Beruflich Dokumente
Kultur Dokumente
dseGenset
dse8810
ENVIRONMENTAL TESTING STANDARDS
TEMPERATURE
BS EN 60068
Ab/Ae Cold Test -30oC
The DSE8810 is an easy-to-use, The event log will record 250 events KEY LOAD SHARE FEATURES: BS EN 60068-2-2
loadshare module, designed to to facilitate easy maintenance. An • Sequential set start Bb/Be Dry Heat +70oC
synchronise and work within a extensive number of fixed and • R.O.C.O.F. and vector shift VIBRATION
loadshare system of up to 32 flexible monitoring, metering and • Generator load demand BS EN 60068-2-6
generators including electronic and protection features are included • Automatic hours run balancing Ten sweeps in each of three major axes
5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
non-electronic engines. as well as comprehensive • Dead bus sensing
communication and system • Bus failure detection HUMIDITY
The DSE8810 monitors the expansion options. • Direct governor and AVR control BS EN 60068-2-30
Db Damp Heat Cyclic 20/55oC @ 95% RH
generator and indicates operational • Volts and frequency matching 48 Hours
status and fault conditions, Using the DSE PC Configuration • kW and kV Ar load sharing BS EN 60068-2-78
automatically starting or stopping Suite Software allows easy Cab Damp Heat Static 40oC @ 93% RH
48 Hours
the engine on load demand or fault alteration of the operational
condition. sequences, timers and alarms. With SHOCK
all communication ports capable of BS EN 60068-2-27
Three shocks in each of three major axes
System alarms are annunciated on being active at the same time, the 15gn in 11mS
the LCD screen (multiple language DSE8810 is ideal for a wide variety
DEGREES OF PROTECTION
options available), illuminated LED of demanding load share PROVIDED BY ENCLOSURES
and audible sounder. applications. BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.
DSENET ®
RS232 AND USB USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS SENDERS STOP SUPPLY 8-35V
+
ETHERNET
DEUTZ
DSE8810 MSC
ISUZU
PERKINS
CATERPILLAR
MTU
7 8x60 8x10 8x80 8x10 8x60 VOLVO
OTHER
CUMMINS
SCANIA
BUS VOLT FREE GENERATOR SENSING FUEL & CRANK CHARGE ELECTRONIC MAGNETIC
SENSING OUTPUTS OUTPUTS ALTERNATOR ENGINES PICK-UP
FLEXIBLE WITH CAN
CURRENT VOLTS
D+
+ W/L
ISSUE 1
®
dseGenset
dse8810
SPECIFICATION
DC SUPPLY
CONTINUOUS VOLTAGE RATING
COLOUR AUTO START LOAD SHARE MODULE 8 V to 35 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout
and
FEATURES supply recovers to 5 V. This is achieved
without the need for internal batteries
OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage
OUTPUT B (CRANK)
15 A DC at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
AUXILIARY OUTPUTS E TO J
2 A DC at supply voltage
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK-UP
KEY FEATURES • Configurable event log (250) • DSENet® expansion compatible VOLTAGE RANGE
• Configurable inputs (11) • Easy access diagnostic page • Integral PLC editor +/- 0.5 V to 70 V
• Configurable outputs (8) • CAN and Magnetic Pick-up/Alt.
FREQUENCY RANGE
• Built-in governor and AVR sensing KEY BENEFITS 10,000 Hz (max)
control • Fuel usage monitor and low fuel • Dual processor for improved
• Comprehensive electrical alarms response BUILT-IN GOVERNOR CONTROL
MINIMUM LOAD IMPEDANCE
protection • Manual fuel pump control • RS232, RS485 & Ethernet can be 1000Ω
• Comprehensive loadshare • “Protections disabled” feature used at the same time Fully isolated
capabilities • kW overload protection • High number of inputs and GAIN VOLTAGE
• RS232, RS485 & Ethernet • Reverse power protection outputs 0 V to 10 V DC
remote communications • Power monitoring (kW h, kV Ar, • Worldwide language support Fully isolated
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-116/03/12 (1)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457