Product data sheet MCset4-OG-S

Characteristics MCset with SF6 SF CB up to 24kV, 2500A,


31.5kA 3s - Outgoing

Main

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range of product MCset
Device short name Mcset 4
Product or component type Incomer outcomer cubicle
Circuit breaker application Secondary main breaker
Network frequency 50/60 Hz
[Ur] Rated voltage 24 kV
[Ud] Insulation voltage power 28 kV 50 Hz 1 min
frequency 38 kV 50 Hz 1 min
20 kV 50 Hz 1 min
[Up] Insulation voltage lightning 125 kV peak
impulse withstand
Bus rated current 2500 A
1250 A
[Ir] Rated current 1250 A
630 A
2500 A
[Ik] Short time withstand current 25 kA for 3 s
31.5 kA for 3 s
IP degree of protection IP4X
IP3x
IPx1
Electrical connection Cable - 1 x 630...3 x 630 mm² single core per phase
Cable - 1 x 240...3 x 240 mm² three core per busbar
Product weight 1200 kg
800 kg
Height 2325 mm
Width 900 mm
Depth 1750 mm

Complementary
Internal arc classification Internal arc class AFL
Internal arc class AFLR
Internal arc protection 25 kA 1 s
31.5 kA 0.15 s
Additional device type Relay SEPAM
Relay MiCOM
May 10, 2019
1
Relay Easergy P3
Power meter PowerLogic PM200
Power meter PowerLogic PM800
Power meter Eon
Monitoring function Pressure monitoring SF6 gas
Local signalling LED for presence of voltage
Arc fault detector option Yes vamp - (ordered separately)

Environment
Standards IEC 62271-200
Type of installation Indoor installation
Ambient air temperature for operation -5...40 °C
Operating altitude <= 1000 m