ELECTRICAL BOQ

SR. DESCRIPTION BOQ UNIT RATE


NO. QTY.

A MEDIUM VOLTAGE CABLES & MAINS WIRING


A1 Supply, Laying & connection of 2 # 4.0 & 1 # 2.5 SQ.MM. FRLS copper 60 Mtrs.
wires in 25mm Dia. MMS PVC conduit in wall / slab / floor from
Distribution board to AC point with connector. The unit rate shall include
rate of Supply, Laying & connection of wires & pipes.
A2 Supply, Laying & connection of 2 # 2.5 & 1 # 1.5 SQ.MM. FRLS copper 150 Mtrs.
wires in 25mm Dia. MMS PVC conduit in wall / slab / floor from
Distribution board to switch board / Power Point in 25mm Dia. MMS PVC
conduit in wall / slab / floor. The unit rate shall include rate of Supply,
Laying & connection of pipes & wires.
A3 Supply, Laying & connection of 3 # 1.5 SQ.MM. FRLS copper wires in 150 Mtrs.
25mm Dia. MMS PVC conduit in wall / slab / floor from Distribution board
to switch board / Power Point in 25mm Dia. MMS PVC conduit in wall /
slab / floor. The unit rate shall include rate of Supply, Laying & connection
of pipes & wires.
A4 Supply and laying of 4.0 Cx 10.0 sq.mm.YWY copper cable 100 Mtrs.
A5 Supply and laying of 4.0 Cx 6.0 sq.mm.YWY copper cable 0 Mtrs.
A6 Supply and laying of 1C x 6.0 sq.mm. Cu. Flexible Wire 10 Mtrs.
A7 Supply and Laying of CAT-6 Cable in Existing 25mm dia. PVC conduit 500 Mtrs.

A8 Supply and Laying of 2C x 1 Speker Cable in Existing 25mm dia. PVC 200 Mtrs.
conduit ( Speker Cable )
A9 Supply & laying of 3+1 CCTV Camera cable in Existing 25mm dia. PVC 200 Mtrs.
conduit
A10 Supply & laying of RG6 cable in Existing 25mm dia. PVC conduit 100 Mtrs.
A7 Supply and installation of 200 x 50 x 1.5 thickness GI Perforated Cable 57.5 Mtrs.
tray with 8 MM Threded Rods hanging arrangment
B CABLE CONNECTIONS & TERMINATIONS
B Supply, Connections & Termination of Medium voltage PVC insulated
cables as per the specification & instruction of Engineer-in-charge. The
unit rate shall include supply & connection of adequate size single
compression type brass cable glands and tinned copper / AL. lugs
including cutting/stripping of cable insulation, fixing of cable glands,
crimping the lugs,PVC insulated tape and all other material required.

B1 4.0 Cx 10.0 sq.mm.YWY copper cable 2 Nos.


B2 4.0 Cx 6.0 sq.mm.YWY copper cable 0 Nos.
B3 1C x 6.0 sq.mm. Cu. Flexible Wire 2 Nos.
C INTERNAL WIRING
C1 LIGHT POINT WIRING
C1 Supply, Installation, Testing & commissioning of Light point, Plug point,
Fan point, Exhaust Fan point as per specification, drawing and as per
instruction of Engineer-in-charge. The unit rate shall comprise of
switch, socket, plate, Box and PVC pipe & wires. Rate for MCB &
MCBDB should not be included in unit rate.
Wire size for off wiring shall be 3 # 1.0 sq.mm copper flexible wires from
Switch board to point.
All above wiring shall be done in 25 mm dia. PVC conduit in concealed
manner on wall / slab or in floor. Unit rate shall comprise of conduits & off
wiring.
ELECTRICAL BOQ
SR. DESCRIPTION BOQ UNIT RATE
NO. QTY.
C1.1 One light point control by one 6A Switch. 15 Nos.
(Primary Light Point) - Mains to be considered in Runnig Meter & Off
wiring shall be 5Mtr.
C1.2 Secondary Light by same 6A switch. Off wiring shall be 3Mtr. 45 Nos.
C1.3 One light point control by MCB. 15 Nos.
2 # 2.5 sq.mm & 1# 1.5 sq.mm copper flexible wires as an off wiring shall
be from MCBDB to looped point.
(Primary Light Point) Average Length 12Mtr.
C1.4 Secondary Light point control by same MCB. 25 Nos.
2 # 2.5 sq.mm & 1# 1.5 sq.mm copper flexible wires as an off wiring shall
be from MCBDB to looped point. Average Length 5Mtr.
C1.5 Two way light point control by Two way switch. Mains to be considered 1 Nos.
in Runnig Meter & Off wiring shall be 10Mtr.
C1.6 One Fan point control by one switch & hume free electronic Regulator. 2 Nos.
Mains to be considered in Runnig Meter & Off wiring shall be 5Mtr.

C1.7 One Exhaust Fan point control by one switch without plug. Mains to be 1 Nos.
considered in Runnig Meter & Off wiring shall be 5Mtr.
C1.8 6A plug point controlled by one switch on switchboard. Mains to be 5 Nos.
considered in Runnig Meter.
C1.9 Primary 6A plug point controlled by one switch at separate location. 5 Nos.
Mains to be considered in Runnig Meter.
C1.10 Secondary 6A plug point controlled by one switch at separate location. 5 Nos.
Mains to be considered in Runnig Meter.
C2 PLUG POINT WIRING
C2 Supply, Installation, Testing & commissioning of 6/16A Plug point as per
specification, drawing and as per instruction of Engineer-in-charge.6/15A
universal plug point controlled by one 16A switch on switchboard es in
25mm dia. PVC conduits as a mains from MCBDB to point. The unit rate
shall comprise of universal socket, switch, plate, Box and PVC pipe &
wires.

C2.1 5/15A plug point primary - Mains to be considered in runnig meter. 30 Nos.

C2.2 5/15A plug point secondary - Mains to be considered in runnig meter. 29 Nos.

C3 Supply, Installation, Testing & commissioning of 6/16A Plug point as per


specification, drawing and as per instruction of Engineer-in-charge.6/15A
universal plug point controlled by one 16A switch on other switchboard
(Diffrent Location) es in 25mm dia. PVC conduits as a mains from
MCBDB to point. The unit rate shall comprise of universal socket, switch,
plate, Box and PVC pipe & wires.

C3.1 5/15A plug point primary - Mains to be considered in runnig meter. 4 Nos.

C3.2 5/15A plug point secondary - Mains to be considered in runnig meter. 4 Nos.
ELECTRICAL BOQ
SR. DESCRIPTION BOQ UNIT RATE
NO. QTY.
C3 LIGHT FIXTURE INSTALLATION
C3 Installation, testing, Connection & commissioning of Light Fixture as per
specification and drawings.The unit rate shall include supply, assembling,
marking of light fixture at false ceiling or ceiling.( if using additional
supporting then that cost will be extra as per design)

C3.1 2ft/4ft T-5 light 36 Nos.


C3.2 Linear light 0 Mtrs.
C3.3 Down/Spot Light 51 Nos.
C3.4 4ft linear type light for kitchen 9 Nos.
C3.5 Decorative Light 2 Nos.
C4 Supply & laying of MMS PVC conduit concealed in slab / floor / wall as
per point requirement. The rate shall be included with necessary
bends,tee,Junction,floor / skirtinh junction & also with necessary
hardware.
C4.1 25mm dia. MMS PVC conduit 400 Mtrs.
C4.2 50mm dia. MMS PVC conduit 0 Mtrs.
D MCB WITH ENCLOUSER
Supply, Installation, testing & commissioning of Three Phase / Single
Phase - Single Door type, MCB enclouser with FP/DP MCB as per
drawings,specifications & as per the insturction of engineer-in-charge.
D1 The unit rate shall include supply & fixing on wall / column, checking of
wiring, connection and operation of MCBs and supply of necessary
hardware.

D1.1 40A FP, MCB with Enclouser (10kA) 1 Nos.


D1.2 32A / 16A FP, MCB with Enclouser (10kA) 1 Nos.
Supply, Installation, testing & commissioning of Three Phase / Single
Phase - Double Door type, MCB enclouser with FP/DP MCB as per
drawings,specifications & as per the insturction of engineer-in-charge.
D2 The unit rate shall include supply & fixing on wall / column, checking of
wiring, connection and operation of MCBs and supply of necessary
hardware.( ELCB-100ma,MCB-10kA)

1 Nos.
D2.1 12Way SPN DD DB With 1no.#32A DP ELCB and 10no.#10A SP MCB
D2.2 16A SP MCB 12 Nos.
6Way TPN DD DB With 1no.#63A FP ELCB,3no.#32A DP 1 Nos.
D2.3
MCB,12no.#16A SP MCB

E EARTHING WIRE
E1 8 SWG CU.wire 10 Mtrs.

TOTAL

NOTES
1 Billing As per Site Measurements
2 In Switchboard and there Accessoires we have consider Legrand
( Britzy ),MK ( Blenze ) or equivalent
3 This BOQ made by take a refrence from Drawing so at that exicution
time qty will be increase or decrease up to 30%
4 At the Execution time if we will need or found NT ( Extra Item ) Item
then its rate share sepretly
TOTAL
RATE
TOTAL
RATE
TOTAL
RATE