Beruflich Dokumente
Kultur Dokumente
a r t i c l e i n f o a b s t r a c t
Article history: The transient stability of power systems is highly affected by the changes in the power generation and
Received 21 February 2014 load levels. Due to the variability of the generating resources, the system stability can be provoked
Received in revised form 16 January 2015 and the system stability limits can be reached as a result of certain sudden drop in the power generation.
Accepted 31 January 2015
In these cases, the load shedding can act as an effective emergency corrective action for keeping system
stability; however, over-shedding of loads results in severe economical as well as social security prob-
lems. Therefore, minimization of the load shedding required for the restoration of the system stability
Keywords:
is one of the main objectives of this paper. Another critical issue related to successful load shedding is
Transient stability
Equal area criterion (EAC)
the fast assessment of the system stability, and the amount of the load shedding as well as the implemen-
Extended equal area criterion (EEAC) tation of the load shedding corrective action. Therefore, this paper presents a fast method of stability
Variability in power generation assessment and load shedding requirements in the weakly interconnected power system. The method
Renewable energy is an improved form of the extended equal area criterion (EEAC) where the required system equivalence
Load shedding is based on the availability of wide area monitoring (WAM) devices in modern power systems. The paper
also investigates the impact of the implementation duration of the required load shedding. The results
are verified through time domain simulations which confirm the accuracy of the presented method
and its suitability for real-time applications.
Ó 2015 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.ijepes.2015.01.034
0142-0615/Ó 2015 Elsevier Ltd. All rights reserved.
100 M. El-Shimy / Electrical Power and Energy Systems 70 (2015) 99–107
renewable energy sources may not provide the main operation components or faults, emergency control and protection schemes
requirements of power grids. must be used to restore the system frequency and stability [22].
From the security point of view, the sudden significant changes Under frequency load shedding (UFLS) is an effective and fast
in the power production (or power swings) from variable renew- emergency corrective action. UFLS shows success in preventing
able can upset the stability of power systems especially when probable system instability due to large disturbances [10,22]. The
the amounts of variable generation are large. Variability in the main objective of an UFLS strategy is rapidly balancing the demand
power generation can be detected in conventional and renewable with the available supply. For weakly interconnected systems, this
energy sources. The main reason of this variability is the lack of paper presents a simple and fast method for real-time estimation
the required input primary resources such as non-renewable fuels of the necessary load shedding in generation drop situations. The
or renewable resources. In addition, some of the generation vari- method is based on extended equal area criterion (EEAC) approach
ability is attributed to the forced outage of generating units due which extended the application of the traditional equal area
to failures. These failures can be internal (i.e. within the generating criterion (EAC) [20,21] to multimachine systems [23–28].
units) or external (i.e. in the power networks). This paper focuses The first step in the EEAC is reducing the system to a single
on the real-time impact of the sudden changes in the power pro- machine infinite bus (SMIB) system. To do so, the machines are
duction on the stability of power systems. decomposed into two clusters or groups. The first group contains
Currently, wind energy is one of the most prevalent adopted the critical machine(s) while the second group contains the rest
renewable power sources [11,12]. Historically, there was an agree- of the machines. Each group is then aggregated into one equivalent
ment that wind turbines do not engage in the electromechanical machine and these two machines are further aggregated into one
oscillations (EMOs) [13–15]. This was based on the facts that wind equivalent machine. Therefore, the multimachine system is
power sources were considered as current sources. For example, a reduced finally to a SMIB system on which the EAC can be easily
DFIG was considered as a current source under the traditional applied. It is found that the EEAC system reduction method and
power factor control operation [13–15]. In either a weak grid or the resulting equivalent will not accurately represent the dynamics
a grid with large amounts of wind power, the ancillary voltage/fre- of the original power system unless the machines comprising each
quency control of wind farms are required for stabilization of pow- group are coherent [25,29,30].
er systems [8,16]. Consequently, recent wind farms react as The impact of sudden changes in the power production consid-
synchronous generators and engage in EMOs; however, there are ering weakly interconnected systems is presented in this paper. In
already many grid-connected uncontrollable wind farms that addition, transient stability-based minimization of load shedding is
made up with squirrel cage induction generators (SCIG) that are determined. The equivalence of power systems required for the use
directly connected to the grid. These kinds of wind farms may sig- of EEAC is improved by determination of its parameters from pow-
nificantly affect the stability of power systems as their power con- er system measurements available from WAMs. In addition, the
trol capability is very limited. presented equivalency method is not only applicable for standard
Unlike conventional power sources, the placement renewable conventional synchronous generators, but also covers any electric
power sources are mainly dependent on the availability of the power sources. In addition, the method can be applied at any bus
renewable resources. Usually, the feasible locations for renewable in a power system if the required measurements are available.
energy projects are remotely located with respect to the power The EEAC approach is utilized for providing fast analysis and deci-
grid [17–19]. Therefore, renewable sources are usually connected sion making for real-time applications. The impact of the delay in
to the grid via long transmission systems that presents weak links. the implementation of the load shedding corrective action is inves-
Generally, a transmission link (or tie-line) interconnecting two sys- tigated. In addition, the presented method and results are verified
tems or two areas is said to be weak if its power capacity is smaller through time domain simulation.
than the capacity of the smaller system by about 15–20% [20].
Traditional generation loss contingency analysis considers
forced outage of generating units caused by internal or external Study system and modeling
failures [10]; however, integration of variable renewable sources
adds additional power production contingencies [6,7]. These new Fig. 1 shows the study system and its equivalent. It consists, as
contingencies are due to the resource-based power production shown in Fig. 1(a), of two weakly interconnected areas or systems.
loss. The intense variability and intermittency of a renewable It is assumed that the generators in area 2 are highly variable while
resources cause significant sudden changes in the power produc- area 1 comprises less variable power sources. In both areas sudden
tion and stability harassment. drop in the power generation may be attributed to forced outage of
Following a large generation loss, the system frequency may generators, or faults, or unavailability of the primary energy
drop quickly if the remaining generation no longer matches the resources. In area 2, the variability of the power sources causes
load demand. Without adequate system response, loss of gen- sudden changes in the output power of the generators. These sud-
eration can produce extreme frequency excursions outside the den changes may cause emergency stability problems if the drop in
acceptable range of power plants, degradation of the load response, the power sources is intense and rapid. In such situations, load
overloading transmission lines, and may lead to system collapse shedding is implemented to ensure system stability by curtailing
[21,22]. Therefore, real-time assessment of the impact of sudden sufficient system loads for matching the available generation with
generation loss on the stability should be provided. In addition, fast the remaining loads and keeping the system stability.
and effective emergency corrective actions should be taken to pre- Typically, load shedding is implemented to protect the system
vent cascaded outage of generating units, instability and islanding against the decline of either the frequency or the voltage or both
of the system, and even system blackout. of them. In this analysis, the load shedding is implemented to pro-
Depending on the size of the frequency deviation caused by a tect the system interconnection against frequency declines that
disturbance, emergency control and protection schemes may be cause system instability. Due to the delay in the propagation of fre-
required for maintaining the system frequency and stability. quency changes in weakly interconnected systems, there is a ten-
Normal operation frequency deviations are small enough to be dency to localize the power adjustments following large
controlled by the governor natural autonomous response (i.e. contingencies [22,31,32]. In addition, the localized power adjust-
primary control) and load frequency control (LFC). With large ments have a significant improvement on the system stability
frequency deviations that may be caused by the outage of [31]. Therefore, drop of generation in a specific area will be pri-
M. El-Shimy / Electrical Power and Energy Systems 70 (2015) 99–107 101
Fig. 1. The study system: (a) schematic diagram; (b) two-machine equivalence; (c) equivalent circuit of the two-machine system; (d) SMIB equivalence.
marily compensated by load shedding within that area unless The equivalent inertia at a specified bus can be estimated using
more necessary actions should be taken. active power and frequency measurements at that bus [32,33,36–
For implementation of the EEAC, the original system shown in 40]. These measurements are performed under disturbed condi-
Fig. 1(a) should be subjected to two processes of electromechanical tions. Since this method treats the original subsystem as a black
reductions. In the first process shown in Fig. 1(b) and (c), each area box, it is general and can be applied to any mix of generating tech-
is reduced to one equivalent generator while a SMIB equivalent is nologies. Conventional equivalency methods did not provide that
determined in the second process as shown in Fig. 1(d). The main flexibility [29,30,41].
assumption here is that the dynamic coupling between the aggre- In [33,36–40] a simple approach is presented for the estimation
gated generators is strong enough for accurate dynamic equiva- of the system inertia and time of the disturbances. The approach is
lence. The first reduction process can be easily achieved through based on the fundamental swing equation which takes the form
the application of the standard Center of Area (COA) method [10,20,21,33]
[24,25,28]; however, emerging and future power systems are
expected to contain numerous generation technologies. The main Mdf ðtÞ=dt ¼ Pm ðtÞ Pe ðtÞ ð1Þ
issue related to these emerging technologies, especially those with where M is the angular momentum at rated speed or the inertia
Full-Scale Converter (FSC) interface, is inertia of these generating constant in seconds (M = 2 H), f is the electrical frequency in p.u, t
systems and their appropriate dynamic representation. is the time, Pe is the electrical power in p.u, and Pm is the mechanical
In the first reduction process, each area is reduced to a single power in p.u. Since the mechanical power changes are significantly
equivalent synchronous generator (see Fig. 1(a)–(c)). Each equiva- slow in comparison with the electrical changes, then the swing
lent generator is represented by three quantities or parameters; equation for a small measurement interval (Dt) can be represented
the inertia constant (M), a transient impedance (Zeq), and a con- with only measurable electrical quantities. Consequently the inertia
stant voltage (Eeq). Although the assumption of the constant volt- can be determined at the location of measurements using
age during the transients is not valid in systems with automatic
-1
excitation control, the use of this fixed voltage is acceptable within M ¼ ff_ ðt þ Þ f_ ðt Þg=ðP e ðt Þ Pe ðtþ ÞÞ ð2Þ
the initial instants (t+) of the transient process [34]. In addition, in
the EEAC and EAC analysis, the impact of generator automatic con- where f_ is df/dt. Eq. (2) is valid for times immediately before and
trols is usually neglected. The parameters of the equivalent gen- after a disturbance (i.e. t and t+) reaching the location of the fre-
erators are determined by measurements at the interface buses quency and active power measurements. Therefore, the equivalent
using appropriate monitoring devices [32,33,35]. At the interface inertia of each area in the study system shown in Fig. 1(a)–(c) can
buses, the required measurements are bus frequency, bus voltage, be determined at the interface buses. Based on the measurements
active power, and reactive power. In this paper, required measure- at t+, the equivalent impedances and voltages shown in Fig. 1(c)
ments are obtained from system simulation. are determined by the method presented in [34].
102 M. El-Shimy / Electrical Power and Energy Systems 70 (2015) 99–107
Fig. 4. The study system and its equivalence: (a) detailed system; (b) first reduction process; (c) second reduction process (SMIB).
Table 1
Equivalent inertia (M) in sec, p.u transient reactances, and p.u transient emf (E0 ); all values are on 100 MVA base.
the change electric power demand shows that the same impact as nario becomes 550 MW in the second scenario. The wind farm is
the changes in the mechanical power. formed of 100 identical squirrel-cage induction-generator (SCIG)
based wind turbine generators (WTGs) each of 2 MVA rating. The
parameters of the wind turbines are available at [42–44]. The
Case study
Table 2
The IEEE two-area weakly interconnected system [21,34] Study cases for verification.
shown in Fig. 4(a) is used to represent the study system shown
Scenario 1 (no wind) Scenario 1 (with wind)
in Fig. 1(a).
The parameters of the generators and network are taken from Case 1 5.0 MW drop in the 4.0 MW drop in the
generation of area 2 generation of area 2
[34] while the loads, generator active power settings, and reactive
Case 2 5.6 MW drop in the 4.9 MW drop in the
power compensation values are taken from [21]. All loads are rep- generation of area 2 generation of area 2
resented by a constant impedance model. With these values, area 1 Case 3 6.0 MW drop in the 6.0 MW drop in the
is exporting 400 MVA to area 2. Two structural scenarios are con- generation of area 2 generation of area 2
sidered. In the first scenario, no wind power is included in the sys- Case 4 6.0 MW drop in the 6.0 MW drop in the
generation of area 2 and generation of area 2 and
tem generation mix. In the second scenario, 150 MW of the 0.4 p.u simultaneous load 1.1 p.u simultaneous load
conventional power generated in area 2 is replaced by wind power. shedding shedding
Therefore, the 700 MW power generations from G4 in the first sce-
104 M. El-Shimy / Electrical Power and Energy Systems 70 (2015) 99–107
DPmin
d2 ¼ DP g2 þ 5:6 ð17Þ
DPmin
d2 ¼ DP g2 þ 4:9 ð18Þ
Fig. 5. Dynamic performance associated with sudden changes in the generation and
load – Scenario 1; (a) cases 1, 2, and 4; (b) case 3.
equivalents of the system (shown in Fig. 4(b) and (c)) are deter-
mined by the presented equivalency method. Evaluation of the
equivalency results is performed by the comparing the transient
performance of the detailed system and its equivalent SMIB sys-
tem. The following section presents these results as well as the
use of EAC for minimum load shedding estimation.
Fig. 7. Impact of load shedding delay; (a) simultaneous load shedding; (b) delayed load shedding.
Fig. 8. Impact of load shedding delay on the minimum required load shedding
considering both scenarios – EAC approach.
figures show the rotor angle swing of area 2 relative to area 1. The
time-domain simulations are performed using PSAT 1.8 [45] on
Matlab 2012 [46]. These figures ensure the accuracy of the present-
ed method in predicting the system transient response and
minimization of the load shedding requirements.
From a practical point of view, the simultaneous drop in the
power generation and the required load shedding is technically
impossible. Therefore, the impact of delayed load shedding on Fig. 9. Impact of shedding delay time on the minimum amount of load shedding –
the system stability and the validity of the presented results are time-domain simulation.
106 M. El-Shimy / Electrical Power and Energy Systems 70 (2015) 99–107
[13] Yuanzhang S, Lixin W, Guojie L, Jin L. A review on analysis and control of small [31] You H, Vittal V, Yang Z. Self-healing in power systems: an approach using
signal stability of power systems with large scale integration of wind power. islanding and rate of frequency decline-based load shedding. IEEE Trans Power
In: IEEE International conference on power system technology (POWERCON), Syst 2003;18(1):174–81.
2010 Hangzhou; 2010. p. 1–6. [32] Tsai S-J, Zhang L, Phadke AG, Liu Y, Ingram MR, Bell SC, et al. Frequency
[14] Slootweg J, Kling W. The impact of large scale wind power generation on sensitivity and electromechanical propagation simulation study in large power
power system oscillations. Electr Power Syst Res 2003;67(1):9–20. systems. IEEE Trans Circ Syst I: Regul Papers 2007;54(8):1819–28.
[15] Domínguez-García JL, Gomis-Bellmunt O, Bianchi FD, Sumper A. Power [33] Wall P, González-Longatt F, Terzija V. Demonstration of an inertia constant
oscillation damping supported by wind power: a review. Renew Sustain estimation method through simulation. In: 45th International universities
Energy Rev 2012;16(7):4994–5006. power engineering conference (UPEC), Cardiff, Wales: IEEE; 2010. p. 1–6.
[16] Jadhav H, Roy R. A comprehensive review on the grid integration of doubly fed [34] Chow JH, Chakrabortty A, Vanfretti L, Arcak M. Estimation of radial power
induction generator. Int J Electr Power Energy Syst 2013;49:8–18. system transfer path dynamic parameters using synchronized phasor data.
[17] Ackermann T, editor. Wind power in power systems. USA: Wiley Online IEEE Trans Power Syst 2008;23(2):564–71.
Library; 2005. [35] Ota Y, Hashiguchi T, Ukai H, Sonoda M, Miwa Y, Takeuchi A. Monitoring of
[18] El-Shimy M. Optimal site matching of wind turbine generator: case study of interconnected power system parameters using PMU based
the Gulf of Suez region in Egypt. Renew Energy 2010;35(8):1870–8. WAMS. Lausanne: IEEE Power Tech; 2007. p. 1718–22.
[19] El-Shimy M. Viability analysis of PV power plants in Egypt. Renew Energy [36] Inoue T, Taniguchi H, Ikeguchi Y, Yoshida K. Estimation of power system
2009;34(10):2187–96. inertia constant and capacity of spinning-reserve support generators using
[20] Venikov VA. Transient processes in electrical power systems. Moscow: Mir measured frequency transients. IEEE Trans Power Syst 1997;12(1):136–43.
Publishers; 1977. [37] Chassin DP, Huang Z, Donnelly MK, Hassler C, Ramirez E, Ray C. Estimation of
[21] Kundur P, Balu NJ, Lauby MG. Power system stability and control. New WECC system inertia using observed frequency transients. IEEE Trans Power
York: McGraw-hill; 1994. Syst 2005;20(2):1190–2.
[22] Bevrani H. Robust power system frequency control. Springer; 2008. [38] Wall P, Gonzalez-Longatt F, Terzija V. Estimation of generator inertia available
[23] Xue Y, Van Custem T, Ribbens-Pavella M. Extended equal area criterion during a disturbance. In: Power and energy society general meeting. San
justifications, generalizations, applications. IEEE Trans Power Syst Diego, CA: IEEE; 2012. p. 1–8.
1989;4(1):44–52. [39] Gonzalez-Longatt FM. Effects of the synthetic inertia from wind power on the
[24] Xue Y, Pavella M. Extended equal-area criterion: an analytical ultra-fast total system inertia: simulation study. In: 2nd International symposium on
method for transient stability assessment and preventive control of power environment friendly energies and applications (EFEA). Newcastle: IEEE; 2012.
systems. Int J Electr Power Energy Syst 1989;11(2):131–49. p. 389–95.
[25] Dong Y, Pota H. Transient stability margin prediction using equal-area [40] Zhang Y, Bank J, Wan YH, Muljadi E, Corbus D. Synchrophasor measurement-
criterion. IEE Proc C (Generat, Transm Distrib) 1993;140(2):96–104. based wind plant inertia estimation. In: IEEE Green technologies conference.
[26] Chang H-C, Wang M-H. Another version of the extended equal area criterion Denver: IEEE; 2013. p. 494–9.
approach to transient stability analysis of the Taipower system. Electr Power [41] Milano F, Srivastava K. Dynamic REI equivalents for short circuit and transient
Syst Res 1992;25(2):111–20. stability analyses. Electr Power Syst Res 2009;79(6):878–87.
[27] Chiodo E, Lauria D. Transient stability evaluation of multimachine power [42] El-Shimy M, Badr M, Rassem O. Impact of large scale wind power on power
systems: a probabilistic approach based upon the extended equal area system stability. In: Power system conference, 12th international middle-east
criterion. IEE Proc Gener, Transm Distrib 1994;141(6):545–53. power conference (MEPCON). Aswan, Egypt: IEEE; 2008. p. 630–6.
[28] Choo YC, Kashem MA, Negnevitsky M. Transient stability assessment of a small [43] El-Shimy M, Ghaly N, Abdelhamed M. Parametric study for stability analysis of
power system subjected to large disturbances. Australasian Universities Power grid-connected wind energy conversion technologies. In: 15th International
Engineering Conference (AUPEC); 2006. p. 1–5. middle-east power conference (MEPCON). Alex., Egypt: IEEE; 2010. p. 1–8.
[29] Abuel-wafa AR, EL-Shimy M. Coherency-based electromechanical equivalents [44] EL-shimy M, Ghaly B. Grid-connected wind energy conversion systems:
for use in power system stability studies. Sci Bull – Facul Eng – Ain Shams Univ transient response. In: Encyclopedia of energy engineering and Technology.
2003;38(3):475–87. 2nd ed., vol. IV. CRC Press, Taylor & Francis Group; 2014. p. 2162–83.
[30] Abuel-wafa AR, EL-Shimy M. Treatment of large-scale power systems in [45] PSAT 2.18, Jan. 6; 2013. <http://faraday1.ucd.ie/psat.html>. [accessed:
transient stability studies. Sci Bull – Facul Eng – Ain Shams Univ 20.02.14].
2003;48(4):675–87. [46] MATLAB; 2012. <http://www.mathworks.com/>. [accessed: 20.02.14].