Sie sind auf Seite 1von 4

Eaton姞 IQ 250 and IQ 260

Electronic Power Meters


Compact, digital meter
Product Focus delivers high-end power
management performance

Introduction Eaton’s IQ 250 and IQ 260


With energy costs skyrocketing, meters provide direct-reading
you need the ability to verify metered values for the most
the accuracy of utility billing critical power aspects, such as
and allocation of energy costs watts, watt demand, watt-
among business units, different hours, voltage-amperes (VA),
manufacturing areas or facilities, VA-hours, vars, var-hours and
and tenants. Production power factor. They have high
equipment and IT systems are sampling speed and accuracy.
vulnerable to power anomalies; The IQ 260 meter also meas-
therefore you must ensure ures power quality, such as total
power is always up to specifica- harmonic distortion (THD) up to
tions. If your infrastructure is the 40th order. The IQ 260 also
an established facility, you may provides configurable limit
have addressed these concerns alarming/control capability of up
in the past by deploying a to eight measured parameters
variety of analog gauges and for more sophisticated
meters — one for volts, one power management.
for amperes, and so on, with Is the utility company billing
separate meters for each accurately? The IQ 250 and IQ
measurement. If you’re planning 260 models provide a traceable
an upgrade or new power infra- KYZ watt-hour test pulse (used
structure, no doubt you would with a watt-hour pulse recorder
like to capitalize on the latest or totalizer), so you can verify
IQ 250/260 Electronic Power Meter technology to improve upon that the accuracy of your meter, and
cumbersome architecture and in turn, the accuracy of billing
its patchwork view. from the utility company and to
Eaton姞 IQ 250/260 • Monitor power utilization
internal customers.
Electronic Power Meters and quality with ANSI C12.20
accuracy (0.2 percent) High-End Capabilities You In addition, Eaton’s IQ 250/260
Would Not Expect From An meters are “prepared for the
Typical Applications • Verify meter accuracy Ultra-Compact Meter
with KYZ test pulse future,” providing flexible
• Utility and Providing the first line of input/output options for access
self-certification capabilities
commercial metering defense against costly power to future upgrades, some yet
• Standard Modbus姞 RTU problems, Eaton’s IQ 250 and to be conceived. The meters
• Substations, industrial
communications IQ 260 electronic power meters are also designed to integrate
facilities, power generation
sites and campuses • Available as transducer only can perform the work of an into Eaton’s Power Xpert
or with display entire wall of legacy metering Architecture for end-to-end man-
• Sub-metering equipment utilizing today’s agement of your entire power
• “Prepared for the future” — system, giving you a holistic
• Load studies and technology. Eaton’s IQ 250 and
The meters are designed to system-level view. Further, field
voltage recording IQ 260 meters use 24-bit A/D
accommodate upgrades and upgradeability allows you to add
Analog meter replacement converters that sample at more
• capabilities not yet conceived features, as you need them.
than 400 samples per cycle and
• Integrate into Eaton’s Power meet ANSI C12.20 standards for
Features and Benefits Xpert姞 Architecture for a accuracy of 0.2 percent. With
• Measure and display holistic system-level view such high-performance meas-
real-time information about urement capability, these
critical power parameters meters can be confidently used
with a sampling rate of 400 for primary revenue metering
samples per cycle and sub-metering applications.
FEATURES OF IQ 250/260 ELECTRONIC POWER METERS Mix-and-Match power conditions. Simply
Features IQ 250 IQ 260 Input/Output Options connect your meter to a Power
Perhaps you need to: Xpert Gateway to translate
Instrumentation Modbus-based information
Current, per Phase X X • Monitor the status of a piece from the meter into HTML-
Current Demand X X of equipment based Web pages, accessible
Calculated Neutral Current X X • Activate a warning light from any standard Web
Voltage, per Phase (L-L, L-N) X X if voltage exceeds a browser. With access to
certain threshold accurate, real-time information
Frequency X X
from IQ 250/260 meters, the
Power, Energy & Demand • Trigger a relay contact- Power Xpert Architecture can
Real, Reactive & Apparent Power, Total & per Phase X X closure device transform your power system
(kW, kvar, kVA) • Transmit power information into an integrated, agile system,
Real, Reactive & Apparent Energy, Total & per Phase X X directly to a process-control an easily managed entity that
(kWh, kvarh, kVAh) system or building performs better and costs less.
Real, Reactive & Apparent Power Demand X X management system,
Power Factor, Total & per Phase X X or to a legacy system that Designed for the User
Min./Max. Readings, I, V, PF, F, THD (IQ260), kW, kvar, kVA X X doesn’t use Modbus
When space is at a premium,
Demand Methods For any of these scenarios, IQ yet you need ANSI C12.20 accu-
Block Interval (Sliding, Fixed) X X 250/260 power meters provide racy, Eaton IQ 250/260 meters
Communications optional input/output (I/O) cards fit the bill. These ultra-compact
that meet the need for either meters are ideal for electrical
RS-485 X X manual or automatic operation. equipment assemblies, machine
KYZ Output X X control panels, such as panel-
Eaton’s IQ 250 and IQ 260
Modbus RTU X X board and switchboard mains
meters provide flexible
Modbus ASCII X X configuration, with four optional and feeders, low voltage
DNP 3.0 X X cards available (analog and metal-enclosed switchgear
digital), which can be combined feeders and motor control
I/O
in any fashion in two universal centers. Requiring far less
2 Digital In / 2 Digital Out 1 Opt. Opt. space than other meters with
communication slots. The
4 Digital In / 4 KYZ Out Opt. Opt. similar functionality, IQ 250/260
meters auto-detect the installed
4 Analog Output (4 – 20 mA) 2 Opt. Opt. I/O modules, so you can easily meters fit into a standard
4 Analog Output (0 – 1 mA) Opt. Opt. add or change I/O cards after ANSI or IEC cutout on a
Power Quality Analysis installation, giving you the panelboard or other electrical
ability to upgrade as needed. equipment, and therefore fit
Total Harmonic Distortion (THD) Voltage and Current per Phase X easily into retrofit applications.
Alarming
Industry-Standard Most meters in this class have
Set Point Driven Alarm X
Communication Protocols small or dark displays that can
1 Digital Out with the IQ 250 requires external command. be hard to see, especially from a
IQ 250 and IQ 260 meters use
2 Requires external power supply.
distance. Eaton’s IQ 250 and IQ
the open Modbus protocol.
260 meters have a large, bright
This industry-standard protocol
red, three-line LED display, each
provides serial communications
line more than a half-inch tall.
with Eaton or third-party
This display is very easy to read,
platforms, such as a building
even if the meter is installed at
management system, power
a height or distance. Using the
management system, or
keypad and menus on the local
Eaton’s Power Xpert Gateway
display, users can display a
for Web-based monitoring
variety of electrical system
as part of Eaton’s Power
values or program the meter
Xpert Architecture.
(see Figure 1). The IQ 250
and IQ 260 meters can also be
Integrated with Eaton’s configured remotely using Eaton
Power Xpert Architecture configuration software, provided
IQ 250/260 meters integrate with the meter.
into Eaton’s Power Xpert In addition, the meters are
Architecture, where meters, available with or without the
gateways and monitoring display module. You might
devices collaborate to create choose to forego the display
a unified, centralized view of for applications where there is
the end-to-end power and no need to configure or read
facility’s infrastructure. the meter locally. This option
When used in this architecture reduces costs, especially
and in conjunction with Eaton’s where many meters will be
Power Xpert Gateway, IQ 250 monitored from a central
and IQ 260 meters can provide operations system.
Web-based graphics of current

IQ 250/260 Meter (Rear View) With Connection and Communication Ports

2 EATON CORPORATION IQ 250/260 Electronic Power Meters


The Reading Type indi- The Parameter
cator shows what type Designator shows
of information you’re the parameter being
viewing, such as mini- displayed, such
mum, maximum or as volts, amps,
%THD and above frequency, power
or below limits or energy.
exceeded (IQ 260).

These lights show The watt-hour test


how loaded the pulse is used to
circuit is, from verify the accuracy
10 to 100 percent, of the meter.
relative to the
programmed
maximum.

The scaling factor Configurable Auto


shows the scale of Scroll to display all
the displayed value, key values in turn
which varies or fixed display.
between low-
and high-voltage
applications.

Figure 1 — IQ 250/260 Meter Faceplate Display

IQ 250/260 Meter Dimensions

4.85 (123.2) 4.97 (126.2) 4.93 (125.2)


4.20 (106.7) 4.16 (105.7)

4.85 5.02 3.54


(123.2) (127.5) (89.9)

Expandable I/O Componentry

3.25 (82.6) 3.25 (82.6)

IQ 250/260 Face IQ 250/260M Side IQ 250/260T Side

IQ 250/260 Meter Dimensions — Face and Side Views

Ordering Information
IQ 250/260 METER IQ 250 M A 6 5 1 1 0

Model Series I/O Slot 2


250 = Power 0 = None
260 = Power Quality Frequency Power Supply
1 = 2 Relay Outputs/2 Status Inputs
5 = 50 Hz System Current Input 1 = 90 – 265 Vac/dc 2 = 4 KYZ Pulses/4 Status Inputs
6 = 60 Hz System 1 = 1 Amp Secondary 4 = 24 – 48 Vdc 3 = 4 Analog Outputs: 0 – 1 mA
Meter Type
5 = 5 Amp Secondary 4 = 4 Analog Outputs: 4 – 20 mA
M = Meter (with integral display)
T = Transducer Only (no display)
I/O Slot 1
0 = None
1 = 2 Relay Outputs/2 Status Inputs
2 = 4 KYZ Pulses/4 Status Inputs
3 = 4 Analog Outputs: 0 – 1 mA
4 = 4 Analog Outputs: 4 – 20 mA

EATON CORPORATION IQ 250/260 Electronic Power Meters 3


IQ 250/260 Electronic Power Meter Technical Information

CURRENT INPUTS UPDATE RATE

Class 10 5 Amp Nominal, 10 Amp Max. Watts, Var and VA 100 msec at 60 Hz
Class 2 1 Amp Nominal, 2 Amp Max. All Other Parameters 1 Second at 60 Hz
Fault Current Withstand
100 Amps for: 10 Seconds POWER SUPPLY
300 Amps for: 3 Seconds
AC/DC Voltage Option 90 – 265 Vac at 50/60 Hz or
500 Amps for: 1 Second 100 – 370 Vdc, Universal AC/DC Supply
Continuous Current Withstand 20 Amps for Screw Terminated or DC Voltage Option 18 – 60 Vdc
Pass-through Connections
Burden 10 VA Max.
Programmable Current Full Scale to Any CT Ratio
Burden 0.005 VA per Phase Max. at 11 Amps
STANDARD COMMUNICATIONS FORMAT
Pickup Current 0.1% of Nominal
Class 10 5 mA Connection Type RS-485 (Through Back Plate)
Class 2 1 mA Com Port Baud Rate 9600 – 57,600 Bauds
Connections Com Port Address 01 – 247
Pass-through Wire Gauge Dimension 0.177 Inches (4.5 mm) Data Format 8-Bit, No Parity
Quick Connect 0.25-Inch Male Tab Protocols Modbus ASCII, RTU or DNP 3.0

VOLTAGE INPUTS KYZ PULSE

Range Contacts 1 Form A


Line-to-Neutral 20 – 576 Vac On Resistance, Max. 35 Ohms
Line-to-Line 0 – 721 Vac Peak Switching Voltage 350 Vdc
Programmable Voltage Range Full Scale to Any PT Ratio Continuous Load Current 120 mA
Supported Systems 3 Element Wye, 2.5 Element Wye, Peak Load Current 350 mA (10 ms)
2 Element Delta, 4-Wire Delta Systems Off-state Leakage Current at 350 Vdc 1 uA
Input Impedance 1 Meg Ohm/Phase Opto-isolation 3750 Vac
Burden 0.36 VA/Phase Max. at 600 V;
0.014 VA at 120 Volts
Connection 7-Pin 0.400-Inch Pluggable Terminal DIMENSIONS AND SHIPPING
Block, AWG #12 – 26 (0.129 – 3.31 mm2)
Weight 2 lbs.
Basic Unit H 5.00 x W 4.90 x L 5.00 Inches
ISOLATION
IQ 250/260 Mounts in 92 mm DIN and ANSI
All inputs and outputs are galvanically isolated to 2500 volts. C39.1 Round Cut-outs
Shipping Container Dimensions 6-Inch Cube
Tolerance +/-0.1 Inches (2.54 mm)
ENVIRONMENTAL RATINGS

Operating Temperature -20ºC to +70°C COMPLIANCE


Storage Temperature -20ºC to +70°C
IEC 687 0.2% Accuracy
Operating Humidity To 95% RH Non-condensing
ANSI C12.20 0.2% Accuracy
Faceplate Rating NEMA姞 12
Water-resistant ANSI C62.41 Burst
Mounting Gasket Included UL姞/cUL姞 Electrical & Electronic
Measuring & Test
Equipment 22CZ
SENSING METHOD

Voltage, Current True RMS


Power Sampling at Over 400 Samples per
Cycle On All Channels
Harmonics Resolution 40th Order

Note: Features and specifications listed in this


document are subject to change without notice
and represent the maximum capabilities of the
software and products with all options installed.
This is not a complete feature list. Features and
functionality may vary depending on selected
options.
Eaton Corporation
Electrical Group Eaton and Power Xpert are registered
trademarks of Eaton Corporation. NEMA is the
1000 Cherrington Parkway registered trademark and service mark of the
Moon Township, PA 15108 National Electrical Manufacturers Association. © 2008 Eaton Corporation
United States UL and cUL are registered trademarks of All Rights Reserved
Underwriters Laboratories Inc. Modbus is a Printed in USA
877-ETN-CARE (877-386-2273) registered trademark of Modicon, a division Publication No. PA02601007E / Z7269
Eaton.com of Schneider Electric Industries SA. June 2008