For Testing
1
7SA522- Practical Ref. For Testing
2
7SA522- Practical Ref. For Testing
3
7SA522- Practical Ref. For Testing
Then you can control binary output ,binary input and led
4
7SA522- Practical Ref. For Testing
We will use general mode of ferja to inject current and voltage and get the result
1. OPERATIONAL MEASUREMENTS:
PRIMARY SECONDARY
MEASUREMENT MEASUREMENT %
1.
IA
2.
IB
3.
IC
4.
3IO
5.
VA
6.
VB
7.
VC
8.
V A-B
9.
V B-C
10.
V C-A
11.
3 VO
12.
S
13.
P
14.
Q
15.
FERQUENCY
16.
P.F
*INJECT 3 PHASES CURRENTS & VOLTAGES.
*DITANCE PROTECTION = 1201=OFF.
*The power measurements P, Q are positive, if real power or inductive reactive power
flows into the protected object. This is assuming that this direction has been
parameterized as “forward”.
The sign of the power factor cos j corresponds to the sign of the real power.
5
7SA522- Practical Ref. For Testing
135°
180° V 0°
360°
-45°
270°
To test 3Io, 3Vo, inject:
Ia=1A,∟0, Ib=2A, ∟180, Ic=0 →3Io=1A
Va= 37V, ∟0, Vb= 57V, ∟180,Vc=0→3Vo= 20V
This (3Vo) will not appear if the setting of AD210(U4 volt. Transformer is : Open delta) as
the final setting, because the 3V0 is calculated in this case directly from the open delta. So
to make the relay calculate the 3Vo you have to change the setting to be (Not connected).
6
7SA522- Practical Ref. For Testing
2. IMPEDACE MEASUREMENTS:
Injected Impedance Z = ………………..OHMS
IMPEDANCE Φ = 60 Φ = 240
CALCULATED MEASURED CALCULATED MEASURED
RL1
XL1
RL2
XL2
RL3
XL3
RL12
XL12
RL23
XL23
RL31
XL31
R = Z * COS Φ , X = Z * SIN Φ
Note :-
*Before this test check power system data 2 address (1116-1119) setting should be
zero to get correct readings.!!!!! ﻣﺶ ﻣﻬﻢ
*INJECT ( Z ) WITH ANGLE Φ
. هﻞ هﻮ ﺻﺤﻴﺢ ام ﺧﻄﺎءR وX ( ﺑﺰاوﻳﻪ ﻟﺘﺎآﺪ ﻣﻦ ﻗﺮاءة اﻟﺮﻳﻠﻴﻪ ﻟﻞZ ) *ﻧﺤﻘﻦ
7
7SA522- Practical Ref. For Testing
3. DIRECTIONAL TEST:
0112 PHASE DISTANCE: QUAD 0113 EARTH DISTANCE: QUAD
ANGLE
DIRECTION FROM TO
339° 120°
FORWARD
121° 158°
UNDEFINED
159° 300°
REVERSE
301° 338°
UNDEFINED
Note :-
*3-PHASE FAULT INJECTION.1PHASE FAULT INJECTION & PH-PH FAULT
INJECTION.
(MUST BE SAME FOR ALL TYPS OF FAULTS)
*PHASE DISTANCE: QUAD ,EARTH DISTANCE: QUAD, LED13
=3719= FORWARD (Unlatch u)
LED14 = 3720=REVERSE (Unlatch u)
120°
FORWARD
159°
339°
REVERSE
300°
8
7SA522- Practical Ref. For Testing
At isa:
use z-Pro, insert z with any required angles by click & test
if you want to use X-pro you have to calculate the Z value to be inside
zone 5 at all angles, because if you changr the engle of the current only
the impedance value will be changed and it does not give the right value
of the Z angle- you can see it at the z-pro.
At OMICRON:
-:( آﻤﺎ ﻳﻠﻲOMICRON)*ﻧﺨﺘﺎر ﻣﻦ ﺟﻬﺎز اﻻﺧﺘﺒﺎر
*Distance..--Æ *Advanced Distance -Æ *Check
أي ﻗﻴﻤﻪz * ﻧﻀﻊ ﻗﻴﻤﻪ ل
Seguence *
.• ﺗﺤﺪﻳﺪ اﻟﻤﺪي اﻟﻤﺮاد اﺧﺘﺒﺎرﻩ وﺗﺤﺪﻳﺪ اﻟﺰﻳﺎدﻩ ﻓﻲ اﻟﺰواﻳﻪ
9
7SA522- Practical Ref. For Testing
1. Now you have created “rio” file and ready to import it on freja.
10
7SA522- Practical Ref. For Testing
11
7SA522- Practical Ref. For Testing
4. A window will prompt. Type all the related information e.g. station,
line, relay in respective text boxes. And then click “proceed”.
12
7SA522- Practical Ref. For Testing
6. On the top there will be a sign of “start the rio converter” at the
end of tool bar. Select that one and a window will open.
7. Do as follow.
13
7SA522- Practical Ref. For Testing
0.25 0.26
Note:-
*You must inject voltage more than the setting voltage at address (2913A)
or make fuse fail (2915) OFF
*MEASUREMENT SUPERVISION=2901 = OFF
*INJECT CURRENT IN PHASE TO PHASE.
14
7SA522- Practical Ref. For Testing
15
7SA522- Practical Ref. For Testing
Note:-
* Make UN balance and check the measurements in the relay to see the 3Io
values.
*You must inject voltage more than the setting voltage at address (2913A) or
make fuse fail (2910) OFF
16
7SA522- Practical Ref. For Testing
SETTING
TIME
AXES
TIME
1 R
0
Z1
2.5 X
FORWARD
1.3 R
Z1B
0.3
3.5 X
FORWARD
2 R
Z2
0.5
5 X
REVERSE
3 R
Z3
1.0
6 X
5 R
FORWARD
Z4
1.5
10 X
7 R
NON DIRECTIONAL
12 X
Z5
2.5
7 R
12 X
0013 Distance ﺛﻢ اﻟﻲSetting Group A ﺛﻢ اﻟﻲSettings ﻣﻦZONE ﻳﺘﻢ ﺿﺒﻂ الZONE ﻷﺧﺘﺒﺎر ال
zones
Device ﺛﻢ إﻟﻰSettings وذﻟﻚ آﻤﺎ ﻳﻠﻲ ﻣﻦQuadrilateral واﺧﺘﻴﺎرDistance وﻧﻘﻮم ﻗﺒﻞ ذﻟﻚ ﺑﻲ ﺿﺒﻂ ال
configuration
وهﺬا90 ﺑﻲ زاوﻳﻪZ ﺗﻜﻮن الX وﻋﻨﺪ اﺧﺘﺒﺎر ال0 ﺑﻲ زاوﻳﻪZ ﺗﻜﻮن الR ﻋﻨﺪ اﺧﺘﺒﺎر
وﻋﻨﺪ180 ﺑﻲ زاوﻳﻪZ ﺗﻜﻮن الR ﻋﻨﺪ اﺧﺘﺒﺎرReverse اﻣﺎ ﻓﻲ الForward ﻓﻲ ال
17
7SA522- Practical Ref. For Testing
-:*ﻣﻠﺤﻮﻇﻪ
. وﻟﻜﻦ ﻧﻌﻜﺲ اﻟﺘﺎ رﻳﺾ ﻓﻲ اﻟﺮﻳﻠﻴﻪ او اﺗﺠﺎﻩ اﻟﺤﻘﻦForward ﻳﻤﻜﻦ ﺣﻘﻦ ﺑﻨﻔﺲ زواﻳﻪ الReverse ﻓﻲ
.Distance -1
.Shot -2
ﺑﺤﻲ. ﻧﻀﻊ اﻟﻨﻘﺎط-3
Add To -4
ALL ﻧﺨﺘﺎر-5
OK ﻧﻌﻤﻞ-6
وهﻜﺬا-7
. ان ﻳﻜﻮن اﻟﺘﺎرﻳﺾ ﻣﻄﺎﺑﻖ ﻟﻠﻮاﻗﻊParameter * اﻟﺘﺎآﺪ ﻣﻦ ال
By isa: Using Z-pro
)ﻟﻮﺗﻴﺎر اﻟﺤﻘﻦ ﺛﺎﺑﺖ ﻋﻠﻰ ﻗﻴﻤﺔBACKUP E/F ﻻﺣﻆ أن ﺑﻌﺪ اﻟﻤﺮﺣﻠﺔ اﻟﺨﺎﻣﺴﺔ ﻳﻔﺼﻞ:ﻣﻠﺤﻮﻇﺔ
0.25 أﻣﺎ اﻷرﺿﻲ1.22 ﻣﺎ ﻳﻔﺼﻞ ﻷن اﻟﻀﺒﻂ أﻋﻠﻰ ﻣﻦL-L ( أﻣﺎ ﻟﻮ ﺣﻘﻨﺖ0.25Aأآﺒﺮ ﻣﻦ
2. Now you have created “rio” file and ready to import it on freja.
18
7SA522- Practical Ref. For Testing
11. A window will prompt. Make sure, freja serial to usb cable is
plugged in and “connect freja” icon is appearing in the right
bottom. Now click “distance”.
19
7SA522- Practical Ref. For Testing
13. A window will prompt. Type all the related information e.g. station,
line, relay in respective text boxes. And then click “proceed”.
20
7SA522- Practical Ref. For Testing
21
7SA522- Practical Ref. For Testing
15. On the top there will be a sign of “start the rio converter” at the
end of tool bar. Select that one and a window will open.
16. Do as follow.
17. Browse to desktop, select your file and now click open.
22
7SA522- Practical Ref. For Testing
23
7SA522- Practical Ref. For Testing
19. Now the graph will come into the RX Ramp window of the freja
win.
20. Then go to the “config.” And give some pre fault current value. e.g.
0.2A and time % e.g. 500 m sec as shown in the window below. The
timing for different zones will come according to your rio file so
don’t consider these timing values for zones. Make “max fault
setting” “voltage” 150.
24
7SA522- Practical Ref. For Testing
Phase fault
setting
Resolution
setting
25
7SA522- Practical Ref. For Testing
3. Now draw the Ramps for each phase selection on the graph.
4. Right click the graph and option will come “add ramp”.
5. Select it and a window will appear to insert the values for the
ramp impedance magnitude and angle of the ramp.
26
7SA522- Practical Ref. For Testing
8. Now ramps will automatically appear on the graph. And you can
also select the phase spacing between the ramps. Type starting
angle i.e. 0 deg and type your stop angle i.e. 360 deg and now
type the phase spacing between the ramps i.e. 15 deg.
27
7SA522- Practical Ref. For Testing
9. Then select all options for auto reaches for P-N and P-P as
shown and press start.
Select it
for all
Zones selection
TIMING TEST:
1. Now go to the “Zt” window of the freja by single left clicking the
red colour icon.
28
7SA522- Practical Ref. For Testing
3. Click the graph button and the graph will come automatically to
the window. Just select the resolution to fit all the zones into the
same window. And single left click the “start” button to start test as
To start
shown below. test
Graph
import
Resolution
29
7SA522- Practical Ref. For Testing
5. ZONE CHECK:
B) POLAR CHARECTERISTIC
LINE ANGLE = ……….
0 2.5
Z1
FORWA
Z1B
RD
0.3 3.0
FORWA
RD
Z2
0.5 5.0
REVERSE
Z3
1.0 6.0
FORWARD
Z4
1.5 10.0
FORWARD
Z5
2.5 12.0
85 ﺑﺰاوﻳﻪ z *ﺣﻘﻦ
30
7SA522- Practical Ref. For Testing
(…2.1. ) MORE THAN THE SETTING ADDRESS NO 2404 W/O BINARY INPUT : NO TRIP
(…2.1.. ) MORE THAN THE SETTING ADDRESS NO 2404 + BINARY INPUT : TRIP
(…2.1…) LESS THAN THE SETTING ADDRESS NO 2404 + BINARY INPUT : :NO TRIP
*ﻳﻤﻜﻦ اﻟﺘﺤﻜﻢ ﻓﻲ اﻟﺰﻣﻦ اﻟﺬي ﻳﻜﻮن ال ل Biﻧﺸﻂ ﻣﻦ AD1150A
*ﻳﻤﻜﻦ اﻻﺳﺘﻐﻨﺎء ﻋﻦ CB MANULE CLOSE BINARY INPUTﺑﺎن اﻟﺮﻳﻠﻴﻪ ﻻ ﻳﺮاى
ﺗﻴﺎر اﻋﻠﻲ ﻣﻦ ADDRESS NO 1130Aﻟﻤﺪة 250 msوﺑﺬﻟﻚ ﻳﻌﺮف اﻟﺮﻳﻠﻴﻪ ان اﻟﻔﻴﺪر ﻣﻔﺼﻮل وﻳﺴﺎهﻢ اﻟﺰﻣﻦ
ADDRESS NO1132ﺑﻲ ﺟﻌﻞ اﻟﺮﻳﻠﻴﻪ ﻳﺮاﻗﺐ زﻳﺎدة اﻟﺘﻴﺎرﺑﻌﺪ اﻋﺎدة ﺗﺸﻐﻴﻞ اﻟﻔﻴﺪرﻓﻠﻮ ﺣﺪث اﺛﻨﺎء هﺬا اﻟﺰﻣﻦ زﻳﺎدﻩ
ﺗﺼﻞ ﻟﻘﻴﻤﺔ اﻟﻀﺒﻂ ﻳﻔﺼﻞ ﺑﻠﺨﺎ ﺻﻴﻪ وﺑﺬﻟﻚ ﺗﺨﺘﺒﺮ آﻤﺎ ﻳﻠﻲ -:
*ﻧﺤﻘﻦ ﻃﺒﻴﻌﻲ ﺛﻢ ﻧﻔﺼﻞ اﻟﺤﻘﻦ ﻟﺰﻣﻦ اﻋﻠﻲ ﻣﻦ 250 msﺛﻢ ﻧﺤﻘﻦ ﻃﺒﻴﻌﻲ زﻣﻦ اﻗﻞ ﻣﻦ 2 sﺛﻢ ﻧﺤﻘﻦ ﺗﻴﺎر اﻋﻠﻲ
ﻣﻦ 2 Aﺳﻮف ﻳﻔﺼﻞ ﺑﺎﻟﺨﺎﺻﻴﻪ
-ﻓﻲ isaﺗﺠﻌﻞ زﻣﻦ ال prefaultﻣﺮة أﻗﻞ ﻣﻦ 2ﺛﺎﻧﻴﺔ ﻓﻴﻔﺼﻞ وﻣﺮة أﻋﻠﻰ ﻓﻼ ﻳﻔﺼﻞ
Also prefault value should be > AD 1130A: pole open current threshold(0.1A),
otherwise the relay don’t detect that the line is live.
*ﻧﺤﻘﻦ ﻃﺒﻴﻌﻲ ﺛﻢ ﻧﻔﺼﻞ اﻟﺤﻘﻦ ﻟﺰﻣﻦ اﻋﻠﻲ ﻣﻦ 250 msﺛﻢ ﻧﺤﻘﻦ ﻃﺒﻴﻌﻲ زﻣﻦ اﻋﻠﻲ ﻣﻦ 2 sﺛﻢ ﻧﺤﻘﻦ ﺗﻴﺎر
اﻋﻠﻲ ﻣﻦ 2 Aﺳﻮف ﻻ ﻳﻔﺼﻞ ﺑﻠﺨﺎﺻﻴﻪ
*ﻧﺤﻘﻦ ﻃﺒﻴﻌﻲ ﺛﻢ ﻧﻔﺼﻞ اﻟﺤﻘﻦ ﻟﺰﻣﻦ اﻗﻞ ﻣﻦ 250 msﺛﻢ ﻧﺤﻘﻦ ﻃﺒﻴﻌﻲ زﻣﻦ اﻗﻞ ﻣﻦ 2 sﺛﻢ ﻧﺤﻘﻦ ﺗﻴﺎر اﻋﻠﻲ
ﻣﻦ 2 Aﺳﻮف ﻻ ﻳﻔﺼﻞ ﺑﻠﺨﺎﺻﻴﻪ
-اﺣﻘﻦ ﻃﺒﻴﻌﻲ ﺛﻢ ﻗﺒﻞ ال ms250ﻳﻌﻨﻲ ﺳﺘﻜﻮن اﻟﺨﺎﺻﻴﺔ ﻟﻢ ﺗﻔﻌﻞ ﺑﻌﺪ ﻷن اﻟﺠﻬﺎز ﻣﺎزال ﻳﺮي اﻟﺨﻂ ﺷﻐﺎﻻ
-ﻓﻲ isaﺗﺠﻌﻞ زﻣﻦ ال prefaultﻣﺮة أﻗﻞ ﻣﻦ 2ﺛﺎﻧﻴﺔ وﺗﺤﻘﻦ ﺛﻢ ﺗﻮﻗﻒ ﺣﻘﻦ ﻗﺒﻞ ﺗﻤﺎم اﻟﻮﻗﺖ ﺛﻢ ﺗﺤﻘﻦ
ﺑﺴﺮﻋﺔ ﻓﻲ ﺧﻼل ال ms 250ﻓﻼ ﻳﻔﺼﻞ
31
7SA522- Practical Ref. For Testing
7. SOTF FUNTION
2) SWITCH ON TO FAULT (SOTF)
A) SOTF WITH BACKUP O/C:
ADDRESS NO2615 O/C I> = ON
ADDRESS NO2625 O/C I>> = ON
ADDRESS NO2671 O/C Ip = ON
ADDRESS NO2601 SOTF WITH O/C = ON
Note:-
-LED: SOTF P/U. because the trip is not tagged(SOTF) but still(O/C)! but with 0 sec
not 2.5 sec.so this led will inform you the cause of accelerating the time. But the led did
not pick up?!
- also you can read the EVENT LOG, TRIP LOG but you can not see
any thing about SOTF like the first case.only if you open the fault
recorder(oscillograph) you will find the pulse (Line closure).
32
7SA522- Practical Ref. For Testing
7. SOTF FUNCTION
2) SWITCH ON TO FAULT (SOTF)
B) SOTF WITH DISTANCE PROTECTION: (1232 = ZONE PICK UP )
ADDRESS NO1201 Dis. = ON
ADDRESS NO1232 SOTF WITH Dis. = ON :هﺬﻩ ﻟﻬﺎ اﺧﺘﻴﺎرات
- with Z1B : the trip time on the relay is 0ms
so OK, but
the contact working with the zone time??!because the
contact must be programmed to close also with Z1B
because the tripping now is with Z1B 1-phase or 3-ph
- with pick up (non- directional) results is ok with this option.
- with Z1B un directional
Note:-
-LED: SOTF P/U.
-BI: MANUAL CLOSED
-BO: GENERAL TRIP OR SOTF.
-MAKE FAULT WITH ALL -NO SOTF TRIP
LED WILL GLOW . BUT ZONE TRIP TIME WILL BE BYPASSED)
وﺳﻮف ﻳﻜﻮن الDIS وﺑﺬﻟﻚ ﺳﻮف ﻳﻌﺘﻤﺪ ﺿﺒﻂ اﻟﺘﻴﺎر هﻮ ﺿﺒﻂ الADDRESS NO 2404 =OFF * ﻋﻤﻞ ال
ﻋﺎم ﻣﻊ اﻟﺨﺎﺻﻴﺔ ﺳﻮئ ﺗﻢ ﺗﺸﻐﻴﻠﻬﺎ ﻣﻨﻔﺼﻠﺔ او ﺗﻢADDRESS NO 1132 والADDRESS NO1134
DIS. أوO/C ﺗﺸﻐﻴﻠﻬﺎ ﻣﻊ
33
7SA522- Practical Ref. For Testing
Note:-
-LED: FAILURE FEEDER VT MCB TRIP.(AD3615)
-BI: FAILURE FEEDER VT MCB TRIP.(AD3615)
-LED: Distance Block (AD3652)
- MAKE FAULT WITH ALL ZONES WITH AND WITHOUT (BI)
-DISTANCE PROTECTION WILL BLOCK.
- MAKE O/C = ON
34
7SA522- Practical Ref. For Testing
هﺎم ﺟﺪا
وﺳﻬﻞ أن ﺗﺤﻘﻦ أي ﻋﻴﺐ ﺑﻬﺬﻩ اﻟﻄﺮﻳﻘﺔ. -
ﻟﻜﻦ اﻟﻤﻼﺣﻆ أن ﻟﻤﺒﺔ اﻟﺒﻠﻮك ﺗﻨﺰل أول ﻣﺎ ﻧﺼﻞ ﻟﻠﻀﺒﻂ وﺗﻨﺰل ﻟﻤﺒﺔ ال fuse failﺑﻌﺪهﺎ )ﻋﺸﺮ ﺛﻮان آﺎﻟﺒﺮﻣﺠﺔ أﻣﺎ
ﻟﻮ اﺧﺘﺮت ﺑﺮﻣﺠﺔ اﻟﻠﻤﺒﺔ LED 14 = FUSE FAILURE=1670ﺑﺪون اﻟﻌﺸﺮ ﺛﻮان ﻓﻴﻨﺰﻻﻣﻌﺎ (
-ﺑﻌﺪ ﻣﺎ ﺗﻨﺰل ﻧﺰل ﺗﻴﺎر ﻧﻔﺲ اﻟﻔﺎزة ﻓﺘﺴﺒﺐ 3Ioﻓﺘﺨﺘﻔﻲ اﻟﻠﻤﺒﺔ ﻷن اﻟﺠﻬﺎز ﻳﺮاﻩ ﻋﻴﺐ .وهﺬا ﻧﺤﻘﻘﻪ ﺑﺄن ﺗﺠﻌﻞ
ال prefaultهﻮ ﺣﺎﻟﺔ اﻟﺒﻠﻮك ﺛﻢ ﺗﺤﻘﻦ آﻤﺎ ﻗﻠﻨﺎ
-اﻟﻤﻔﺮوض ﺗﺤﻘﻦ ﻋﻴﺐ وﺗﺘﺄآﺪ أن اﻟﺠﻬﺎز ﺑﻠﻮك ﺗﺤﻘﻦ ﺗﻴﺎر ﻋﺎﻟﻲ زاوﻳﺘﻪ ﺑﺎﻟﺴﺎﻟﺐ ﻋﻦ اﻟﺠﻬﺪ وﺗﻈﺒﻂ ﻣﻦ ﻗﺮاءة
اﻟﻤﻌﺎوﻗﺔ ﻋﻠﻰ اﻟﺠﻬﺎز وﺗﺘﺄآﺪ أﻧﻪ ﻟﻮﺣﺪﻩ ﻋﻴﺐ ﺛﻢ ﺗﺤﻘﻨﻪ ﺑﻌﺪ اﻟﺒﻠﻮك ﻓﺎﻟﺠﻬﺎز ﻣﺎ ﻳﻔﺼﻠﺶ.
-1ﺿﺒﻂ 3Ioﺑﻘﻴﻤﻪ ﺻﻐﻴﺮﻩ وﻧﺤﻘﻦ ﺗﻴﺎر ﻣﺘﺴﺎوي ﻧﺤﻘﻖ 0 = 3Ioﻳﻌﻨﻲ أﻗﻞ ﻣﻦ اﻟﻀﺒﻂ ﻳﻌﻨﻲ اﻟﺘﻴﺎر ﻣﺴﻤﻮح أن
ﻳﺤﺪث ﺑﻪ ﻋﺪم اﺗﺰان ﺑﺤﺪ أﻗﺼﻰ اﻟﻀﺒﻂ وإﻻ أﻋﻠﻰ ﻣﻦ ذﻟﻚ ﻳﻌﺘﺒﺮﻩ ﻋﻴﺐ ﺣﻘﻴﻘﻲ وﺑﻌﺪ ذﻟﻠﻚ ﻧﺮﻓﻊ 3Voاﻟﻲ اﻋﻠﻲ ﻣﻦ
35
7SA522- Practical Ref. For Testing
اﻟﻀﺒﻂ آﻴﻒ ذﻟﻚ؟ ﺑﺄن ﺗﻘﻠﻞ ﺟﻬﺪ ﻓﺎزة واﻟﺒﺎﻗﻲ آﺎﻟﺴﻠﻴﻢ ﻓﺎﻟﻔﺮق ﺑﻴﻨﻬﺎ وﺑﻴﻨﻬﻢ هﻮ اﻟـ .3Voوﺑﺬﻟﻚ ﺳﻮف ﻳﻌﻤﻞ اﻟﺮﻳﻠﻪ
ﺑﻠﻮك ﻓﻮرا وﻟﻤﺒﺔ اﻟـ fuse failﺗﻨﺰل ﺑﻌﺪ زﻣﻦ 10 S
-2ﺿﺒﻂ 3Voﺑﻘﻴﻤﻪ ﺻﻐﻴﺮﻩ وﻧﺤﻘﻖ اﻟﻔﺮق ﺑﺎﻟﺤﻘﻦ اﻋﻠﻲ ﻣﻦ اﻟﻀﺒﻂ وﺑﻌﺪ ذﻟﻚ ﻧﺤﻘﻦ 3Ioاآﺒﺮ ﻣﻦ اﻟﻀﺒﻂ وﻧﻨﺰل
ﺑﻠﺤﻘﻦ .وﺑﺬﻟﻚ ﺳﻮف ﻳﻌﻤﻞ اﻟﺮﻳﻠﻪ ﺑﻠﻮك زﻣﻦ 10 S
ﻳﻌﻨﻲ ﺗﺨﻠﻲ ﺷﺮط أﻧﻪ ﻳﻮﺟﺪ 3Voﻣﺘﺤﻘﻖ ﻟﻜﻦ ﺷﺮط أن 3Ioأﻗﻞ ﻣﻦ (AD 2912A max I Thresd.) 0.1ﺗﺠﻌﻠﻪ
ﻏﻴﺮ ﻣﺘﺤﻘﻖ ﻳﻌﻦ ﺗﺠﻌﻞ 3Io>0.1Aﻓﺎﻟﺠﻬﺎز ﻻ ﻳﻌﻤﻞ ﺑﻠﻮك ﻳﻌﺘﺒﺮهﺎ ﺣﺎﻟﺔ faultyﺛﻢ ﺗﻘﻠﻞ 3Ioﺑﺄن ﺗﻨﺰل ﺑﺎﺗﻴﺎر آﻤﺎ
ﺑﺎﻟﺼﻮرة ﻓﺘﺠﺪ اﻟﺠﻬﺎز ﻳﻌﻤﻞ ﺑﻠﻮك ﻋﻨﺪ 0.1A
*ﻧﻌﻤﻞ ) (AD2915= OFFوﻧﺤﻘﻦ ﻃﺒﻴﻌﻲ وﺑﻌﺪ ذﻟﻚ ﻧﺤﻘﻦ ﺟﻬﺪ ﻣﺘﺴﺎوي ﻟﻠﻔﻴﺰات اﻗﻞ ﻣﻦ اﻟﻀﺒﻂ)(AD2913A
وﻧﺤﻘﻦ ﺗﻴﺎر ﻟﻠﻔﻴﺰات ﻳﺤﻘﻖ اﻟﻔﺮق ﺑﻴﻨﻪ وﺑﻴﻦ اﻟﺤﺎﻟﻪ اﻟﻄﺒﻴﻌﻴﻪ (AD2914A).
*ﺷﺮﻃﺎن ﻻﺑﺪ ان ﺗﺘﺤﻘﻖ ان ﻳﻜﻮن ال Vﻓﻲ اﻟﻔﻴﺰات اﻟﺜﻼﺛﻪ اﻗﻞ ﻣﻦ اﻟﻀﺒﻂ و اﻟﻔﺮق ﺑﻴﻦ اﻟﺘﻴﺎرات ﻓﻲ ﺣﺎﻟﺔ اﻟﺠﻬﺪ ﻃﺒﻴﻌﻲ واﻟﺠﻬﺪ ﺗﺤﺖ اﻟﻀﺒﻂ
هﺬﻩ اﻟﻮﻇﻴﻔﺔ ﺗﺴﺘﻌﻤﻞ اﻟﺘﻴﺎر اﻟﻤﺨﺰن وﺗﺸﺘﺮط 3ﺷﺮوط:
-1آﻞ اﻟﺠﻬﻮد ﻣﻊ اﻷرﺿﻲ أﻗﻞ ﻣﻦ اﻟﻀﺒﻂ ).(5V
ﻣﻦ ). (AD2914A آﻞ ﻓﺮوق اﻟﺘﻴﺎرات أﻗﻞ -2
آﻞ ﻗﻴﻢ اﻟﺘﻴﺎرات أآﺒﺮ ﻣﻦ > Iphاﻟﺨﺎﺻﺔ ﺑﺎﻟـ . Distance -3
وإﻻ ﻟﻮ آﺎن اﻟﺘﻴﺎر اﻟﻤﺨﺰن ﻏﻴﺮ ﻣﻮﺟﻮد ﻓﻼﺑﺪ ﻣﻦ ﺗﺤﻘﻖ ال 3ﺷﺮوط اﻻﺗﻴﺔ:
آﻞ اﻟﺠﻬﻮد ﻣﻊ اﻷرﺿﻲ أﻗﻞ ﻣﻦ اﻟﻀﺒﻂ ).(5V -4
ﻣﻦ > Iphاﻟﺨﺎﺻﺔ ﺑﺎﻟـ . Distance أﻗﻞ -5آﻞ ﻗﻴﻢ اﻟﺘﻴﺎرات
-6آﻞ ﻗﻴﻢ اﻟﺘﻴﺎرات أآﺒﺮ ﻣﻦ .40mA
36
7SA522- Practical Ref. For Testing
voltage absent ﻟﻢ ﺗﻨﺰل وﻧﺰل ﻓﻲ ﺳﺠﻞ اﻷﺣﺪاثFuse failure ﺗﻨﺰل اﻟﺒﻠﻮك ﻟﻜﻦ
(AD2913A=5V) . (AD2914A=0.2A)
STAT1 STAT2
L1 L1
I=1 V=30 I=0.9 V=5
L2 L2
I=1 V=30 I=0.9 V=5
L3 L3
I=1 V=30 I=0.9 V=5
• اذا اﻟﻔﺮق ﺑﻴﻦ اﻟﺘﻴﺎر ﻓﻲ اﻟﺤﻠﺘﺎﻧﻦ اﻗﻞ ﻣﻦ اﻟﻀﺒﻂ واﻟﺠﻬﺪ اﻗﻞ ﻣﻦ اﻟﻀﺒﻂ
9. FUSE FAIL MONITOR:( 2910)
D)BROKEN CONDUCTOR.
405 * ﻣﻮﺟﻮد ﺻﻔﺤﻪ
وهﻮ اﺷﺎرﻩ ﻓﻘﻂ. • ﻧﺤﻘﻦ ﺟﻬﺪ ﻃﺒﻴﻌﻲ وﺗﻴﺎر ﻃﺒﻴﻌﻲ ﺛﻢ ﻧﻔﺘﺢ داﺋﺮة ﺗﻴﺎر اﺣﺪ اﻟﻔﻴﺰات
10 .SCHEME CHECK:
E) BLOCKING SCHEME
37
7SA522- Practical Ref. For Testing
13.
At isa tester:
Choose:
- transit time 0.2, Z start= 40.55 Ohm, Zend=0.5Ohm.
ok psw block and the led is on,now you have tested Z1
For Z2: Zend= 2.5,Z3:Zend =4.5, Z5:Zend=8.5( According to you
settings!)
if more rapid (t=0.175 for Z1 and 0.14 for Z5) the relay make trip after
the time at AD2007 (trip delay after PS blocking)
The max. limit is about:
If dZ/Sec>(-229) Ohm/sec, the relay trip
(AD2002)ALL ZONE BLOCK ………………..
Z2 → Z5 BLOCK ………………..
OUT OF STEP TRIPPING ………………..
) وهﻨﺎ ﺳﻴﻌﻤﻞ ﺗﺎﻳﻤﺮ( وهﻲ ﻗﺒﻞPPOL * ﻧﺤﻘﻦ ﺗﻴﺎر وﺟﻬﺪ ﻃﺒﻴﻌﻲ ﺛﻢ ﻧﻨﺰل ﺑﺎﻟﺠﻬﺪ وﺳﻴﺪﺧﻞ ﻓﻲ ال
أﻣﺎ إذا ﺧﺮﺟﺖ ﻣﻦ اﻟﺠﻬﺔ. ﺑﻲ ﺧﻤﺴﻪ اوم ﻓﻠﻮ ﻗﻄﻌﺖ اﻟﺨﻤﺴﺔ اوم ﺑﺒﻂء ﺳﻮف ﻳﻌﻤﻞ ﺑﻠﻮكZ5ال
OUT OF STEP TRIPPING ﺑﻲTRIPاﻟﻤﻌﺎآﺴﺔ ﺳﻴﻌﻤﻞ
OUT OF STEP TRIP????? ﻣﺎ ﻋﺮﻓﺘﺶ أﻋﻤﻞ
38
7SA522- Practical Ref. For Testing
39