Sie sind auf Seite 1von 6

FAN ENGINEERING

Information and Recommendations for the Engineer


Twin City Fan

FE-2500

Safety Agency Listing


Introduction
Safety is a major concern when fans and blowers are These products are rated 600 volts or less and are
designed and manufactured. Any product sold for use intended to be employed in accordance with the
by the general public containing electrical components National Electrical Code, ANSI/NFPA 70.
must carry the Underwriters Laboratories Inc. (UL) listing
mark. Federal, state and local building codes also 2) These requirements do not cover air heaters
dictate that any electrically operated equipment sold for incorporating fans, heating- ventilating units, or blowers
use on a new public building must carry the UL listing comprising components of such equipment as furnaces,
mark. Building inspectors will check for this mark on all mechanical-refrigeration equipment or air conditioners.
electrically operated equipment. OSHA will look for this
mark during safety inspections in the workplace. Since 3) These requirements do not cover fusible links, and
its founding in 1894, UL has played a key role in the the like, provided to disconnect a fan or close shutters
U.S. safety system. The UL mark has become America’s in the event of fire.
most familiar safety symbol.
As the primary North American product safety 4) These requirements do not cover fans for use in
organization and the leading developer of U.S. product cooking areas when the fan is intended for other than
safety standards, UL participates internationally in the household use.
harmonization of national product safety standards used
in countries around the world. UL is accredited by the 5) These requirements do not cover fans intended to be:
Standards Council of Canada (SCC), the Canadian a) Used in hazardous locations as defined in the
national organization responsible for accrediting product National Electrical Code, ANSI/NFPA 70;
testing and certification organizations for Canada. The b) Installed over solvents or chemically flammable
UL mark for Canada is officially accepted by authorities liquids or vapors; or
in all the provinces and territories of Canada. UL is an c) Located in chemically corrosive environments.
integral part of the Canadian safety system.
In December 1993, UL signed a landmark cooperative 6) These requirements do not cover humidifiers.
assistance agreement with the Association Nacional de
Normalizacion y Certificacion del Sector Electrico (ANCE); UL705 – Standard for Safety for Power Ventilators
the first government accredited private sector standards 1) These requirements cover power ventilators of the
and product certification organization for electrical roof and wall mounted types and duct fans of the
products in Mexico. UL can work with manufacturers straight-through type intended for commercial or
anywhere in the world to help them obtain the NOM industrial use and for connection to permanently installed
mark, the certification mark required by Mexican wiring systems in accordance with the National Electrical
regulations and issued by ANCE for electrical products. Code, NFPA 70.
UL has been testing products for over 100 years.
That is longer than any other certification organization in 2) These requirements do not cover the following:
North America. UL marks have come to represent a) Ventilating equipment such as attic, hood, or
something unique, an organization that always puts canopy fans or blowers;
public safety first. UL will never adopt a practice or b) Air moving equipment with integral air tempering
short cut anything that may compromise product safety. means;
c) Ventilators rated more than 600 volts;
UL Standards d) Ventilators employing universal motors rated more
than 250 volts;
Fans and blowers fall under several standards. e) Air heaters equipped with fans;
f) Draft fans for furnaces;
UL507 – Standard for Safety for Electric Fans g) Heating-ventilating units;
1) These requirements cover: h) Blowers employed as components in equipment
a) Fans and blowers that circulate air, such as desk, such as furnaces, mechanical refrigeration equip
ceiling-suspended, and hassock fans; ment or air conditioners;
b) Fans and blowers that ventilate air, such as attic, i) Fusible links, and the like, that may be provided
wall-insert, ceiling-insert, household hood and to disconnect a fan or close shutters in the event
canopy types, and window fans; of fire;
c) Dryer type fans used for drying carpets or floors; j) Ventilators specifically intended for use in
d) Evaporative coolers; exhausting any of the following: gases other
e) Air-filtering appliances; than air, atmospheres causing corrosion to the
f) Fan type deodorizers and air fresheners; ventilator, air with water spray or flammable
g) Component fans; vapors;
h) Low voltage component fans. k) Ventilators for the removal or conveyance of
dust, stock or refuse.
UL762 – Power Roof Ventilators for Restaurant Exhaust b) electric motors for use in aircraft, marine service
Appliances installations, drives for land transportation equipment
1) These requirements cover roof or wall mounted or motors used in underground mining.
ventilators for restaurant exhaust appliances.
CSA C22.2 No. 113-M1984 Fans and Ventilators
2) Power ventilators for restaurant exhaust appliances 1) This standard applies to cord connected and
covered by these requirements are intended for permanently connected fans and ventilators intended to
installation in accordance with the Standard of the be connected to supply circuits of 600 V and less, for
National Fire Protection Association for the installation of use in nonhazardous locations and intended to be used
Equipment for the removal of Smoke and Grease-Laden in accordance with the Rules of the Canadian Electrical
Vapors from Commercial Cooking Equipment. Code, Part 1.

3) Power ventilators for restaurant appliances shall 2) This Standard applies to fans and ventilators for
comply with ANSI/UL 705: Power Ventilators, modified ventilating or exhaust purposes and filter units consisting
in that wiring system shall not be located in the path of an air circulating fan and a mechanical filter.
of travel of exhaust products.
3) This standard applies to fans and ventilators of the
UL793 – Automatically Operated Roof Vents for Smoke air circulating type such as desk, pedestal, hassock,
and Heat utility, suitcase and pendent ceiling fans.
1) These requirements cover automatically operated roof
vents for smoke and heat that fall into two general 4) This standard applies to fans and ventilators of the
categories: mechanically-opened and gravity-opened. ventilating type such as wall insert, ceiling insert, attic,
Mechanically-opened vents consist primarily of a body household hoods, or canopy and window fans.
frame, one or more damper covers and hatches, and
operating mechanisms that generally include a heat 5) This standard does not apply to air conditioning
responsive device and spring(s). The vents covered by equipment, electric air heaters, fan coil units, humidifiers,
these requirements are operated manually or automatically evaporative coolers or electrostatic air cleaners.
in the event of fire to remove smoke and heat from the
building. Automatic operation does not depend on UL has developed more than 800 standards for
electrical power or other energy sources that may be safety. They also have been accredited by the Standards
interrupted during a fire, but rather depends upon Council of Canada to test products to Canadian
operation of a heat responsive device or on the action standards and authorize the use of the UL mark for
of a plastic cover shrinking and falling from place due Canada (cUL). UL tests more than 14,000 products every
to fire exposure, or the like. These vents are not year.
intended for use as general-purpose building ventilation UL uses many other agencies and standards to help
devices. Fans use the mechanically-opened type installed guarantee safety in products. Some of those are NEMA
on the discharge of a fan discharging air up and away (National Electrical Manufacturers Assoc.), NFPA (National
from the building. Fire Protection Agency), IEC (International Electrotechnical
A product that contains features, characteristics, Commission), IEEE (Institute of Electrical and Electronic
components, materials or systems new or different from Engineers), IBI (Intelligent Building Institute), ASME
those covered in these standards and involves a risk of (American Society of Engineers), and so forth.
fire, electric shock or injury to persons shall be evaluated UL standards are developed using an open process
using the appropriate additional component and end that gives all interested parties the opportunity to
product testing standards as determined necessary to comment as Standards are developed or revised. This
maintain an acceptable level of safety as originally process results in the development of Standards that are
anticipated by the intent of the standards. practical for the manufacturer, compatible with other
standards and installation codes and effective in
Canadian Standards addressing public safety issues.
CSA C22.2 No. 100-95 Motors and Generators
1) This standard applies to electric motors and Product Evaluations and Lab
generators for installation and use, in accordance with Testing per UL507 and 705
the rules of the Canadian Electrical Code, Part 1, in UL Lists or Classifies products depending on the type
nonhazardous locations. of product and intended use. Listing, the most
comprehensive UL service, means that samples of the
2) Clause 7 – AC and DC motors (including universal product have been evaluated and found to comply with
motors), in IEC frame size 80 and smaller. all applicable UL requirements. Products distributed in
Clause 8 – AC motors (including universal motors) in IEC Canada are evaluated to Canadian standards and carry
frame sizes 90 to 280 inclusive and rated 750 V and the listing mark for Canada (the cUL mark), which
less. Clause 9 – AC motors rated over 750 V or in IEC specifically indicates compliance with Canadian standards.
frame size 315 and larger. Classification means that samples of the product have
Clause 10 – all DC motors in IEC frame size 90 and been evaluated with respect to standards of other
larger. organizations, specific properties of the product, a
Clause 12 – Inverter duty variable speed AC motors. limited spectrum of hazards, suitability for certain uses
or other special conditions.
3) This standard provides basic requirements for motors Fans and blowers are tested in accordance with the
and does not exclude any additional requirements given testing requirements listed in the Standards that pertain
in other Standards of the Canadian Electrical Code. to their intended usage. Those standards are listed
previously in sections II and III. The tests and testing
4) This standard does not apply to: processes are as follows:
a) sealed (hermetic) type motors such as those used
in refrigerant compressors

2
FAN ENGINEERING – FE-2500
Starting Current Test Multiple speed motors are to be tested at each speed.
A ventilator shall start and attain normal running speed Reversible ventilators are to be tested in both directions.
without opening a fuse when energized on a circuit This is to be done until a constant motor temperature
protected by a fuse of other than the time delay type. is attained. The test voltages are also dictated.
The fuse is to have a current rating corresponding to
that of the motor branch circuit to which the ventilator Undervoltage Test
may be connected in accordance with NEC, ANSI/NFPA The ventilator shall start and operate continually with a
70 – 1993. The ventilator is to be started three times restricted inlet as described previously, which produce
when connected to a circuit of minimum rated voltage. maximum loading, but with the voltage reduced to 85
The motor is allowed to come to a rest then must be percent of the rated voltage of the motor.
restarted immediately.
Dielectric Voltage Withstand Test
Input Test A ventilator shall withstand for one minute without
The current input to a ventilator shall not be more than breakdown the application of a 60 Hz electrical charge
110 percent of the rated value when the ventilator is between live parts and dead metal parts with the
operated under conditions of actual service and ventilator at the maximum temperature reached in normal
connected to a supply circuit of maximum rated voltage use. The test voltage shall be:
and rated frequency. Unless otherwise specified, each a) One thousand volts for a ventilator employing a
ventilator is to be tested at the appropriate potential motor rated 1⁄2 hp or less and 250 volts or less.
voltage. b) One thousand volts plus twice the rated voltage for
Table 1. Input Test Voltage a ventilator employing a motor rated more than 1⁄2
hp or more than 250 volts.
RATED VOLTAGE TEST VOLTAGE
110 - 120 120 To determine if the ventilator complies with the
200 - 208 208 requirements, it is tested with a 500-volt ampere or
220 - 240 240 larger capacity transformer in which the output voltage
254 - 277 277 can be varied. The applied load is increased gradually
440 - 480 480 from zero to the required test voltage and is held at
550 - 600 600 that value for one minute. The increase in load is to be
at a uniform rate and as rapid as is consistent with
correct indication of its value by a voltmeter.
For the input test, the ventilator is to be connected
to a structure that can be adjusted to uniformly restrict Water Spray Test
the air supply. The input is considered to be the A ventilator is to be mounted as in actual service and
maximum input measured while restricting the ventilator is to be subjected to a water spray as described in the
inlet to not more than one-half the cross sectional area standard for a period of 4 hours. If the ventilator draws
of the inlet. air into the unit for motor cooling then the unit must be
operating during the test period. An insulation resistance
Temperature Test and dielectric test are to be performed immediately upon
A ventilator shall be tested and shall not reach conclusion of exposure to the water spray and are to
temperatures high enough to cause a risk of fire, to be repeated 1⁄2 hour later.
damage materials used, or to exceed the temperature After the test there shall be no water at any point
rises specified. A protection device shall not operate that may be contacted by a splice in field-installed
when the ventilator is tested. See Table 2 below. wiring and on uninsulated live parts or on film-coated
All values of temperature rise are based on an wire other than motor windings.
ambient of 86°F. however, tests may be conducted at
any ambient within the range of 50° – 104°F. Metallic Coating Thickness Test
A thermocouple is to be used for determining This test is used for determining the thickness of zinc
temperature of the winding if it can be mounted without and cadmium coatings to ensure against the effects of
removal of the encapsulating compound of the integrally damaging rust and corrosion on metal surfaces.
applied insulation on the motor. The change of resistance
method is to be used if the thermocouple measurement Permanence of Marking Testing
cannot be conducted. These series of tests were developed to insure that any
The standard covers the attachment, placement, size labels used for identification or warnings on a UL listed
of wires to be used, calibration of the instrumentation product demonstrate good adhesion and resists
used and the procedure for running the tests. defacement or removal by scraping. These tests include
The ventilator is to be operated under load conditions. oven aging, immersion, standard atmosphere, unusual
condition exposure and outdoor exposure tests.
Table 2. Temperature Test Values
MOTOR CLASS A INSULATION MOTORS CLASS B INSULATION MOTORS
METHOD
TYPE DIA. > 7" DIA. ≤ 7" DIA. > 7" DIA. ≤ 7"
Open Motor 126°F 126°F 162°F 162°F
Totally Enclosed 135°F 135°F 171°F 171°F
Resistance
Totally Enclosed
126°F — 162°F —
Fan Cooled
Open Motor 108°F 126°F 144°F 162°F
Totally Enclosed 117°F 135°F 153°F 171°F
Thermocouple
Totally Enclosed
117°F — 153°F —
Fan Cooled

3
WWW.TCF.COM
Capacitor Tests undergone a battery of testing. UL subject 762 is
Capacitor burnout and leakage current testing are used basically a test procedure for elevated temperature
to force a breakdown in the insulation surrounding a testing.
capacitor. If the capacitor attains a temperature during
the test hot enough to ignite the testing material, then Normal Temperature Test
it fails. If the capacitor exceeds a certain leakage A representative sample of a ventilator is installed in
current, it fails. accordance with the manufacturer's instructions. A gas-
fired generator is used to supply hot gases to a 4-foot
Overload Testing of Switches and Controls duct connected to the ventilator. When the generator is
These tests are used to ensure that no electrical or fired it will establish and maintain a minimum temperature
mechanical breakdown or undue pitting or burning of the through the duct of 300°F or higher if specified by the
contacts of a motor switch or control occurs during manufacturer. Thermocouple grids are placed at points
repeated cycling. all over the fan and in the duct leading to the ventilator.
The ventilator and gas-fired generator are started to
Manufacturing and Production simulate a restaurant exhaust. During the test, the
maximum temperature at any portion of the ventilator
Testing per UL 507 & 705 shall not exceed the maximum specified in the standard.
Production Dielectric Voltage-Withstand Test
Each ventilator shall withstand without electrical breakdown Abnormal Flare Up Test
as a routine production line test, the application of an Once the ventilator reaches equilibrium conditions during
electrical charge as previously described. The test is the normal temperature test, one pint of liquified refined
conducted with the ventilator fully assembled. pork lard is then placed in a shallow pan in the center
of the inlet duct. The grease is heated to 600°F and
Rating ignited. No attempts are made to extinguish the fire. The
A ventilator shall be rated in volts, amps, horsepower, fire is allowed to burn out normally.
frequency in hertz, the number of phases and a code The temperature rise attained by any part of the
letter, in accordance with the NEC, ANSI/NFPA 70-1993, ventilator during the test shall not be more than
indicating the locked rotor motor input. permitted by the UL standard. Parts of the ventilator
shall not warp, deteriorate or become damaged to any
Marking extent which would cause unsafe operation.
A ventilator shall be legibly and permanently marked,
where visible after installation, with the manufacturer’s
name, trademark, trade name or other descriptive
Product Listing
marking which may identify the product manufacturer. Once the product testing is completed, you will hear
The product must also contain a date code, distinctive from your project engineer about whether or not your
catalog or model number and the electrical rating. product complies with UL’s requirements. For products
A ventilator that incorporates motor-overload protection meeting the requirements, the project engineer will
shall be marked to indicate the presence of such develop a formal report based on the test results. These
protection. A ventilator that does not incorporate motor- test results will also be used to develop a Follow-Up
overload protection must be marked to indicate that the Services program and will serve as a basis of a Follow-
unit should be installed with remote overload protection Up Services Procedure.
and the motor rating data shall be listed so that proper The Follow-Up Services Procedure is a document that
protection may be determined. describes in detail the construction of the product tested
Other typical markings are as follows: A wiring and found to meet the UL requirements. UL’s field
diagram for connecting the motor to the field supplied representatives use this as a guide when conducting
power or other voltages. A direction of rotation arrow. their quarterly examinations of UL certified products in
A distinctive marking for point of manufacture when the factory.
multiple facilities are involved. A ventilator not intended Before UL’s engineering staff will issue your testing
for outdoor use shall be so marked. Pertinent warning report, you must agree to participate in UL’s Follow-Up
and mounting labels shall also be used. Services Agreement.
A ventilator is intended to be shipped from the point If, for some reason, your product does not meet UL’s
of manufacture fully assembled and labeled. A ventilator requirements, you will receive a letter from UL describing
that is shipped without the motor and drives assembled the specific requirements your product did not meet. If
shall be permanently and plainly labeled with all of the you choose, you can modify the product and have it
motors suitable for installation on that ventilator. This retested.
marking must identify the motors requiring remote A product that has been produced under UL’s Listing
overload protection and the ones containing overload and Follow-Up Service program in accordance with the
protection. A provision for marking the unit to indicate terms of UL’s Service Agreement may bear the UL
which motor has been installed must also be provided. Listing Mark as the manufacturer's declaration that the
This becomes a very complex system for the product complies with all the UL requirements.
manufacturer and the installer with ventilators containing Only the components that were approved by UL in
hundreds of combinations of motors. It is generally the test samples are permitted to be used on the
intended for fans where just one or two motors are manufactured product. Any deviation from the electrical
involved. These are usually shipped in a box or boxes or mechanical construction of the unit must be approved
broken down and field assembled. by UL. Some additional testing may be required.
Listing of the product can only take place in the
facility that is specified in the Follow-Up Services
Product Evaluations and Lab procedure. A product cannot be listed until the electrical
Testing per UL 762 components intended for use on that product are
mounted and wired if applicable. The only exception is
A ventilator to be used for restaurant exhaust must first
listed in the Manufacturing and Production Testing
be listed under UL705. This means that it has already
section above under Marking.

4
FAN ENGINEERING – FE-2500
UL Marks and Descriptions evaluated. Products carrying this mark have been
evaluated for specific properties, a limited range of
As mentioned above, there are several types of hazards, or suitability for use under limited or special
UL marks. Each has its own specific meaning and conditions. Typically, products Classified by UL fall into
significance. The only way to determine if a product has the general categories of building materials and industrial
been certified by UL is to look for the UL mark on the equipment. Examples of types of equipment Classified
product itself or, in a few instances, on the product by UL include immersion suits, fire doors, protective
packaging. gear for fire fighters and industrial trucks.
The UL marks are registered certification marks of
Underwriters Laboratories Inc. The UL marks may only
be used on or in connection with products certified by
UL and under the terms of written agreement with UL.

Below are some of the most common UL marks, along


with a description of their meaning: C-UL Classification Mark
This Classification marking is used for products intended
for the Canadian marketplace. It indicates that UL has
used Canadian standards to evaluate the product for
specific hazards or properties. Examples of C-UL
Classified products include air filter units, firestop
devices, certain types of roofing systems and others.
UL Listing Mark
This is one of the most common UL Marks. If a product
carries this mark, it means UL found that samples of
this product met UL's safety requirements. These
requirements are primarily based on UL's own published
Standards for Safety. This type of mark is seen
commonly on appliances and computer equipment,
furnaces and heaters, fuses, electrical panelboards, C-UL US Classification Mark
smoke and carbon monoxide detectors, fire extinguishers UL introduced this new Classification Mark in early 1998.
and sprinkler systems, personal floatation devices such It indicates compliance with both Canadian and U.S.
as life jackets and life preservers, bullet resistant glass requirements. The Canada/U.S. UL Mark is optional. UL
and thousands of other products. encourages those manufacturers with products certified
for both countries to use this new, combined Mark, but
they may continue using separate UL Marks for the
United States and Canada.

C-UL Listing Mark
This mark is applied to products for the Canadian
market. The products with this type of mark have been
evaluated to Canadian safety requirements, which may Recognized Component Mark and
be somewhat different from U.S. safety requirements. Canadian Recognized Component Mark
You will see this type of Mark on appliances and Consumers rarely see these marks because they are
computer equipment, vending machines, household specifically used on component parts that are part of a
burglar alarm systems, lighting fixtures and many other larger product or system. These components may have
types of products. restrictions on their performance or may be incomplete
in construction. The Component Recognition marking is
found on a wide range of products, including some
switches, power supplies, printed wiring boards, some
kinds of industrial control equipment and thousands of
other products. Products intended for Canada carry the
Recognized Component mark "C."
C-UL US Listing Mark
UL introduced this new Listing Mark in early 1998. It
indicates compliance with both Canadian and U.S.
requirements. The Canada/U.S. UL Mark is optional. UL
encourages those manufacturers with products certified
for both countries to use this new, combined Mark, but Recognized Component Mark for Canada and the
they may continue using separate UL Marks for the United States
United States and Canada. This new UL Recognized Component Mark, which
became effective April 1, 1998, may be used on
components certified by UL to both Canadian and U.S.
requirements. Although UL had not originally planned to
introduce a combined Recognized Component Mark, the
popularity of the Canada/U.S. Listing and Classification
Marks among clients with UL certifications for both
Classification Mark Canada and the United States has led to the new Mark.
This mark appears on products that UL has also

5
WWW.TCF.COM
Twin City Fan

TWIN CITY FAN & BLOWER | WWW.TCF.COM


5959 Trenton Lane N. | Minneapolis, MN 55442 | Phone: 763-551-7600 | Fax: 763-551-7601

©2018 Twin City Fan Companies, Ltd.

Das könnte Ihnen auch gefallen