circuit-breaker
acc. to UL 489 A 350 450 500 500 700 800

NEMA/EEMAC ratings NEMA/EEMAC SIZE – 4 – – – 5


Conventional thermal current Free air A – 150 – – – 300
Enclosed A – 135 – – – 270
Ratings at 200 V hp – 40 – – – 75
of three-phase motors 230 V hp – 50 – – – 100
at 60 Hz 460 V hp – 100 – – – 200
575 V hp – 100 – – – 200

Overload relay Type 3RB10 56 3RB10 66

Contactor Size S12 S12


Type 3RT10 75 3RT10 76

Rated insulation voltage AC V 600

Continuous current, at 40 °C Free air and enclosed A 400 540

Maximum horsepower ratings


(s and u-approved values)
Ratings at 200 V hp 125 150
of three-phase motors 230 V hp 150 200
at 50/60 Hz 460 V hp 300 400
575 V hp 400 500

Short-circuit protection kA 18 30
CLASS RK5 fuse A 1000 1200
Circuit-breaker
acc. to UL 489 A 900 900

NEMA/EEMAC ratings NEMA/EEMAC SIZE – 6


Conventional thermal current Free air A – 600
Enclosed A – 540
Ratings at 200 V hp – 150
of three-phase motors 230 V hp – 200
at 60 Hz 460 V hp – 400
575 V hp – 400

Overload relay Type 3RB10 66

3/120 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Switching Motors
3RT12 vacuum contactors

Technical data

Contactor Size S10 S10 S10 S12 S12


Type 3RT12 64 3RT12 65 3RT12 66 3RT12 75 3RT12 76
s and u ratings of the contactors
Rated insulation voltage AC V 600 600

Continuous current, at 40 °C Free air and enclosed A 330 540

Maximum horsepower ratings


(s and u-approved values)
Ratings at 200 V hp 60 75 100 125 150
of three-phase motors 230 V hp 75 100 125 150 200
at 50/60 Hz 460 V hp 150 200 250 300 400
575 V hp 200 250 300 400 500

Short-circuit protection kA 10 18 18 18 30
CLASS RK5 fuse A 700 800 800 1200 1200
Circuit-breaker
acc. to UL 489 A 500 700 900 1000 1200

NEMA/EEMAC ratings NEMA/EEMAC SIZE – 5 – 6


Conventional thermal current Free air A – –
Enclosed A – –
Ratings at 200 V hp – –
of three-phase motors 230 V hp – –
at 60 Hz 460 V hp – –
575 V hp – –

Overload relay Type 3RB10 66 3RB10 66

Siemens NS K · 2002 3/121