TECHNICAL PARTICULAR AND GUARANTEE
PENGADAAN DAN PEMASANGAN BUS SECTION HYBRID DI GI.NEW BALARAJA

TPG : GENERAL 150 KV HYBRID INSULATION SWITCHGEAR


No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

1 Manufacturer to be mentioned Siemens, China


Hybrid Insulation Switchgear - Double Busbar for
2 Type Hybrid Insulation Switchgear
Bus Section
3 Type of arc quenching medium - SF6 SF6
4 Standard IEC 62271-205 IEC 62271-205
5 Quantity SF6 gas required kg to be mentioned 130.8 per Hybrid Switchgear
6 Service Condition
OUTDOOR Outdoor
Altitude above sea level m < 1000 < 1000
Humidity % 70 - 90 % 70 - 90 %
Ambient temperature Max ºC 45 45
Seismic Acceleration Constant Consideration g 0.3 0.3
Polution Level mm/kV 31 31
Solar Radiation W/m2 1120 1120
7 Design Outdoor Outdoor
8 Number of Phase pcs 3 phase 3 phase
9 Free of partial discharge pC ≤5 ≤5
10 Rated Voltage kV rms 170 170
11 Rated Frequency Hz 50 50
12 Rated normal current Amp ≥4000 ≥4000
13 Basic Insulation Level (BIL) kV 750 750
14 Leakage rate of SF6 gas per annum % ≤ 0.5 ≤ 0.5
15 Rated power frequency withstand voltage, dry for 1 min
- To earth kV rms 325 325
- Across the isolating distance kV rms 375 375
16 Rated Switching Impulse withstand voltage (at 250/2500 µs)
- To earth kV Peak n/a n/a
- Across the isolating distance kV Peak n/a n/a
17 Rated lightning impulse withstand voltage (at 1.2/50 µs)
- To earth kV Peak 750 750
- Across the isolating distance kV Peak 860 860

18 Rated short time whitstand current (Ik) kA rms 40 40

Page 1 of 3
PT. PLN (PERSERO)
TRANSMISI JAWA BAGIAN BARAT

PT. PLN (Persero)


TECHNICAL PARTICULAR AND GUARANTEE
PENGADAAN DAN PEMASANGAN BUS SECTION HYBRID DI GI.NEW BALARAJA

TPG : GENERAL 150 KV HYBRID INSULATION SWITCHGEAR


No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE
19 Rated Duration of short circuit sec 3 3
20 Rated peak withstand current (Ip) kA Peak 100 100
21 Maximum temperature rise of any section at rated current
- Conductor o
C Less than 65 Less than 65
- Enclosure o
C Less than 30 Less than 30
22 Test pressure of enclosure (gauge pressure at 20 ºC)
- Positive internal pressure bar 35 20 bar for routine pressure test
- Vacuum bar 0.0005 0.0005
23 Rated operating pressure of rupture disk (gauge pressure at 20
- Circuit Breaker bar 10 14.5-16
- Others bar 10 14.5-16
24 Rated operating pressure (gauge pressure at 20 ºC)
- Circuit Breaker bar to be mentioned 6
- Others bar to be mentioned 6
25 Refill pressure (gauge pressure at 20 ºC)
- Circuit Breaker bar to be mentioned 6
- Others bar to be mentioned 6
Minimum Operating pressure (Guaranteed value) (gauge
26
pressure at 20 ºC)
- Circuit Breaker bar to be mentioned 5(general lockout pressure)
- Others bar to be mentioned 5(general lockout pressure)
27 Enclosure
Phase segregated or three phases pcs segregated ( single phase / enclosure) segregated ( single phase / enclosure)
Material (Rolling plate tube - steel or Al) - to be mentioned Al alloy casting
Overall diameter mm to be mentioned 560
Painting outside (air) to be mentioned as per customer requirement
28 Conductor
Material Al OR Cu Al
29 Voltage Control Equiptment VDC 110 110
30 Density monitor with non return valve piece/enclusur Yes Yes
31 Grounding System
For each compartment - provided provided

Page 2 of 3
PT. PLN (PERSERO)
TRANSMISI JAWA BAGIAN BARAT

PT. PLN (Persero)


TECHNICAL PARTICULAR AND GUARANTEE
PENGADAAN DAN PEMASANGAN BUS SECTION HYBRID DI GI.NEW BALARAJA

TPG : GENERAL 150 KV HYBRID INSULATION SWITCHGEAR


No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE
32 Absorbent
Switching compartment per yes filtering material absorbing the residual
Non switching comparment per yes as the switching compartment and non
33 Protection System for Pressure
- 1 st Stage Alarm and Signal Alarm and Signal
- 2 nd Stage Trip and Block Trip and Block
34 Minimum clearence in air :
35 - between phase mm 1800 refer to outline drawing
36 - phase to earth mm 1500 refer to outline drawing
37 - live conductor to ground level mm 3800 refer to outline drawing
38 - live insulator to ground level mm 2300 refer to outline drawing
39 Period of time the equipment has been in commercial operation year to be mentioned 30(service life)
40 Tolerance range for auxiliary supply voltage (in % of rated voltage)
41 - opening coil % 85-110 85-110
- closing coil % 85-110 85-110
- motor % 85-110 85-110
Kind of filtering material absorbing the residual decomposition
42 Submitted Yes
products of SF6 gas
43 Safety Margin 1.1 times from minimum functional pressure according to IEC design requirement
44 Catalog, drawing or other references yes yes
45 Type Test Certificate yes yes
46 Guarantee min 5 (five) years after operation (from manufacture) 5 (five) years after delivery

Page 3 of 3
PT. PLN (PERSERO)
TRANSMISI JAWA BAGIAN BARAT

PT. PLN (Persero)


TECHNICAL PARTICULAR AND GUARANTEE
PENGADAAN DAN PEMASANGAN BUS SECTION HYBRID DI GI NEW BALARAJA

TPG : 150 KV HYBRID INSULATION SWITCHGEAR


No. Description Unit Required Proposed And Guarantee REFERENCE
Circuit Breaker
1 Rated normal current Amp ≥4000 ≥4000
Rated making and breaking current to Normal/Reclose operating
2
sequence
* Three phase terminal fault rating
- Making current kAp 100 100
- Breaking current (symmetrical) kA 50 50
- Breaking current (asymmetrical) % dc Yes according to IEC standard Yes according to IEC standard
* Single phase earth full rating
- Making current kAp 100 100
- Breaking current (symmetrical) kA 50 50
- Breaking current (asymmetrical) % dc Yes according to IEC standard Yes according to IEC standard
* Breaking current under out phase condition kA Yes according to IEC standard Yes according to IEC standard
3 Insulation class :
- Power frequency withstand voltage (1 min) kV 325 325
- Impulse withstand voltage (1.2/50 microsec. full wave) kV 750 750
4 Operating mechanism -
a. Type of mechanism Motor Spring Motor Spring
b. Number of operating mechanism 3-pole operated 3-pole operated
5 Supply voltage
- Control voltage Vdc 110 110
- Motor voltage V Vdc= 110 Vdc= 110
Basic Design
6 Operating duty cycle :
- nominal sequence - O - 0.3s - CO - 1 min - CO O - 0.3s - CO - 3 min - CO
- out of phase - O - CO O - CO
- autoreclose :
- high speed single phase - NA NA
- high speed three phase - NA NA

Page 1 of 6
PT. PLN (PERSERO)
TRANSMISI JAWA BAGIAN BARAT

PT. PLN (Persero)


TECHNICAL PARTICULAR AND GUARANTEE
PENGADAAN DAN PEMASANGAN BUS SECTION HYBRID DI GI NEW BALARAJA

TPG : 150 KV HYBRID INSULATION SWITCHGEAR


No. Description Unit Required Proposed And Guarantee REFERENCE
7 Radio influence voltage level, measured at 1.1 Us/V3 at 1 MHz
- circuit closed to ground uV to be mentioned 15@300Ω
- circuit breaker open, grounded terminal uV to be mentioned 10@300Ω
8 Mechanical performance
Maximum - total break time (trip initation to final arc extinction) ms < 50 < 50
9 Opening time :
- without current ms < 40 < 40
- at 100% of rated breaking current ms < 40 < 40
10 Number of tripping coils per phase pcs 2 2
11 Number of closing coils per phase pcs 1 1
12 Number of auxiliary contacts (NO/NC) per phase pcs >8 >8

125(line breaking current)


13 Rated Capacitive switching current Arms 160 250(cable breaking current)
400(capacitor bank breaking current)

Maximum time interval between opening of interrupters of first and


14 ms <4 <4
last phase
15 Maximum time interval between opening of interrupters of one phase ms NA NA
16 Closing time ms < 100 < 100
17 Making time
- without current ms < 102 < 102
- 100% rated breaking current ms < 102 < 102
18 Maximum time interval between closure of the first and last pole ms <10 <10
19 Maximum time interval between closure of interrupters of one phase ms NA NA
20 Maximum arcing duration of any duty cycle ms to be mentioned 23(max. arcing time)
to IEC (62271-100) at ..%
21 Duty on which maximum arc duration occurs closing time ms < 60 < 60
Minimum time for arc extinction to contact remake when adapted for
22 ms < 300 < 300
auto reclosing
Time for closing of control-switch to completition of closing-stroke
23 ms < 300 TBD
during fault making

Page 2 of 6
PT. PLN (PERSERO)
TRANSMISI JAWA BAGIAN BARAT

PT. PLN (Persero)


TECHNICAL PARTICULAR AND GUARANTEE
PENGADAAN DAN PEMASANGAN BUS SECTION HYBRID DI GI NEW BALARAJA

TPG : 150 KV HYBRID INSULATION SWITCHGEAR


No. Description Unit Required Proposed And Guarantee REFERENCE
24 Reclosing :
- Incoming/outgoing feeder - N.A N.A
- Transformer feeder - N.A N.A
- Bus-coupler feeder - N.A N.A
25 Rated TRV at 100 % rated short ciruit breaking current
a. Peak Uc KkV-Peak 291 420
b. Rated of rise of restriking volt kV 2
26 Maximum guaranteed switching overvoltage : kV N/A N/A
27 Main contacts :
Material of contact surfaces submitted silver plated
Material of main contacs to be mentioned CuCrZr/aluminium alloy
Main Circuit contact resistance at rated current micro Ohm < 180 < 180
28 Leakage rate of SF6 gas per annum % ≤ 0.5 ≤ 0.5

29 Temperature rise of contacs and terminals at rated continuous current °C to be mentioned contacts<75terminals<60
30 Classes :
Electrical endurance E1 E1
refered to IEC 62271-100 2008 : table
Transient Recovery Voltage refered to IEC 62271-100 2008 : table 28
28
Mechanical endurance M2 M2
Restrike Performance C2 C2
31 Power consumption for closing per pole W ≤ 300 ≤ 300
32 Power consumption for opening per pole W ≤ 300 ≤ 300
Combine Disconnecting Switch / Earthing Switch
33 Rated normal current Amp ≥3150 ≥3150
34 Operating mechanism -
a. Type of mechanism Motor Drive Motor Drive
b. Number of operating mechanism 3 pole 3 pole
35 Motor operating voltage Vdc 110 110
36 Control voltage Vdc 110 110
37 Power consumption for closing W Approx. 180 Yes

Page 3 of 6
PT. PLN (PERSERO)
TRANSMISI JAWA BAGIAN BARAT

PT. PLN (Persero)


TECHNICAL PARTICULAR AND GUARANTEE
PENGADAAN DAN PEMASANGAN BUS SECTION HYBRID DI GI NEW BALARAJA

TPG : 150 KV HYBRID INSULATION SWITCHGEAR


No. Description Unit Required Proposed And Guarantee REFERENCE
38 Power consumption for opening W Approx. 180 Yes
39 Operating time sec. <4s <4s
40 Number of pole per complete unit pcs 3 3
41 Opening time of the disconnector sec. <4s <4s
42 Closing time of the disconnector sec. <4s <4s
43 Material of the main contacts - Aluminium/Copper Aluminium/Copper
Fast Acting Earthing Switch
44 Manufacturer to be mentioned NA
45 Type to be mentioned NA
46 Standards IEC 62271-1 & 62271-102 NA
47 Motor of operating mechanisms -
- Operating Voltage VDC 110 VDC NA
- Power consumption kW to be mentioned NA
- Operating time sec. max.3 NA
b. Number of operating mechanism 3-pole NA
48 Control voltage Vdc 110 NA
49 Rated operating sequence According to IEC standard NA
50 Number of pole per complete unit pcs 3 NA
51 Material of contact surface - Copper Tungsten and Silver Plated Copper NA
Classes NA
- Electrical endurance - E2 NA
- Mechanical endurance M2 NA
Current Transformer
Shanghai Zhenggang,Shanghai
52 Manufacturer - to be mentioned Zhuogao,Shenyang Trench,Zhida Nanda
etc.
53 Type of current transformer - Ring Ring
54 Standards - IEC 61869-1, 61869-2 IEC 61869-1, 61869-2
55 Number of core - 5 / to match with bill of quantity 5 / to match with bill of quantity

Page 4 of 6
PT. PLN (PERSERO)
TRANSMISI JAWA BAGIAN BARAT

PT. PLN (Persero)


TECHNICAL PARTICULAR AND GUARANTEE
PENGADAAN DAN PEMASANGAN BUS SECTION HYBRID DI GI NEW BALARAJA

TPG : 150 KV HYBRID INSULATION SWITCHGEAR


No. Description Unit Required Proposed And Guarantee REFERENCE
56 Ratio (for detail, see Bill of Quantity/BOQ)
CT 1
Core no. 1 (main protection) A/A 4000-4000/1 2000-4000/1
Core no. 2 (back up protection) A/A 4000-4000/1 2000-4000/1
CT 2
Core no. 1 (metering devices) A/A 4000-4000/1 2000-4000/1
Core no. 2 (busbar protection) A/A 4000-4000/1 2000-4000/1
Basic Design
57 Accuracy class :
CT 1
Core no. 1 (main protection) - Class PX Class PX
Core no. 2 (back up protection) - 5P20 5P20
CT 2
Core no. 1 (metering devices) - 0.2 0.2
Core no. 2 (busbar protection) - Class PX Class PX
58 Rated burden or Knee Point Voltage (on lowest ratio) :
(Rlead = 1.85 ohm for Isr = 1 A)
Rated burden (indicate on what ratio it is applied)
CT 1
Vk≥2000V;Ie≤20mA at
2000V;Rct≤12Ω at 2000/1;
V Vk ≥ 2 x (Ifault/Ratio x (Rct + Rlead))
Vk≥4000V;Ie≤10mA at
Core no. 1 (main protection) 4000V;Rct≤24Ω at 4000/1
Core no. 2 (back up protection) VA ≥ 20 (for Isr = 1) ≥ 20 (for Isr = 1)
CT 2
Core no. 1 (metering devices) VA ≥ 15 (for Isr = 1) ≥ 15 (for Isr = 1)
Vk≥2000V;Ie≤20mA at
2000V;Rct≤12Ω at 2000/1;
V Vk ≥ 2 x (Ifault/Ratio x (Rct + Rlead))
Vk≥4000V;Ie≤10mA at
Core no. 2 (busbar protection) 4000V;Rct≤24Ω at 4000/1
59 Instrument security factor - < FS 10 < FS 10

Page 5 of 6
PT. PLN (PERSERO)
TRANSMISI JAWA BAGIAN BARAT

PT. PLN (Persero)


TECHNICAL PARTICULAR AND GUARANTEE
PENGADAAN DAN PEMASANGAN BUS SECTION HYBRID DI GI NEW BALARAJA

TPG : 150 KV HYBRID INSULATION SWITCHGEAR


No. Description Unit Required Proposed And Guarantee REFERENCE
Bushing
60 Name manufacturer to be mentioned Jiangsu Shenma
61 Standards - IEC 60137 IEC 60137
62 Insulator Composite Composite
63 Type of Designation SF6 - Air SF6 - Air
64 Type of Insulation SF6 SF6
65 Current A ≥3150 ≥3150
66 Dielectric Dissipation Factor (Tan Delta) % < 0.5 < 0.5
67 Dimensions :
- Approx Length mm to be mentioned 2523
- Approx Diameter per unit mm to be mentioned 300(inner diameter)
- Approx Weight kg to be mentioned 141
Local Control Cubicle
68 Name manufacturer to be mentioned Siemens
69 Type Outdoor Outdoor
70 Protection Class IP 55 IP 55
71 Mounting Position Free Standing Free Standing
72 Material Hot deep galvanized Hot deep galvanized
73 Dimensions :
- Approx Length mm to be mentioned refer to outline drawing
- Approx Width mm to be mentioned refer to outline drawing
- Approx Weight mm to be mentioned refer to outline drawing
74 Mimic Diagram Provided Provided
75 Earthing Connection Provided Provided
Accesories
76 Steel supporting structure include include
77 Gas Filling Device include include
78 Standard Special Tools include include
79 Evacuating and refilling device include include
80 Cover Set include include
81 Guarantee min 5 (five) years after operation (from manufacture) 5 (five) years after delivery