Switchgear Factory, Navi Mumbai L&T Switchgear, a part of the Electrical & Automation
business, is India's largest manufacturer of low voltage
switchgear, with the scale, sophistication and range to
meet global benchmarks. With over five decades of
experience in this field, the Company today enjoys a
leadership position in the Indian market with a growing
international presence.
Pages
Pages
9
Reverse Power Relay - MRP11
Voltage Relay - MV12 9
1
Time - Current Characteristics
1,000
100
Trip Time (Sec.)
10
1 B
C
01
1 10 20
For Trip time at TMS other than 1 A : Normal Inverse 3.0 sec
Trip time = (Trip time at TMS = 1) x TMS or B : Normal Inverse 1.3 sec
50 msec whichever is more. C : Very Inverse
D : Extreme Inverse
2
Over Current and Earth Fault Relays
• Three phase over current & earth fault relays for Feeder, AC Machines and Transformer Protection in
LV & MV Systems
MC31AnX – 51, 51N
MC61AnX – 51, 51N, 50, 50N
MC61CnX – 51, 51N, 50, 50N + RS485 port
Salient Features
MC31AnX / MC61AnX
R Y B R Y B
1 1
2 2 MICRO
CONTROLLER R1
9
3 3
10
4 4
R2
13 13 11
5 5
12
6 6 R3
17
15 15
16 16 18
7 7 R4
27
8 8 R Y B E
28
21
22 R5
PROG. 29
25 ERROR
L/+ 30
˜
N/- 26
MC61CnX
R Y B R Y B
1 1
9
R1
2 2 MICRO
CONTROLLER 10
3 3 11
R2
MC61C-nX
4 4 12
PROTECTION
13 13 17
R3
5 5 F51 18
6 6 F51N 27
R4
15 15 F50 28
16 16 F50N
7 7 D2
31 BI*
R Y B E
8 8 32
21 29
R5
PROG
22 30
ERROR
25 S+
L/+
COMM. S-
26 C
N/-
9 PIN MALE
* BLOCKING INPUT
4
Trip Circuit Supervision Relay
• TCS01-nX is an electronic relay, designed to monitor the healthiness of trip coil circuit
of a circuit breaker
Salient Features
• TCS01-nX will work for any Trip coil supply between 20V to 264V
AC/DC. It can be set to monitor standard voltages
i.e., 24, 48,110, 220V DC and 110, 240V AC
Model TCS01NX
Description Trip Circuit Supervision Relay
Device code 74
Design static
Settings Trip coil supply 24, 48,110,220V DC & 110, 240V AC
Trip time delay 600 msec ± 100 msec
Trip time Trip time delay in low
< 3 sec
TC voltage condition
Reset Time < 150 msec
Burden on CT Not applicable
Burden on PT Not applicable
Operating temp -10°C to 55°C
weight Around 1 kg
Output contacts 2 C/O contacts (self reset)
Output contact Rating 8 A, (250 VAC / 30 VDC)
Construction Draw-out
Dim (W x H x D) in mm 71 x 158 x 204
Panel cutout (WxH) in mm 62 x 142
Ordering information
Type 1 20-110 VAC/ DC
Auxiliary supply
Type 2 88-264 VAC/ DC
5
Wiring Diagrams
TCS01NX
15 9
BKR. 12 TCS 10
AUX. CKT.
Cont. 11 8
14
TC
Dimensions
158.5
142
62
71
204
6
Current Sensing Relays
• Single phase over current / earth fault relay - MC12
Salient Features
Model MC12A
Description 1 Ph O/C or E/F
Device code 50/51 or 50N/51N
Design Microcontroller based
Lowset O/C - Is
Highset O/C - Ihs
Functions available
Lowset E/F - Os
Highset E/F - Is
O/C Is = 50 - 200% Step 10% or
E/F Is = 10 - 40% Step 2% or
E/F Is = 20 - 80% Step 4%
HS O/C = (2 - 16) xls step 2 Is
Settings HS E/F = (2 - 16) xls step 2 Is
Time characteristics available -
Nl, VI, EI, Definite time
3 ranges of def time (1, 10, 100)
TMS : 0.1 - 1.6 Step 0.1
Site selectable trip time char.
Other features
Highset can be disabled
Burden on CT 0.25 VA on CT
Burden on PT Not applicable
Operating temp 00C - 600C
Weight < 1.5kg
Burden on auxiliary supply 5.5 VA
Output contacts 2 C/O Contacts (S/R)
Construction Drawout
Dim W x H x D in mm 71 x 158 x 224
Panel cutout 62 x 142
Ordering Information
Type 1 20 - 110 V AC / DC or
Auxiliary supply
Type 2 88 - 264 V AC / DC
CT Rating 1 A or 5 A
10 - 40% or 20 - 80% or 50 - 200%
Range setting
Site selectable
7
Wiring Diagrams
MC12A
1 COM
2 +VE/PH.
Aux. Supply
R1
3 -VE/N
µP. Control
Ckt.
F50/50N COM
10
F51/51N
11
12
MC12A
8
Reverse Power Relay, Under Voltage or
Over Voltage Relay
Salient Features
9
Wiring Diagrams
MRP11
1
4
R Y B 2 + VE / PH. 5
Aux. Supply
3 R1
– VE / N µP.
Control
11
Ckt. 7
F32
8
12
6
9
10 MRP11
Vn In AUX SUPPLY
110 V AC 1A 24–110 V AC/DC
415 V AC 5A 95–240 V AC/DC
MV12
1
5
2 4
R1
3 +VE/PH. µP.Control 6
Aux. Supply Ckt.
4 F27
-VE/N F59 8
11
9
12
7
MV12
10
Power Factor Control Monitoring Relays
• Intelligent Power factor controllers with Automatic set-up
w
Salient Features Ne
11
Wiring Diagrams
etaCON L3/L5/L7
MAINS
L1L2 L3
1 2 3 4 5 6 7
Current Voltage
/5A 415V
S1 S2 9 10 C 1 2 3 4 5 6 7 8
FU11
CT1
OS1
FU1 FU2 FU7
LOAD
K1 K2 K7
etaCON L8/L12
MAINS
L1L2 L3
1 2 3 4 5 6 7 8 9 10 11 12
Current Voltage
/5A 415V
S1 S2 15 16 C 1 2 3 4 5 6 7 8 9 10 11 12 13 14
CT1
FU16
OS1
LOAD
K1 K2 K12 12
Power Factor Control Monitoring Relays
• Intelligent power factor controller relay
Salient Features
• Measurement sensitivity of 1%
Model RPM-14
Description Automatic power factor controller 14 stage
Design Microcontroller based
Functions available Automatic PF control upto 14 stage
Switching time 1-255 sec
in step of 1 sec for same
Settings Bank switching
Auto C/K selection
PF control range 1% to 120% of rated current
Can accept unequal banks
Display of PF, V, l, kVAr
LED indications for faults
Other features Alarm signal for CT reversal,
under current, under compensation,
over compensation, over voltage,
1 A / 5 A field selectable
Burden on CT 0.3 VA
Burden on PT 15 VA
Operating temp 00C to 600C
Weight < 2kg
14 N/O
Output contacts
1 N/O contact for alarm
Dim W x H x D in mm 144 x 144 x 100
Panel cutout 138 x 138
Ordering Information
Auxiliary supply 240 V AC
13
Wiring Diagrams
RPM-14
Ph
240V AC
R1 1 R13 13 50 Hz
N
R2 2 R14 14
R3 3 15
R4 4
- 16 S2
R5 5 + 17 S1(1A)
R6 6 + 18 S1(5A)
R7 7 19 Bank #1
ALARM
R8 8 20
R9 9 21
R10 10 22
R11 11 23
R12 12 24
Bank #14
Y
To
B Load
14
Motor Protection Relay
• Motor protection relay - MM30-743
• Motor protection relay with voltage input - MM30-W74
Salient Features
15
Wiring Diagrams
MM30
A B C A B C 21
R1 (21) (10)
25 25 Display 10
11 N.O. N.O.
26 26 Microp. 22
R2 7
27 27 MM30 9 N.C. N.C.
8
28 28 R3 18
Function 20
39 39
29 29 19
F37 R1 R4 4
41 41 F46 6
30 30 F49
R2 5
32 F51
32
F51R R5 15
43
43
31
In=5A
31 ˜˜˜ F64
St.No.>
AI.0>
R3
R4
17
16
42 42 Itr 14
In=1A
33 33 Progr. 3
R5
Int. Fault 2
44
1
C
PRESA/TAP 31: Ion=5A Keyboard S- 34/38
S+ 23
PRESA/TAP 33: Ion=1A L/+ 12
˜ ˜= 24
N/- 13
˜ 9 Pin Male
IEC 255
16
Motor Protection Relay
• Economical motor protection relay - MPR 200nX / MPR 300
• Intelligent motor protection & control relay - MCOMP
17
Wiring Diagrams
MCOMP Relay
R
Y
B
N
SFU / MCCB
FUSE
L/+
N/-
1 2 3 4 71 72
N B Y R N/- L/+
2 4 6 2 4 6
3-PH.VOLT AUX.VOLT
1 3 5 1 3 5
START1 82
61 DI1
START2 83 FORWARD RELAY
62 DI2
DIGITAL INPUTS
CONTACTOR A CONTACTOR B
M COMP
CBCT
ALARM/PICKUP
CM UNIT RTD/PTC ANALOG O/P RS485 L
RST ENT
TI1 TI2 AO1 AO2 D+ D- TRIP
Mini USB Port N
S1
MODBUS RS485 LOOPING
S2
R Y B 4-20mA OUTPUT
TO FIELD AMMETER
RTD/PTC
R Y B N
Stop
(N/C)
1 2 3 4 5 6 7 8
NC NO Aux
Supply
MPR200nX / MPR300
Model MM10
Description Motor protection
Device code 37, 46, 49, 50/ 51, 51LR, 64
Frequency 50 Hz
Design Numerical relay
Thermal overload with warning
Short circuit
Undercurrent
Unbalance
Functions available
Phase loss
Phase sequence reversal
Earth fault
Prolonged starting, Locked rotor
Burden on CT 0.3 VA at rated current
Burden on PT not applicable
Maximum power consumption 3 VA typical
Output Contact 2 C/O
Operating temperature -5⁰C to +55⁰C
Degree of protection IP52
Weight 0.75 kg
Mounting Panel mounted
Dim W×H×D in mm 96 × 96 × 110
Panel Cut Out in mm 90 × 90
Ordering Information
Cat nos. Auxiliary supply CT input
MM10240X005 110 - 240 V AC/DC 5 A secondary
19
Wiring Diagrams
MM10 relay
L3 L2 L1 F4
F1 F2 F3
K1 MM10
L
9 1
Aux
N
10 2
11 3 NO
12 4 NC S2
R1 Stop
COM
13 5
Protection
class CT’S COM
14 6 S1
Start K1
R2
15 7 NC
Binary
Input NO
16 8
K1
M H1
Bloack R1/
Reset/
Trip
N
External CT's - Protection class CT's [5 - 1000 Amps] with 5 Amp secondary
Dimensions
110 mm
96 mm
100 mm
96 mm
Front
Side
90 mm
90 mm
Panel Cutout
20
Generator Protection Relays
• Multifunction generator protection relays
• Percentage based generator differential relay
Salient Features
21
Wiring Diagrams
MG30
25 21 (21 – 22)
Display R1 10
1/5A
N.O. N.C.
26 Microp. 11
22 (10 – 11)
1/5A MG30 7
R2
27 Funzioni 9 N.O. N.C.
1/5A
Function 8
28 R3 18
20
G 39 1>,Z<,Uo>
19
29
12>,T> R1 R4 4
1/5A 6
Zc<, O> R2 5
30
R5 15
41 U,f 17
1/5A
31 W<, Ir> 16
R3
42
32 1/5A IC, 60FL 14 14
R4
43 B.I./B.F. 3 3
2 2
33 1
MG30 1/5A Progr. 37(b)
R5
44 Int. Fault To Rex
C
38(a) Relay
S– Expansion
S+ 23
24
12 Keyb0ard
Tastiera 9 PIN MALE
13
CE
MS-SCE 1629-R0 In=1A In=5A Un=100V
MG30-I
25 21 (21 - 22)
Display R1 10
N.O. N.C.
26 Microp. 11
22 (10 - 11)
MG30-I R2 7
27 9 N.O. N.C.
Funzioni
Function 8
28 R3 18
20
G 39 I>, Z<, Io> 19
29
I2>, T> R1 R4 4
1/5A 6
30 Zc<, > R2 5
R5 15
41 1/5A
U, 1 17
31 w<+ Ir> 18
R3
42 14
1/5A IC, 60FL 14
32 R4
43 B.I / B.F. 3 3
2 2
1
Progr. 37(b)
1/5A R5
33 Int.fault To Rex
c
38(0) Relay
s- Expansion
s+ 23
24
12 Keyboard RS485
In = 1A Tastiera
13
In = 5A MS-SCE1759-R0
MD32-G
A B C
87G + 87N (21)
I1A 25 R1 21
Display 10
I1B 1/5A N.O.
11
I1C 26 Microp. 22
1/5A R2 7 N.C.
9
27 MD32-G (10)
8
1/5A
28 R3 18 N.O.
Function 20
39
G 19 N.C.
F187G R1 R4 4
F287G 6
29 F87N R2
5
1/5A R3 15
I2A R5
30 R4 17
I2B 41 1/5A 16
R = Stabilising resistor
I2C 31 14
Z = Protection surge B3
arrester (if required) 42 Progr. B2 3
1/5A R5
32 Int. Fault
B1 2
43
Z 1
˜˜˜
1/5A C 34/38
33 S-
23
R 50-60
Keyboard S+
_ 24
L/+ 12
N/- 13 ˜ ˜= 9 Pin Male
˜ 22
Transformer Protection Relay
• Percentage based transformer differential relay
Salient Features
Model MD32TM
Description Transformer differential
Device code 87 RYB
Design Numeric
Lowset differential
Lowset op time : < = 30mS
Highset differential
Highset op time : 6 - 20mS
Dual slope bias
Functions available Highset can be Biased / Unbiased
2nd harmonic restraint setting
5th harmonic restraint setting
Auto correction of CT ratio
Zero sequence compensation
Blocking function
Display of parameters
Built in self supervision
Other features RS485 port
1 A or 5 A site selectable
Waveform capture feature
Burden on CT 0.2 VA for 5 A, 0.01 VA for 1 A
Operating temp 100C to 600C
Weight < 2kg
Burden on auxiliary supply 8.5 VA
Output contacts 5 C/O, S/R or H/R or Time del
Construction Draw out
Dim W x H x D in mm 121 x 158 x 224
Panel cutout 113 x 142
Ordering Information
Type 1 20 - 110 V AC / DC
Auxiliary supply
Type 2 88 - 264 V AC / DC
23
Wiring Diagrams
MD32T / MD32TM
A B C
(21)
I1A 25 R1 21
87T + 87N 10
Display
1/5A N.O.
I1B
In1 11
I1C 26 Microp. 22
R2 7 N.C.
1/5A
MD32T 9 (10)
27
8
1/5A
V1 28 R3 18 N.O.
39 Function 20
V2 V1
α V1 19 N.C.
Kv =
V2 V2 F187T R1 R4 4
F287T 6
29 F87N R2
5
1/5A R3 15
I2A R5
R4 17
30
R = Stabilising resistor
I2B 41 16
Z = Protection surge 1/5A
arrester (if required) I2C 31 B3 14
42 Progr. 3
1/5A R5 B2
32 Int. Fault
43 B1 2
1
Z
R
33
1/5A
˜˜˜
50-60
Keyboard
C
S-
S+
34/38
23
24
L/+ 12
IEC 255 ˜ ˜ = 9 Pin Male
N/- 13
˜
24
Voltage and Frequency Relay
• With vector shift protection - UM30A
• With df/dt protection - UFD34
• With zero sequence Over Voltage / Neutral shift Protection - MC3V
Salient Features :-
25
Wiring Diagrams
UM30A
(21)
25 R1 21
A Display 10
N.O.
26 11
Microp. 22
27 R2 7 N.C.
B UM30A 9 (10)
28 8
Function 18 N.O.
39 R3
29 F27 / 59 20
C R1
F27d / 59d 19 N.C.
41 R2 R4 4
30 F59s 6
F59U R3 5
EA F81 R5 15
R4 17
F59 / 81
˜˜
˜
Uo 16
UC UA BT 2 50 Progr. 14
R5 14
44 Int. Fault BI< 3
BI> 2
EC EB 1
UB _ C
34/38
L/+ 12 Keyboard S-
N/- 13 ˜ ˜= S+ 23
24
˜ 9 Pin Male
IEC 255
24 (-20%) - 110 (+20%) Vac 24 (-20%) - 125 (+20%) Vdc 80 (-20%) - 220 (+20%) Vac 90 (-20%) - 250 (+20%) Vdc
UFD34
(21)
25 R1 21
A Display 10
N.O.
26 11
Microp. 22
R2 7 N.C.
27 9
B UFD34 (10)
28 8
Function 18 N.O.
39 R3
20
29 F81 - 1 R1
C N.C.
F81 - 2 19
R2 R4 4
41 6
F81 - 3
30
F81 - 4 R3 5
Fdf / dt R5 15
R4 17
F27 / 59
16
Progr. 14 14
R5
Int. Fault BI<
3
BI> 2
1
_ C
34/38
L/+ 12 S-
˜ ˜ =
Keyboard S+
23
24
IEC 255
N/- 13 ˜ 9 Pin Male
MC3V
4 Display R1
16 R1
A 16
Microp.
5 Output
R2 R2
6
MC3V 18
Output
18 Relays
Introduction
Features
Total
along with an efficient micro-controller based Clearing Time
algorithm to generate a trip within 1 ms of arc
detection.
27
PGR-8800 ARC Flash Relay Sensors
28
Typical Installation
Arc Flash
Fiber-Optic Sensor
Point Sensors
Figure 1: Scenario with point sensor placement on the Figure 2: Scenario with point sensor placement on
bottom of each compartment, looking up. Arc detection the wall of each compartment. Arc detection area for
area for each sensor is shown in green shade. In this each sensor is shown in green shade. In this case,
case, both Point sensor 2 and the Fiber-optic Sensor both Point sensor 1 and the Fiber-optic Sensor
detected the flash as it was within their viewing area detected the flash as it was within their viewing area
(shown in orange). (shown in orange).
29
Technical Specifications
Trip Coil Output 2 Programmable Form C Output Contact: 5 A @ 250 Vac / 30 Vdc
Status Output Contact: 3 A @ 50 Vac / 50Vdc
PGA-LS10/20/25/30 SENSORS
Detection Radius 180 Deg (PGA-LS10), 360 Deg (PGA-LS20/25/30), Line of sight
Trip Status LED Displays “tripped” state on each sensor
Healthy Status LED Displays “ready” state on each sensor
Fiber Sensor Length PGA-LS20: 8 m (26.2 ft) active, 10 m (32.8 ft) total
PGA-LS25: 5 m (16.4 ft) active, 8 m (26.2 ft) total
PGA-LS30: 18 m (59 ft) active, 20 m (66 ft) total
Configuration Software
The configuration parameters for the relay are loaded using a simple plug and play software. The
relay can be connected to the PC using the front USB port. Relay will automatically go in the ‘Service’
mode once it is connected to the PC.
30
31
MV12/MC3V
MC61AnX
MD32TM
MC12
MC61AnX
MC31AnX
MV12/MC3V
SCM21
UFD34, UM30
Schematic - Relay Application
SPM21 etaCON L /
MG30/
RPM14
MG30I
MV12
MC61AnX
MRP11
MD32G MM30/
MPR300/
G1 G2 MM10 MCOMP
Motor Motor
APFC Panel
Please contact any of the training centres for participation and detailed training programme schedule.
Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.
Registered Office: L&T House, N. M. Marg, Ballard Estate, Mumbai 400 001, INDIA CIN: L99999MH1946PLC004768
SP 50297 R5