Sie sind auf Seite 1von 113

CABIN ATMOSPHERE

CONTROL
INTRODUCTION
The crew and passengers of modern, high-performance aircraft are physically unable to survive the extreme envi-
ronment in which these airplanes fly without some sort of conditioning of the air within the cabin and cockpit.
Primarily because of the various altitudes at which an aircraft operates, the cabin atmosphere must be controlled
to increase the comfort of the occupants or even to sustain their lives. This chapter will discuss the physiology of
the human body that determines the atmospheric conditions required for life, how oxygen and cabin altitude are
controlled to provide a livable atmosphere for the aircraft occupants, and how the comfort needs of the passen -
gers and crew are met.
FLIGHT PHYSIOLOGY
In order to few seconds, this cold and TI
understand the permanent damage to oxygen-deficient air, O
reasons for the brain or even so some provision N
controlling the cabin death may result. must be made to The human body is
atmosphere or Water vapor and provide an artificial made up of living
environment, it is carbon dioxide are environment to cells that must be
necessary to also extremely sustain life. continually supplied
understand both the important with food and
characteristics of the compounds. The Standard conditions oxygen and must
atmosphere and the other gases in the air, have been have their waste
physiological needs such as argon, neon, established for all of carried away and
of the persons flying and krypton are the important removed from the
within that relatively parameters of the body. Blood,
atmosphere. Each unimportant earth's atmosphere. circulated through
type of aircraft will elements The pressure exerted the body by the
have specific physiologically. by the blanket of air heart, carries food
requirements is considered to be and oxygen to the
according to the The density of air 29.92 inches, or cells and carries
altitudes and speeds refers to the number 1013.2 hectoPascals away waste
at which the aircraft of air molecules (millibars), which products.
is flown. within a given are the same as
volume of the 14.69 pounds per When people
THE atmosphere. As air square inch at sea inhale, or take in
ATMOSPHERE pressure decreases, level, and decreases air, the lungs
The atmosphere the density of the air with altitude as seen expand and the
envelops the earth also decreases. in figure 14-1. The atmospheric
and extends upward Conversely, as standard temperature pressure forces air
for more than 20 temperature of the air at sea level in to fill them. This
miles, but because increases the density is 154 Celsius, or air fills millions of
air has mass and is of the air decreases. 594 Fahrenheit. The tiny air sacs called
compressible, the This change in air temperature also alveoli, and the
gravity of the earth density has a decreases with oxygen in the air
pulls on it and tremendous effect altitude, as diffuses through the
causes the air at the on the operations of illustrated in figure extremely thin
lower levels to be high altitude aircraft 14-1. Above 36,000 membrane walls of
more dense than the as well as feet, the temperature these sacs into
air above it. This physiological effects of the air stabilizes, blood vessels
accounts for the fact on humans. [Figure remaining at -554 C called arteries.
that more than one- 14-1] (-69.74 F). Nitrogen is not able
half of the mass of to pass through
the air surrounding Turbine engine- H these walls. The
the earth is below powered aircraft are U blood circulates
about 18,000 feet. efficient at high M through the body in
altitudes, but the A the arteries and then
The atmosphere is a human body is N into extremely thin
physical mixture of unable to exist in R capillaries to the
gases. Nitrogen E cells, where the
makes up S oxygen is used to
approximately 78% PI convert the food in
of the air, and oxygen R the blood into
makes up 21% of the A chemicals that are
total mixture. The TI usable by the cells.
remainder is O The waste product,
composed of water N carbon dioxide, is
vapor, carbon diox- A then picked up by
ide and inert gases. N the blood and
Oxygen is extremely D carried back into the
important for both CI lungs through blood
animal and plant life. R vessels called veins.
It is so important for C The carbon dioxide
animals that if they U is able to diffuse
are deprived of L through the
oxygen for even a A
Cabin Atmosphere Control 14-3
FEET IN. OFHG. MM OFHG. PSI C ° po

0 29.92 760.0 14.69 15.0 59.0

2,000 27.82 706.7 13.66 11.0 51.9

4,000 25.84 656.3 12.69 7.1 44.7

6,000 23.98 609.1 11.77 3.1 37.6

8,000 22.23 564.6 10.91 -0.8 30.5

10,000 20.58 522.7 10.10 -4.8 23.4

12,000 19.03 483.4 9.34 -8.8 16.2


14,000 17.58 446.5 8.63 -12.7 9.1

16,000 16.22 412.0 7.96 -16 .7 1.9

18,000 14.95 379.7 7.34 -2 0 .7 -5.1

20,000 13.76 349.5 6.76 -2 4 .6 -1 2 .3

22,000 12.65 321.3 6.21 -28 .6 19.4


24,000 11.61 294.9 5.70 -32 .5 -26.5
26,000 10.64 270.3 5.22 -36.5 -33.6

28,000 9.74 237.4 4.78 -40.5 -40.7

30,000 8.90 226.1 4.37 - 44 .4 -4 7 .8

32,000 8.12 206.3 3.99 - 48 .4 -54.9


34,000 7.40 188.0 3.63 -52 .4 -62.0

36,000 6.73 171.0 3.30 -55.0 -69 .7

38,000 6.12 155.5 3.00 -55.0 -69 .7

40,000 5.56 141.2 2.73 -55.0 -69 .7

42,000 5.05 128.3 2.48 -55 .0 -69 .7


44,000 4.59 116.6 2.25 -5 5 .0 -69 .7

46,000 4.17 105.9 2.05 -55.0 - 69.7

48,000 3.79 96.3 1.86 -55 .0 - 69 .7

50,000 3.44 87.4 1.70 -55 .0 -69 .7

55,000 2.71 68.8 1.33


60,000 2.14 54.4 1.05

64,000 1.76 44.7 .86


70,000 1.32 33.5 PSF TEMPERATURE

113.2 REMAINS CONSTANT


74,000 1.09 27.7 77.3

80,000 .82 20.9 58.1


84,000 .68 17.3 47.9

90,000 .51 13.0 35.9

94,000 .43 10.9 29.7

100,000 .33 8.0 22.3

Figure 14-1. This chart illustrates that as altitude increases from sea level, the pressure decreases. It also shows that to a point,
temperature decreases before finally leveling off.
74-4 Cabin Atmosphere Control
membrane walls into the alveoli, where it is impaired that they cannot help themselves. One of
expelled during exhalation. [Figure 14-2] the worst things about hypoxia is the subtle way it
attacks. When the brain is deprived of the needed
There are two important considerations in provid- oxygen, the first thing people lose is their judgment.
ing sufficient oxygen for the body. There must be The effect is similar to intoxication; people are
enough oxygen in the air to supply the body with unable to recognize how badly their performance
the amount needed, and it must have sufficient and judgment are impaired. Fortunately, hypoxia
pressure to enter the blood by passing through the affects every individual the same way each time it is
membrane walls of the alveoli in the lungs. encountered. If a person can experience hypoxia
symptoms in an altitude chamber under controlled
Oxygen makes up approximately 21% of the mass of conditions, they are more likely to recognize the
the air, and so 21% of the pressure of the air is symptoms during subsequent encounters.
caused by the oxygen. This percentage remains
almost constant as the altitude changes, and is Two of the more common first indications of
called the partial pressure of the oxygen. It is the hypoxia occur at about ten thousand feet altitude.
partial pressure of the oxygen in the lungs that These are an increased breathing rate and a
forces it through the alveoli walls and into the headache. Some other signs of hypoxia are light-
blood. At higher altitudes there is so little total pres- headedness, dizziness with a tingling in the fingers,
sure that there is not enough partial pressure of the vision impairment, and sleepiness. Coordination
oxygen to force it into the blood. This lack of oxy- and judgment will also be impaired, but normally
gen in the blood is called hypoxia. this is difficult to recognize. Because it is difficult to
recognize hypoxia in its early stages, many pressur-
HYPOXIA ized aircraft have alarm systems to warn of a loss of
Any time the body is deprived of the required pressurization.
amount of oxygen, it will develop hypoxia. As
hypoxia becomes more severe, a person's time of CARBON MONOXIDE POISONING
useful consciousness decreases. Time of useful con- Carbon monoxide is the product of incomplete com-
sciousness is defined as the time a person has to bustion of fuels which contain carbon and is found
take corrective action before becoming so severely in varying amounts in the smoke and fumes from
Figure 14-2. The cardiovascular system is made up of the heart, lungs, arteries, and veins. This system transports food and oxy-
gen to the cells of the body and transports waste in the form of carbon dioxide from the cells back out of the body.
Cabin Atmosphere Control 14-5
burning aviation fuel and lubricants. Carbon Early symptoms of carbon monoxide poisoning are
monoxide is colorless, odorless and tasteless, but similar to those of other forms of oxygen depriva-
since it is normally combined with other gases in tion; sluggishness, a feeling of being too warm, and
the engine exhaust, you can expect it to be present a tight feeling across the forehead. These early
when exhaust gases are detected. symptoms may then be followed by a headache and
a throbbing in the temples and ringing in the ears.
When carbon monoxide is taken into the lungs, it Finally, there may be severe headaches, dizziness,
combines with the hemoglobin in the blood. It is the dimming of the vision and if something is not done
hemoglobin that carries oxygen from the lungs to the soon, this can continue until unconsciousness and
various organs of the body. Since hemoglobin has a death.
far greater attraction for carbon monoxide than it has
for oxygen, it will load up with carbon monoxide If carbon monoxide poisoning is suspected, the
until it cannot carry the much-needed oxygen. This heater should be shut off and all possible vents
results in oxygen starvation, and when the brain is opened. If the aircraft is equipped with oxygen,
deprived of oxygen the ability to reason and make 100% oxygen should be breathed until the symp-
decisions is greatly impaired. Exposure to even a toms disappear, or until landing. Carbon monoxide
small amount of carbon monoxide over an extended detectors are available that can be installed on the
period of time will reduce the ability to operate the instrument panel. These are simply small contain-
aircraft safely. The effect of carbon monoxide is ers of a chemical that changes color, generally to a
cumulative, so exposure to a small concentration darker color, when carbon monoxide is present. As
over a long period of time is just as bad as exposure an example, light yellow ones will turn dark green
to a heavy concentration for a short time. and white ones will turn dark brown or black. If
there is any indication of carbon monoxide in the
The decrease in pressure as altitude increases cabin, every part of the exhaust system should be
makes it more difficult to get the proper amount of checked to find and repair the leak before the air-
oxygen. If there is carbon monoxide in the cabin, or craft is returned to service. [Figure 14-3]
if a person is smoking tobacco while flying, it will
intensify the problem and even further deprive the
brain of the oxygen it needs.

Most small single-engine airplanes are heated with


exhaust-type heaters in which the cabin ventilating
air passes between a sheet metal shroud and the
engine exhaust pipes or muffler. If a crack or even a
pinhole size leak should exist in any of the exhaust
components, carbon monoxide can enter the cabin.
The possibility of this type of poisoning is most
likely in the winter months when heat is most
needed and when the windows and vents are usu-
ally closed to keep out cold air. Combustion heaters
that burn fuel from the aircraft tanks to produce heat
can also be a source of carbon monoxide. This type
of heater is found on many small and medium-sized
Figure 14-3. One type of carbon monoxide detector consists
twin engine general aviation aircraft as well as on of a tablet that changes color when exposed to carbon
older airliners. monoxide.
OXYGEN AND PRESSURIZAT!ON SYSTEMS
As an aircraft climbs combine with any fire, hot material sources of breathing
from sea level to almost all other or petroleum oxygen. Among the
increasingly high elements and with products. If pure more common ones
altitudes, the crew many compounds. oxygen is allowed are gaseous oxygen
and passengers move When any fuel to come in contact stored in steel cylin-
further and further burns, it unites with with oil, grease or ders, liquid oxygen
from an ideal oxygen to produce any other petroleum stored in specially
physiological condi- heat, and in the product, it will com- constructed
tion. In order to human body, the bine violently and containers called
compensate for an tissues are generate enough Dewars, and oxygen
atmosphere that continually being heat to ignite the generated by certain
becomes thinner as oxidized which material. chemicals that give
altitude increases, causes the heat off oxygen when
two different produced by the Commercial oxygen heated. A Dewar,
approaches have body. This is the is used in great sometimes called a
been developed. One reason an ample quantities for Dewar flask, is a spe-
of these is to provide supply of oxygen welding and cutting cial type of
pure oxygen to must be available at and for medical use thermos bottle
supplement the all times to support in hospitals and designed to hold
ever-decreasing life. ambulances. extremely cold
amount of oxygen Aviator's breathing liquids. Recently, a
available in the Oxygen is produced oxygen is similar to system using
atmosphere. The commercially by that used for microscopic filters
other is to pressurize liquefying air, and commercial to separate oxygen
the aircraft to create then allowing purposes, except from other gases in
an atmosphere that is nitrogen to boil off, that it is additionally the air has been
similar to that leaving relatively processed to remove developed for
experienced pure oxygen. almost all of the medical uses, and is
naturally at lower Gaseous oxygen water. Water in being investigated
altitudes. For aircraft may also be aviation oxygen for use in aircraft.
that fly at extremely produced by the could freeze in the
high altitude, a electrolysis of water. valves and orifices GASEOUS OXYGEN
combination of When electrical and stop the flow of Most of the aircraft
pressurization and current is passed oxygen when an in the general
supplementary through water aircraft is flying in aviation fleet use
oxygen for emer- (H2O), it will break cold conditions gaseous oxygen
gencies is required. down into its two found at high stored in steel
elements, altitude. Because of cylinders under a
OXYGEN hydrogen and the additional purity pressure of between
oxygen. required, aircraft 1,800 and 2,400 psi.
SYSTEMS The main reason for
At higher altitudes oxygen systems
Oxygen will not must never be using gaseous
(generally above oxygen is its ease of
burn, but it does serviced with any
10,000 feet) the air is handling and the fact
support combustion oxygen that does not
thin enough to that it is available at
so well that special meet the
require most of the airports
care must be taken specifications for
supplemental used by these
when handling. It aviator's breathing
oxygen for humans aircraft. It does have
should not be used oxygen. This is
to function normally. all the disadvantages
anywhere there is usually military
Modern aircraft with of dealing with
the capability to fly specification MIL-
O-27210. These high-pressure gases,
at,high altitudes
usually have oxygen specifications require
systems installed for the oxygen to have
the use of crew no more than two
and/or passengers. milliliters of water
per liter of gas.
CHARACTERISTI
CS OF OXYGEN SOURCES OF
Oxygen is colorless, SUPPLEMENTAL
odorless and OXYGEN
tasteless, and it is Aircraft oxygen
extremely active systems employ
chemically. It will several different
Cabin Atmosphere Control 14-7
and there is a weight penalty because of the heavy CHEMICAL, OR SOLID, OXYGEN
storage cylinders. [Figure 14-4] A convenient method of carrying oxygen for emer-
gency uses and for aircraft that require it only occa-
sionally is the solid oxygen candle. Many large
transport aircraft use solid oxygen generators as a
supplemental source of oxygen to be used in the
event of cabin depressurization.

Essentially, a solid oxygen generator consists of a


shaped block of a chemical such as sodium chlorate
encased in a protective steel case. When ignited,
large quantities of gaseous oxygen are released as a
combustion by-product. They are ignited either
electrically or by a mechanical igniter. Once they
Figure 14-4. Most general-aviation aircraft store oxygen in start burning, they cannot be extinguished and will
steel, high-pressure cylinders.
continue to burn until they are exhausted. Solid
oxygen candles have an almost unlimited shelf life
LIQUID OXYGEN and do not require any special storage conditions.
Most military aircraft now carry their oxygen in a There are specific procedures required for shipping
liquid state. Liquid oxygen is a pale blue, transpar- these generators and they may not be shipped as
ent liquid that will remain in its liquid state as long cargo aboard passenger carrying aircraft. They can
as it is stored at a temperature of below 15181 蚌 . be shipped aboard cargo only aircraft and must be
This is done in aircraft installations by keeping it properly packaged, made safe from inadvertent acti-
in a Dewar flask that resembles a double-wall vation, and identified properly for shipment. They
sphere having a vacuum between the walls. The are safe to use and store because no high pressure is
vacuum prevents heat transferring into the inner involved and the oxygen presents no fire hazard.
container. They are relatively inexpensive and lightweight. On
the negative side, they cannot be tested without
Liquid oxygen installations are extremely economi- actually being used, and there is enough heat gener-
cal of space and weight and there is no high pres- ated when they are used that they must be installed
sure involved in the system. They do have the dis- so that the heat can be dissipated without any dam-
advantage, however, of the dangers involved in han- age to the aircraft structure. [Figure 14-6]
dling the liquid at its extremely low temperature,
and even when the oxygen system is not used, it
requires periodic replenishing because of losses

Figure 14-6. Solid oxygen generators, called candles, are


used in many large aircraft to provide supplemental oxygen
for the passengers in case of depressurization. They are
Figure 14-5. Military aircraft usually use liquid oxygen, also found in some smaller business aircraft.
stored in special insulated containers called Dewars.
from the venting system. [Figure 14-5]
14-8 Cabin Atmosphere Control
MECHANICALLY-SEPARATED OXYGEN Cylinders must be hydrostatically tested to 5/3 of their
A new procedure for producing oxygen is its working pressure, which means that the 3AA cylin-
extraction from the air by a mechanical separation ders are tested with water pressure of 3,000 psi every
process. Air is drawn through a patented material five years and stamped with the date of the test. 3HT
yim"u:ersr~iinlsl"" "uㄏ cesceu ~Wuu a vtfaier pressurtr roi
nitrogen and other gases are trapped in the sieve 3,083 psi every three years, and these cylinders must
and only the oxygen passes through. Part of the be taken out of service after 24 years, or after they have
oxygen is breathed, and the rest is used to purge the been filled 4,380 times, whichever comes first. E-8162
nitrogen from the sieve and prepare it for another cylinders are tested to the same standards as the 3HT
cycle of filtering. This method of producing oxygen cylinders, but must be taken out of service after 15
is currently being used in some medical facilities years or 10,000 filling cycles, whichever occurs first.
and military aircraft. It appears to have the possi-
bility of replacing all other types of oxygen because All oxygen cylinders must be stamped near the filler
of the economy of weight and space, and the fact neck with the approval number, the date of manu-
that the aircraft is no longer dependent upon facture, and the dates of all of the hydrostatic tests.
ground facilities for oxygen supply replenishment. It is extremely important before servicing any oxy-
gen system that all cylinders are proper for the
OXYGEN SYSTEMS AND COMPONENTS installation and that they have been inspected
The aviation maintenance technician will encounter within the appropriate time period.
oxygen systems during the course of servicing and
repairing aircraft. Actual servicing or repair of the Oxygen cylinders may be mounted permanently in the
oxygen system itself must be accomplished in accor- aircraft and connected to an installed oxygen plumbing
dance with the manufacturer's instructions, but a system. For light aircraft where oxygen is needed only
general knowledge of gaseous, liquid, and chemical occasionally, they may be carried as a part of a portable
oxygen systems and how they operate will enable oxygen system. The cylinders for either type of system
the technician to better prepare the aircraft for flight. must meet the same requirements, and should be
painted green and identified with the words AVIA-
GASEOUS OXYGEN SYSTEMS TOR'S BREATHING OXYGEN written in white letters
Gaseous oxygen systems consist of the tanks the on the cylinder. Many high-pressure oxygen systems
oxygen is stored in, regulators to reduce the pres- use pressure-reducing valves between the supply
sure from the high pressure in the tanks to the rela- cylinders and the flight deck or cabin equipment.
tively low pressure required for breathing, plumb- These valves reduce the pressure down to 300-400 PSI.
ing to connect the system components, and masks to Most systems incorporate a pressure relief valve that
deliver the oxygen to the crewmember or passenger. prevents high-pressure oxygen from entering the sys-
tem if the pressure-reducing valve should fail.
Storage Cylinders
Most military aircraft at one time used a low-pres- On a hot day, the temperature inside a parked air-
sure oxygen system in which the gaseous oxygen craft can cause the pressure in an oxygen cylinder to
was stored under a pressure of approximately 450 rise to dangerous levels. Permanently mounted
psi in large yellow-painted low pressure steel cylin- gaseous oxygen systems, especially in large aircraft,
ders. These cylinders were so large for the amount normally have some type of thermal relief system to
of oxygen they carried that they never became pop- vent oxygen to the atmosphere if the cylinder pres-
ular in civilian aircraft, and even the military has sure becomes too high. Venting systems may be tem-
stopped using these systems. perature or pressure activated. To alert the crew that
a thermal discharge has occurred, many systems use
Today, almost all gaseous oxygen is stored in green a "blow-out" disk as a thermal discharge indicator. A
painted high-pressure steel cylinders under a pres- flush-type fitting containing a green plastic disk
sure of between 1,800 and 2,400 psi. All cylinders about 3/4 inch in diameter is mounted on the out-
approved for installation in an aircraft must be side of the aircraft near the location of the oxygen
approved by the Department of Transportation bottles. If a thermal discharge occurs, the disk blows
(DOT) and are usually either the ICC/DOT 3AA 1800 out of the fitting, and leaves the vent port visible. If
or the ICC/DOT 3HT 1850 type. Aluminum bottles the disk is found missing, there is no oxygen in the
are also available, but are much less common. system and the aircraft must not be flown in condi-
Newer, light-weight "composite" bottles that comply tions where supplemental oxygen might be required.
with DOT-E-8162 are becoming more common.
These bottles are made of lighter, thinner metals A thermal discharge requires maintenance on the
combined with a wrapping of composite material. oxygen system. The discharge mechanism must be
Cabin Atmosphere Control 14-9
reset or replaced, the indicator disk replaced and Automatic Continuous Flow Regulators have a
the system serviced with oxygen to the correct pres- barometric control valve that automatically adjusts
sure. Consult the maintenance manual for the par- the oxygen flow to correspond with the altitude.
ticular aircraft to determine the proper procedures. The flight crew need only open the valve on the
front of the regulator, and the correct amount of oxy-
Regulators gen will be metered into the system for the altitude
There are two basic types of regulators in use, and being flown. [Figure 14-8]
each type has variations. Low-demand systems, such
as are used in smaller piston-engine powered gen-
eral aviation aircraft, generally use a continuous
flow regulator. This type of regulator allows oxygen
to flow from the storage cylinder regardless of
whether the user is inhaling or exhaling. Continuous
flow systems do not use oxygen economically, but
their simplicity and low cost make them desirable
when the demands are low. The emergency oxygen
systems that drop masks to the passengers of large jet
transport aircraft in the event of cabin depressuriza-
tion are of the continuous flow type.

Continuous Flow Regulators are of either the man-


ual or automatic type. Both of these are inefficient
in that they do not meter the oxygen flow according
to the individual's needs. Figure 14-8. Automatic continuous flow regulators adjust
oxygen flow automatically as altitude changes.
Manual Continuous Flow Regulators typically con-
sist of two gauges and an adjustment knob. One typ-
ical regulator has a gauge on the right that shows the Oxygen is usually supplied to the flight crew of an
pressure of the oxygen in the system and indicates aircraft by an efficient system that uses one of sev-
indirectly the amount of oxygen available. The eral demand-type regulators. Demand regulators
other gauge is a flow indicator and is adjusted by allow a flow of oxygen only when the user is inhal-
the knob in the lower center of the regulator. The ing. This type regulator is much more efficient than
user adjusts the knob so that the flow indicator nee- the continuous flow type. [Figure 14-9]
dle matches the altitude being flown. The regulator
meters the correct amount of oxygen for the selected
altitude. If the flight altitude changes, the pilot must
remember to readjust the flow rate. [Figure 14-7]

Figure 14-9. This demand-type regulator is fitted to a


portable oxygen bottle and a full-face type mask. This type
of system is often used aboard cargo aircraft as a smoke
Figure 14-7. Manual continuous flow regulators must be combat unit to allow a crewmember to locate and extin-
reset as altitude changes. guish a cargo fire.
74-70 Cabin Atmosphere Control
Diluter Demand Regulators are used by the flight on the face of the regulator can be moved from the
crews on most commercial jet aircraft. When the NORMAL position to the 100% position. This
supply lever is turned on, oxygen can flow from the closes the outside air passage and opens a supple-
supply into the regulator. There is a pressure mental oxygen valve inside the regulator so pure
reducer at the inlet of the regulator that decreases oxygen can flow to the mask.
the pressure to a value that is usable by the regula-
tor. The demand valve shuts off all flow of oxygen An additional safety feature is incorporated that
to the mask until the wearer inhales and decreases bypasses the regulator. When the emergency lever is
the pressure inside the regulator. This decreased placed in the EMERGENCY position, the demand
pressure moves the demand diaphragm and opens valve is held open and oxygen flows continuously
the demand valve so oxygen can flow through the from the supply system to the mask as long as the
regulator to the mask. [Figure 14-10] supply lever is in the ON position.

A diluter demand regulator dilutes the oxygen sup- When a person breathes normally, the lungs expand
plied to the mask with air from the cabin. This air and atmospheric pressure forces air into them. But
enters the regulator through the inlet air valve and at altitudes above 40,000 feet not enough oxygen
passes around the air-metering valve. At low alti- can get into the lungs even with the regulator on
tude, the air inlet passage is open and the passage to 100%. Operation of unpressurized aircraft at and
the oxygen demand valve is restricted so the user above 40,000 feet requires the use of pressure
gets mostly air from the cabin. As the aircraft goes demand regulators. These regulators have provi-
up in altitude, the barometric control bellows sions to supply 100% oxygen to the mask at higher
expands and opens the oxygen passage while clos- than ambient pressure, thus forcing oxygen into the
ing off the air passage. At an altitude of around user's lungs.
34,000 feet, the air passage is completely closed off,
and every time the user inhales, pure oxygen is Pressure Demand Regulators operate in much the
metered to the mask. same way as diluter demand regulators except at
extremely high altitudes, where the oxygen is forced
If there is ever smoke in the cabin, or if for any rea- into the mask under a positive pressure. Breathing
son the user wants pure oxygen, the oxygen selector at this high altitude requires a different technique
Figure 14-10. The flight crews of most commercial aircraft use diluter demand oxygen systems.
Cabin Atmosphere Control 14-11
from that required in breathing normally. The oxy- and when the user inhales, the first air to enter the
gen flows into the lungs without effort on the part of lungs is that which was first exhaled and still has
the user, but muscular effort is needed to force the some oxygen in it. This air is mixed with pure oxy-
used air out of the lungs. This is exactly the oppo- gen, and so the wearer always breathes oxygen rich
site of normal breathing. [Figure 14-11] air with this type of mask. More elaborate
rebreather-type masks have a close-fitting cup over
OXYGEN REGULATOR
the nose and mouth with a built-in check valve that
PRESSURE DEMAND allows the air to escape, but prevents the user from
breathing air from the cabin.

The oxygen masks that automatically drop from the


overhead compartment of a jet transport aircraft in
the event of cabin depressurization are of the
MERGENCY
100%
■>( OXYGEN . ON I rebreather type. The plastic cup that fits over the
mouth and nose has a check valve in it, and the
I
Y SUPPLY plastic bag attached to the cup is the rebreather bag.
NORMAL n

With demand-type masks the regulator is set up to


Figure 14-11. This pressure demand regulator supplies oxy- meter the proper amount of oxygen to the user, so
gen under pressure for flights above 40,000 feet.
outside air would upset the required ratio of air to
oxygen. Demand-type masks must fit tightly to the
Masks face so no outside air can enter. [Figure 14-13]
Masks are used to deliver the oxygen to the user.
These are either of the continuous flow or demand
type.

Continuous flow masks are usually the rebreather


type and vary from a simple bag-type disposable
mask used with some of the portable systems to the
rubber bag-type mask used for some of the flight
crew systems. [Figure 14-12]

Figure 14-13. Demand-type masks deliver oxygen only


when the wearer inhales.

A full-face mask is available for use in case the


cockpit should ever be filled with smoke. These
Figure 14-12. Rebreather type masks are used with contin-
uous flow oxygen systems. masks cover the eyes as well as the mouth and nose,
and the positive pressure inside the mask prevents
any smoke entering.
Oxygen enters a rebreather mask at the bottom of the
bag, and the mask fits the face of the user very Most of the rigid plumbing lines that carry high-
loosely so air can escape around it. If the rebreather pressure oxygen are made of stainless steel, with the
bag is full of oxygen when the user inhales, the end fittings silver soldered to the tubing. Lines that
lungs fill with oxygen. Oxygen continues to flow carry low-pressure oxygen are made of aluminum
into the bag and fills it from the bottom at the same alloy and are terminated with the same type fittings
time the user exhales used air into the bag at the top. used for any other fluid-carrying line in the aircraft.
When the bag fills, the air that was in the lungs The fittings may be of either the flared or flareless
longest will spill out of the bag into the outside air,
74-72 Cabin Atmosphere Control
type. It is essential in any form of aircraft mainte- flight crewmembers require more oxygen since they
nance that only approved components be used. This are more active, and their alertness is of more vital
is especially true of oxygen system components. importance than that of the passengers.
Only valves carrying the correct part number should
be used to replace any valve in an oxygen system. Some installations incorporate a therapeutic mask
adapter. This is used for any passenger that has a
Many of the valves used in oxygen systems are of health problem that would require additional oxy-
the slow-opening type to prevent a rapid in-rush of gen. The flow rate through a therapeutic adapter is
oxygen that could cause excessive heat and become approximately three times that through a normal
a fire hazard. Other valves have restrictors in them passenger mask adapter.
to limit the flow rate through a fully open valve.
Each tube to the mask has a flow indicator built into
Typical Installed Gaseous Oxygen Systems it. This is simply a colored indicator tfiat is visible
If an aircraft has an installed oxygen system, it will when no oxygen is flowing. When oxygen flows, it
be one of three types: the continuous flow type, the pushes the indicator out of sight.
diluter demand type or the pressure demand type.
Pressurized aircraft do not normally have oxygen
Most single engine aircraft utilize a continuous flow available for passengers all of the time, but FAR Part
oxygen system. The external filler valve is installed 91 requires that under certain flight conditions, the
in a convenient location and is usually covered with pilot operating the controls wear and use an oxygen
an inspection door. It has an orifice that limits the mask. Because of this requirement, most executive
filling rate and is protected with a cap to prevent aircraft that operate at high altitude are equipped
contamination when the charging line is not con- with diluter demand or pressure demand oxygen
nected. The DOT approved storage cylinder is regulators for the flight crew and a continuous flow
installed in the aircraft in a location that is most system for the occupants of the cabin. Aircraft oper-
appropriate for weight and balance considerations. ating at altitudes above 40,000 feet will usually have
The shutoff valve on the cylinder is of the slow- pressure demand systems for the crew and passen-
opening type and requires several turns of the knob gers. [Figure 14-15]
to open or close it. This prevents rapid changes in
the flow rate that could place excessive strain on the The masks for the flight crew normally feature a
system or could generate too much heat. Some quick-donning system. The mask is connected to a
installations use a pressure-reducing valve on the harness system that fits over the head. This system
cylinder. When a reducer is used, the pressure is designed so that the mask can be put on with one
gauge must be mounted on the cylinder side of the hand and be firmly in place, delivering oxygen,
reducer to determine the amount of oxygen in the within a few seconds.
cylinder. [Figure 14-14]
LIQUID OXYGEN SYSTEMS
The pressure gauge is used as an indication of the Civilian aircraft do not generally use liquid oxygen
amount of oxygen in the cylinder. This is not, of (LOX) systems because of the difficulty in handling
course, a direct indication of quantity, but within this form of oxygen, and because it is not readily
the limitations seen when discussing system servic- available to the fixed-base operators who service
ing, it can be used to indicate the amount of oxygen general aviation aircraft. The military, on the other
on board. hand, uses liquid oxygen almost exclusively
because of the space and weight savings it makes
The pressure regulator reduces the pressure in the possible. One liter of liquid oxygen will produce
cylinder to a pressure that is usable by the masks. approximately 860 liters of gaseous oxygen at the
This regulator may be either a manual or an auto- pressure required for breathing.
matic type. There must be provision, one way or
another, to vary the amount of pressure supplied to The regulators and masks are the same as those used
the masks as the altitude changes. for gaseous oxygen systems, the difference in the
systems being in the supply. Liquid oxygen is held
The mask couplings are fitted with restricting ori- in a spherical container and in normal operation the
fices to meter the amount of oxygen needed at each buildup and vent valve is back-seated so some of the
mask. In figure 14-14 the pilot's coupling has an ori- LOX can flow into the buildup coil where it absorbs
fice considerably larger than that provided for the enough heat to evaporate and pressurize the system
passengers. The reason is that the pilot and other to the amount allowed by the container pressure
Cabin Atmosphere Control 14-13
Figure 14-14. The typical general aviation aircraft has an installed system similar to this one.
74-74 Cabin Atmosphere Control
Figure 14-15. Aircraft that do not require oxygen to be constantly available to passengers will have a diluter or pressure demand
regulator for the flight crew.
regulator, normally many applications. C
about 70 psi. This The chemical a
gaseous oxygen oxygen generator
maintains a requires
relatively constant approximately one-
pressure in the third the space for
container and equivalent amounts
supplies the oxygen of oxygen as a
to the regulator. bottled system. The
[Figure 14-16] canisters are inert
below 400 蚌 , even
When the supply under severe impact.
valve on the Oxygen candles
regulator is turned contain sodium
on, LOX flows from chlorate mixed with
the container into the appropriate binders
supply evaporator and a fuel formed
coil where it absorbs into a block. When
heat and turns into the candle is
gaseous oxygen. If, activated, it releases
for any reason, oxygen. The shape
excessive pressure and composition of
should build up in the candle
the system, it will determines the
vent overboard oxygen flow rate.
through one of the As the sodium
relief valves. chlorate
decomposes, it
CHEMICAL OXYGEN produces oxygen by
SYSTEMS a chemical action.
Another source of [Figure 14-17]
oxygen is the
chemical system. An igniter, actuated
This system uses either electrically
chemical oxygen or by a spring, starts
generators also the candle burning.
called "oxygen The core of the
candles" to produce candle is insulated to
breathing oxygen. retain the heat
The size and needed for the
simplicity of the chemical action and
units, and minimal to prevent the
maintenance housing from getting
requirements make too hot. Filters are
them ideal for located at the outlet
to prevent any
contaminants
entering the system.
Figure 14-16. Liquid oxygen systems require specialized plumbing to handle the conversion from liquid to gas and the venting of
excess pressures.
The long shelf life of 1
unused chemical 4
oxygen generators
makes them an ideal
source of oxygen for
occasional flights
where oxygen is
needed, and for the
emergency oxygen
supply for
pressurized aircraft
where oxygen is
required only as a
standby in case cabin
pressurization is lost.

The emergency
oxygen systems for
pressurized aircraft
have the oxygen
generators mounted
Figure 14-17. Chemical
in either the overhead
oxygen candles produce rack, in seat backs, or
oxygen by heating in bulkhead panels.
sodium chlorate. The The masks are
sodium chlorate is located with these
converted to salt and
oxygen. generators and are
enclosed, hidden
from view by a door
that may be opened
electrically by one of
the flight crew
members or
automatically by an
aneroid valve in the
event of cabin
depressurization.
When the door
opens, the mask
drops out where it is
easily accessible to
the user. Attached to
the mask is a lanyard
that, when pulled,
releases the lock pin
from the flow
initiation mechanism,
so the striker can hit
the igniter and start
the candle burning.
Once a chemical
oxygen candle is
ignited, it cannot be
shut off. It must burn
until it is exhausted,
and the enclosure
must not be closed
until the cycle has
completed. [Figure
14-18]
sary to replace the fitting and reflare the tube or
install a new flareless fitting.
Draining the Oxygen System
Draining of the oxygen system should normally be
done after the high-pressure bottle has been
removed or isolated from the system. Either out-
doors or in a well-ventilated hangar, the system's
pressure should be bled off by opening the appro-
priate fitting. Normally a system will require purg-
ing after the system has been drained. All the
safety precautions mentioned later in this chapter
should be followed during any oxygen draining
procedure.
Filling an Oxygen System
Fixed base operators who do a considerable amount
of oxygen servicing will usually have an oxygen ser-
Figure 14-18. Pulling a lanyard on some chemical oxygen vicing cart. Such carts usually consist of six large
candles removes the safety pin to allow the spring to actu- cylinders, each holding approximately 250 cubic
ate the igniter.
feet of aviator's breathing oxygen. A seventh cylin-
der, facing the opposite direction and filled with
OXYGEN SYSTEM SERVICING compressed nitrogen, is normally carried to charge
Care and attention to detail is the mark of profes- hydraulic accumulators and landing gear struts.
sional aviation maintenance, and nowhere is this Fittings on the nitrogen cylinders are different from
characteristic more important than when servicing those on the oxygen cylinders to minimize the pos-
aircraft oxygen systems. Compressed gaseous sibility of using nitrogen to fill the oxygen system,
oxygen demands special attention because of both or of servicing the other systems with oxygen.
its high storage pressure and its extremely active [Figure 14-19]
chemical nature.
When possible, all oxygen servicing should be done
outdoors, or at least in a well-ventilated area of the
hangar. Removable or portable supply cylinders
should be removed from the aircraft for servicing.
When oxygen servicing is performed in the aircraft,
suspend all electrical work. In all cases the manu-
facturer's service information must be used while
performing service, maintenance or inspection of
aircraft oxygen systems.

SERVICING GASEOUS OXYGEN SYSTEMS


Some generic procedures are listed here as an ori- Figure 14-19. Oxygen service carts consist of a battery of O2
bottles hooked to a common service manifold. Sometimes
entation to the oxygen system servicing. a nitrogen bottle is on the same cart, but with different
hose fittings to prevent inadvertently interchanging the
Leak Testing Gaseous Oxygen Systems
two systems.
Searches for leaks are made using a special leak
detector. This material is a form of non-oily soap
solution. This solution is spread over every fitting Each oxygen cylinder has its own individual shutoff
and at every place a leak could possibly occur, and valve, and all of the cylinders are connected into a
the presence of bubbles will indicate a leak. If a leak common service manifold that has a pressure gauge.
is found, the pressure is released from the system, A flexible line with the appropriate fittings con-
and the fittings checked for proper torque. Flareless nects the charging manifold to the aircraft filler
fittings can leak from both under and overtighten- valve.
ing. If the fitting is properly torqued and still leaks,
remove the fitting and examine all of the sealing Various manufacturers of oxygen equipment use dif-
surfaces for indications of damage. It may be neces- ferent types of connections between the supply and
Cabin Atmosphere Control 14-17
the aircraft, and a well-equipped service cart should container with chalk or in a record kept with the
have the proper adapters. These adapters must be cart.) The valve on the cylinder should be opened
kept clean and protected from damage. Leakage dur- slightly to allow some oxygen to purge all of the
ing the filling operation is not only costly, but it is moisture, dirt and air from the line; then the line
hazardous as well. Before filling any aircraft oxygen should be connected to the aircraft filler valve and
system, all of the cylinders being refilled must be the valve on the cylinder opened slowly. Most
checked to ensure that they are of the approved filler valves have restrictors that prevent an exces-
type, and have been hydrostatically tested within sively high flow rate into the cylinder. When the
the required time interval. pressure in the aircraft system and that in the
cylinder with the lowest pressure stabilizes and
No oxygen system should be allowed to become there is no more flow, this new pressure should be
completely empty. When there is no pressure inside recorded and the cylinder valve closed. The valve
the cylinder, air can enter, and most air contains on the cylinder having the next lowest pressure
water vapor. When the water vapor mixes with the should be opened slowly and oxygen allowed to
oxygen the mixture expands as it is released flow into the system until it again stabilizes.
through the small orifices in the system. This Continue this procedure until the aircraft system
expansion lowers the temperature and the water is has been brought up to the required pressure.
likely to freeze and shut off the flow of oxygen to the [Figure 14-20]
masks. Water in a cylinder can also cause it to rust
on the inside and weaken it so it could fail with cat- The ambient temperature determines the pressure
astrophic results. A system is considered to be that should be put into the oxygen system, and a
empty when the pressure gets down to 50 to 100 psi. chart should be used to determine the pressure
If the system is ever allowed to get completely needed. For example, if the ambient temperature is
empty, the valve should be removed and the cylin- 9036 F and a stabilized pressure in the system of
der cleaned and inspected by an FAA-approved 1,800 psi is desired, the oxygen should be allowed
repair station. to flow until a pressure of 2,000 psi is indicated on
the system pressure gauge. When the oxygen in the
When an aircraft's oxygen system is being filled system drops to the standard temperature of 70 蚌,
from a large supply cart, the cylinder having the the pressure will stabilize at 1,800 psi. If the ambi-
lowest pressure should be used first. (The pressure ent temperature is low, the filling of the system
in each tank should have been recorded on the must be stopped at a lower pressure, because the
Figure 14-20. The design of the hose manifold for oxygen servicing allows each bottle to be connected in turn to the receiving sys-
tem. Over time, this setup allows each cylinder to be expended down to its allowable limit. Normally a small amount of pressure
is kept in each tank, even when "empty."
14-18 Cabin Atmosphere Control
oxygen will expand and the pressure will rise warm converter, it vaporizes rapidly and cools the
when it warms up to its normal temperature. entire system. Considerable gaseous oxygen is
[Figure 14-21] released during the filling procedure, and it vents to
AMBIENT TEMP.
the outside air through the buildup and vent valve.
FILLING PRESSURE
DEGREES FAHRENHEIT This venting of the gaseous oxygen will continue
FOR 1800 FOR 1850 until liquid oxygen starts to flow out of the vent
PSI AT 70° PSI AT 70°
valve. A steady stream of liquid indicates that the
0 1600 1650
system is full.
10 1650 1700
20 1675 1725 The system should vent freely as it is being filled and
30 1725 1775 frost should form only on the outlet and the hoses. If
40 1775 1825
any frost forms on the supply container, it could be
an indication of an internal leak, and since the pres-
50 1825 1875
sure can build up extremely high, any trace of a leak
60 1875 1925
demands that the equipment be shut down immedi-
70 1925 1975 ately and the cause of the frosting determined.
80 1950 2000
90 2000 2050 When the liquid oxygen cart is attached to the air-
100 1050 2100 craft system, the valve should be fully opened, then
110 2100 2150 closed slightly. If it is not, it is possible that the oxy-
120 2150 2200
gen flowing through the valve could cause the valve
to freeze in the open position and be difficult or
130 2200 2250
impossible to close.
Figure 14-21. Charts such as this one are used to determine There are two ways LOX converters are serviced.
the proper filling pressure for various ambient temperatures. Some are permanently installed in the aircraft and
are serviced from an outside filler valve. The
Purging A Gaseous Oxygen System buildup and vent valve is placed in the vent posi-
If the oxygen system, has been opened for servicing, tion, the service cart is attached to the filler valve,
it should be purged of any air that may be in the and liquid oxygen is forced into the system until
lines. To purge a continuous flow system, oxygen liquid runs out of the vent line. When the system
masks are plugged into each of the outlets and the is full, the buildup and vent valve is returned to
oxygen supply valve turned on. Oxygen should be the buildup position to build up pressure in the
allowed to flow through the system for about ten converter. Other installations have quick-discon-
minutes. Diluter demand and pressure demand sys- nect mounts for the converters so the empty con-
tems may be purged by placing the regulators in the verter can be removed from the aircraft and
EMERGENCY position and allowing the oxygen to replaced with a full one. Exchanging converters
flow for about ten minutes. After the system has allows oxygen servicing to be done much more
been thoroughly purged, the cylinders should be quickly and safely than can be done by filling the
filled to the required pressure. converter in the aircraft.

FILLING A LIQUID OXYGEN SYSTEM INSPECTING THE MASKS AND HOSES


Service carts for liquid oxygen normally carry the Disposable masks such as those used with many of
LOX in 25- or 100-liter containers. Servicing systems the portable systems should be replaced with new
from these carts is similar to that described in the masks after each use, but the permanent masks used
previous section on gaseous oxygen systems. by crew members are normally retained by each
Protective clothing and eye protection must be worn individual crewmember. These masks are fitted to
since liquid oxygen has such a low boiling point that the face to minimize leakage and are usually treated
it would be sure to cause serious frostbite if spilled as personal flight gear. They should be occasionally
on the skin. Any empty LOX system or one that cleaned by washing them with a cloth wet with a
hasn't been in use for some time should be purged lukewarm detergent solution and then allowing
for a few hours with heated dry air, or nitrogen. them to dry at room temperature. The face portion
of the mask may be disinfected with a mild
The service cart should be attached to the aircraft antiseptic.
system and, after placing the buildup and vent valve
in the vent position, the valve opened on the service The quick-donning masks for use by airliner flight
cart. As the LOX flows from the service cart into the crews are part of the aircraft and not crew personal
Cabin Atmosphere Control 14-19
equipment. Most airlines require each crewmember is likely to be permeated with oxygen, smoking
to don and test the mask as part of the required pre- should be avoided for ten to fifteen minutes after
flight inspection. Alcohol swabs in small sealed completing the oxygen servicing.
packets are provided to sterilize the mask before the
crewmember dons the mask. The most important consideration when servicing
any type of oxygen system is the necessity for
The masks and hoses should be checked for leaks, absolute cleanliness. The oxygen should be stored
holes or rips, and replaced rather than repaired. in a well ventilated part of the hangar away from
When storing the mask in the airplane, it should be any grease or oil, and all high pressure cylinders not
protected from dust and dampness, and especially mounted on a service cart should be stored upright,
from any type of grease or oil. out of contact with the ground and away from ice,
snow or direct rays of the sun.
REPLACING TUBING, VALVES AND FITTINGS
Protective caps must always be in place to prevent
It is extremely important when installing any oxygen possible damage to the shutoff valve. The storage
line in an aircraft that no petroleum product is used area for oxygen should be at least 50 feet away from
as a thread lubricant, and that the lines are thor- any combustible material or separated from such
oughly cleaned of any trace of oil that was used in material by a fire resistant partition. When setting
the flaring or presetting operation. Triclilorethylene up an oxygen storage area, you should be sure that
or some similar solvent may be used to clean the tub- it meets all insurance company and Federal/State
ing and fittings. After they are thoroughly clean, they Occupational Safety and Health Act (OSHA)
should be dried either with heat or by blowing them requirements.
with dry air or dry nitrogen.
Because of the extreme incompatibility of oxygen
Tapered pipe threads must never be lubricated with and any form of petroleum products, it is a good
a thread lubricant that contains any form of petro- idea to dedicate all necessary tools to be used exclu-
leum. Oxygen-compatible thread lubricant that sively with oxygen equipment. Any dirt, grease or
meets specification MIL-G-27617 may be used, or oil that may be on the tools or on any of the hoses,
the male threads may be wrapped with Teflon tape adapters, cleaning rags, or even on clothing is a pos-
and the fittings screwed together. sible source of fire.
Before any tubing or fitting is replaced in an oxygen PRESSURIZATION SYSTEMS
system, the part must be thoroughly cleaned and The air that forms our atmosphere allows people to
inspected. The part should be checked for evidence live and breathe easily at low altitudes, but flight is
of corrosion or damage, and degreased with a vapor most efficient at high altitudes where the air is thin
degreaser or ultrasonic cleaner. The new line should and the aerodynamic drag is low. In order for
be flushed with stabilized trichlorethylene, acetone, humans to fly at these altitudes, the aircraft must be
or some similar solvent, and dried thoroughly with pressurized and heated so that it is comfortable for
dry air or nitrogen. If neither dry air nor nitrogen are the aircraft occupants.
available, the part may be dried by baking it at a tem-
perature of about 25041 F until it is completely dry. PRESSURIZATION PROBLEMS
When the parts are dry, close them with properly fit- Turbine engines operate effectively at these high
ting protective caps or plugs, but never use tape in altitudes, but piston engines (as well as human
any form to seal the lines or fittings, as small particles occupants of an aircraft) require a supply of addi-
of the tape are likely to remain when it is removed. tional oxygen. Superchargers compress the air
before it enters the cylinders of a reciprocating
PREVENTION OF OXYGEN engine, and the occupants can be furnished supple-
FIRES OR EXPLOSIONS mental oxygen to maintain life at these high, but
Safety precautions for oxygen servicing are similar aerodynamically efficient, altitudes.
to those required for fueling or defueling an aircraft.
The airplane and service cart should be electrically Oxygen was used by some flight crews as early as
grounded and all vehicles should be kept a safe dis- World War I, and its inconvenience was tolerated by
tance away. There should be no smoking, open the crew as a necessary part of the flight. By the
flame or items which may cause sparks within 50 middle 1930s, airplanes and engines had been built
feet or more depending upon the ventilation of the that could carry passengers to altitudes where sup-
area during servicing operations. Since the clothing plemental oxygen was needed, but the inconve-
of a person involved in servicing an oxygen system nience of requiring passengers to wear oxygen
74-20 Cabin Atmosphere Control
masks proved to be a real deterrent to high altitude Most cabin pressurization systems have two modes
passenger flights. of operation; the isobaric mode in which the cabin is
maintained at a constant altitude (iso means same,
In 1934 and 1935, the American aviator Wiley Post and baric means pressure), and the constant pressure
made a series of flights in his Lockheed Vega, the differential mode. In the isobaric mode, the pressure
Winnie Mae, to altitudes near 50,000 feet. When fly- regulator controls the outflow valve as the aircraft
ing at these altitudes, Post wore a rubberized pres- goes up in altitude to maintain the same pressure in
sure suit that resembled the suit worn by a deep-sea the cabin. When the pressure differential between
diver. As a result of his experiments, Post felt that that inside the cabin and that outside reaches the
flights at altitudes up to 30,000 feet would be practi- maximum structural pressure limitation, the pres-
cal if some method were possible to enable the pas- sure controller shifts to the constant differential
sengers to breathe. Pressurization was the answer, mode and maintains a constant pressure differential.
but the technology of aircraft structures in the 1930s As the flight altitude increases, so does the cabin
did not allow for pressurization of the aircraft itself. altitude, always maintaining the same differential
pressure between the inside and the outside.
During World War II, the need for bombers to oper-
ate at extremely high altitudes for long flights SOURCES OF PRESSURIZING AIR
caused some of the manufacturers, notably the The pressurization of modern aircraft is achieved
Boeing Airplane Company, to develop a pressurized by directing air into the cabin from either the com-
structure 43 or pressure vessel, as it is called. pressor section of a jet engine, from a turbosuper-
This allows the occupants of the aircraft to operate charger, or from an auxiliary compressor.
in a cabin that is artificially held at an altitude far
below the flight altitude of the airplane. This RECIPROCATING ENGINE AIRCRAFT
means the pressure inside the aircraft's cabin is When pressurization was first used, it was for large
much higher than the ambient pressure (outside aircraft such as the Lockheed Constellation and the
pressure) when the aircraft is at high altitude. Douglas DC-6. These large cabins required great vol-
umes of compressed air, and this was provided by a
Many of the piston engine transport aircraft of the positive displacement Roots-type compressor or by
1950s had pressurized cabins and were able to carry a variable displacement centrifugal compressor dri-
passengers in comfort over the top of most bad ven by one of the engines. Pressurization air for
weather. This type of aircraft made flying truly prac- smaller piston-engine aircraft is provided by bleed
tical as a means of mass transportation. air from the engine turbochargers. [Figure 14-22]

Piston engines were limited to relatively low alti-


tudes and did not require a high cabin pressure, so
no great structural problems showed up with pres-
surized piston engine airplanes. But, when the jet
transport airplane began to fly in the early 1950s, the
large pressure differential required for the altitudes
they flew created metal fatigue. Metal fatigue caused
by the repeated pressurization and depressurization
cycles caused several disastrous accidents.

Today, aircraft structural design has advanced to the


point that pressurized aircraft are able to safely and
comfortably carry large loads of passengers at effi-
ciently high altitudes for long distance flights.
Flight crews must be aware of the structural limita-
tions of the aircraft and not exceed the maximum
allowable differential between the pressure inside
the structure and the pressure on the outside. The
amount of air pumped into the cabin is normally in
excess of that needed, and cabin pressure is con-
trolled by varying the amount of air leaving the
cabin through outflow valves controlled hy the Figure 14-22. Pressure from the turbocharger of some light
cabin pressure controller. aircraft is used to provide cabin pressurization.
Cabin Atmosphere Control 14-21
Figure 14-23. Theturbocharger is driven by hot exhaust gases. The compressor portion of this system is turned by a shaft attached
directly to the turbine. The turbine is driven by bleed air from the turbine engine. The ram air is compressed by the compressor
and then blended with bleed air to the correct pressure and temperature.
TURBINE ENGINE AIRCRAFT bleed air that has been used to drive the turbocom-
The compressor in a turbine engine is a good source pressor. [Figure 14-23]
of air to pressurize the cabin, and since this air is
quite hot it is used to provide heat as well as pres-
surization. Engine power is required to compress A jet pump flow multiplier can provide cabin pres-
this air, and this power is subtracted from that avail- surization air without the complexity of the turbo-
able to power the aircraft. compressor. Compressor bleed air flows through the
nozzle of a jet pump at high velocity and produces
Compressor bleed air may be used directly, or it may a low pressure that draws air in from the outside of
be used to drive a turbocompressor. Outside air is the aircraft. The bleed air and the outside air mix
taken in and compressed, and then, before it enters and flow into the cabin to provide the air needed for
the cabin, it is mixed with the engine compressor pressurization. [Figure 14-24]
Figure 14-24. The jet-pump type pressurization uses aerodynamic principals to eliminate most moving parts.
74-22 Cabin Atmosphere Control
Air Cycle Machines are used by many modern tur- (intermittent horn) will sound, alerting the flight
bine-engine aircraft to provide both pressurization crew to take action. [Figure 14-25]
and temperature control. Air Cycle Machines use a
clever application of the laws of physics to cool hot CABIN AIR PRESSURE REGULATOR AND
engine bleed air. Boeing calls these systems OUTFLOW VALVE OPERATION
"packs," an acronym for pneumatic air conditioning Cabin pressure regulators and outflow valves may
kit, The theory and operation of air cycle machines be pneumatically or electrically operated. Modern
will be discussed in detail in Section C of this systems are almost entirely electronically con-
Chapter. Three identical packs are installed on each trolled. The outflow valve is controlled by the cabin
747 and any one can supply all the conditioned air pressure regulator and can be closed, open or mod-
needed for pressurization, temperature control and ulated. This means that it is working at a position
ventilation. somewhere between the two extremes to maintain
the pressure called for by the controller. The cabin
CONTROL OF CABIN PRESSURE pressure regulator contains an altitude selector and
It would be impractical to build the pressure vessel a rate controller.
of an aircraft that is airtight, so pressurization is
accomplished by flowing more air into the cabin Pneumatic Regulator and Outflow Valve Operation
than is needed and allowing the excess air to leak Pneumatic regulators use variations in air pressure
out. There are two types of leakage in an aircraft to activate the outflow and safety valves. The out-
pressure vessel; controlled and uncontrolled. The flow valve and the safety valve are normally located
uncontrolled leakage is the air that escapes around in the pressure bulkhead at the rear of the aircraft
door and window seals, control cables and other cabin. The safety valve is normally closed (except
openings in the sealed portion of the structure. on the ground) and is used primarily as a backup in
Controlled leakage flows through the outflow valve case of a malfunction of the outflow valve. [Figure
and the safety valve. This controlled leakage is far 14-26]
greater than the uncontrolled, and it determines the
amount of pressure in the cabin. Pressurization con- When the aircraft is on the ground and prepared for
trol systems can be of the pneumatic or electronic flight, the cabin is closed and the safety valve is
type, with the electronic type incorporating electri- held off its seat by vacuum acting on the diaphragm.
cally controlled outflow valves. The dump solenoid in the vacuum line is held open
because the circuit through the landing gear safety
PRESSURIZATION COCKPIT CONTROLS switch is completed when the weight of the aircraft
Most pressurization systems have cabin altitude, is on the landing gear. As soon as the aircraft takes
cabin rate-of-climb, and pressure differential indi- off, the safety switch circuit opens and the dump
cators. The cabin altitude gauge measures the actual solenoid shuts off the vacuum line to the safety
cabin altitude. The cabin altitude is almost always valve, which allows the valve to close. If for any rea-
much below that of the aircraft, except when the air- son the pressure in the cabin should exceed a set
craft is on the ground. An example would be an air- limit, the safety valve will open fully. This will pre-
craft cruising at 40,000 feet would normally have a vent cabin over-pressurization that could cause the
cabin altitude of about 8,000 feet. The cabin rate-of- structure of the aircraft to fail.
climb indicator allows the pilot or flight engineer to
adjust the rate the cabin altitude is climbing or The outflow valve is closed until it receives a signal
descending to levels that are comfortable for the from the controller, and as soon as the safety valve
passengers. Normal climb rate is 500 feet per minute closes, the cabin begins pressurize at the rate
and normal descending rate is 300 feet per minute. allowed by the rate controller. This increase in pres-
The cabin rate-of-climb can be automatic or manual sure is sensed by the controller. When the cabin
according to the type of aircraft. The differential reaches the selected altitude, the diaphragm in the
pressure gauge reads the current difference in pres- controller moves back and vacuum is sent into the
sure between the aircraft's cabin interior and the outflow valve to open it and allow some of the pres-
outside air. The modes of operation of the pressur- surizing air to escape from the cabin. This modula-
ization system are generally automatic and manual tion of the outflow valve will maintain the cabin
control. In the manual control mode, the pilots can pressure at the altitude selected. As the flight alti-
control the outflow valves directly through switches tude increases, the outside pressure decreases.
and indicators that are used to position the outflow When ambient pressure becomes low enough that
valves if the automatic mode fails. If the cabin alti- the cabin differential pressure nears the structural
tude exceeds 10,000 feet, on most aircraft, an alarm limit, the upper diaphragm in the outflow valve
Cabin Atmosphere Control 14-23
Figure 14-25. The cockpit control panel for a typical transport-category aircraft pressurization system displays information on the
cabin vertical speed, cabin altitude and differential pressure and provides controls for selecting automatic or manual mode, set-
ting the desired cabin altitude and the reference barometric pressure. A means of manually controlling the outflow valve position
and system warning indications are also provided.

Figure 14-26. The cabin pressure is set at the control panel in the cockpit and controlled by the outflow valve. The safety valve is
similar to the outflow valve and functions as a backup for the outflow valve, and to dump pressurization when the wheels are on
the ground.
74-24 Cabin Atmosphere Control
Figure 14-27. The outflow valve maintains a set altitude until the pressure differential with outside air approaches the structural
limit of the aircraft. It then maintains a differential with the outside pressure.
moves up until the prevents accidentally These valves are
adjusting screw obtaining altitude, completely
depresses the valve which is higher than independent of the
and releases some of the aircraft altitude. rest of the
the reference This possibility pressurization
pressure to the would exist during system. [Figure 14-
outside air. This descent. The outflow 28]
decrease in pressure valves automatically
allows the outflow drive to the full-open
valve to open so it position whenever
can maintain the the aircraft weight is
cabin pressure at a on the wheels.
constant amount Pneumatically
above the outside air operated pressure
pressure. [Figure 14- relief valves open
27] automatically if the
cabin differential
Electronic Regulator pressure becomes
and Outflow Valve too great.
Operation. Figure 14-28. The
Electronic regulators pressurization control
and electrically system regulates and
actuated outflow maintains cabin
valves perform the pressure, and the rate
of cabin pressure
same function as change, as a function
pneumatic systems, of settings on the
only the power source control panel. This is
is different. Electrical accomplished by
signals are sent to the regulating the flow of
air vented from the
cabin pressure cabin through motor
controller from the driven outflow valves.
cockpit control panel
to set the mode of
operation, the desired
cabin altitude and AIR DISTRIBUTION
either standard or The air distribution
local barometric system on most
pressure. In aircraft mixes cold
automatic mode, the air from the air-
cabin pressure conditioning
controller sends packages (packs)
signals to the AC and hot engine
motors, which bleed air in the
modulate as required conditioned air
to maintain the manifold according
selected cabin to the temperature
altitude. In manual called for by the
mode, the controller flight crew. This
uses the DC motors pressurized air
to operate the passes through a
outflow valves. combination check
Interlocks prevent valve/shutoff valve
both motors from on its way to the
operating at the same delivery air ducts.
time. All pressurized This check valve
aircraft require some prevents the air
form of a negative pressure from being
pressure-relief-valve. lost through an
This valve opens inoperative
when outside air compressor. The
pressure is greater pressurized air is
than cabin pressure. then distributed
The negative
pressure-relief-valve
Cabin Atmosphere Control 14-25
to side wall or overhead vents in the cabin. The the gasper fan located in the overhead panel above
cabin air is then drawn back into the conditioned air each seat. [Figure 14-29]
manifold by recirculating fans, mixed with new
incoming air, then redistributed to the aircraft CABIN PRESSURIZATION TROUBLESHOOTING
cabin. Each passenger can turn the conditioned air If a malfunction occurs in the pressurization sys-
"on" or "off" by adjusting the air outlet control on tem, the aircraft manufacturer's service manual
Figure 14-29. The Boeing 747 air distribution system is typical of systems found on large aircraft.
74-26 Cabin Atmosphere Control
should always be used to troubleshoot and repair bleshooting charts can be very helpful in isolating
the system. Fault isolation systems and trou- the defective system components. [Figure 14-30]
Figure 14-30. Most aircraft service manuals have troubleshooting charts to assist the technician in locating problems within the
cabin pressurization system.
CABIN CLIMATE CONTROL SYSTEMS
Aircraft fly in a wide consists of a gasper One of the problems minute cracks to start
variety of climatic fan, ducts and the with this type of where the studs are
conditions. Flights overhead ventilating heater is the welded onto the
might begin on the air outlets above the possibility of carbon muffler. [Figure 14-
ramp at 9562 passenger seats. monoxide poisoning 31]
Fahrenheit (3562 Cooling air is blown if there should be a
Celsius) and then over the passengers, leak in the exhaust
climb to cruise at a which is refreshing, system. For this rea-
temperature of but only 'when the son, it is very
-4062 Fahrenheit (- passenger opens the important that the
40 degrees Celsius). air outlet for that shrouds be
Climate control seat. removed and the
systems then must exhaust pipes and
be able to provide HEATING mufflers carefully
comfortable cabin inspected on the
temperatures, SYSTEMS schedule
regardless of the EXHAUST recommended by
outside air SHROUD the aircraft
temperature. The HEATERS manufacturer. Some Figure 14-31. Some
exhaust shroud heaters
quality of the air The most common leaks may be present utilize welded-on studs
supply is also type of heater for but not large enough to increase the
important: it must be small single-engine to show up clearly effective surface area
free of contaminants, aircraft is the when the metal is for heat transfer.
fumes, odors or other exhaust-shroud cold, so these
factors that might heater. A sheet-metal components should
affect the health or shroud is installed be tested with air ELECTRIC
comfort of the around the muffler pressure. It is HEATING
passengers or crew. in the engine exhaust possible to test some SYSTEMS
system. Cold air is of them on the Electric heating on
taken into this aircraft by aircraft is generally
VENTILATION a supplemental
shroud and heat connecting the
SYSTEMS that would output of a vacuum heating source. The
Most small general otherwise be cleaner to the heaters use heating
aviation aircraft have expelled out the exhaust stack and
relatively simple exhaust is transferred covering the muffler
systems to supply to the ambient air. with a soapy water
unconditioned This air is then solution and watch-
ambient air to the routed into the ing for bubbles.
cabin, primarily for cabin through a Some aircraft have
cooling. The system heater valve in the Airworthiness
may consist simply firewall. When the Directives that
of a window that can heater is not on, this require the mufflers
be opened in flight air is directed to be removed,
or by any of several overboard. This type submerged in water,
types of air vents of heater is quite and pressurized
that deliver ram air economical for small with air to search for
to the occupants. aircraft, as it leaks.
Occasionally, the utilizes heat energy
system may include that would The surface area of
a fan to assist in otherwise be wasted. the muffler
moving air when the .62,-. determines the
aircraft is on the amount of heat that
ground. is transferred to the
air from the muffler.
Business jets and Some manufacturers
airliners generally have increased this
have a system that area by using
supplies cool, welded-on studs.
conditioned air to This type of muffler
individual air vents is more efficient but
at each seat. The air it must be checked
vent system with special care as
(sometimes called it is possible for
the gasper system)
14-28 Cabin Atmosphere Control
elements that create heat through electrical resis- Combustion heaters consist of two stainless steel
tance. Some aircraft use this type of heat when the cylinders, one inside the other. Air from outside the
aircraft is on the ground and the engines are not aircraft is directed into the inner cylinder, and avia-
running. A fan blows air over the heating coils to tion gasoline drawn from the fuel tank is sprayed
heat and circulate the air back into the cabin. Safety over a continually sparking igniter plug. The com-
devices are installed in these systems to prevent bustion gases are exhausted overboard. Ventilating
them from overheating if the ventilating fan should air flows through the outer cylinder around the
become inoperative. combustion chamber, picks up the heat, and is dis-
tributed throughout the cabin.
COMBUSTION HEATERS
Exhaust shroud heaters are used for small single- The hot air ducts are normally located where they
engine aircraft, and compressor bleed air heating is will blow warm air over the passengers' feet and the
primarily used on large turbine-powered aircraft. lower parts of their bodies. This type of heater has a
Light and medium twin-engine aircraft are often number of safety features that prevent it creating a fire
heated with combustion heaters. [Figure 14-32] hazard in the event of a malfunction. [Figure 14-33]
Figure 14-32. Combustion heaters that utilize the same fuel as the engines are installed in many twin-engine aircraft.
Cabin Atmosphere Control 14-29
Figure 14-33. The combustion heater uses engine fuel to heat ram air, which heats the cockpit.
COMBUSTION AIR gases are then vented 7 C
SYSTEM overboard at a 4 a
A scoop on the location where they
outside of the cannot recirculate
aircraft picks up the into the ventilation
air that used in the system.
combustion process.
The combustion air FUEL SYSTEM
blower forces this Fuel is taken from
air into the combus- the aircraft fuel
tion chamber when system and pres-
there is insufficient surized with a
ram air. A constant pressure
combustion-air- pump, and passed
relief valve or a through a fuel filter.
differential pressure Fuel flow is
regulator prevents controlled by a
too much air from solenoid valve
entering the heaters that may be
as air pressure turned off by the
increases. The
exhaust
overheat switch, the limit switch, or by the pressure will close the fuel supply solenoid valve and will
switch. There is a second solenoid valve in the fuel also shut off the combustion air flow and the igni-
line that is controlled by the cabin thermostat. It tion. A warning light will illuminate, alerting the
shuts off the fuel at a point just before it enters the pilot that the heater has been shut down because of
combustion chamber. an overheat condition. This switch, unlike the oth-
ers, cannot be reset in flight, but can only be reset on
VENTILATION AIR SYSTEM the ground at the heater itself.
Ram air enters the heater from outside the aircraft,
and flows over the outside of the combustion cham- MAINTENANCE AND INSPECTION
ber, where it picks up heat and carries it inside the Combustion heaters are relatively trouble-free, but
aircraft. There is a ventilating fan in the heater that they should be carefully inspected in accordance
operates when the aircraft is on the ground. When with the recommendations of the aircraft manufac-
the aircraft becomes airborne, a switch on the land- turer and should be overhauled according to the
ing gear shuts off the ventilating fan and all airflow schedule established by the heater manufacturer. The
is provided by ram air. The ventilating air pressure fuel filter should be cleaned regularly and the spark
is slightly higher than the pressure of the combus- plug should be cleaned and gapped at the recom-
tion air, so in the event of a crack in the combustion mended interval. The entire system should also be
chamber, ventilating air will flow into the combus- checked for any indication of fuel or exhaust leakage.
tion chamber rather than allowing the combustion
air that contains carbon monoxide to mix with the COMPRESSOR BLEED AIR HEATERS
ventilating air. Turbine engines have a large amount of hot air in their
compressors that is available for heating the cabin.
CONTROLS The hot bleed air is mixed with cold ambient air to
The only action required to start the combustion provide air of the proper temperature to the cabin.
heater is to turn the cabin heater switch ON and This form of heating is usually combined with an air-
adjust the cabin thermostat to the desired tempera- cycle air-conditioning system. The air-conditioning
ture. When the cabin heater switch is turned on, the system of a large jet transport aircraft provides a
fuel pump starts, as well as the blowers for ventila- means to cool or heat the pressurizing air as required.
tion air and combustion air. As soon as the combus-
tion air blower moves the required amount of air, it
trips a pressure switch that starts the ignition coil AIRCRAFT AIR
supplying current to the igniter plug. The fuel sup- CONDITIONING SYSTEMS
ply solenoid valve is opened and fuel can get to the Air conditioning is more than just the cooling of air.
heater. When the thermostat calls for heat, the sec- A complete air-conditioning system for an aircraft
ond fuel solenoid valve opens and fuel sprays into should control both the temperature and humidity
the combustion chamber and burns. As soon as the of the air, heating or cooling it as is necessary. It
temperature reaches the value for which the ther- should provide adequate movement of the air for
mostat is set, the contacts inside the thermostat ventilation, and there should be provision for the
open and de-energize the fuel solenoid valve, shut- removal of cabin odors.
ting off the fuel to the heater, and the fire goes out.
The ventilating air cools the combustion chamber, AIR-CYCLE AIR CONDITIONING
and the cool air causes the thermostat to call for In a jet transport aircraft, hot compressor bleed air is
more heat. The cycle then repeats itself. taken from the engine compressors. An air-cycle
machine (ACM) applies several basic laws of
SAFETY FEATURES physics to cool this bleed air and then mix it with
The duct limit switch is in the circuit to the main hot bleed air to provide air at the desired tempera-
fuel solenoid, and will shut off the fuel to the heater ture for ventilation and pressurization. The air-cycle
if for any reason there is not enough air flow to carry machine and its associated components are often
the heat out of the duct, or if the duct temperature referred to as a "pack." [Figure 14-34]
reaches the preset maximum value.
SHUTOFF VALVE
The overheat switch is the final switch in the sys- The air-conditioning shutoff valve, often called the
tem. It is set considerably higher than the duct limit pack valve, is used to control the flow of air into the
switch, but below a temperature that could cause a system. It can either shut off the air flow or modu-
fire hazard. If the temperature put out by the heater late the flow of air to provide that which is needed
reaches the limit allowed by this switch, the switch to operate the air-conditioning package.
Cabin Atmosphere Control 14-31
Figure 14-34. The air cycle system utilizes bleed air from the turbine engine(s) to heat and cool air for cabin air conditioning.
PRIMARY HEAT SECONDARY HEAT side of the ACM. through the primary
EXCHANGER EXCHANGER The compressor heat exchanger,
The primary heat As cooling raises both the where some of the
exchanger is a requirements pressure and heat is transferred to
radiator through increase, air exiting temperature of the ram air passing
which cold ram air the primary heat air passing through around the tubes in
passes to cool the exchanger is routed it. The warmer, high the radiator-like
hot bleed air from to the compressor pressure air is then cooler. The high-
the engines. As the directed to the pressure
cold ram air passes secondary heat
over the radiator's exchanger. This heat
fin-like tubes, exchanger provides
bleed air passing an additional stage
through the tubes is for cooling the hot
cooled. The flow of engine bleed air after
ram air through the it has passed through
heat exchangers is the primary heat
controlled by move- exchanger and the
able inlet and exit compressor of the
doors, which ACM. It operates in
modulate in flight to the same manner as
provide the required the primary heat
cooling. On many exchanger.
aircraft, the heat
exchangers are sized REFRIGERATION
to provide most, if BYPASS VALVE
not all, of the Some systems use a
necessary cooling in refrigeration bypass
flight. On the ground valve to keep the
there is not enough temperature of the
air passing through air exiting the ACM
the cooling doors, so from becoming too
fans called pack fans cold. Generally this
provide adequate air- air is kept at about
flow to cool the heat 3572 F (272 C) by
exchangers. passing warm bleed
air around the ACM
AIR CYCLE MACHINE and mixing it with
BYPASS VALVE the output air of the
When cooling ACM. The primary
requirements are purpose of this valve
low, some or all of is to prevent water
the hot bleed air from freezing in the
from the engines can water separator.
be bypassed around
the ACM (the REFRIGERATION
compressor and TURBINE UNIT
turbine) if warm air Pressure and
is needed in the temperature, are
cabin. There would interchangeable
be no purpose in forms of energy. A
cooling all the air if turbine engine
warm air is called extracts energy from
for by the the burning fuel to
temperature controls. turn the compressor,
This outlet air from and this energy
the primary heat raises both the
exchanger may be pressure and the
routed directly to the temperature of the
inlet side of the engine inlet air.
secondary heat Compressed air with
exchanger in some this energy in it is
systems to provide taken from the
additional cooling. engine and passed
74-32 Cabin Atmosphere Control
air, somewhat cooled, is then ducted into the air WATER SEPARATORS
cycle machine where most of the remainder of its The rapid cooling of the air in the turbine causes
energy is extracted by the air cycle machine. It con- moisture to condense in the form of a fog, and when
sists of a centrifugal air compressor and an expan- this foggy air passes through the water separator, the
sion turbine that drives the compressor. When the tiny droplets of water coalesce in a fiberglass sock
compressor bleed air passes through the primary and form large drops of water. The louvers over
heat exchanger, it loses some of its heat but almost which the sock fits are shaped to impart a swirling
none of its pressure. This air then enters the com- motion to the air, and the drops of water are slung to
pressor of the air cycle machine, and its pressure is the sides of the container by centrifugal force, where
further increased. With the increase in pressure, they are carried overboard through the drain valve.
there is some increase in its temperature, but this is
removed by the secondary heat exchanger. Now the This water is kept from freezing by mixing the air in
somewhat cooled high-pressure air flows into the the separator with warm air. A temperature sensor
expansion turbine where a large percentage of its in the outlet of the water separator regulates a tem-
remaining energy is used to drive the compressor. perature control valve in a bypass line around the
As this air expands across the turbine, there is a air cycle machine. If the temperature of the air at the
large decrease in pressure. The decrease in pressure, outlet of the water separator ever drops below 3874
coupled with the energy extracted to drive the com- F, the control valve opens so warm air can mix
pressor, results in a very large decrease in tempera- with that in the water separator. This precludes
ture. There are two forms of cooling used in this sys- cabin airflow blockage and possible damage to the
tem. Some is done by transferring heat to the ram separator.
air, but most of the heat is removed by expansion
and converting it into work to drive the compressor. RAM AIR DOOR
This type of cooling system is called a bootstrap sys- Some aircraft are equipped with a ram air door to
tem. [Figure 14-35] allow cool outside air to ventilate the cabin with fresh
air during unpressurized flight. It is generally fully
Figure 14-35. The air-cycle air conditioner utilizes bleed air to heat and cool the cabin.
Cabin Atmosphere Control 14-33
open or closed and is seldom used on pressurized air- the controller for that zone adjusts the position of a
craft except in emergencies. An electric heater may be trim air valve to mix warm bleed air with the cold
provided to warm this ram air as necessary. air from the conditioned air manifold. If all the zone
temperature controllers are in manual mode, the
CABIN TEMPERATURE PICKUP UNIT pack controllers will set the ACM outlet tempera-
Normally, temperature sensors are located in each ture to 3577 F (277 C). If any one zone controller is
passenger zone in the aircraft's cabin for the pur- in auto with the remainder in manual, the controller
pose of controlling the zone temperature. The cabin in auto determines the pack outlet temperature.
zone controller uses the sensed difference between
the temperature demand signal from the selector VAPOR-CYCLE AIR CONDITIONING
and the actual supply temperature to position the Temperature is a measure of the effect of heat on a
associated air mix valve. body or material, and is a convenient way of
expressing this physical phenomenon numerically.
ZONE TEMPERATURE CONTROLLER While there is a relationship between heat and tem-
Some aircraft, such as the Boeing 747, use a slightly perature, heat can be added to or removed from a
different method to provide conditioned air at the refrigerant without changing its temperature. The
proper temperature to each cabin zone. In this air- heat put into a material as it changes its state with-
craft, the zone temperature controllers have two out changing its temperature is called latent heat,
modes of operation, automatic and manual, and and this heat will be returned when the material
send signals to each pack controller. If all the zone reverts to its original state. This process acts in a
temperature controllers are in auto, the zone calling continuous cycle. A refrigerant changes state from a
for the coldest temperature sets the output tempera- liquid into a vapor, and in doing so, it absorbs heat
ture for all the air-conditioning packs. The output from the cabin. This heat is taken outside of the air-
air from each pack enters the conditioned air mani- craft and is given off to the outside air as the refrig-
fold. For each zone requiring a warmer temperature, erant returns to a liquid state. [Figure 14-36]
Figure 14-36. The vapor-cycle air conditioning system is the same basic system as used in modern automobiles.
14-34 Cabin Atmosphere Control
TRANSFER OF HEAT and when the air emerges from the evaporator, it is
Heat is a form of energy, and can neither be created cool. When heat is absorbed by the refrigerant, it
nor destroyed. It can, however, be transformed or changes from a liquid into a gas without increasing
moved from one place or material to another. This its temperature. The heat remains in the refrigerant
energy continues to exist regardless of its form or in the form of latent heat.
location. Heat will flow from an object having a cer-
tain level of energy into an object having a lower The refrigerant vapor that has the heat from the
level. Any material that allows this transfer easily is cabin is taken into the compressor, where additional
said to be a conductor of heat, while any material energy is added to it to increase both its pressure
that impedes the transfer is called an insulator. and temperature. It leaves the compressor as a hot,
high-pressure vapor. The heat trapped in the refrig-
The refrigerant used in an aircraft air-conditioning erant vapors in the condenser escapes into the walls
system is a liquid under certain conditions. When it of the coil and then into the fins that are pressed
is surrounded by air having a higher level of heat onto these coils. Relatively cool air from outside the
energy, heat will pass from the air into the liquid. As aircraft flows through these fins and picks up the
the liquid absorbs the heat, it changes state and heat that is given up by the refrigerant. When it
becomes a gas. The air that gave up its heat to the loses its heat energy, the refrigerant vapor con-
refrigerant is cooled in the process. denses back into a liquid and then flows into the
receiver-dryer where it is held until it passes
The system is divided into two sides, one that through the system for another cycle.
accepts the heat and the other that disposes of it.
The side that accepts the heat is called the low side, REFRIGERANT
because here the refrigerant has a low temperature Almost any volatile liquid can be used as a refriger-
and is under a low pressure. The heat is given up on ant, but for maximum effectiveness, it must have a
the high side, where the refrigerant is under high very low vapor pressure and therefore a low boiling
pressure and has a high temperature. Notice in fig- point. The vapor pressure of a liquid is the pressure
ure 14-36, that the system is divided at the com- that will exist above a liquid in an enclosed con-
pressor where the refrigerant vapor is compressed, tainer at any given temperature. For example, a par-
increasing both its pressure and temperature, and at ticular liquid refrigerant in an open container boils
the expansion valve where both pressure and tem- vigorously as the liquid turns into a gas at a temper-
perature drop. ature of 7080 F. If the container is closed, the
liquid will continue to change into a vapor and the
The refrigeration cycle starts at the receiver-dryer pressure of the vapor will increase. When the
which acts as a reservoir to store any of the liquid pressure reaches 70.1 psi, no more vapor can be
refrigerant that is not passing through the system at released from the liquid. The vapor pressure of this
any given time. If any refrigerant is lost from the particular material is then said to be 70.1 psi at
system, it is replaced from that in the receiver-dryer. 7080 F.
A desiccant agent is used in the receiver-dryer to
trap and hold any moisture that could possibly be in Many different materials have been used as refriger-
the system. This is necessary since a tiny droplet of ants in commercial systems, but for aircraft air-condi-
water in the refrigerant is all that is needed to freeze tioning systems, dichlorodifluoromethane is almost
in the orifice of the expansion valve, completely universally used. It is a stable compound at both high
stopping operation of the system. and low temperatures and does not react with any of
the materials in an air-conditioning system. It will not
Liquid refrigerant leaves the receiver-dryer and attack the rubber used for hoses and seals, and is col-
flows under pressure to the expansion valve where orless and practically odorless. Rather than calling
it sprays out through a tiny metering orifice into the this refrigerant by its long chemical name, it is just
coils of the evaporator. The refrigerant is still a liq- referred to as Refrigerant-12, or, even more simply as
uid, but it is in the form of tiny droplets, affording R-12. It may also be known by one of its many trade
the maximum amount of surface area so the maxi- names such as Freon-1280, Genetron-1280, Isotron-
mum amount of heat can be absorbed. 1280, Ucon-1280, or by some other proprietary
name. The important thing to remember is the
The evaporator is the unit in an air-conditioning number. Any of these trade names associated with
system that produces the cold air. Warm air is blown another number is a different product. Freon-2280,
through the thin metal fins that fit over the evapo- for example is similar to Freon-12, except that its
rator coils. This heat is absorbed by the refrigerant, vapor pressure is different. It is the refrigerant
commonly used in commercial refrigerators and
freezers. When servicing an aircraft
Cabin Atmosphere Control 14-35
air-conditioning system, it is extremely important to will be cold enough to cool the air, but not cold
use only the refrigerant specified in the aircraft man- enough to cause ice to form. [Figure 14-37]
ufacturer's service manual. R-12 is the refrigerant dis-
cussed in this section, but the procedures used for Refrigerant-12 boils at normal sea level pressure at
other refrigerants are basically the same. 21.682 F, and if a drop of liquid R-12 contacts skin, it
will cause frostbite. Even a tiny drop of liquid R-12 in
One of the characteristics of R-12 that makes it the eye is hazardous. If liquid refrigerant gets in the
desirable for aircraft air-conditioning systems is its eye, the eye should be flooded "with cool water, treated
temperature-vapor pressure relationship. In the with mineral oil or petroleum jelly and a physician
temperature range between 2082 and 8082 F, the seen immediately. It is extremely important to wear
range where most air conditioning occurs, there is eye and skin protection any time air conditioning sys-
an approximate relationship of one psi of vapor tems are being serviced. R-12 is not normally toxic.
pressure for each degree of Fahrenheit However, when R-12 is burned its characteristics
temperature. While this relationship is not exact, change drastically, becoming deadly phosgene gas.
it is close enough to make servicing relatively easy.
If the low-side pressure is 28 psi, the temperature of REFRIGERATION OIL
the refrigerant in the evaporator coils is about 3082 Since the air-conditioning system is completely
F. This is the temperature of the refrigerant and not sealed, the oil used to lubricate the compressor seals
of the air passing through the evaporator. That will and expansion valve must be incorporated within a
be somewhat higher (34 or 3582 F.) This temperature sealed a system. The oil is a special, highly refined
will give the most effective cooling, since the mineral oil, free from such impurities as water,
evaporator coils
TEMP PRESSURE TEMP PRESSURE TEMP PRESSURE TEMP PRESSURE TEMP PRESSURE

蚌 PSI 蚌 PSI 蚌 PSI 蚌 PSI 蚌 PSI


0 9.0 35 32.5 60 57.7 85 917 110 136.0
2 10.1 36 33.4 61 58.9 86 93.2 111 138.0
4 11.2 37 34.3 62 60.0 87 94.8 112 140.1
6 12.3 38 35.1 63 61.3 88 96.4 113 142.1
8 13.4 39 36.0 64 62.5 89 98.0 114 144.2
10 14.6 40 36.9 65 63.7 90 99.6 115 146.3
12 15.8 41 37.9 66 64.9 91 101.3 116 148.4
14 17.1 42 38.8 67 66.2 92 103.0 117 151.2
16 18.3 43 39.7 68 67.5 93 104.6 118 152.7
18 19.7 44 40.7 69 68.8 94 106.3 119 154.9
20' 21.0 45 41.7 70 70.1 95 108.1 120 157.1
21 21.7 46 42.6 71 71.4 96 109.8 121 159.3
22 22.4 47 43.6 72 72.8 97 111.5 122 161.5
23 23.1 48 44.6 73 74.2 98 113.3 123 163.8
24 23.8 49 45.6 74 75.5 99 115.1 124 166.1
25 24.6 50 46.6 75 76.9 100 116.9 125 168.4
26 25.3 51 47.8 76 78.3 101 118.8 126 170.7
27 26.1 52 48.7 77 79.2 102 120.6 127 173.1
28 26.8 53 49.8 78 81.8 103 122.4 128 175.4
29 27.6 54 50.9 79 82.5 104 124.3 129 177.8
30 28.4 55 52.0 80 84.0 105 126.2 130 182.2
31 29.2 56 53.1 81 85.5 106 1281 131 182.6
32 30.0 57 55.4 82 87.0 107 130.0 132 185.1
33 30.9 58 56.6 83 88.5 108 132.1 133 187.6
34 31.7 59 57.1 84 90.1 109 135.1 134 190.1

Figure 14-37. Each refrigerant has its own temperature-vapor pressure chart. This chart allows the technician to estimate the tem-
perature at the evaporator coils by measuring low side pressure.
74-36 Cabin Atmosphere Control
sulfur or wax. The identification number of the oil
refers to its viscosity. The lower the number, the less
viscous the oil. It is very important to use the oil
specified in the aircraft manufacturer's service man-
ual when servicing the system. Whenever opening
the system, you must purge all of the refrigerant.
However, when purging the system, do not open the
valves to the point at which the refrigerant can
escape fast enough to blow out the oil with the
vapor. To reduce the chance of contamination,
tightly close the oil container when it is not in use.
Never pour refrigerant oil from one container into
another, and, discard oil removed from the system.
Always service refrigerant systems with new oil.

RECEIVER-DRYER
The receiver-dryer is the reservoir for the system and
is located in the high side between the condenser Figure 14-38. The receiver-dryer removes moisture from the
and the expansion valve. Liquid refrigerant enters system. If moisture remains in the system, the low temper-
from the condenser and is filtered and passed atures will cause it to freeze, clog the small orifices within
the system, and cause the system to stop working.
through a desiccant such as silica-gel to absorb any
moisture that might be in the system. A sight glass is refrigerant completely evaporates before it reaches
normally installed in the outlet tube to indicate the the end of the evaporator, it will continue to absorb
amount of charge in the system. Bubbles can be seen heat and become superheated. It is still very cold
in the glass when the charge is low. A pickup tube to touch, but it is considerably warmer than it
extends from the top of the receiver-dryer to near the would be if it had not absorbed this additional
bottom where the liquid refrigerant is picked up. A heat. The expansion valve is adjusted to a given
filter is installed either on the end of the pickup tube amount of superheat. When the pressure of the
or between the tube and the desiccant to prevent any refrigerant vapor reaches this value, the diaphragm
particles getting into the expansion valve. It is of pushes down against the superheat spring and
extreme importance that all moisture be removed opens the valve, allowing more refrigerant to enter
from the system, as a single drop can freeze in the the evaporator. A balance between the vapor pres-
expansion valve and stop the entire air conditioning sure on the diaphragm and the superheat spring
process. Water will also react with the refrigerant to controls the amount of refrigerant flow. These
form hydrochloric acid that is highly corrosive to the valves are calibrated at the factory and cannot nor-
metal in the system. [Figure 14-38] mally be adjusted in the field. If there is a lot of
THERMAL EXPANSION VALVE
heat in the cabin, the liquid refrigerant will evapo-
The thermal expansion valve is the control device rate quickly, and more superheat will be added to
which meters the correct amount of refrigerant into the vapor, so the valve will open and allow more
the evaporator. The refrigerant should evaporate refrigerant to flow into the evaporator. When the
completely by the time it reaches the end of the heat load is low, the liquid will use most of the
coils. The heat load in the aircraft cabin controls evaporator length to evaporate. Little superheat
the opening, or orifice, in the valve. There are two will be added, and a smaller amount of refrigerant
types of thermal expansion valves, the internally will be metered into the coils. [Figure 14-39]
equalized valve, and the externally equalized valve.
The externally equalized expansion valve equalizes
The internally equalized thermal expansion valve temperature against high-side temperature. There is a
is controlled by the amount of heat in the evapora- noticeable pressure drop across large evaporators
tor. A capillary tube to the evaporator connects the because of the opposition to the flow of refrigerant.
diaphragm chamber of the valve. The end of the An externally equalized expansion valve has an addi-
capillary is coiled into a bulb and is held tightly tional port to adjust for this loss of pressure. This
against the discharge tube of the evaporator. increased flow provided by the pressure equalization
Coiling this tube allows a greater area to be held in will maintain a constant pressure across the evapora-
intimate contact with the tube, allowing for a more tor. The temperature sensing function of the valve is
accurate temperature measurement. If the liquid therefore able to meter the refrigerant as a function of
the actual heat load in the cabin. [Figure 14-40]
Cabin Atmosphere Control 14-37
Figure 14-39. The internally equalized thermal expansion valve adjusts the amount of refrigerant so it finishes turning to a gas as
it leaves the evaporator coils.
EVAPORATOR compressor is at a
The evaporator is the high temperature and
actual cooling unit in pressure. Aircraft
a vapor-cycle air- air-conditioning
conditioning system. systems usually use
An evaporator con- recip-rocating-type
sists of one or more compressors, which
circuits of copper have reed valves and
tubing arranged in a lubricating system
parallel between the that uses crankcase
expansion valve and pressure to force oil
the compressor. into its vital parts.
These tubes are [Figure 14-42]
silver-soldered into a
compact unit, with On small aircraft,
thin aluminum fins these compressors
pressed onto their are usually belt
surface. The driven by the engine,
evaporator is usually very similar to the
mounted in a arrangement used in
housing with a an automobile. The
blower. The blower compressors in
forces cabin air over systems used on
the evaporator coils. larger aircraft are
The refrigerant driven by electric or
absorbs heat from hydraulic motors, or
the cabin air, thereby by compressor bleed
cooling it before it air powered turbines.
returns to the cabin. Engine-driven
A drip pan is compressors are
mounted below the single speed pumps
evaporator to catch whose output is
water that condenses controlled by a
out of the air as it magnetically
cools. The capillary actuated clutch in
of the thermostat is the compressor
placed between the drive pulley. When
fins of the evaporator no cooling is needed,
core to sense the the clutch is de-
temperature of the energized and the
coil, and it is this compressor does not
temperature that operate. When the
controls the cycling air conditioner is
of the system. turned on, and the
[Figure 14-41] thermostat calls for
cooling, the
COMPRESSOR magnetic clutch is
The compressor energized, causing
circulates the the drive pulley to
refrigerant through turn the compressor
the system. and pump refrigerant
Refrigerant leaves through the system.
the evaporator as a [Figure 14-43]
low-pressure, low-
temperature vapor Electric motor-
and enters the driven compressors
compressor. The are controlled by a
compressor provides thermostat that turns
the energy necessary the compressor
to operate the motor on and off as
system. The gas required. Hydraulic
leaving the motors are turned off
and
1
4
Figure 14-40. The externally equalized thermal expansion valve is used on large evaporators to compensate for pressure loss due
to length of the evaporator coils.
on by solenoid motor is not being
valves controlled by driven, the output of
the thermostat. the engine-driven
When the valve is hydraulic pump is
opened, hydraulic returned to the
fluid is directed reservoir. In all of
under pressure to these systems, the
the motor. When cabin blower
the operates
C
a
Figure 14-43. A magnetically controlled clutch turns the
compressor on and off as required to cool the cabin. This is
Figure 14-41. The evaporator removes heat from the cabin similar to the system used on most modern cars.
air and transfers it to the refrigerant flowing through the
evaporator coils.
continually, forcing the cabin air over the evapora- the evaporator are similar in both construction and
tor so heat from cabin air can be transferred into the appearance, differing primarily in strength. Since
refrigerant. the condenser is in the high side of the system, it
must be capable of withstanding the high pressure
CONDENSER found there. Condensers normally operate at a pres-
The condenser is the radiator-like component that sure of about 300 psi and have a burst pressure in
receives the hot, high-pressure vapors from the excess of 1,500 psi.
compressor and transfers the heat from the refriger-
ant vapors to the cooler air flowing over the con- In some of the smaller airplanes the condenser is
denser coils. When heat is removed from the vapor, mounted under the fuselage where it can be
the refrigerant returns to a liquid state. extended down into the air stream when the system
is operating, and retracted into the fuselage when
The condenser is made of copper tubing with alu- the system is off. An interlock switch on the throttle
minum fins pressed onto it, formed into a set of retracts the condenser and de-energizes the com-
coils, and mounted in a housing. The condenser and pressor clutch when the throttle is opened for full
power, to prevent the compressor loading the
Figure 14-42. The reciprocating, piston-type, compressor is commonly used in aircraft air conditioning systems.
74-40 Cabin Atmosphere Control
engine and the condenser causing drag when the
airplane needs maximum performance such as
for takeoff.
In larger aircraft the condenser is mounted in an
air duct where cooling air can be drawn in from the
outside and blown over the coils. In flight, ram air
usually provides sufficient airflow over the con-
denser for proper operation, For ground operation,
a fan must be used to supply the necessary cooling
airflow.
Many vapor-cycle-cooling systems incorporate a
sub-cooler that cools the liquid before it enters the
compressor in addition to cooling the vapor after
the condenser. Cooling the refrigerant in a sub-
cooler prevents premature vaporization or flashoff.
SERVICE VALVES
The refrigeration system is sealed so that there is no
opening to the atmosphere, but there must be some
provision made to service it with refrigerant.
Service valves provide access to the system, and
there are two types of valves commonly found in
aircraft air-conditioning systems: Schrader valves
and compressor isolation service valves.
Schrader valves are often used when it is not conve-
nient to service an aircraft system at the compressor
because of the proximity of the propeller. The valves
are mounted on either side of the evaporator or in
some other part of the system where they can be
reached for servicing. One of the valves is in the high
side of the system, and the other is in the low side.
Schrader valves have a core similar to that used in a
tire valve, and have only two positions, seated and
open. To enter a system using Schrader valves, the
service hose is screwed onto the valve, and a pin
inside the hose will depress the valve core stem.
When the hose is removed, the valve seats. A pro-
tective cap must be in place any time a hose is not
attached to the valve to keep out contaminants. Figure 14-44. Schrader-type service valves are similar to
those found on automobile tires.
[Figure 14-44]
Compressor isolation service valves are normally screwed onto the service port and the valve turned
mounted on the compressor itself, and in addition three or four turns. In this intermediate position, the
to allowing entry into the system for the service system can function normally, and the service line
hoses, this valve can also be used to isolate the com- has access to the system for measuring the pressure
pressor from the system for servicing without losing or for adding or removing refrigerant. When the
the refrigerant charge. [Figure 14-45] valve is front seated, turned all the way clockwise,
the line to the system is closed and the compressor
This valve has three positions. The valve is back-
is isolated. The service valves must both be front-
seated for normal system operation, and when back-
seated when checking the refrigerant oil in the com-
seated, the service port is closed, and the passage
pressor or for any other type of compressor servic-
from the system line to the compressor is open. To
ing. When the system is closed for normal opera-
open the system for servicing, the service hose is
tion, a protective cap should be screwed onto the
Cabin Atmosphere Control 14-41
MANIFOLD SET
The manifold set consists of three fittings to which
the service hoses are attached, two hand valves with
O-ring seals, and two gauges, one for measuring the
pressure in the low side of the system and one for
the pressure in the high side. [Figure 14-46]

Figure 14-46. A manifold set is required to do most servic-


ing of air conditioning systems.

The low-side gauge is a compound gauge, meaning


that it will read pressure on either side of atmos-
pheric pressure. Its range is from 30 inches of mer-
Figure 14-45. Compressor isolation service valves allow ser- cury (approximately 60 psi) gauge pressure below
vicing of the system with the compressor isolated.
that of the atmosphere, to about 30 inches of mer-
cury (approximately 60 psi) gauge pressure above
service port and a plastic or metal cap installed over atmospheric. The high-side gauge is a high-pressure
the squared drive end of the valve stem. gauge that has a range of from zero up to around 600
psi, gauge pressure.
SERVICE EQUIPMENT
Specialized equipment is required to perform ser- The manifold connects the gauges, the valves, and the
vicing on air conditioning systems. Manifold sets charging hoses. The low-side gauge is connected to
that allow selective measuring of pressures as well the manifold directly at the low-side fitting. The high-
as selective pressurizing and depressurizing of the side gauge is likewise connected directly to the high-
two sides of the system have been in use for some side fitting. The center fitting of the manifold can be
time. In recent years, environmental concerns have isolated from both of the gauges and from the high-
dictated that refrigerants not be released into the and low-side service fittings by the hand valves.
atmosphere. Recycling/recovery equipment has
been combined with the vacuum pump that has When these valves are turned fully clockwise, the
previously been used to depressurize the system. center fitting is isolated. When the low-side valve is
These units allow the reuse of the refrigerant that opened by turning it counterclockwise, the center
formerly was released to the atmosphere. fitting is opened to the low-side gauge and the
74-42 Cabin Atmosphere Control
low-side service line. The same is true for the high cylinders. The exact amount of refrigerant put into a
side when the high-side valve is opened. system is determined by its weight rather than by its
volume. In the late 1990s, concern for the ozone
The charging hoses are attached to the fittings of the layer caused a shift away from use of R-12 refriger-
manifold set for servicing the system. The high side ant. New refrigerants do not have the same damag-
fitting may be located either at the compressor dis- ing chlorofluorocarbons (CFCs) as R-12. In most
charge, the receiver-dryer, or on the inlet side of the cases, new refrigerants are not compatible with sys-
thermal expansion valve. The low-side service tems designed to use R-12 and components of the
valve may be located at the compressor inlet, or at system must be replaced with components compat-
the discharge side of the expansion valve. The cen- ible with the new refrigerants. Procedures for ser-
ter hose attaches to the recovery/recycling/vacuum vicing systems using the new refrigerants are simi-
unit for evacuating the system, or to the refrigerant lar to those for R-12, but service manuals should
supply for charging the system. Charging hoses used always be consulted for exact procedures.
with Schrader valves must have a pin to depress the
valve, and these hoses are normally color-coded to The smaller cans of refrigerant are opened with a
quickly identify them. The high-side hose is red, the special valve tap that is screwed onto the can to
low-side hose is blue, and the center hose is usually attach the manifold set. When the valve is attached
yellow. When not using the manifold set, the hoses to the can, the seal is pierced and the refrigerant can
should be capped to prevent moisture from contam- flow into the manifold set. Larger cylinders have a
inating the valves. The caps are sometimes an inte- built-in shutoff valve to which the service hoses
gral part of the charging hoses. [Figure 14-47] attach directly. A charging stand is the preferred
Figure 14-47. When the manifold set is not in use, the charg- way of handling the refrigerant since it provides all
of the needed equipment and tools for servicing air-
craft air-conditioning systems. [Figure 14-48]

ing hoses should be protected by screwing their end fit-


tings into plugs provided with the set.
REFRIGERANT SOURCE Figure 14-48. A charging stand provides all of the needed
The refrigerant used in aircraft air-conditioning sys- equipment and tools for servicing aircraft air-conditioning
systems.
tems has, until recently, been Refrigerant-12 (R-12).
This material can be purchased in handy one-pound
or two-and-a-half pound cans, ten- or twelve-pound R-12 is normally put into the system in its vapor
disposable cylinders, or in larger returnable form after the system has been evacuated and is still
under vacuum. Vapor is put into the system on the
Cabin Atmosphere Control 14-43
low side by holding the container upright. Heat will
hasten the discharge of the refrigerant vapor, but
care must be taken when you use heat. Use only
water heated to about 120104 F. NEVER USE
DIRECT FLAME OR AN ELECTRIC HEATER. When
the container is inverted, liquid will flow out. If
allowed by the service manual, liquid should go
into the high side, where it can go directly into the
receiver-dryer. (NOTE: In some systems having the
service valves quite a long way from the
compressor, it is permissible to put liquid into the
low side when the low-side pressure is low enough
and the outside air temperature is high enough. Be
sure to use only the procedures recommended in the
aircraft service manual.) Special precautions should
be observed to be sure that only the correct
refrigerant is used. Refrigerant-22 is similar to R-
12, but its pressure is higher for the same Figure 14-49. A vacuum pump is attached to the center
temperature, and there is a danger of damaging the hose of the manifold set to evacuate the air-conditioning
system or causing leaks due to excessive pressure. system in the airplane.

VACUUM PUMP paintbrush to any part of the system where a leak is


Just a few drops of water is all that is necessary to suspected. Bubbles will indicate the presence
completely block an air-conditioning system. If this of a leak.
water freezes in the thermal expansion valve, the
vapor cycle ceases. To eliminate any water from the A common type of leak detector used in automotive
system, the system must be evacuated. In this proce- air conditioning and commercial refrigeration service
dure, a vacuum pump (a part of the recovery/recy- is a propane-burner-type detector. The torch type
cling/vacuum unit) is attached to the manifold set leak detector is definitely NOT RECOMMENDED for
and all of the air, refrigerant and water vapor is use with an aircraft air-conditioning system, because
pumped out of the system. As the vacuum pump of the danger of an open flame around the aircraft.
reduces the system pressure below atmospheric pres- The most acceptable type of leak detector for aircraft
sure, the boiling point of water decreases and the air-conditioning servicing is an electronic oscillator
resulting vapor will be drawn from the system. The that produces an audible tone. The presence of R-12
vacuum pump used for the evacuation must produce will cause the frequency to increase to a high-pitched
an extremely low pressure, but the flow is of little squeal. This type of detector is recommended
importance. A typical pump used for evacuating air- because it is both safe and sensitive. A good elec-
conditioning systems pumps about 0.8 cubic foot of tronic leak detector can detect leaks as small as one-
air per minute and will evacuate a system to about half ounce per year. [Figure 14-50]
minus 29 inches of mercury, that is, below standard
sea-level pressure. At this low pressure, water boils
at temperatures as low as 45104 F, becomes vapor,
and is evacuated. [Figure 14-49]

LEAK DETECTOR
The continued operation of an air-conditioning sys-
tem depends upon the system maintaining its
charge of refrigerant, and all of the charge can be
lost to even a tiny leak. Naturally a small leak of a
colorless, odorless gas is difficult to find, and with-
out the aid of a leak detector, it would be almost
impossible.

Of the several types of leak detectors available, the


Figure 14-50. An electronic-type leak detector is being used
most simple is a soap solution. A relatively thick to search for a leak around the service valves on the com-
solution of soap chips and water is applied with a pressor.
74-44 Cabin Atmosphere Control
SYSTEM SERVICING retracts and the compressor clutch de-energizes
Understanding the operation of an aircraft air-con- when the throttle is fully opened. The microswitch
ditioning system and the function of each compo- on the throttle should be checked for the proper
nent makes servicing the system less difficult. There adjustment and positive operation.
is not a great deal involved in maintaining these sys-
tems. An aircraft maintenance technician will nor- The compressor mounting brackets should all be
mally only inspect the system and replace/repair checked, since the compressor is subject to
portions of the air delivery systems. A certified extremely hard service. If the compressor is belt dri-
refrigeration technician will normally do any ser- ven, the belt should be checked for tension and
vice and repair to the vapor-cycle components condition. A belt tension gauge should be used if
themselves. available; otherwise the belt should be adjusted
until there is about a half-inch deflection between
TESTS AND INSPECTION pulleys when the pressure specified in the manual
A visual inspection of the aircraft air conditioning is put on the belt.
system will reveal most defects. All of the units in
the system should be checked for indications of The entire run of hose from the compressor and con-
looseness, misalignment, and any indications of denser into the cabin should be checked for chafing
leakage. Since the refrigerant oil is dispersed or interference with the structure or any of the com-
throughout the system, it is quite possible for a leak ponents. Grommets should be installed anywhere
to be indicated by oil seeping out at the point of the chafing could occur.
leakage. All of the air ducts should be inspected for
indication of obstructions or deformation, and the A leak test is used to detect a loss of refrigerant.
blower motor should spin freely without any bind- Lack of refrigerant is one of the most common
ing or excessive noise. The evaporator fins should causes of failure to cool. The sight glass on the
be clean and free from dust, lint, or any other receiver-dryer should be inspected while the system
obstruction, and any fins that are bent over enough is in operation. If bubbles are visible in the sight
to obstruct airflow should be straightened with a fin glass, there is not enough refrigerant in the system.
comb. Distorted fins on the evaporator will block A complete absence of cooling with no bubbles in
the air flow and prevent heat being absorbed by the the sight glass could mean that there is no refriger-
refrigerant. Too much blockage can cause the evap- ant in the system. In order to find the leak that
orator to ice up. [Figure 14-51] caused the loss of refrigerant, the system must be at
least partially charged.
The manifold set should be connected into the sys-
tem with both the high- and the low-side valves
closed. There should be at least 50 psi refrigeration
pressure in the system. If there is not enough pres-
sure for the test, refrigerant must be added. The
high-side valve is opened and the proper type of
refrigerant is allowed to flow into the system until
the low-side gauge indicates about 50 psi; then the
high side valve is closed.
The entire system is then checked with a leak detec-
tor. The probe should be held under every fitting
where a leak could be present, especially at any point
in the system where there is an indication of oil seep-
Figure 14-51. Distorted fins on the evaporator can reduce air age. It is possible for there to be a very small leak at
flow and can possibly cause the evaporator to ice up.
the front end of the compressor through the front
seal, and since this seal is lubricated with refrigera-
The condenser should be checked for obstructions tion oil that is full of refrigerant, it may show up as a
and security of mounting. If it is a retractable con- leak. To prevent this false indication, wash the oil out
denser, the mechanism that extends and retracts it of the seal cavity with some solvent such as Xylene.
should be checked, and it should come up stream- A leakage of about one ounce of refrigerant per year
lined with the structure when the system is turned is normally permissible through these seals, and this
off. On this type of installation, the condenser small leak should not be cause for worry.
Cabin Atmosphere Control 14-45
One source of leakage which can cause a refrigerant If the atmospheric conditions are especially humid,
loss without being found by a leak detector is the the amount of cooling will be reduced because of
loss through the flexible hoses used in the system. the water that condenses on the evaporator. When
Even though this type of hose is in good condition, ■water changes from a vapor into a liquid, it gives
it can allow several ounces of refrigerant to seep out off heat which goes into the refrigerant and
each year through its pores. Since this leakage is decreases the amount of heat the refrigerant can
spread throughout over the length of the hose, it is absorb from the air in the cabin.
difficult to detect.
PURGING THE SYSTEM
If a leak is found, the system should be evacuated Any time the system is to be opened, all of the
and the leak repaired. The compressor oil should be refrigerant must be purged. To accomplish this, the
checked whenever the system is evacuated. manifold set is connected into the system with both
valves closed, and the center hose attached to the
A performance test is used to determine how well recycling/recovery equipment. Environmental
the system is functioning. The manifold set should Protection Agency (EPA) regulations require that all
be connected into the system with both valves CFC-12 refrigerants and substitute refrigerants be
closed. Run the engine at approximately 1,250 rpm, reclaimed when servicing air conditioning equip-
with the air-conditioning controls set for maximum ment. When the system is empty, it may be opened.
cooling. Place a thermometer into the evaporator as Any time a system is opened, all of the lines should
near the coil as possible, and then turn on the be capped to prevent the entry of water vapor, dirt
blower to low or medium speed. [Figure 14-52] or foreign matter.

CHECKING COMPRESSOR OIL


In order to check the oil, the system should be oper-
ated for at least fifteen minutes, then completely
evacuated. When there is no pressure in the system,
remove the oil filler plug from the compressor and
use a special oil dipstick made according to draw-
ings furnished by the airframe manufacturer. A
range of oil level is indicated in the compressor ser-
vice manual, and it should not be allowed to go
below the minimum level, nor should it be filled
above the maximum. [Figure 14-53]

Figure 14-52. Part of the performance test of the air-condi-


tioning system is to measure the temperature of the
output air.

After the system has operated for a few minutes, the


low-side gauge should read between 20 and 30 psig,
and the high-side gauge should read in the range of
225 to 300 psig. The evaporator temperature should
be somewhere around 40108 to 50108 Fahrenheit.

Touch can also used to determine that the system is


operating normally. If the system is operating cor-
rectly, there should be no appreciable temperature
difference between the inlet and the outlet side of
the receiver-dryer; both sides should be warm to the
touch. All of the lines and components in the high
side of the system should be warm, and all of the
lines and components in the low side of the system Figure 14-53. The correct amount of compressor oil is
should be cool. essential for proper functioning of the compressor.
14-46 Cabin Atmosphere Control
Only oil recommended by the compressor manufac- With the manifold set connected in the system, a
turer should be used, and should be kept tightly recovery/recycling/vacuum unit is attached to the
capped at all times it is not being used. After the center hose. The low-side manifold valve should be
proper amount of oil has been added to the system, the opened and the gauge should indicate a vacuum.
filler plug should be replaced and the system charged. After pumping for about five minutes, the high-side
gauge should indicate somewhat below zero, but the
SYSTEM EVACUATION high range of this gauge will prevent any readable
Any time an air-conditioning system has been indication. After about fifteen minutes, the system
opened, it must be evacuated before it is recharged. should be down to around 25 inches of mercury
Evacuating the system simply means "pumping gauge pressure, but the pump should be run for at
the system down" by attaching a recovery/recy- least thirty minutes, and longer if possible. After
cling/vacuum unit to the system and lowering the closing both manifold valves, the recovery/recy-
pressure so any water in the system will turn into a cle/vacuum unit should be removed, and the pro-
vapor and be drawn out. tective caps replaced on the pump fittings.

Water boils at 212110 F at the standard sea level CHARGING THE SYSTEM
pressure of 29.92 inches of mercury absolute With the system still under vacuum from the evacu-
(zero inches of mercury, gauge pressure). If the ation process, both valves should be closed on the
pressure is lowered 27.99 inches of mercury, gauge manifold set and the refrigerant source connected to
pressure (1.93" ABS) the water will boil at 100110 the center hose. The high-side valve is then opened
F. At 0.52 inches of mercury, gauge pressure (ABS), and the low-side gauge observed. As refrigerant
it will boil at 60110 F. And, at 0.04 inches of flows into the system, the low-side gauge should
mercury, gauge pres-sure(ABS), it will boil at 0110 come out of a vacuum, indicating that the system is
F. [Figure 14-54]
Figure 14-54. This chart shows the boiling point of water at low absolute pressures (deep vacuum).
Cabin Atmosphere Control 74-47
clear of any blockage and is taking the charge of
refrigerant. [Figure 14-55]

Both manifold valves are then closed and the engine


started and run at about 1,250 rpm. The air-condi-
tioning controls should be set for full cooling. With
the R-12 container upright so vapor will come out, the
low-side valve is opened to allow the vapor to enter
the system. When the low-side pressure is down to
below 40 psig, the can may be inverted and liquid
allowed to enter the system. At this pressure, the liq-
uid will turn into a vapor before it enters the com-
pressor and will do no damage. NOTE: Do not invert
the can if the outside air temperature is below 80113
F. All of the R-12 may not be vaporized by this cool
air.

The system should be charged with as many pounds


of refrigerant as called for by the system specifica-
tions. A full charge will be indicated by the absence
of bubbles in the sight glass in the receiver-dryer.
Usually an additional quarter- or half-pound of
Figure 14-55. This air-conditioning system is being charged
refrigerant is added after the bubbles stop. When the from a can of R-12.
charge is completed, the manifold valve is closed
and performance tests performed.

Das könnte Ihnen auch gefallen