Product Description
ZXDU58 B121(V2.0) Product Description

ZXDU58 B121 (V2.0) Product Description

About the Document


Version Date Author Approved By Remarks
V1.00 8/25/2006 GongChen Not open to the Third Party

Copyright © 2005 ZTE Corporation Shenzhen P. R. China

ZTE CONFIDENTIAL: This document contains proprietary information of ZTE Corporation


and is not to be disclosed or used except in accordance with
applicable agreements.

Due to update and improvement of ZTE products and technologies,


information of the document is subjected to change without notice.

ZTE Confidential Proprietary I


ZXDU58 B121(V2.0) Product Description

Table of Contents

1 Overview.................................................................................................................................. 1
1.1 Application ..................................................................................................................... 1
1.2 Features .......................................................................................................................... 1
1.3 Technical Specifications ................................................................................................ 2
2 Structure and Principle.......................................................................................................... 4
2.1 System Structure and Principle ...................................................................................... 4
2.1.1 System Composition ............................................................................................ 4
2.1.2 Operating Principles of the System...................................................................... 4
2.2 Integrated Chassis .......................................................................................................... 5
2.3 Power Distribution Unit ................................................................................................. 6
2.3.1 Operating Principles of AC Distribution Unit ..................................................... 6
2.3.2 Operating Principles of DC Distribution Unit ..................................................... 6
2.3.3 Front Panel ........................................................................................................... 7
2.3.4 Backplane............................................................................................................. 8
2.4 Rectifier.......................................................................................................................... 8
2.4.1 Structure Description ........................................................................................... 8
2.4.2 Performance Indices............................................................................................. 9
2.4.3 Status Display .................................................................................................... 10
2.4.4 Interfaces............................................................................................................ 11
2.5 Monitor Unit................................................................................................................. 11
2.5.1 Appearance ........................................................................................................ 11
2.5.2 Functions of the Monitor Unit ........................................................................... 13
2.6 Monitor Networking Mode .......................................................................................... 14

ZTE Confidential Proprietary II


ZXDU58 B121(V2.0) Product Description

Figures and Tables


Figures
Figure 1 ZXDU58 B121 Structure (From front view and back view ) ... 4
Figure 2 Operating Principles of the ZXDU58 B121 ............................. 5
Figure 3 Integrated Chassis with Power Distribution Unit ..................... 5
Figure 4 Operating Principles of AC Power Distribution Unit ............... 6
Figure 5 Operating Principles of DC Power Distribution Unit ............... 6
Figure 6 Front panel of the Power Distribution Unit .............................. 7
Figure 7 Backplane of the Power Distribution Unit................................ 8
Figure 8 Front Panel and Back Panel...................................................... 9
Figure 9 Rectifier Indicators ................................................................. 10
Figure 10 Input/Output Integrated Socket............................................... 11
Figure 11 Outer View of the Monitor Unit ............................................. 12
Figure 12 Monitor Networking of Serial Port......................................... 14

Tables
Table 1 Integrated chassis Specification................................................ 2
Table 2 AC power distribution Specification ........................................ 2
Table 3 DC power distribution Specification ........................................ 2
Table 4 Environment Specification ....................................................... 3
Table 5 measurement accuracy of the monitor unit............................... 3
Table 6 Composition of the ZXDU58 B121 System ............................. 4
Table 7 Installation Slots of the Rectifiers and the Monitor Unit.......... 5
Table 8 Components on the Power Distribution Unit Front Panel ........ 7
Table 9 Backplane of the Distribution Unit........................................... 8
Table 10 Rectifier Component Names and Functions ............................. 9
Table 11 Performance Parameters of the ZXD1500 (V4.0) .................... 9
Table 12 Meanings of the Rectifier Indicators ...................................... 10
Table 13 Definitions of Pins of Input/Output Integrated Socket ........... 11
Table 14 Indicators of the Monitor Unit ................................................ 12
Table 15 Data Collection and Processing .............................................. 13
Table 16 Alarm reporting management and protection ......................... 13

ZTE Confidential Proprietary III


ZXDU58 B121(V2.0) Product Description

1 OVERVIEW
This chapter describes the application, features and technical parameters of the
ZXDU58 B121 system.

1.1 Application
The ZXDU58 B121 system is a 30A rectifier and -48 VDC power supply system. It
has such functions as centralized monitor and battery maintenance & management
and allows no attendance. The ZXDU58 B121 can be mounted into the cabinet of
the powered equipment.
ZXDU58 B121 adopts advanced rectifier conversion technologies in the world. It is
applicable to provide power supply for access network equipment, remote switch
offices, mobile communication devices, transmission equipment, ground satellite
transceiver stations, and microwave communication devices.

1.2 Features
The ZXDU58 B121 system offers the following features:
1. Advanced power control technologies and components and following the latest
trend in DC power supply.
2. Uses modular design, automatic current equalization technology, and capable
of N+1 backup and easy expansion.
3. Good electromagnetic compatibility.
4. Intelligent design with a centralized monitor unit capable of “3-remote”
functions (remote measurement, remote information and remote control) and
PC-based management. The monitor unit can communicate with the remote
monitor center so that no human attendance is needed on site. This complies
with the requirement of modern communications technology development.
5. Combination of power control and computing technologies to monitor and
control the parameters and status of rectifiers and AC/DC power distribution
unit in real time.
6. Single-phase AC input and wide range of input voltage, which enables the
system to be used in areas with unstable voltage.
7. Flexible configuration: allowing a maximum of four rectifiers, which are hot-
pluggable.
8. Automatic battery management: The monitor unit measures the charge and
discharge current automatically and enables floating charge and equalized
charge mode of battery.
9. LVD (low voltage disconnect) function: The system will generate audible and
visible alarms when the battery voltage is too low. According to the importance,
loads are divided to two groups. Less important load are powered off firstly to
ensure that important loads can work longer.
10. Multi-class lightning protection assures high reliability of the whole system.
11. Intelligent air cooling with low noise.
12. High reliability with MTBF ≥ 2.2×105 h.
13. Compact structure: Various units, including AC/DC power distribution unit,
rectifiers and the monitor unit, are built in one chassis.

ZTE Confidential Proprietary Page 1 of 14


ZXDU58 B121(V2.0) Product Description

1.3 Technical Specifications


1. Integrated chassis
Table 1 Integrated chassis Specification
Item Specification
265.5 mm x 482.6 mm x 350 mm (height x width x
Dimensions depth)
(19 inches, 6 U in height; 1U = 44.45 mm)
Weight Total weight in full configuration: 32.7 kg (see Note)
Note:
Total weight = 17.5 kg (weight of integrated chassis) + 3.4 kg (weight of rectifier) x 4
+ 1.6 kg (weight of monitor unit) = 32.7 kg
2. AC power distribution
Table 2 AC power distribution Specification
Item Specification
Rated input voltage Single phase 220 V
Voltage range 80 V to 300 V (see Note)
Maximum input current 100 A
Input power factor ≥ 0.99 (with full load)
Class C lightning discharge current ≤ 40 kA
Class D lightning discharge current ≤ 20 kA
Note:
Power control measures are described on next page. Please refer to technical specifications of
rectifier.
3. DC power distribution
Table 3 DC power distribution Specification
Item Specification
Rated output voltage -42 VDC to -58 VDC, adjustable
Output current 120 A (full configuration)
Load output Six output channels, each capacity 6A to 63 A
Standard configuration: two battery input branches
Battery input
and 100 A air switch
Weighted noise voltage < 2 mV
Peak-peak noise voltage ≤ 150 mV (20 MHz bandwidth)
Efficiency ≥ 90% (rated input; full load)
In standard configuration:
Five 1st-shutdown loads (see Note);One 2nd-shutdown
Protection load (see Note).The number of the 1st-shutdown load
and 2nd-shutdown load can be configured according
to the user’s requirements.
DC lightning discharge current ≤ 5 kA
Safety standard Compliant with IEC950 standards
Note:
1st-shutdown load: When the battery voltage falls to a limit, the system will shut down the less-
important loads, which are called 1st-shutdown loads.
2nd-shutdown load: When the battery voltage falls to a lower limit, the system will shut-down all
the loads. The loads that are shut down for the second time are called 2nd-shutdown loads.
4. Rectifier

ZTE Confidential Proprietary Page 2 of 14


ZXDU58 B121(V2.0) Product Description

AC input over/under-voltage protection and power control measures are as follows:


If AC input voltage ≤ 80 V, rectifier has no output.
If 80 V ≤ AC input voltage ≤ 110 V, Imax = (10 ± 2) A and rectifier outputs 33.3%
power.
If 110 V ≤ AC input voltage ≤ 150 V, Imax = (20 ± 2) A and rectifier outputs 66.7%
power.
If 150 V ≤ AC input voltage ≤ 300 V, Imax = (32 ± 1) A and rectifier can output
maximum power.
If AC input voltage ≥ 300 V, rectifier has no output.
Refer to section 2.4 for other technical specifications of the rectifier.
5. Environment
Table 4 Environment Specification
Item Specification
Operating temperature –40°C to +55°C (+15°C to +25°C recommended)
Storage temperature –40°C to +70°C
Relative humidity 10% to 90% (40% to 60% recommended)
Air pressure 70 kPa to 106 kPa
No conductive dusts or corrosive gases; no explosion
Other requirements hazard; no shake or jolt; floor slope angle is no more
than 5°

6. Monitor unit
Local monitoring: The monitor unit of the system has LCD and operation panel,
which enable the user to set system parameters and query system operation data.
Background monitoring: The system provides the RS232/RS485 interface to be
connected to a PC, where the monitor software serves to monitor the ZXDU58 B121
system. Or the system can be connected to a remote PC through modem or others; in
this way, the monitor software in the PC serves to monitor the system remotely.
Note: Please refer to ZTE Background Power Supply Monitor Software (V3.21)
User’s Manual for details.
The table below gives the measurement accuracy of the monitor unit.
Table 5 measurement accuracy of the monitor unit
Item Accuracy
AC voltage ±1%
Battery current and output current ±1%
Battery voltage and output voltage ±0.5%
Temperature ±3°C
Humidity ±5%
Boolean value 100%

ZTE Confidential Proprietary Page 3 of 14


ZXDU58 B121(V2.0) Product Description

2 STRUCTURE AND PRINCIPLE


This chapter describes the system structure and principle of ZXDU58 B121.

2.1 System Structure and Principle


2.1.1 System Composition
The ZXDU58 B121 system is designed as a standard 19-inch chassis with a height
of 6U and consisting of a power distribution unit, rectifiers, and a monitor unit.
Figure 1 shows the system structure.

3
4

1. Integrated chassis 2. Power distribution unit front panel 3. Rectifiers


4. Monitor unit 5. Power distribution unit backplane
Figure 1 ZXDU58 B121 Structure (From front view and back view )
Table 6 lists the components of the ZXDU58 B121 system. One to four ZXD1500
(V4.0) rectifiers can be flexibly configured. For backup, it is recommended that at
least two rectifiers be installed.
Table 6 Composition of the ZXDU58 B121 System
Component Description
Standard 19-inch subrack, 6 U high. The power distribution unit is
Integrated chassis
installed in the chassis before delivery.
The AC and DC power distribution unit are mounted in the
Power distribution unit
integrated chassis.
When fully configured, a ZXDU58 B121 system can contain four
Rectifiers ZXD1500 (V4.0) rectifiers to form a power system up to 120 A
output.
Inserted to the utmost right of the integrated chassis to provide
display, control, alarm and monitoring functions.
Monitor unit Without the monitor unit, the system can still work normally but
without the “3-remote” functions (remote measurement, remote
information, and remote control) and the batteries will be in
floating charge mode.

2.1.2 Operating Principles of the System


Figure 2 shows the operating principles of the system.

ZTE Confidential Proprietary Page 4 of 14


ZXDU58 B121(V2.0) Product Description

Figure 2 Operating Principles of the ZXDU58 B121


z The AC distribution unit inputs and distributes the AC power supply.
z The rectifiers perform AC/DC conversion.
z The DC distribution unit outputs DC power, connects battery to the
system and performs load protection.
z The monitor unit collects information, and implements signal
conversion and alarm function.

2.2 Integrated Chassis


The integrated chassis is designed as a standard 19-inch subrack, with a height of 6U.
The power distribution unit is placed in the chassis before delivery, as shown in
Figure 3.

4
5
7
6
8

1. Integrated chassis 2. Power distribution unit front panel


3. Input/output integrated socket 4. Slot 1 5. Slot 2
6. Slot 3 7. Slot 5 8. Slot 4

Figure 3 Integrated Chassis with Power Distribution Unit


1. There are 5 slots in the integrated chassis. Table 7 lists the components layout
in the slots.
Table 7 Installation Slots of the Rectifiers and the Monitor Unit
Slot Component
Slot 1 ZXD1500 (V4.0) rectifier 1
Slot 2 ZXD1500 (V4.0) rectifier 2
Slot 3 ZXD1500 (V4.0) rectifier 3
Slot 4 ZXD1500 (V4.0) rectifier 4
Slot 5 Monitor unit

ZTE Confidential Proprietary Page 5 of 14


ZXDU58 B121(V2.0) Product Description

2. Four input/output integrated sockets are equipped on the inner wall of the
integrated chassis, as shown in Figure 3. All electrical connections between the
rectifiers and ZXDU58 B121 are realized through these sockets.

2.3 Power Distribution Unit


The power distribution unit integrates AC power distribution and DC power
distribution. The AC power distribution unit completes the access, protection and
distribution of AC power supply. The DC power distribution unit completes the DC
output, access of storage batteries, and load protection.

2.3.1 Operating Principles of AC Distribution Unit


Figure 4 shows the operating principles of AC power distribution unit.
z The single-phase AC input supplies AC power to the rectifiers
through the AC input switch.
z The AC transducer transmits AC input information to the monitor
unit.
z The power distribution unit has the lightning protection function.

Figure 4 Operating Principles of AC Power Distribution Unit

2.3.2 Operating Principles of DC Distribution Unit


Figure 5 shows the operating principles of DC power distribution unit.

Figure 5 Operating Principles of DC Power Distribution Unit

ZTE Confidential Proprietary Page 6 of 14


ZXDU58 B121(V2.0) Product Description

z The output power of rectifiers is transmitted to the DC distribution


unit through the input/output integrated socket.
z Each load and battery loop is configured with a shunt, which detects
the total load current and battery current. In addition, at the load
output port and battery input port are configured with air switches for
over-current protection and short-circuit protection.
z The DC distribution unit has the LVD (low voltage disconnect)
function. When the batteries are discharging, the system will
disconnect the less-important loads if the battery voltage falls to a
limit; the system will disconnect all the loads if the battery voltage
falls to a lower limit to prevent batteries from damage caused by
over-discharge.

2.3.3 Front Panel


Figure 6 shows the front panel of the power distribution unit. Table 8 describes the
air switches and the surge arresters equipped on the front panel.

1. AC input air switch 2. Class C surge arrester


3. Class D surge arrester 4. Load air switches (six totally)
5. Battery air switches (two totally)

Figure 6 Front panel of the Power Distribution Unit


Table 8 Components on the Power Distribution Unit Front Panel
Designation Component Description
To turn on/off the AC input branch with
overload protection;
AC Input AC input air switch
When the AC Input switch is turned on, the
rectifier is powered on.

Surge Arrester Normally, the arrester window is green. When the


Class C surge arrester arrester is damaged by a lightning strike, the window
(Class C) turns red. The surge arrester is hot-pluggable.

Surge Arrester Normally, the arrester window is green. When the


Class D surge arrester arrester is damaged by a lightning strike, the window
(Class D) turns red. The surge arrester is hot- pluggable.

1 Air switch of load 1

2 Air switch of load 2

3 Air switch of load 3 To turn on/off various DC output branches with


DC Output
4 Air switch of load 4 overload protection.

5 Air switch of load 5

6 Air switch of load 6

Battery 1 Air switch of battery 1 To turn on/off battery 1 and battery 2 branch with

ZTE Confidential Proprietary Page 7 of 14


ZXDU58 B121(V2.0) Product Description

Designation Component Description


Input 2 Air switch of battery 2 overload protection.

2.3.4 Backplane
The backplane of the distribution unit is at the back of the cabinet, as shown in
Figure 7.

1
2 3

Figure 7 Backplane of the Power Distribution Unit


Table 9 Backplane of the Distribution Unit
S/N Component Description
External connections to ZXDU58 B121 are completed on
Electrical connection
1 the backplane. The layout of electrical connection terminals
terminal
and signal interfaces are shown in Figure 7.
Normally, the arrester window is green. When the arrester is
2 DC surge arrester damaged by a lightning strike, the window turns red. The
DC surge arrester is hot-pluggable.
3 AC transducer The AC transducer measures the AC input parameters.
Signal
The SIB board provides the interfaces of external signals
4 Interconnecting
for the user.
Board (SIB)

2.4 Rectifier
When fully configured, a ZXDU58 B121 system can contain four ZXD1500 (V4.0)
rectifiers to form a power system up to 120A.

2.4.1 Structure Description


The front panel of the ZXD1500 (V4.0) is equipped with such components as
indicators, section display and handle; the back panel is equipped with input-output
integrated socket. The structure is shown in Figure 8. The component names are
explained in Table 10 .

ZTE Confidential Proprietary Page 8 of 14


ZXDU58 B121(V2.0) Product Description

3
ZXD1500

4 5 7

Figure 8 Front Panel and Back Panel


Table 10 Rectifier Component Names and Functions
No. Component Name Function
1 Section indicator There are 10 section indicators, each of which
represents 3A output current.
2 Indicator There are four indicators, showing the rectifier working
status.
3 Shutter Air inlet
4 Handle Used in installing/uninstalling and handling the
rectifier.
5 Spacer pin Locking the rectifier in position
6 Ventilation holes To ensure the heat dissipation, no barrier can be placed
in front of ventilation holes.
7 Integrated Input/output interface of the rectifier, used for
input/output socket connecting with the power system.

2.4.2 Performance Indices


The performance parameters of the rectifier are listed in Table 11 .
Table 11 Performance Parameters of the ZXD1500 (V4.0)
Technical Feature Parameter
Input mode 1-phase 3-wire mode (L/N/PE)
Input voltage Nominal voltage: 220 VAC; fluctuation range:
80 VAC ~ 300 VAC.
Input Nominal frequency: 50 Hz; fluctuation range:
AC input frequency 45 Hz ~ 65 Hz
Input current Not greater than 10 A.
Efficiency ≥ 90%
Power factor ≥ 0.99
Output power Nominal output: 1500 W; maximum output:
DC output
1800 W
Output voltage Nominal output: 48 VDC
Adjustable range: 42 VDC ~ 58 VDC
continuous adjustable
Current (32 ± 1) A for input voltage 150 VAC ~ 300
limiting VAC (20 ± 2) A for input voltage 110 VAC ~
threshold 150 VAC (10± 2) A for input voltage 80 VAC ~
110 VAC. After current limiting, flyback
occurs when the output voltage decreases to 35

ZTE Confidential Proprietary Page 9 of 14


ZXDU58 B121(V2.0) Product Description

Technical Feature Parameter


VDC ~ 39 VDC.
Voltage ≤ ±0.6%
stabilizing
accuracy
Current A difference below 1.5 A between the
equalizing maximum and the minimum values.
capability
Mechanical Dimensions H × W × D: 134 mm × 87 mm × 290 mm
parameters (excluding integrated socket)
Weight 3.5 kg

2.4.3 Status Display


The working status of the ZXD1500 (V4.0) is represented through the section
indicators and status indicators on the front panels, as shown in Figure 9.

Section indicator

0 30A
IN OUT CL ALM

Input Output Current limiting Alarm

Figure 9 Rectifier Indicators


1. Section Display
Consisting of 10 green section indicators, the section display is used to indicate the
output current. Each section represents 3A output current.
For example, when the output current of the rectifier is 6A, the left two section
indicators are on. For example, when the output current of the rectifier is 8A, the left
two section indicators are on. When the output current of the rectifier is 8A, the left
two section indicators are on and the third indicator is off or dim.
2. Indicator Meanings
There are four status indicators on the front panel of the rectifier. They serve to
indicate the running status of the rectifier. Their meanings are described in Table 12 .
In a normal condition, only the input and output indicators are on.
When current limiting occurs to the output, the current limiting indicator is on.
When an alarm occurs, the alarm indicator is on.
Table 12 Meanings of the Rectifier Indicators
No. Label Name Status Indication Description
1 IN Input Green It is always on for normal AC input.
indicator
2 OUT Output Green It is always on for normal DC output.
indicator
3 CL Current Yellow It is always on for current limiting of
limiting indicator output.
4 ALM Alarm Red indicator It is always on when alarm occurs.

ZTE Confidential Proprietary Page 10 of 14


ZXDU58 B121(V2.0) Product Description

2.4.4 Interfaces
The input/output integrated socket is used for connecting with the power system,
with the interfaces arrangement shown in Figure 10.

26 28
1 3
5 8 11 14 17 20 23
6 9 12 15 18 21 24 27 29
2 4
7 10 13 16 19 22 25

Figure 10 Input/Output Integrated Socket


Note: The numerals stand for the pin numbers.
The pin definitions are described in Table 13 . The electrical connection between
rectifier and power system is implemented through this socket, requiring no other
connections.
Table 13 Definitions of Pins of Input/Output Integrated Socket
Pin No. Signal Definition Description
1 Input 48V+ Corresponding to XJ4 of the MAIN board
3 Output 48V- corresponding to XJ5 of MAIN board
11 REMOTE This signal is the OFF signal, used in the
ON/OFF control over the rectifier by the system.
When high level is input, the rectifier is turned off
(level of 5V). When low level or high resistance
is input, the rectifier is turned on.
12 ALARM Low-resistance output: Corresponding to the
startup process, internal faults or alarms/over-
temperature statuses of the rectifier.
High-resistance output: Corresponding to the
normal working status
13 COM Control ground of the monitoring system
14 ON-LINE Rectifier in-position signal: Directly connected to
the COM signal on the MAIN board
15 PWM Input signal: Requiring a pulse signal with
amplitude of 5 V
16 SHARE-BUS Equalizing current bus: Bidirectional signal
17 FOUT Output signal: 1.5 kHz corresponding to 15 A
26 AC input PE Directly connected to the case through conductor
27 AC input N Corresponding to XJ2 of MAIN board
28 AC input L corresponding to XJ1 of MAIN board
Note: The pins absent from this list are reserved. The MAIN board is a board inside the
rectifier.

2.5 Monitor Unit


2.5.1 Appearance
The monitor unit is inserted to the chassis like a drawer as shown in Figure 11.

ZTE Confidential Proprietary Page 11 of 14


ZXDU58 B121(V2.0) Product Description

1
2
3
4
5
6
7
8
9

1. Appearance 2. LCD 3. Interface 4. Indicator 5. Reset hole


6. Keys 7. Handle 8. Power switch 9. Captive bolt

Figure 11 Outer View of the Monitor Unit


There are an LCD, indicators, a reset hole, keys, a power switch, a handle, and a
captive bolt on the front panel.
z LCD: Displays the real-time data, history data, monitoring
information and alarm information of the ZXDU58 B121 system.
z Indicators: Indicate the operation state of the ZXDU58 B121 system.
Table 14 describes the indicators. When a fault occurs to the
ZXDU58 B121 system, the buzzer will ring, the ALM indicator will
glow, and detailed alarm information will be displayed on the LCD.
Table 14 Indicators of the Monitor Unit
Designation Name Description
PWR Power indicator Glows in green: The unit is electrified.
RUN Run indicator Flashes in green: The unit is running normally.
Equalized Glows in green: The system is in equalized charge
EQU charge mode.
indicator
Communication Flashes in yellow: The unit is communicating with the
COMM
indicator background PC.
ALM Alarm indicator Glows in red: A fault occurs to the system, for
example, the AC input fails, or some rectifier is faulty.
z Keys: Refer to the “ZXDU58 B121 (V2.0) 30A Series Power Supply
System User's Manual” for the definitions and functions of the keys.
z Reset hole: Resets the monitor unit.
z Power switch: This switch is a wane switch. Pressing down the ON
end can turn the monitor unit on. Pressing down the OFF end can turn
the monitor unit off. Restarting the system can reset the monitor unit.
The monitor unit is inserted on the utmost right of the integrated chassis (slot 5). It is
connected to the ZXDU58 B121 system through its back interfaces directly. There’s
no need to connect any other cables between the monitor unit and the system.

ZTE Confidential Proprietary Page 12 of 14


ZXDU58 B121(V2.0) Product Description

2.5.2 Functions of the Monitor Unit


The monitor unit detects the operation status of system and automatically controls
the operation of the whole system. In addition, it transmits the data to the remote
monitor PC or remote monitor center through the communication interface, realizing
unattended maintenance.
The functions of the monitor unit are described as follows:
1. Data collection and processing
Table 15 Data Collection and Processing
Monitored Object Data Collection and Processing
AC distribution unit
AC voltage, AC current, AC input air switch status and class C and D
arrester status

DC distribution unit DC output voltage, battery voltage, battery current, total load current,
status of load output air switch, status of DC contactors and DC
arrester status
Rectifier Power-on/off control of rectifier, recharge status control and in-
position and fault detection

2. Man-machine interactive interface


The LCD and keys enable the user to set the system running parameters and query
the related information.
3. Communication
The monitor unit provides multiple communication interfaces, such as
RS232/RS485/modem. Centralized monitoring can be implemented through modem
or in other ways.
4. Alarm reporting management and protection
The monitor unit processes real-time data, as set by users. If a serious fault occurs,
the unit generates an alarm and reports it to the background PC automatically; in
addition, the unit records and stores fault information. The user can also have access
to alarms through the monitor unit directly. The details are shown below:
Table 16 Alarm reporting management and protection
Item Description
The user can set the upper and lower limits of the system parameters
Alarm setting
according.
Alarm management The system has reliable and real-time alarm management function.
Alarm mode In case of any alarm, the monitor unit generates audible and visual
signal to inform the maintenance personnel and reports the alarm
information to a background PC through its communication interface.
Press any key to mute the alarm sound; then the ALM indicator keeps
glowing until the fault is eliminated.

5. Battery management function


1) Battery charging management
In periodic equalized charging mode and power-on equalized charging
mode after power failure, the monitor unit manages storage battery
charging. The periodic equalized charging indicates that the system makes
the equalized charging for the battery according to the period set by the
user. The power-on equalized charging mode after power failure means
that the AC supply which is cut off resumes to normal after the battery has

ZTE Confidential Proprietary Page 13 of 14


ZXDU58 B121(V2.0) Product Description

been discharged for a period long enough (to be set by users). In this case,
the system automatically charges a storage battery.
2) Battery protection function
When the mains supply is cut off, the battery supplies the power. The
alarm is generated when the voltage of the battery decreases to a certain
degree (adjustable).
When the voltage of the battery decreases to the protection voltage of
primary power-off, cut off the secondary load first. When the further
discharge of battery reaches the protection voltage of the secondary
power-off, cut off the primary load, to prevent the battery from being
damaged due to discharge.
This ensures that the basic load is maintained for a long period of standby
time even after power failure, that the battery is not damaged due to any
over-discharge.
6. Control
Control the power-on, power-off, equalized charging and float charging of the
rectifier through the control instruction of the foreground man-machine interaction
operation or background computer. Adjust the output voltage of the rectifier (-42 V
~ -58 V adjustable continuously) according to the requirements of the user.

2.6 Monitor Networking Mode


The ZXDU58 B121 system supports multiple monitor networking modes, with the
details below:
1. Serial port mode
The ZXDU58 B121 system provides RS232/RS485 serial port. In the serial port
mode, the ZXDU58 B121 system is connected to a background PC through the
serial port (see Figure 12). The background monitor software installed in the PC
serves to realize the local centralized monitoring. The mode is the simplest, but the
distance between the system and the background PC should be no more than 15 m.

RS232

Monitor
ZXDU58 B121 background
system

Figure 12 Monitor Networking of Serial Port


2. Modem mode and other modes
The ZXDU58 B121 system can be connected to a remote PC through modem,
telephone line, or other transmission channel (like the auxiliary channel of
microwave equipment and optical transmission equipment) and auxiliary
communication equipment. For details, refer to the ZTE Background Power Supply
Monitor Software (V3.21) User’s Manual.