| DIgSILENT | Project: |
| |
| PowerFactory |-------------------------------
| |
| 15.1.7 | Date: 6/28/2019 |
-----------------------------------------------------------------------------------
------------------------------------------------
-----------------------------------------------------------------------------------
------------------------------------------------
| Load Flow Calculation
Busbars/Terminals |
-----------------------------------------------------------------------------------
------------------------------------------------
| AC Load Flow, balanced, positive sequence | Automatic Model
Adaptation for Convergence No |
| Automatic Tap Adjust of Transformers No | Max. Acceptable
Load Flow Error for |
| Consider Reactive Power Limits No | Nodes
1.00 kVA |
| | Model
Equations 0.10 % |
-----------------------------------------------------------------------------------
------------------------------------------------
-----------------------------------------------------------------------------------
------------------------------------------------
| Grid: Grid System Stage: Grid | Study Case: Study
Case(2) | Annex: / 1 |
-----------------------------------------------------------------------------------
------------------------------------------------
| rated Active Reactive Power |
|
| Voltage Bus-voltage Power Power Factor Current Loading|
Additional Data |
| [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] |
|
-----------------------------------------------------------------------------------
------------------------------------------------
|Barra 1 |
|
| 13.80 1.00 13.80 0.00 |
|
| Cub_2 /Sym Generador 1 70.56 59.87 0.76 3.87 92.54 |
Typ: SL |
| Cub_1 /Tr2 T1 70.56 59.87 0.76 3.87 92.54 |
Tap: 0.00 Min: 0 Max: 0 |
| |
|
|Barra 2 |
|
| 230.00 0.94 216.84 145.71 |
|
| Cub_3 /Lod SL2 50.00 30.00 0.86 0.16 |
Pl0: 50.00 MW Ql0: 30.00 Mvar |
| Cub_1 /Tr2 T1 -70.56 -51.31 -0.81 0.23 92.54 |
Tap: 0.00 Min: 0 Max: 0 |
| Cub_2 /Lne L1 20.56 21.31 0.69 0.08 8.34 |
Pv: 23.68 kW cLod: 2.32 Mvar L: 15.00 km|
| |
|
|Barra 3 |
|
| 230.00 0.94 215.95 145.55 |
|
| Cub_3 /Lod SL3 50.00 30.00 0.86 0.16 |
Pl0: 50.00 MW Ql0: 30.00 Mvar |
| Cub_1 /Lne L1 -20.54 -23.48 -0.66 0.08 8.34 |
Pv: 23.68 kW cLod: 2.32 Mvar L: 15.00 km|
| Cub_2 /Lne L2 -29.46 -6.52 -0.98 0.08 8.07 |
Pv: 45.59 kW cLod: 4.63 Mvar L: 30.00 km|
| |
|
|Barra 4 |
|
| 230.00 0.94 216.58 146.08 |
|
| Cub_4 /Lod SL4 50.00 30.00 0.86 0.16 |
Pl0: 50.00 MW Ql0: 30.00 Mvar |
| Cub_1 /Lne L3 -30.71 -11.54 -0.94 0.09 8.75 |
Pv: 69.22 kW cLod: 6.23 Mvar L: 40.00 km|
| Cub_2 /Lne L2 29.51 2.17 1.00 0.08 8.07 |
Pv: 45.59 kW cLod: 4.63 Mvar L: 30.00 km|
| Cub_3 /Lne L5 -48.79 -20.64 -0.92 0.14 14.12 |
Pv: 227.01 kW cLod: 7.84 Mvar L: 50.00 km|
| |
|
|Barra 5 |
|
| 230.00 0.95 217.83 146.79 |
|
| Cub_3 /Lod SL5 50.00 30.00 0.86 0.15 |
Pl0: 50.00 MW Ql0: 30.00 Mvar |
| Cub_1 /Lne L4 -80.78 -35.74 -0.91 0.23 23.41 |
Pv: 195.27 kW cLod: 2.37 Mvar L: 15.00 km|
| Cub_2 /Lne L3 30.78 5.74 0.98 0.08 8.75 |
Pv: 69.22 kW cLod: 6.23 Mvar L: 40.00 km|
| |
|
-----------------------------------------------------------------------------------
------------------------------------------------
-----------------------------------------------------------------------------------
------------------------------------------------
| Grid: Grid System Stage: Grid | Study Case: Study
Case(2) | Annex: / 2 |
-----------------------------------------------------------------------------------
------------------------------------------------
| rated Active Reactive Power |
|
| Voltage Bus-voltage Power Power Factor Current Loading|
Additional Data |
| [kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%] |
|
-----------------------------------------------------------------------------------
------------------------------------------------
|Barra 6 |
|
| 230.00 0.95 219.48 147.47 |
|
| Cub_4 /Lod SL6 50.00 30.00 0.86 0.15 |
Pl0: 50.00 MW Ql0: 30.00 Mvar |
| Cub_1 /Tr2 T2 -180.00 -78.81 -0.92 0.52 102.96 |
Tap: 0.00 Min: 0 Max: 0 |
| Cub_2 /Lne L4 80.98 34.60 0.92 0.23 23.41 |
Pv: 195.27 kW cLod: 2.37 Mvar L: 15.00 km|
| Cub_3 /Lne L5 49.02 14.21 0.96 0.13 14.12 |
Pv: 227.01 kW cLod: 7.84 Mvar L: 50.00 km|
| |
|
|Barra 7 |
|
| 15.00 1.00 15.00 2.88 |
|
| Cub_2 /Sym Generador 2 180.00 100.01 0.87 7.93 102.96 |
Typ: PV |
| Cub_1 /Tr2 T2 180.00 100.01 0.87 7.93 102.96 |
Tap: 0.00 Min: 0 Max: 0 |
| |
|
-----------------------------------------------------------------------------------
------------------------------------------------