Sie sind auf Seite 1von 13

SHV LPG Cooling Tower Water

Treatment Program
Month:DECEMBER-2018

SHV LPG COOLING TOWER MONTHLY REPORT


DECEMBER-2018
Report on the performance of SHV LPG cooling water treatment programme for the
month of December 2018

SUBMITTED TO:
Mr. R.Prabakaran– Manager (SHV LPG)

1
SHV LPG Cooling Tower Water
Treatment Program
Month:DECEMBER-2018

CONTENTS
Page no

1. Chemical Treatment Program 3

2. Recommended CWT Program 4

3. Chemicals Consumption 4

4. Water Analysis Parameters 5

5. Parameters Trend 6

6. Microbiological Analysis Report 12

7. Corrosion Monitoring 12

8. Recommendation 12

9. Conclusion 13

2
SHV LPG Cooling Tower Water
Treatment Program
Month:DECEMBER-2018

1. CHEMICAL TREATMENT PROGRAM

 Make up water sample collection and analysis were carried out on daily basis
at SHV LPG Analysis Laboratory by Sicagen & it was noted that all the
parameters of makeup water with results have little deviations, due to
operational problem and the day to day analysis results were mentioned
herewith in this report.
 Cooling water sample collection & its analysis were carried out on daily basis at
SHV LPG Analysis Laboratory by Sicagen & the obtained results have little
deviations, due to operational problem and the day to day analysis results
were mentioned herewith in this report.
 Bacterial counts TVC and SRB counts were analysed one time in this month and
it was observed that the TVC & SRB counts were in control limits. The obtained
results were mentioned in the report.
Cooling Tower Systems Details

Tower SHV LPG Cooling Tower


Designed and supplied by M/s Paharpur Tower Limited
Service Conditions Continuous
Type Induced Draft Cross flow dual intake
No of Cells 2
Circulation Pumps 3
Inlet Water º C 18
Out Let Water º C 28
Cooling Range ° C 10
System Volume M3 150 M3

3
SHV LPG Cooling Tower Water
Treatment Program
Month:DECEMBER-2018

2. RECOMMENDED COOLING WATER REGULAR TREATMENT


PROGRAM:-

Chemical Name Normal Condition


SCI-3164 40ppm
SCI-3040 10ppm
STRESSPERZ 50ppm
MBR-20P 10ppm
SB-1 50ppm
SB-2 50ppm
SB-5 100ppm
BIOMAC 50ppm
GENCHLOR A & B 10ppm

3. CHEMICAL CONSUMPTION

3.1 CT Chemical Consumption:

NAME OF Opening Received Closing CONSUMPTION


S.NO
CHEMICALS stock Chemicals stock CHEMICALS

1 SCI-3164 35.85 0 31.25 4.6

2 STRESSPERZ 84.3 0 75.3 9.0

3 MBR-20P 37.5 0 28.5 9.0

4 SB-1 40 0 30 10

5 SB-2 40 0 30 10

6 SB-5 50 0 30 20

7 BIOMAC 50 0 40 10

8 SCI-3040 0 0 0 0

9 GENCHLOR A & B 103.2 0 85.2 18.0

10 SCI 7000M 0 0 0 0

4
SHV LPG Cooling Tower Water
Treatment Program
Month:DECEMBER-2018

4. WATER ANALYSIS PARAMETERS:


Makeup water parameters:

Make up Water parameter


Analysis parameter Unit
Design Range Avg parameter
pH 6.8-7.4 9.55
Turbidity NTU Max 1 4.08
Conductivity Micro mhos Max 250 871.25
M.Alkalinity ppm as CaCO3 20-40 83.13
T.Hardness CaCO3 as ppm 60-80 131.88
Ca.Hardness CaCO3 as ppm 40-60 47.96
Silica ppm 8-15 13.38
Sulphate ppm SO4 20-50 40.08
Chloride ppm 20-50 223.17
T.Iron ppm Max 0.1 0.11

LPG CT water parameters:

ACT Water parameter


Analysis parameter Unit
Design Range Average parameter
pH - 7.2-7.8 8.01
Turbidity NTU Max 50 13.75
Conductivity Micro mhos Max 3000 1611.67
Ca.Hardness CaCO3 as ppm 250-350 95.63
T.Hardness CaCO3 as ppm Max 500 240.83
Silica ppm Max 70 24.29
Sulphate ppm SO4 Max 800 101.29
Chloride ppm Max 700 415.96
T.Iron ppm Max 2 1.95
M.Alkalinity CaCO3 as ppm 100-300 92.71
Zinc ppm 1.5-2.0 1.87
COC - 4-6 1.92
Phosphate ppm 8-10 8.79
FRC ppm 0.3-0.5 0.10
5
SHV LPG Cooling Tower Water
Treatment Program
Month:DECEMBER-2018

5. PARAMETERS TREND:

5.1 pH trend

10
9.8 LPG pH MAKEUP pH
9.6
9.4
9.2
9
8.8
8.6
8.4
8.2
8
7.8
7.6
1 3 4 5 6 7 8 10 11 12 13 14 15 17 18 19 21 22 24 26 27 28 29 31

5.2 Turbidity trend

31
LPG Turb MAKEUP Turb
28
25
22
19
16
13
10
7
4
1
1 3 4 5 6 7 8 10 11 12 13 14 15 17 18 19 21 22 24 26 27 28 29 31

6
SHV LPG Cooling Tower Water
Treatment Program
Month:DECEMBER-2018

5.3 Conductivity trend

2600

2300 LPG Cond


MAKEUP Cond
2000

1700

1400

1100

800

500
1 3 4 5 6 7 8 10 11 12 13 14 15 17 18 19 21 22 24 26 27 28 29 31

5.4 M.Alkalinity trend

120
LPG M-Alk
MAKEUP M-Alk
110

100

90

80

70
1 3 4 5 6 7 8 10 11 12 13 14 15 17 18 19 21 22 24 26 27 28 29 31

7
SHV LPG Cooling Tower Water
Treatment Program
Month:DECEMBER-2018

5.5 Ca.Hardness trend

130
LPG CaH
120 MAKEUP CaH

110

100

90

80

70

60

50

40
1 3 4 5 6 7 8 10 11 12 13 14 15 17 18 19 21 22 24 26 27 28 29 31

5.6 chloride trend

700
LPG CL2

600 MAKEUP CL2

500

400

300

200

100
1 3 4 5 6 7 8 10 11 12 13 14 15 17 18 19 21 22 24 26 27 28 29 31

8
SHV LPG Cooling Tower Water
Treatment Program
Month:DECEMBER-2018

5.7 Silica trend

29 LPG SiO2
27 MAKEUP SiO2

25
23
21
19
17
15
13
11
9
1 3 4 5 6 7 8 10 11 12 13 14 15 17 18 19 21 22 24 26 27 28 29 31

5.8 Total Iron trend

3
2.7 LPG T.Fe
MAKEUP T.Fe
2.4
2.1
1.8
1.5
1.2
0.9
0.6
0.3
0
1 3 4 5 6 7 8 10 11 12 13 14 15 17 18 19 21 22 24 26 27 28 29 31

9
SHV LPG Cooling Tower Water
Treatment Program
Month:DECEMBER-2018

5.9 Ortho phosphate trend

11
LPG O'PO4
10

5
1 3 4 5 6 7 8 10 11 12 13 14 15 17 18 19 21 22 24 26 27 28 29 31

5.10 Dispersant trend

40
LPG DISP
39
38
37
36
35
34
33
32
31
30
1 3 4 5 6 7 8 10 11 12 13 14 15 17 18 19 21 22 24 26 27 28 29 31

10
SHV LPG Cooling Tower Water
Treatment Program
Month:DECEMBER-2018

5.11 FRC trend

0.3
LPG FRC
0.3

0.2

0.2

0.1

0.1

0.0
1 3 4 5 6 7 8 10 11 12 13 14 15 17 18 19 21 22 24 26 27 28 29 31
-0.1

5.12 COC trend

2.4
2.3 LPG COC

2.2
2.1
2
1.9
1.8
1.7
1.6
1.5
1.4
1 3 4 5 6 7 8 10 11 12 13 14 15 17 18 19 21 22 24 26 27 28 29 31

11
SHV LPG Cooling Tower Water
Treatment Program
Month:DECEMBER-2018

6. MICROBIOLOGICAL ANALYSIS REPORT:


Biocide dosed Three times during this month. TBC and SRB were in under control.
6.1 Bactaslyde Results:

TBC(Colonies/ml) SRB(MPN/100ml)
SAMPLE Date Biocide
After After

LPG CW 24-Dec-18 SB 2 <100000


100

7. CORROSION MONITORING:
Sample coupon : Unpassivated MS
Installation date : 06-12-2018
Inspection (Removal) date : 02-01-2019
Evaluation : Sicagen
The results are tabulated as under:
No of
S. No Coupon Type Location Corrosion Rate
days
Limit < 3 MPY
1 MS Return Head 28 0.02

8. RECOMMENDATION:
 Maintain the circulation water PH between 7.2 - 7.8
 The Phosphate – intrusion into the system may be identified and arrested, so
that the contribution on microbial growth may be minimized.
 It is recommended to dose SCI 3040 & SCI 3164 as Zn & OPO4 supplementary
to give cathodic & anodic protection to the system.
 It is recommended to dose SCI-7000M (High chloride & conductivity values
may leads to corrosion into the system)

12
SHV LPG Cooling Tower Water
Treatment Program
Month:DECEMBER-2018

9. CONCLUSION:
From the above, it is found that the cooling water treatment
programme is performing satisfactorily.

For Sicagen India ltd


Speciality Chemicals Division
J.Thanga Selvan
Assistant Manager.

13