SIPROTEC 5

Generator Protection
Unrestricted © Siemens AG 2018 Siemenes.com/siprotec5

Unrestricted © Siemens AG 2018


Page 1
Agenda

• General and device overview


• Typical applications
• Protection Benefits

Unrestricted © Siemens AG 2018


Page 2 October 2018 Automation Products
SIPROTEC 5 –
Fields of use along the entire energy value chain

Generation Transmission Distribution Industry

SIPROTEC 5

Unrestricted © Siemens AG 2018


Page 3 October 2018 Automation Products
SIPROTEC 5
The answer to trends and customers’ challenges

Individually configurable devices –


+
Cost-efficient solution over the entire life cycle

Trendsetting system architecture –


+
Flexibility and security for highly meshed systems

Multilayered security mechanisms –


+
Maximum possible security and availability

Consistent engineering for system and devices –


+
Efficient operation concepts, flexible engineering

SIPROTEC 5 –
The benchmark for protection, automation and monitoring in changing environments
Unrestricted © Siemens AG 2018
Page 4 October 2018 Automation Products
Generator Protection
You need powerful functionality and flexibility?

Then you should go for SIPROTEC 5!

Powerful engineering with DIGSI5

Modular hardware
Basic module +
up to 9 expansion modules
Modular and flexible communication
Different plug-in modules
Different protocols
Flexible Functionality Security inside
87G 87T 40 49T 46 51 64S 51N 67 67Ns 27 59 81 25 32 21 24

Unrestricted © Siemens AG 2018


Page 5 October 2018 Automation Products
Hardware –
tailored, robust and user-friendly

Unrestricted © Siemens AG 2018


Page 6 October 2018 Automation Products
Generator protection
Online-Configurator – Define your device

Define your own device according to your requirements!


Modify the standard variant by adding or changing modules according to the required number of current and
voltage inputs and binary IOs.

7UM85 Generator protection AA3:

Replacement of IO202
by IO201, as 4 VTs are Possible expansion modules
sufficient for the
application

Select the new expansion module

Unrestricted © Siemens AG 2018


Page 7 October 2018 Automation Products
SIPROTEC 5 –
Devices and Fields of Application

Overcurrent and feeder


protection 7SJ8 7SS85 Busbar protection

Distance protection 7SA8 7SK8 Motor protection

Line differential protection 7SD8 7VK8 Breaker management

Combined line differential &


7SL8 7UM85 Generator protection
distance protection

Transformer differential
7UT8 6MD8 Bay controller
protection

Paralleling device 7VE85 7KE85 Fault recorder

Easy engineering and evaluation with DIGSI and SIGRA

Unrestricted © Siemens AG 2018


Page 8 May 2018 Automation Products
DIGSI 5 –
Easy parameter settings

The graphical representation of the characteristics is advantageous

Unrestricted © Siemens AG 2018


Page 9 October 2018 Automation Products
DIGSI 5 –
Integrated Test Suite
The DIGSI 5 Test Suite offers
• Simulation of binary signals and
analog sequences by integrated test
equipment
• Hardware and wiring test
• Testing device functionality and
protection functions
• Circuit-breaker and AR test functions
• Communication test incl. loop test
• Analysis of logic diagrams

Extensive test and diagnostic functions shorten the testing and


commissioning phase significantly
Unrestricted © Siemens AG 2018
Page 10 October 2018 Automation Products
Agenda

• General and device overview


• Typical applications
• Protection Benefits

Unrestricted © Siemens AG 2018


Page 11 October 2018 Automation Products
Generator protection

Tipo de Falla Causa Efecto

Estator a tierra Deterioro aislamiento


Destrucción del laminado del Estator
(59N, 67Ns, 27/59TH), 64S (100%) Sobretensiones
Rotor a tierra
Problemas de aislamiento Fallas subsecuentes
64F (1-3 Hz)
Pérdida de excitación (40) [21] Problemas circuito de excitación Generador Asincrónico
Falla regulador de velocidad
Sobrexcitación (24) (V/Hz) Temperatura excesiva, sobrevelocidad
Carga excesiva (P,Q)
Diferencial de generador (87) Fallas dentro de la zona protegida Afectación de la máquina

Fuera de paso (78) Inestabilidad transitoria Sobrecorrientes variables, esfuerzos mecánicos


Potencia inversa (32R) Pérdida de fuerza motriz primaria Motorización, Cavitación

Energización inadvertida (50/27) Errores de operación Motorización, daño del rotor

Frecuencia (81 O/U) Cambio repentino de carga Sobrevelocidad, SSAA, Pérdida de sincronismo

Sobretension (59) Fallas externas Temperatura excesiva

Asimetría (46) Fallas en la red Temperatura excesiva, 120 Hz

Unrestricted © Siemens AG 2018


Page 12 October 2018 Automation Products
Application template:
Generator Basis

FG Circuit breaker A-QA


A-QA
V-3ph

V-3ph

I-3ph

Ctrl

FG Generator stator BI
CB
MP 24 BO
V-3ph
V-3ph 27
RGF-Coupling
32R
46
MP I-3ph 51V
G I-3ph 59
59N
MP V-SGF 81
V-1ph
I-SGF

Measured values

FG V/I-1ph

V-1ph
64F
I-1ph
MP
I-1ph 1

Measured values

Unrestricted © Siemens AG 2018


Page 13 October 2018 Automation Products
Application template:
Generator Busbar Connection Basis

A-QA

FG Generator side1 FG Circuit breaker A-QA


MP
I-3ph 49 V-3ph
I-3ph 1
V-3ph

Measured values I-3ph

Ctrl

FG Generator stator BI
CB
MP BO
V-3ph 24
V-3ph
RGF-Coupling devices 27
32R
MP I-3ph 40
G I-3ph
46
51V
FG Generator diff

MP 59
V-SGF 59N
V-1ph 87G
67Ns
MP I-SGF 81
I-1ph 1

Measured values

FG V/I-1ph
MP
V-1ph
V-1ph 64F
I-1ph
MP
I-1ph 1

Measured values

Unrestricted © Siemens AG 2018


Page 14 October 2018 Automation Products
Application template:
Generator Unit Connection Extended

A-QA MP
V-1ph

MP
V-1ph
FG Transformer side1
MP
I-3ph
I-3ph 1 FG Transformer diff

Measured values
87T
FG Transformer side 2

I-3ph

FG Circuit breaker A-QA


Measured values
V-3ph
FG Generator side1 25
V-3ph
MP
I-3ph 49
I-3ph 1
I-3ph 50BF

Ctrl
Measured values

FG Generator stator BI
CB
MP 21 BO
V-3ph
V-3ph 24
RGF- Coupling devices
32R
40
MP I-3ph 46 FG Generator diff
G I-3ph 51V
59
MP 59N
V-SGF
V-1ph 64S 87G
78
MP I-SGF 81
I-1ph 1

Measured values

20-Hz- FG V/I-1ph
equipment MP
(7XT33, 34) V-1ph
V-1ph 64F
I-1ph
MP
I-1ph 1

Measured values
Unrestricted © Siemens AG 2018
Page 15 October 2018 Automation Products
Application template:
Generator large
Generator-CB

FG Circuit breaker QA1

FG Generator side1 V-3ph

MP V-3ph
I-3ph 49
I-3ph 2

I-3ph 50BF
Measured values
Ctrl

FG Generator Stator BI
CB
MP BO
V-3ph
V-3ph 1 21
7XR6004 24
3PP1326 32R
MP I-3ph 40
FG Generator

7XT71
G I-3ph 1
46
51V
59
MP 59N
V-SGF
V-1ph 1 64100% 87G
78
MP I-SGF 81
I-1ph 2 50DC
Interface
Measured values
20-Hz-
coupling
FG Voltage/current 1-phase

V-1ph 64 F
1-3Hz
I-1ph
KG6
Interface
Measured values

FG Analog units

Vexc Excitation voltage for the


MT3 underexcitation protection (40)
Vcontrol MT1
RGF 1-3Hz (64F 1-3Hz)
Umeas MT2 RGF 1-3Hz (64F 1-3Hz)

I-DC MT4 (50 DC)

Unrestricted © Siemens AG 2018 MT1 to MT4 from IO210

Page 16 October 2018 Automation Products


Agenda

• General and device overview


• Typical applications
• Protection Benefits

Unrestricted © Siemens AG 2018


Page 17 October 2018 Automation Products
Generator protection
High flexibility in hardware and functionality

• Flexible product with a modular hardware Modular communication


requirement

Modular hardware
Customer

• Selection of functions depending on the application Flexible configuration (IOs) different plug-in modules, protocols
• Flexible allocation of functions to the voltage and
current inputs
• Flexible communication interfaces and protocols
• SIPROTEC 5 platform
• 7UM85: Hardware selection depending on the
Siemens
solution

application and flexible allocation of functions


• Configure the device with the configurator: Expand the basic functionality
according to your needs
hardware and communication modules according
to your needs; order the necessary function points
(flexible loading of functions according your credit)
• Hardware according to the application • Optimization of the hardware for your application
• Definition of a standardized hardware and allowed • Standardize your hardware and functionality
functions

Benefits
functionality (function points) → fix product code • Standardize your engineering
Device

• Function points can be upgraded


• Adapt the application template according to the Cost saving
application and save this as your device template

Unrestricted © Siemens AG 2018


Page 18 October 2018 Automation Products
Generator protection
Powerful fault recording

• Fault recording of all currents and voltages inputs as


requirement
Customer

well as binary signals


• Sampling frequency must be set, variable recording
time, large number records
• Additional recording of function measured values
• 7UM85 uses a powerful fault recording
• Sampling frequency (1, 2, 4, 8 kHz) , max. setting
Siemens
solution

of recording time: 80s; number of records (e.g.


setting 10s: 8 kHz→8 records, at 2 kHz → 32)
• Function measured values can be displayed, send
via protocol and routed to fault record

• Generator protection functions have function • Powerful fault recording supports the fault clearing
measured values (these values are direct used by • Flexible routing of sampled measured values,
functions

Benefits
Device

the protection functions) function measured values and binary signals


• Function measured values are available in the • Flexible setting of the recorder according the
routing matrix and under folder function measured application (sampling frequency, recording time)
values • Large number of stored records

Unrestricted © Siemens AG 2018


Page 19 October 2018 Automation Products
Differential protection functions (transformer and generator)
Improved restraint algorithm

• High sensitivity also for low fault currents Idiff


requirement

IMP1 IMP2
Customer

• Sensitive in 1,5 CB applications with small power


transformers
• High stability against external faults
Trip Area

• 87T, 87G use the conventional restraint IMP3


characteristic with modified settings
Siemens
solution

• New is the calculation of the restraint current Idiff> Restraint


Idiff = |S IMP |
Area
(Maximum of the phase currents)
IStab = Max |IMP|
IStab

• 87T, 87G restraint characteristic has three straight • Higher sensitivity in 1,5 CB applications
lines • More stability against signal distortion (e.g. CT
functions

Benefits
• Flexible setting of the characteristic
Device

saturation)
• Increased system availability

Unrestricted © Siemens AG 2018


Page 20 October 2018 Automation Products
Differential protection functions (transformer and generator)
Improved Idiff – fast stage

• Short tripping time in case of high internal fault IMP1 IMP2


requirement

Idiff
Customer

currents
• Robust in case of CT saturation (internal faults) Trip area
• Stable in case of external faults (in 1,5 CB appl.) Idiff>>

k=0,80 IMP3
• 87T, 87G fast stage evaluates instantaneous values
of the differential current i(t)diff = |S iMP(t) |
Siemens
solution

• Fast differentiation between internal and external


i(t)rest = Max |iMP(t)|
faults based on just a few samples (proven busbar IStab
prot. method) idiff, iStab Evaluation

• 87T, 87G fast stage in addition to the standard • Fast tripping time in case of internal faults also for
restraint characteristic saturated currents
functions

Benefits
• Adaptive algorithm for differential current evaluation: • Stable in case of heavy external faults with CT
Device

first instantaneous values and after 1 cycle filtered saturation (transverse currents in 1,5 CB
values applications)
→ Increased system availability

Unrestricted © Siemens AG 2018


Page 21 October 2018 Automation Products
Generator protection
100% Stator ground fault protection with 20-Hz injection

• Secure detection of stator ground faults


requirement
Customer

independent of the generator operation condition


(at stand still and during starting)
• Redundant function to the 90% principle (V0>); G
function shall cover 100% of the stator winding
• 7UM85 with 100% stator ground fault protection Bandpass R-parallel
20 Hz
Detection of stator ground faults (100% of the Generator
Siemens
solution

stator winding – from the stator point to the lead)


• Consideration of different conditions during startup V-SGF 100% SGF
(dynamic blocking) I-SGF (ANSI 64S)
• Consideration of a parallel load resistor and a load
dependent resistance
• Selection of the 100% stator ground fault protection • Secure detection of stator ground faults (100% of
function (+ accessory 7XT33, 7XT34, CT 400A/5A) stator winding)
functions

Benefits
• Allocation to the FG Generator stator • Independent measuring principle to the V0>
Device

• High sophisticated measuring technique measurement


(compensation of stator ground capacitance, angle • Active during generator start and consideration of
errors, parallel load resistors,..) different plant designs (e.g. parallel load resistor)
• Active during generator standstill (before starting) • Increased system availability
Unrestricted © Siemens AG 2018
Page 22 October 2018 Automation Products
Generator protection
Out of step protection for different fault cases
(Power swing inside generator unit)

• Detection of power swings in the generator – step-


requirement
Customer

up transformer unit
• Detection of power swings for different fault cases Net
(after a 3 phase short circuit or an interruption of 1
phase (CB problems))
• 7UM85 with out of step protection
Detection of power swings by evaluating the Relay
Siemens
solution

impedance trajectory (positive sequence)


• Selection of different zones with different settings
(loss of phase: no I2 blocking, wide impedance
reach, higher number of power swings allowed)

• Selection of the out of step protection • Secure detection of power swings inside the plant
• Allocation to the FG Generator stator and therefore protection of the primary equipment
functions

Benefits
• • Consideration of different fault scenarios
Device

Setting of different zones and reaches


• If necessary, two functions can operate in parallel • Increased system availability
• Coordination of the number of allowed power
swings with the generator/turbine manufacturer

Unrestricted © Siemens AG 2018


Page 23 October 2018 Automation Products
SIPROTEC 5
Automation
Unrestricted © Siemens AG 2018 Siemenes.com/siprotec5

Unrestricted © Siemens AG 2018


Page 24
Evolution in Substation Automation –
SIPROTEC 5 - the core of Digital Substation 4.0

1st generation – 2nd generation – Point- to-point 3rd generation – Digital Digital Substation 4.0 -
Standard cabling connections since 1985 Station bus since 2004 Process bus and IoT Connectivity

Mimic board Control Center Control Center Control Center Apps and Data Analytics
IEC 61850

HMI HMI

Substation
Substation Substation
controller
controller controller
HMI

Fault recorder
Protection IoT Interface
Station bus

IEC 61850
Switch
Other bays

RTU Serial
connection Station bus
3rd
Parallel Process Party

wiring Switch bus


Bay … Bay … Bay …

CT
VT

Parallel wiring Digital and Digital


analog Merging
Parallel wiring Parallel wiring Parallel wiring Merging Unit Unit

Unrestricted © Siemens AG 2018


Page 25 October 2018
Communication Topologies – Ring with integrated switches

RSTP Rapid Spanning Tree


Station Automation
Protocol
• 2 external RSTP-Switches
• SIPROTEC devices with
integrated RSTP switch
Ring configuration with RSTP Rapid Spanning Tree Protocol
• Rings with up to 30 devices
• Several rings can be
connected to external switches
• Setting of RSTP parameters
necessary
Field 1 Field n
→ Well established technology
Device 1 Device n-1 Device n Device m (>400.000 devices)

Devices integrated into the RSTP ring → Field proven interoperability

Unrestricted © Siemens AG 2018


Page 26
Communication Topologies – Seamless redundancy PRP – IEC 62439-3.4

PRP Redundancy
• Two parallel networks
• Device are connected to
PRP-A PRP-B
network PRP-A and PRP-B
• Devices send via both active
links
• RedBox for connection of non
PRP devices
• Seamless

Non PRP devices

Unrestricted © Siemens AG 2018


Page 27
Communication Topologies – Seamless redundancy HSR – IEC 62439-3.5

HSR Redundancy
Substation Controller
• 2 Redboxes
PRP-A PRP-B
• SIPROTEC devices with
integrated HSR switch
• Rings with up to 50 devices
• Redboxes distributed in the ring
• Seamless
Up to 50
SIPROTEC
devices
. per ring

HSR LAN

Unrestricted © Siemens AG 2018


Page 28 July 2016 Automation Products
Comm. Reliability
Seamless process and station bus configuration

Full redundancy Substation Controller

without recovery time

HSR Station Bus LAN

HSR for Process Bus LAN

PRP-A PRP-B

HSR for Process Bus LAN

HSR – High Availability Seamless Redundancy IEC 62439-3.5


Two active links, both sending, ring configuration

PRP – Parallel Redundancy Protocol IEC 62439-3.4


Two active links, both sending, parallel configuration

Unrestricted © Siemens AG 2018


Page 29
Architecture with IEEE 1588 and PRP/HSR Substation

RUGGEDCOM RSG2488
1 Grandmaster with PTP module
GPS Clock GPS Clock
Source 1 HMI 1 Source
RUGGEDCOM RS950G
2 With 1588 transparent clock
2
RUGGEDCOM RSG2488
3 With 1588 transparent clock 2 2
Industrial
Ethernet
RUGGEDCOM RSG2488 3 3
4 With 1588 transparent clock and
RSTP
Station
RSTP
Station
slave clock with PTP module LAN A LAN B
3 3
IE PRP Star Network A IE PRP Star Network B

3 3 3 3

RUGGEDCOM IE HSR Ring RUGGEDCOM RUGGEDCOM IE HSR Ring RUGGEDCOM


4 RedBox with
IEEE1588 TC
(Station bus) RedBox with
IEEE1588 TC
4 RedBox with
IEEE1588 TC
(Station bus) RedBox with
IEEE1588 TC

SIPROTEC 5 SIPROTEC 5 SIPROTEC 5 SIPROTEC 5 SIPROTEC 5 SIPROTEC 5

IE HSR Ring (Process bus) IE HSR Ring (Process bus)

6MU85 6MU85 6MU85 6MU85 6MU85 6MU85 6MU85 6MU85 6MU85 6MU85 6MU85 6MU85

Unrestricted © Siemens AG 2018


Page 30
SIPROTEC 5 –
Integrated Cyber Security

Central logging of
Digitally signed firmware
security-relevant events

• Device-firmware is protected against


manipulation
• Only firmware digitally signed by
Siemens can be loaded and
processed
• This is ensured via an integrated
crypto-chip with secured key
storage and signature technology

Unrestricted © Siemens AG 2018


Page 31 October 2018 Automation Products
Sistema de Supervisión, Control Nivel 2, Control Nivel 3 y Protección
Típicos Unidades 1, 2 y 3 . Playas
TABLERO CONTROL UNIDAD 1
K01 + W00
IHM

SICAM SICAM
F.O. TCP/IP (Monomodo)
AK1703 AK1703 F.O. TCP/IP (Multimodo)

SFTP – TCP/IP

SWITCH 1 SWITCH 2 Red Profibus – RS485

No es Suministro Siemens

CONTROLADOR 1 CONTROLADOR 2 CONTROLADOR 3 CONTROLADOR 4 CONTROLADOR 5 TABLERO DE PROTECCIONES 1 TABLERO DE PROTECCIONES 2

K01 + W01 K01 + W02 K01 + W03 K01 + W04 K01 + W05 K01 + R01 K01 + R02
IHM IHM IHM IHM

7UM622 7UT613 7UT613

SWITCH SWITCH SWITCH SWITCH


SICAM SICAM SICAM
TABLERO EN
AK1703ACP AK1703ACP AK1703ACP 7UM622
7UT613 7UT612 SUBESTACION DE ENERGIA

D00 + W01

7SJ611

SICAM SICAM 7SD52


EQUIPOS 7SD52
EQUIPOS EQUIPOS
AK1703ACP CON PROFIBUS AK1703ACP
CON PROFIBUS CON PROFIBUS

SWITCH 7SJ611 7SD52 7SD52

ION 7550
ENTRADA ANALOGAS/DIGITALES ENTRADA ANALOGAS/DIGITALES
ENTRADA ANALOGAS/DIGITALES
SALIDAS DIGITALES SALIDAS DIGITALES
EQUIPOS SALIDAS DIGITALES
IEC 61850
REGULADOR DE CON PROFIBUS
REGULADOR DE IEC 104
IEC 104

TENSION
VELOCIDAD

Unrestricted © Siemens AG 2018


Page 32
Sistema de Supervisión Servicios Auxiliares y Comunes. Playas

TABLERO CONTROL SSAA-COMUNES

NE + W00
SICAM IHM SICAM
AK1703 AK1703

Sistema Scada S/E Playas


(se debe Instalar Router)
SICAM
SWITCH 1 SWITCH 2 AK1703ACP

IEC 104

SSAA K00 +W10


F.O. TCP/IP (Monomodo) S/E PLAYAS
CONTROLADOR 1 SINCRONIZACIÓN UNIDADES CONTROLADOR 2 CONTROLADOR 3
F.O. TCP/IP (Multimodo) SWITCH
NE + W01 K00 + W01 NE + W02 NE + W03 IEC 104
IHM IHM IHM
SFTP – TCP/IP

Red Profibus – RS485

No es Suministro Siemens 7VE63 7VK61 SUPERVISION DE


SEÑALES DE LA S/E
(se debe Instalar Router)
SWITCH SWITCH SWITCH
SICAM SICAM
SICAM AK1703ACP AK1703ACP
AK1703ACP

+X35 +X45 +X05

TABLERO SIST VIBRACION


EQUIPOS EQUIPOS
CON PROFIBUS CON PROFIBUS

ENTRADA ANALOGAS/DIGITALES ENTRADA ANALOGAS/DIGITALES


ENTRADA ANALOGAS/DIGITALES SALIDAS DIGITALES SALIDAS DIGITALES
SALIDAS DIGITALES

IEC 104

Unrestricted © Siemens AG 2018


Page 33
PCH Sonsón I y II

Unrestricted © Siemens AG 2018


Page 34
SIPROTEC 5
Examples
Unrestricted © Siemens AG 2018 Siemenes.com/siprotec5

Unrestricted © Siemens AG 2018


Page 35
Experiencia
Centrales
Porce III
Riogrande Colombia San Carlos
Venezuela
Playas Jaguas
Sonson I y II Miel
Hidroituango Calderas
Ayurá Amoyá
Ecuador
El Salto
Laguneta Perú
Colegio

Ocaña
Bolivia

Marcel Laniado
Paraguay

Chimay Chile Uruguay


Yanango

Mantaro Argentina

Palmucho
Unrestricted © Siemens AG 2018 Pangue

Page 36 Ralco
Ejemplo
Control Unidad

Unrestricted © Siemens AG 2018


Page 37
Ejemplo
Sistema de Protecciones

Unrestricted © Siemens AG 2018


Page 38
Ejemplo
Secuencia de Arranque

Unrestricted © Siemens AG 2018


Page 39
Ejemplo
Secuencia de Arranque

Unrestricted © Siemens AG 2018


Page 40
Ejemplo
Secuencia paro Normal

Unrestricted © Siemens AG 2018


Page 41
Ejemplo
Secuencia paro Rápido

Unrestricted © Siemens AG 2018


Page 42
Ejemplo
Sistema de Excitación

Unrestricted © Siemens AG 2018


Page 43
Ejemplo
Regulador de Velocidad

Unrestricted © Siemens AG 2018


Page 44
Ejemplo
Sistema de Refrigeración

Unrestricted © Siemens AG 2018


Page 45
Ejemplo
Sistema de Frenos

Unrestricted © Siemens AG 2018


Page 46
Ejemplo
Sistema Oleohidráulico

Unrestricted © Siemens AG 2018


Page 47
Ejemplo
Sellos y drenaje

Unrestricted © Siemens AG 2018


Page 48
Ejemplo
Curva de cargabilidad

Unrestricted © Siemens AG 2018


Page 49
Ejemplo
Transformadores

Unrestricted © Siemens AG 2018


Page 50
Ejemplo
Transformadores

Unrestricted © Siemens AG 2018


Page 51
Spectrum Power™ 7
Power Applications

Overview

The Spectrum Power™ Power Applications suite provides


the complete functionalities for:

• Load Frequency control, i.e. for controlling the system frequency and
the power generation in a control area as well as the interchange with
other control areas in real-time while at the same time maintaining the
equilibrium of generation and demand

• Generation Dispatch control, i.e. for satisfying the real-time ancillary


requirements, e.g. regulating power, whilst meeting energy delivery and
regulation contracts.

Unrestricted © Siemens AG 2018


Page 52
Spectrum Power™ 7
Power Applications

Economic Dispatch (ED)


ED optimally allocates the total generation requirement (sum of base point values
plus system regulation calculated by LFC) among the participating generating units.
The allocation either minimizes the total system production cost or maximizes the
total system profit subject to the

• total generation requirement


• reserve (spinning) requirements
• plant and unit limits
• production cost characteristics

The solution is derived from a two-step algorithm based on incremental costs


(Lambda dispatch algorithm).

ED is executed cyclically, on operator request, or on LFC trigger. It can be executed


either in normal mode or in anticipatory mode.

Unrestricted © Siemens AG 2018


Page 53
Generation Control
Main cockpit for area
f, U, Pinterchange,PFinterchange
Status of LFC History of
main values

Total load
of area
Total reserve
for area
SRC of
all units
in area

Reserve of
tie-lines

Unrestricted © Siemens AG 2018


Page 54
Status of AVC
Generation Control
Influence of LFC History of
Overview for one Unit: on unit control main values

Main
unit status

Spinning
Reserve
Monitor

Dynamic capability curve Influence of AVC on unit control


Unrestricted © Siemens AG 2018
with working point
Page 55
Spectrum Power™ 7
Power Applications UI sample – Area Control

Unrestricted © Siemens AG 2018


Page 56
Spectrum Power™ 7
Power Apps UI sample – Tie Lines

Unrestricted © Siemens AG 2018


Page 57
Recomendaciones

✓ Tanto en los relés de protección como en los controladores de unidad contar con redundancia PRP/HSR.
✓ Puertos Ethernet y cumplimiento de la Norma IEC 61850 edición 2. Posibilidad de contar con varios
protocolos simultáneos (IEC 60870-5-104).
✓ Sincronización de tiempo usando IEEE 1588.
✓ Cyber Security de acuerdo con NERC CIP y BDEW.
✓ Para los relés de protección de generador, funciones falla estator y falla rotor (64S y 64F) 100%. Se
recomienda una protección principal y otra de respaldo de idénticas características por máquina.
✓ Fuentes redundantes para los controladores de unidad, Switch y Firewall.
✓ Hardware flexible y modular para los relés, controladores de unidad, Switch y Firewall
✓ Controladores de unidad con comunicación serial (IEC 60870-5-101/103) y LAN/WAN (IEC 60870-5-104 o
IEC 61850).

Unrestricted © Siemens AG 2018


Page 58
Recomendaciones

✓ Experiencia Específica:
Adjuntar certificados de haber ejecutado proyectos similares, es decir suministro de sistemas de control,
protección y Sistemas Scada para Centrales Hidroeléctricas de Generación.
✓ Experiencia del personal:
Director del proyecto: Ingeniero Electricista con al menos diez (10) años de experiencia comprobable donde
haya cumplido en forma continua o discontinua funciones de dirección de proyectos de montaje y puesta en
servicio de Centrales Eléctricas de Generación.
Ingenieros responsables de diseño e ingeniería: Ingeniero Electricista con al menos ocho (8) años de
experiencia comprobable donde haya realizado y ejecutado labores en actividades de ingeniería, diseño y
pruebas de protección y control en Centrales de Generación.
Ingeniero Especialista de Instalación, montaje y puesta en servicio de sistemas de Control, protección, medida
y sus sistemas de gestión: Ingeniero Electricista con al menos cinco (5) años de experiencia comprobable
donde haya cumplido labores de montaje, pruebas y puesta en servicio de Centrales de Generación.

Unrestricted © Siemens AG 2018


Page 59
Thank you for your
attention!