Sie sind auf Seite 1von 3

Classification: Internal Use

Classification: Internal Use


Rev. No.: 08
Dated: Aug/2017 EQUIPMENT / PIPING THICKNESS MEASUREMENT SHEET
SMP / WI No.: SMP-INSP-051
INSPECTION DEPARTMENT
Page: 1 of 1
Sketch Thickness Thickness Reading
Insulation - No Measurement
Orig.
(mm)
Remark(s)

N Scaffolding- 2 Location *
Thk.
(mm) 0 90 180 270 N E S W
(TMLs)
1-2ӯ 2.9 3.5 3.0 - 2.6 ELBOW
2-2ӯ 2.9 3.8 3.7 3.7 3.5
3-2ӯ 2.9 3.5 3.4 2.8 - ELBOW
4-2ӯ 2.9 3.3 3.8 3.0 3.9
8 5-2ӯ 2.9 3.3 3.6 3.7 3.0
6-2ӯ 2.9 3.3 3.6 3.0 3.4
6 7-2ӯ 2.9 3.5 3.6 3.1 3.8
10 8-2ӯ 2.9 3.5 3.6 2.7 - ELBOW
9-2ӯ 2.9 3.2 3.2 2.4 3.2
7 9 10-2ӯ 2.9 3.5 3.8 3.0 3.5
4
5

3 TW-8201

2
1

TV-8205

Thickness Gauge S.R. No. : GE DM5E (S/N: 1309726)


LINE # 50-KC/CL-8232122-BB31A Calibration date : 23-DEC-2018
Probe # and Frequency : DK-537 - 5 MHz (S/N: 1835/58)
Applicable Procedure : PK SHEM 7.05 & SMP-INSP-051
Criteria for passing Inspection : API 570
Eqpt. / Piping Material : A 106 GR.B / A 53 GR.B
Corrosion Allowance (mm) : 1.2 mm
Corrosion Rate (mm / Year) : -
Remaining Life (Year) : -
Surface Temperature (ºC) : AMBIENT
Condition of Piping : Satisfactory X Unsatisfactory
:
Recommendation (if any)
Classification: Internal Use
Plant : VCM – UNIT 82 Description : FROM TV-8205 TO TW-8201 Inspector(s) : ADAM Date : 06/06/2019
Eqpt / Line No. : 50-KC/CL-8232122-BB31A Service : CAUSTIC JP