DETAIL NUMBER
2
SECTION LETTER
A
SCALE : NONE
(WALL TYPE)
(WALL TYPE)
LIMIT OF DEMOLITION
SCALE : NONE
SYMBOL IS MISSING)
VD
FD
FIRE DAMPER
BDD
SCALE : NONE
SCALE : NONE
[6.4x31.4mm]
IRON PIPE STRAP
EXTERIOR WALL
HIGH DENSITY
POLYETHYLENE (HDPE)
1/4"x1 1/4" SLEEVE WITH INTEGRAL
[6.4x31.4mm] HOLLOW MOLDED WATER
IRON PIPE
STOP RING 4" [100mm]
CLAMP LARGER THAN OUTSIDE
DIAMETER OF PIPE
[100mm]
5/8" [16mm]∅
4"
ROD
SCALE : NONE
REMOVABLE COVER
VARIES
SCALE : NONE
3/4"
SLOPE
TRENCH IN BUILDING
1. COORDINATE TRENCH DETAIL
GREATER THAN 24"[600mm]
WITH ARCHITECTURAL &
STRUCTURAL.
2 - SUPPORTS UP TO 24" [600mm] SPAN
2. REFER TO SPECIFICATION,
DESIGNER'S NOTE:
COORDINATE TRENCH DETAIL WITH ARCHITECTURAL & STRUCTURAL.
SD230511-27.DWG
STEAM LINE CONDENSATE
RETURN LINE
SCHEDULE
ANCHOR INSTALLATION
STEAM/CONDENSATE PIPING IN TRENCH
# NTS
SCALE : NONE
FLEXIBLE
MECHANICAL
COUPLING
ANCHOR (TYPICAL)
SEISMIC d
d
JOINT
DETAIL "A"
(STEEL PIPE FOR WATER/GLYCOL)
NOTE:
1. SEISMIC SEPARATION ASSEMBLY DETAIL SHOWN IN NFPA 13 (SPRINKLER PIPING),
UTILIZING FLEXIBLE MECHANICAL COUPLINGS, MAY BE USED IN LIEU OF PIPING DETAIL
SHOW ABOVE.
- - - - - - - - -
- - - - - - - - -
DESIGNER'S NOTE:
1. THIS CONFIGURATION SHOWN IN THIS DETAIL IS A SUGGESTED ARRANGEMENT, NOT
MANDATED FOR USE IN AS IS CONDITION. THE REGISTERED PROFESSIONAL STRUCTURAL
ENGINEER IN CHARGE OF THE PROJECT SHALL PROVIDE SEISMIC CALCULATIONS AND
MODIFY THE CONFIGURATION AS NEEDED TO MAKE THE ARRANGEMENT PROJECT-SPECIFIC.
THE MECHANICAL DESIGNER SHALL COMPLETE THE BLANK SCHEDULES BY INSERTING THE
DISTANCES, TO BE CALCULATED AND FURNISHED BY PROVIDED BY THE REGISTERED
PROFESSIONAL STRUCTURAL ENGINEER.
SCALE : NONE
RISE UP
12" [300mm]
MINIMUM
HANGER (CLOSE
TO ELBOW)
d ANCHOR ANCHOR
SEISMIC
JOINT
f f
DETAIL "B"
(PLASTIC PIPE FOR PRESSURIZED SYSTEMS)
- - - - - - -
- - - - - - -
DESIGNER'S NOTE:
1. THIS CONFIGURATION SHOWN IN THIS DETAIL IS A SUGGESTED ARRANGEMENT, NOT
MANDATED FOR USE IN AS IS CONDITION. THE REGISTERED PROFESSIONAL STRUCTURAL
ENGINEER IN CHARGE OF THE PROJECT SHALL PROVIDE SEISMIC CALCULATIONS AND
MODIFY THE CONFIGURATION AS NEEDED TO MAKE THE ARRANGEMENT PROJECT-SPECIFIC.
THE MECHANICAL DESIGNER SHALL COMPLETE THE BLANK SCHEDULES BY INSERTING THE
DISTANCES, TO BE CALCULATED AND FURNISHED BY PROVIDED BY THE REGISTERED
PROFESSIONAL STRUCTURAL ENGINEER.
SCALE : NONE
6" [150mm]
A
HANGER
d
ANCHOR
SEISMIC
JOINT
e
e
DETAIL "C"
(COPPER PIPE)
6" [150mm]
COPPER PIPE
4" [100mm]
MINIMUM RISE
FLEXIBLE HOSE
SECTION "A-A"
- - - - - - - -
- - - - - - - -
DESIGNER'S NOTE:
1. THIS CONFIGURATION SHOWN IN THIS DETAIL IS A SUGGESTED ARRANGEMENT, NOT
MANDATED FOR USE IN AS IS CONDITION. THE REGISTERED PROFESSIONAL STRUCTURAL
ENGINEER IN CHARGE OF THE PROJECT SHALL PROVIDE SEISMIC CALCULATIONS AND
MODIFY THE CONFIGURATION AS NEEDED TO MAKE THE ARRANGEMENT PROJECT-SPECIFIC.
THE MECHANICAL DESIGNER SHALL COMPLETE THE BLANK SCHEDULES BY INSERTING THE
DISTANCES, TO BE CALCULATED AND FURNISHED BY PROVIDED BY THE REGISTERED
PROFESSIONAL STRUCTURAL ENGINEER.
SCALE : NONE
HANGER
FLEXIBLE BALL
HANGER
c JOINT HANGER
SEISMIC
JOINT
d d
- - - - - - -
- - - - - - -
DESIGNER'S NOTE:
1. THIS CONFIGURATION SHOWN IN THIS DETAIL IS A SUGGESTED ARRANGEMENT, NOT
MANDATED FOR USE IN AS IS CONDITION. THE REGISTERED PROFESSIONAL STRUCTURAL
ENGINEER IN CHARGE OF THE PROJECT SHALL PROVIDE SEISMIC CALCULATIONS AND
MODIFY THE CONFIGURATION AS NEEDED TO MAKE THE ARRANGEMENT PROJECT-SPECIFIC.
THE MECHANICAL DESIGNER SHALL COMPLETE THE BLANK SCHEDULES BY INSERTING THE
DISTANCES, TO BE CALCULATED AND FURNISHED BY PROVIDED BY THE REGISTERED
PROFESSIONAL STRUCTURAL ENGINEER.
SCALE : NONE
HANGER
FLEXIBLE
b CONNECTOR
HANGER
c
HANGER
SEISMIC
JOINT
e
e
ANCHOR ANCHOR
DETAIL "E"
(STEEL PIPE FOR WATER)
- - - - - - - - -
- - - - - - - - -
DESIGNER'S NOTE:
1. THIS CONFIGURATION SHOWN IN THIS DETAIL IS A SUGGESTED ARRANGEMENT, NOT
MANDATED FOR USE IN AS IS CONDITION. THE REGISTERED PROFESSIONAL STRUCTURAL
ENGINEER IN CHARGE OF THE PROJECT SHALL PROVIDE SEISMIC CALCULATIONS AND
MODIFY THE CONFIGURATION AS NEEDED TO MAKE THE ARRANGEMENT PROJECT-SPECIFIC.
THE MECHANICAL DESIGNER SHALL COMPLETE THE BLANK SCHEDULES BY INSERTING THE
DISTANCES, TO BE CALCULATED AND FURNISHED BY PROVIDED BY THE REGISTERED
PROFESSIONAL STRUCTURAL ENGINEER.
SCALE : NONE
+My
STEAM NOZZLE
+Mz
+Mx
+Fx
+Fz
ISOMETRIC VIEW
BOILER NO. Fx Fy Fz Mx My Mz
BOILER Fx Fy Fz Mx My Mz
NO.
LB [Kg] LB [Kg] LB [Kg] FT LB [J] FT LB [J] FT LB [J]
------
--[--]--[--]--[--] --[--] --[--] --[--]
NOTES:
1. BOILERS SHALL BE DESIGNED TO WITHSTAND THE
FORCES AND MOMENTS SHOWN ABOVE.
SCALE : NONE
N
I VE EN
T
DR M
U IP
EQ
NUMBER OF ISOLATION
UNITS AS REQUIRED
TYPE"B"
WELDED STEEL BASE
SPRING
ISOLATOR
SECTION A-A
MO
T
SH OR
AF
T A
EN T
IV EN
DR M
U IP
EQ A
NUMBER OF ISOLATION
UNITS AS REQUIRED
TYPE "1"
CONCRETE INERTIA BASE
SCALE : NONE
FAN DISCHARGE
FLEXIBLE DUCT
CONNECTIONS
FAN SECTION
VIBRATORS ISOLATORS
AS SCHEDULED OR
SPECIFIED
COIL SECTION
OR DISCHARGE THRUST RESTRAINT
DUCT
TYPE "THR"
NOTES:
1. ATTACH THRUST RESTRAINTS SYMMETRICALLY ON BOTH SIDES OF THE FAN
DISCHARGE.
2. ADJUST RESTRAINT TO ALLOW 1/4" [6 mm] MOVEMENT OF FAN AT START
AND STOP.
DESIGNER'S NOTE:
ON THE VIBRATION ISOLATION SCHEDULE OR UNDER THE TITLE OF THIS DETAIL
DESIGNATE FANS REQUIRING RESTRAINT. THIS IS USUALLY SEPARATELY MOUNTED
FAN SECTIONS FOR STATIC PRESSURE OVER 4" [100 mm] AND POSSIBLY FOR
AXIAL FLOW FANS FOR STATIC PRESSURE OVER 4" [100 mm].
SCALE : NONE
[25mm]
1"
PIPE SLEEVE (5D, 3"
5D
A
[75mm] MIN.)
B B 2D
W
FLOOR
A
5D
CONCRETE BASE WELD HEAD TO PLATE
OR BEND OVER END 5D
PLAN
SECTION B-B
16"
[400mm]
[125mm]
5" MIN.
L/10
PROVIDE DOUBLE SLAB
REINFORCING IN BASE AREA
[125mm]
5" MIN.
L/10
DESIGNER'S NOTE:
THIS DETAIL IS PRIMARILY FOR PUMPS WITHOUT ISOLATORS. COORDINATE DETAIL
WITH ARCHITECTURAL AND STRUCTURAL.
SCALE : NONE
BONDED STEEL
CLAMP
PLATE
SCALE : NONE
LOCK
NUTS
FLOOR
(TYP)
EQUIPMENT WEIGHT
250 LBS. [114KG] OR
LESS
RESILIENT PAD
SD230541-04.DWG
STEEL EXPANSION SHIELD FOR EXISTING
CONSTRUCTION AND INSERTS FOR NEW
CONSTRICTION THIS TYPE SHALL BE
USED ONLY IN SLABS OR BEAMS OF 4"
[100mm] MIN DEPTH
CONCRETE
3/8" [10mm] MIN DIA EXPANSION
FLOOR SLAB BOLTS FOR EXISTING CONSTRUCTION
AND INSERTS FOR NEW CONSTRUCTION
CLIP
3/8" [10mm] MIN
ANGLE DIA INSERTS NEW
CONSTRUCTION ONLY.
SCALE : NONE
DUCT
CEILING DIFFUSER
OR REGISTER
SIDE VIEW END VIEW
COLLAR DIA.
WIDTH OR LENGTH
DUCT
CEILING DIFFUSER
OR REGISTER
SIDE VIEW END VIEW
DESIGNER NOTES:
1.SHOW LOCATION ON FLOOR PLANS
SCALE : NONE
DIFFERENTIAL PRESSURE
BLOWDOWN
ELEVATION
NOTES:
SCALE : NONE
CW OR
SW
N.C.
WATER METER
80 MESH
STRAINER
3'-6"
SUPPORT BRACKET
ANCHORED TO WALL OR
[1.1M]
FLOOR
COLUMN
ELEVATION
SCALE : NONE
RETURN
EXHAUST AIR RETURN FAN PSL AIR
AFMD
D-3 ZC
TT HT
VFD HS
ZC
SPD
PRESSURE SWITCH HIGH
D-4 SST TO DISABLE FAN WHEN HIGH PRESSURE
AIA
FT DPS
DPS DPS LIMIT SETPOINT IS REACHED SUPPLY AIR TO
MINIMUM DIFFUSER TERMINAL UNIT
OUTSIDE SECTION
COMM SD 10' MIN.
AIR
AFTER - FILTER
FINAL FILTER
COIL PREHEAT
PSH HT
SPS
OUTSIDE TT FT
SCALE : NONE
TT TSL TT TT
AIR T-1
T-5 TSL-1 T-3 T-6 SD
CS HHL
IT
D-1 SMOKE
2C
ZC SST DETECTOR
MPS VFD HS V-3
HOT GLYCOL V-2
TT WATER, HOT CHS ONLY WHERE REQUIRED STEAM HUMIDIFIER
V-1
WATER OR 2C V-4
T-2
ELECTRIC COILS
CHR VARIABLE FREQUENCY
ARE LPS
SPD
DRIVE, TYP.
LOCATE SENSOR PERMISSIBLE
OUTSIDE UNDER SUBSTITUTES
SHIELD
VARIABLE AIR VOLUME AIR HANDLING UNIT WITH MINIMUM OUTSIDE AIR CONTROL DIAGRAM
# NTS
ROOM ELECTRIC
EXHAUST FAN UNIT HEATER
D1 PLENUM INTAKE
T T T LOUVER
EMERGENCY
GENERATOR
ACD
NOTES:
1. EMERGENCY GENERATOR SHALL BE INTERLOCKED WITH D3. WHEN EMERGENCY
GENERATOR IS ENERGIZED D3 SHALL OPEN. WHEN EMERGENCY GENERATOR IS
DE-ENERGIZED D3 SHALL CLOSE, PROVIDED ROOM EXHAUST FAN IS OFF.
2. ROOM EXHAUST FAN SHALL BE INTERLOCKED WITH D3 & ROOM THERMOSTAT T1.
WHEN ROOM THERMOSTAT RISES ABOVE 85°F [29°C] ROOM EXHAUST FAN SHALL RUN
& D3 SHALL OPEN. WHEN ROOM THERMOSTAT DROPS BELOW 80°F [27 C] ROOM
EXHAUST FAN SHALL STOP & D3 SHALL CLOSE, PROVIDED EMERGENCY GENERATOR
IS DE-ENERGIZED.
45°F [7.2°C]. ON A DROP IN ROOM TEMPERATURE BELOW 43°F [6.1°C] ELECTRIC UNIT
HEATER SHALL BE ENERGIZED & ON A RISE IN ROOM TEMPERATURE ABOVE 47°F [8.3°C].
DESIGNER'S NOTES:
1. IF THE PROJECT INVOLVES MULTIPLE EMERGENCY GENERATORS, EACH GENERATOR
SHALL HAVE A DEDICATED SECTION OF THE OUTSIDE AIR INTAKE LOUVER & DAMPER
2. WHEN THE ROOM EXHAUST FAN IS RUNNING ALONE, WITHOUT ANY EMERGENCY
GENERATOR, ONLY A DESIGNATED PORTION OF THE OUTSIDE AIR INTAKE LOUVER
SHALL OPEN. THE DESIGNER SHALL SHOW THIS SECTION ON THE FLOOR PLANS.
SCALE : NONE
M
HOIST WAY VENT DAMPER
TWO POSITION, N.O.
TO LOCAL 120 V
POWER
SPACE SMOKE
DETECTOR*
LOCATED AT TOP TO FIRE ALARM CONTROL
OF HOISTWAY PANEL (FACP)*
SD TO FIRE ALARM* &
INITIATE PHASE 1 RECALL
*BY ELECTRICAL
ECC
NOTES:
1. THE DAMPER SHALL REMAIN CLOSED DURING NORMAL OPERATION AND OPEN UPON
LOSS OF POWER FROM A SIGNAL FROM THE SMOKE DETECTOR, LOCATED AT THE
TOP OF THE HOISTWAY. COORDINATE NUMBER OF CONTACTS WITH THE ELECTRICAL
AND FIRE PROTECTION DESIGNS.
DESIGNER'S NOTES:
1. THE AREA OF VENTS SHALL NOT BE LESS THAN 3.0% OF THE TOTAL HOISTWAY
AREA OR 3 SQUARE FEET (0.28 SQUARE METERS) FOR EACH ELEVATOR CAR,
WHICHEVER IS GREATER.
SCALE : NONE
DUCT TRANSITION
SMOKE DAMPER (N.C.)
AS REQUIRED SEE SCHEDULE
AIR
SD AIRFLOW DUCT
AD
TO FIRE
ALARM CONTROL PSH
PANEL (FACP)
120V
ZS M ELECTRICAL
2 POSITION POWER
BINARY POINT
PRESSURE SWITCH HIGH
TO SHUT DOWN FAN UPON
DAMPER POSITION
REACHING HIGH PRESSURE
FEEDBACK TO
SETPOINT
ECC
NOTE:
UPON DETECTION OF SMOKE BY THE SMOKE DETECTOR, THE SMOKE DAMPER SHALL
CLOSE & SEND AN ALARM TO THE ECC.
DESIGNER'S NOTE:
PROVIDE A DAMPER AND DETECTOR ONLY FOR PARTIALLY SPRINKLERED BUILDINGS
WHEN EITHER SIDE OF SMOKE PARTITION IS NOT SPRINKLED AND PROTECTED BY
QUICK RESPONSE SPRINKLER HEADS.
SCALE : NONE
GRAVEL (ALL
AROUND) 3" [75mm]
CONCRETE #4 REBAR TOP
AND BOTTOM
(SQUARE)
ACCESS COVER INTEGRAL DRAIN VALVE WITH
FILL BOX -
GRADE COMPRESSED
V
FOAM BOARD
TANK
FOR TYPICAL PIPE
SCALE : NONE
HOLD-DOWN
STRAPS
HANGER SOUNDING ROD
OVERFILL
PREVENT ON
GAGE
12" VALVE
FOR
FILL
FOS
TURN-BUCKLE
THICK, 12"
[304mm] SQ 6"
12" STEEL (TYP.)
[150mm]
[300mm]
STORAGE TANK
# NTS
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
ELEVATION ELEVATION
THREADED PIPING WELDED PIPING
MV
AIR VENT OR
1/4" [8mm]
AV
ELEVATION
NOTES:
TYPICAL MANUAL AIR VENT
1. VENT ALL HIGH POINTS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.
(HYDRONIC SYSTEMS)
SCALE : NONE
PITCH DOWN
TOWARD DRAIN
CLEAN OUT
A
DRAIN
PAN
[25mm]
B
1"
DIELECTRIC
FITTING
FLOOR SINK
UNIT TYPE A B
SCALE : NONE
(TYPICAL)
(TYPICAL)
H
SUPPLY
PLAN
EXPANSION LOOP
LOOP NO. W H
SCALE : NONE
(TYP.) MV
WATER RETURN
COIL
WATER SUPPLY
DESIGNER'S NOTE:
1. THIS DETAIL IS APPLICABLE TO: 2-PIPE FAN COIL UNITS (CHILLED OR HOT WATER)
○ VAV/CV AIR TERMINAL UNITS ( REHEAT COIL)
○ DUCT-MOUNTED REHEAT COIL
○ CABINET UNIT HEATERS
SCALE : NONE
1 1/2" [40mm]
FULL PORT BALL
VALVE
1 1/2"∅x2" LONG
[40x50mm] PIPE
1 1/2" [40mm]
9
0
°
PLUG
WELD (TYP)
NOTE:
DESIGNER'S NOTE:
SCALE : NONE
PRESSURE GAGE
1/2" [15mm]
BALANCING
DEVICE
FLEXIBLE STRAINER
CONNECTION
BALL OR
BUTTERFLY
TYP.
NOTES:
DESIGNER'S NOTE:
1. CHECK VALVE IS OPTIONAL FOR SINGLE PUMP, EXCEPT FOR COOLING TOWER PUMP.
2. ELIMINATE BALANCING DEVICE WHEN PUMP CONTROLLED BY VARIABLE SPEED DRIVE.
SCALE : NONE
BUTTERFLY OR BALL
INSTALL HANGER AS CLOSE
TO PIPE ELBOW AS POSSIBLE SHUT OFF VALVE, TYP.
(TYPICAL)
OPTIONAL STRAINER
PRESSURE GAUGE
CHECK VALVE
DRAIN
VIBRATION ISOLATOR
CONCRETE INERTIA
(TYPICAL)
BASE 1" [25mm] MIN.
DIA. PIPE STAND
NOTES:
SEE SPECIFICATION SECTION "PUMPS" FOR Y STRAINER OPTION
DESIGNER'S NOTE:
CHECK VALVE IS OPTIONAL FOR SINGLE PUMP, EXCEPT FOR COOLING TOWER PUMP.
SCALE : NONE
HANGER HANGER
BUTTERFLY OR BALL
INSTALL HANGER AS CLOSE
SHUT OFF VALVE, TYP.
TO PIPE ELBOW AS
PRESSURE
GAGE
1/2" [15mm]
1/2" [15mm]
SUCTION DIFFUSER
FLOOR DRAIN
CONCRETE BASE
(SEE DETAIL)
NOTES:
SEE SPECIFICATION SECTION "PUMPS" FOR Y STRAINER OPTION
DESIGNER'S NOTE:
1. CHECK VALVE IS OPTIONAL FOR SINGLE PUMP, EXCEPT FOR COOLING TOWER
PUMP. USE THIS DETAIL ONLY FOR PUMPS IN A MECHANICAL BUILDING WHERE
POSSIBLE VIBRATION WILL NOT BE OBJECTIONABLE AND WHERE APPROVED BY VA.
SCALE : NONE
RIGID PIPE
HANGER
(TYPICAL)
BUTTER OR BALL
INSTALL HANGER AS CLOSE TO PIPE
SHUT OFF VALVE, TYP.
ELBOW AS POSSIBLE (TYPICAL)
CHECK VALVE
OPTIONAL STRAINER
PUMP
SUCTION DIFFUSER WITH
BUILT-IN STRAINER
1" [25mm] MIN. DIA.
PIPE STAND
DRAIN
FLOOR
NOTE:
SEE SPECIFICATION SECTION "PUMPS" FOR Y STRAINER OPTION.
DESIGNER'S NOTE:
CHECK VALVE IS OPTIONAL FOR SINGLE PUMPS, EXCEPT FOR COOLING TOWER PUMP.
SCALE : NONE
RIGID PIPE
HANGER
(TYPICAL)
CHECK VALVE
1/2" [15mm]
DRAIN
FLOOR
NOTES:
SEE SPECIFICATION SECTION "PUMPS" FOR Y STRAINER OPTION.
DESIGNER'S NOTE:
1. CHECK VALVE IS OPTIONAL FOR SINGLE PUMP EXCEPT FOR COOLING TOWER PUMP. USE
THIS DETAIL ONLY FOR PUMPS IN A MECHANICAL BUILDING WHERE POSSIBLE VIBRATION
WILL NOT BE OBJECTIONABLE AND WHERE APPROVED BY VA.
2. COUPLINGS SHALL NOT BE USED IN HOT WATER APPLICATIONS.
SCALE : NONE
RIGID PIPE
HANGER
AV AV
(TYPICAL)
INSTALL HANGER
AS CLOSE TO BUTTER OR BALL
PIPE ELBOW AS SHUT OFF VALVE, TYP.
POSSIBLE (TYPICAL)
NON SLAM CHECK VALVE
WITH COUNTER WEIGHT
1/2" [15mm]
ECCENTRIC REDUCER
FLEXIBLE CONNECTOR
TYP.
NOTE 3
FLOOR
3. ALL PAD, PUMP, AND PIPING DRAINS SHALL BE HARD PIPED TO NEAREST FLOOR DRAIN,
TYPICAL.
DESIGNER'S NOTE:
CHECK VALVE IS OPTIONAL FOR SINGLE PUMP EXCEPT FOR COOLING TOWER PUMP. USE THIS
DETAIL ONLY FOR PUMPS IN A MECHANICAL BUILDING WHERE POSSIBLE VIBRATION WILL NOT
BE OBJECTIONABLE OR WHERE APPROVED BY VA.
SCALE : NONE
TO PUMP SUCTION
1. SIZE WATER FILTER FOR
5% OF TOTAL SYSTEM
FLOW
PRESSURE
GAUGE 1/2" [15mm]
WATER
FILTER LOW POINT
DRAIN
DRAIN
CONNECTION
WATER FILTERS -
CLOSED LOOP HYDRONIC SYSTEMS
# NTS
DESIGNER'S NOTE:
1. PROVIDE SEDIMENT WATER FILTER ON EACH CHILLED WATER, HOT WATER AND GLYCOL
WATER HEATING SYSTEM. CAPACITY SHALL BE APPROXIMATELY 5% OF THE TOTAL
CIRCULATING FLOW. SHOW FILTER LOCATIONS ON THE DRAWINGS. INCLUDE THE FILTER
FLOW RATE IN PUMP CAPACITIES. SIZE PIPES TO WATER FILTER.
2. SELECT PRESSURE RANGE PER PROJECT NEED. SPECIFY PRESSURE RANGE ON DRAWINGS.
SCALE : NONE
CHEMICAL POT
FEEDER-
MINIMUM CAPACITY 5
1" [25mm] TO
DRAIN
TO PUMP SUCTION
FROM PUMP DISCHARGE
NOTE:
TOP OF CHEMICAL POT
FEEDER TANK SHALL NOT BE
DESIGNER'S NOTE:
1. SHOW LOCATION OF ALL CHEMICAL POT FEEDER TANKS ON PIPING DIAGRAMS
FOR EACH CHILLED WATER AND HEATING HOT WATER SYSTEM. FEEDER MAY
SCALE : NONE
LEVEL
REDUCED
CONDENSER WATER SUPPLY
PRESSURE
BACK FLOW (FROM TOWER)
~ PREVENTER SIDE STREAM SOLID
TREATMENT SYSTEM -
~
SEE M
RELIEF BYPASS PLUMBING
VALVE TYP. DWG
MAKE UP
MODULATING LEVEL METER
CONTROL VALVE
COOLING TOWER
SCALE : NONE
HS HS HS
CT
OPTIONAL
SIDE STREAM
SAMPLE
SEPARATOR
TYP.
CONDUCTIVITY
CONDENSERS
TRANSMITTER
TYP.
CHEMICAL FEED
CONTROLLER
(TO TOWER)
# NTS
SPECIFICATIONS AND DETAILS.
CWS
CWS
CONDENSER
WATER PUMP
SEE PUMP
SIDESTREAM SIDESTREAM
SCHEDULE
SEPARATOR SEPARATOR
AND DETAIL
CONDENSER
SOLIDS SOLIDS
RECOVERY RECOVERY
SEPARATOR SEPARATOR
CWS
CWS
FD FD
DESIGNER'S NOTE:
SCALE : NONE
NOTE:
2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE
REGARDLESS OF W DIMENSION.
3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2"
[40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
4. WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE
DOUBLE VANE TYPE.
SCALE : NONE
1/
EQUAL EQUAL EQUAL
1/3W
W 2W
OR BE OR BE OR BE
R GREATER 2/ GREATER GREATER
VANE
R
THAN W. VANE THAN THAN
3W
R
SCALE : NONE
STANDARD RADIUS OR
LONG RADIUS ELBOW
W W
RADIUS ELBOWS
2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS
ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE
CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
DESIGNER'S NOTE:
DO NOT SHOW MITERED ELBOWS AND MITERED OFFSETS (TRANSITIONS) GREATER THAN
15 DEGREES ON DRAWINGS.
SD233100-02.DWG
15°
MAX.
°
0 .
3 X
A
M ° .
5 X
AIR AIR 1 A
M
FLOW FLOW
°
EQUIPMENT
X.
15
MA
MA
15
X.
°
MAX
.
30°
TYPICAL DUCTWORK TRANSITION
TYPICAL DUCTWORK TRANSITION WITH PLAN OR SIDE VIEW
SCALE : NONE
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
SD233100-03.DWG
TURNING VANES VOLUME EXTRACTOR; ADJUSTABLE ADJUSTABLE
FROM FULLY CLOSED POSITION TO METAL ROD
SEE FLOOR PLAN FOR
CFM NOTED ON FLOOR PLANS OR LINKAGE
SPLIT DIMENSION
AIR
SUPPLY REGISTER TAKE-OFF
FLOW
PLAN VIEW
SCALE : NONE
SUPPLY REGISTER
OR BRANCH DUCT AIR
PLAN VIEW
1/4 W OR 4"
PROVIDE VOLUME
FLOW
DUCTWORK TAKE-OFFS
BRANCH DUCT TAKE-OFF PLAN VIEW
FPM [5.1 M/S] OR LESS. THE AIR SPLIT DUCT TAKE-OFF SHALL BE USED IN ALL
OTHER CASES AND MAY BE USED AT ANYTIME.
SD233100-04.DWG
2. SHOW ALL VOLUME DAMPERS ON FLOOR PLANS.
MAIN SUPPLY
45
°M
X.A
DUCT.
"
PLAN VIEW
SCALE : NONE
PLAN VIEW
SCALE : NONE
1/4W OR 4"
[100mm] MIN.
VD
PROVIDE VOLUME DAMPER
BRANCH DUCT AT EACH BRANCH DUCT
PLAN VIEW
DESIGNER'S NOTE:
SCALE : NONE
INSULATION
STAND-OFF
DAMPER BLADE
HANDLE WITH
LOCKING
QUADRANT
INSIDE END BEARING
1/8" [6mm]
CLEARANCE
NOTE:
SCALE : NONE
"A"
INSULATION
DUCT
GASKET
INSULATION
SECTION "A-A"
ACCESS PANEL
CASING
GASKET
HANDLE INSIDE
"B" "B"
INSULATION
FLEXIBLE
WASHER
SECTION "B-B"
ACCESS DOOR FACTORY
FABRICATED
NOTES: LATCH
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS
TIGHTLY.
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE
PINS.
3. SEE SMACNA 2005, FIGURE 9-15
DESIGNERS NOTES:
1. USE ACCESS DOORS ON AIR HANDLING UNITS AND DUCTWORK INSTALLED IN EQUIPMENT
ROOMS.
2. USE ACCESS PANELS ON ALL EQUIPMENT AND DUCTWORK INSTALLED ABOVE FINISHED
CEILINGS.
SCALE : NONE
SCALE : NONE
WASHER
SHEET METAL AS 1 1/2" [40mm] MIN. TO 3" [75mm]
FLANGED SPECIFIED FOR
CONNECTION
MAX. INSTALLED. 6" [150mm]
DUCTWORK. NOMINAL WITH MATERIAL TAUT
ON FAN SIDE
SCALE : NONE
[25mm]
TYPICAL DUCT DAMPER COLLAR
1"
INSULATION EXTENSION INTEGRAL
PART OF SLEEVE
DAMPER,
NOTE 1
ACCESS
PANEL DUCT
NOTE 5 CONNECTION
NOTE 4
SLEEVE, NOTE 2
PERIMETER ANGLE, NOTE 3
(NOTE FASTENED TO PARTITION)
NOTE:
2. GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO
DAMPER FRAME AND TO PERIMETER ANGLES.
3. PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2" [40x40mm],
14 GAGE, TO PROVIDE 1" [25mm] MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.
4. BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.
ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR
LINKS.
5.
PROVIDE 1/4" TO 1/2" [6 TO 15mm] CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN
SPACE WITH ROCK WOOL FIRESTOP FIBER.
6.
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS
AND MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" [75mm] HIGH
7. CONCRETE CURB AROUND OPENING FOR DUCT.
SECTION THRU
FIRE DAMPER INSTALLATION
# NTS
SCALE : NONE
MINIMUM 3/8"
[10mm]∅
INSULATION
GALVANIZED ANGLE
IRON OR EQUIVALENT
STRENGTH CHANNEL
NOTE:
UP TO 26 [650] NONE
3. INSULATION: FOR COLD DUCTS INSULATE BRACES AND PROVIDE VAPOR BARRIER.
SCALE : NONE
SCALE : NONE
NOTE:
TABULATED DATA FROM SMACNA
ALLOWS FOR DUCT REINFORCING AND
BAND
DUCT HANGERS
DESIGNER'S NOTE:
DESCRIBE OR DETAIL UPPER ATTACHMENTS APPLICABLE TO PARTICULAR
PROJECTS.
SD233100-14.DWG
DUCT RISER - SEE FLOOR
PLANS FOR SIZES SHEET METAL SCREWS 4"
[100mm] ON CENTER
EXTEND ANGLE 3"
[75mm] BEYOND DUCT 1 1/2"x1 1/2"x1/8" [40x40x3mm]
ANGLE INSTALL ON BOTH LONG
DIMENSION SIDES OF DUCT. FOR
2"x2"x1/4" [50x50x6mm]
ANGLE INSTALL ON BOTH LONG
DIMENSION SIDES OF DUCT. FLOOR
NOTE:
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS
AND FAN ROOM FLOORS SHALL BE PROVIDED WITH A 3" [75mm] HIGH CONCRETE
CURB AROUND OPENING FOR DUCT.
DESIGNER'S NOTE:
INDICATE ON DRAWING THE DUCT PRESSURE CLASS 2" WG [500Pa] WG, 3" WG
[750Pa] OR 4" WG [100OPa].
SCALE : NONE
15
°
WELDED STAINLESS STEEL
AS REQUIRED
EXHAUST STACK
[3000mm]
10'-0" MIN.
TRANSITION
(AS REQUIRED)
F.C.
EXHAUST
FAN DRAIN,
1/2"
[15mm]
WELDED
COUPLING
BLANK PLATE
SECURE
SECURE GUY
STACK TO
ROOF WIRE TO
ROOF
SCALE : NONE
2"
[50mm]
CEILING REGISTER
NOTE:
SCALE : NONE
WIDTH
SEE NOTE 1
"A" LENGTH
CLG. SUPPORT
ANGLE-SEE
-
SEE NOTE 4 ARCHITECTURAL
SPECIFICATIONS
NORMAL 9'-0"
-
3/4"
1"x1/8"[25x6mm]
STIFFENING BAR- [20mm]
SEE NOTE 3
SECTION
"B-B"
NOTES:
1. HOODS SHALL BE STAINLESS STEEL, SEE SPECIFICATIONS. FOR HOOD SIZE &
LOCATION SEE EQUIPMENT SCHEDULE. FOR EXHAUST DUCT CONNECTIONS - SEE FLOOR
PLANS.
2. ALL HOODS SHALL BE 6'-6" [2m] ABOVE FINISHED FLOOR UNLESS OTHERWISE
NOTED. HOODS OVER URNS SHALL BE 7'-6" [2.3m] MINIMUM ABOVE FINISHED FLOOR.
3. HOODS OVER 6'-0" [1.9m] LONG WITH 2 OR MORE SECTIONS, SHALL HAVE INSIDE
STANDING SEAM AND 1"x1/8" [25x6mm] STIFFENING BAR - SEE SECTION "B-B".
4. EXTEND SIDE & END SHEET TO SUIT HIGH CEILING WHEN REQUIRED.
5. DETAIL SHOWS HOOD IN OPEN SPACE. WHEN HOOD IS INSTALLED AT WALL OR
PARTITION SECURE TO WALL OR PARTITION WITH EXPANSION BOLTS.
DESIGNER'S NOTE:
VERIFY ALL DIMENSIONS. SEE ARCHITECTURAL FLOOR PLANS FOR REQUIRED HOOD
LOCATIONS.
SCALE : NONE
MANUAL VOLUME
DAMPER
CEILING
WASHER DOOR
GLASSWARE WASHER
(SEE ARCHITECTURAL
FLOOR PLANS)
FLOOR
DESIGNER'S NOTES:
1. SEE VA STANDARD DETAIL 23 31 00-20 FOR CONSTRUCTION & INSTALLATION DETAILS.
2. COORDINATE HOOD DIMENSIONS AND EXHAUST AIR VOLUME SHOWN ON THE EQUIPMENT
DRAWINGS. EXHAUST AIR VOLUME SHALL BE BASED ON THE 100 FPM [.5 M/sec]
VELOCITY THRU THE FACE AREA OF THE HOOD.
SCALE : NONE
NOTE:1
NOTE 2
EXTERIOR
WALL
CMU WALL
[1400mm]
4'-8"
24"x24" [600mmx600mm]
BOLTED 1/2" [15mm]
STEEL ACCESS PANEL
DETAIL KEYNOTES:
SCALE : NONE
12"
SHEET METAL VOLUME DAMPER W/
SADDLE LOCKING QUAD
[300mm]
TYPICAL
DIFFUSER OR CEILING
REGISTER IN
LAY-IN CLG.
NOTE:
THE USE OF FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED
FOR THE DEDICATED AHU SERVING THE SURGICAL SUITE.
SCALE : NONE
SURGICAL
SUITE
SUPPLY
DIFFUSER
SYSTEM
HEPA FILTRATION
AIR VELOCITY
MAX. 400 FPM
ACCESS DOOR [2.0 M/sec]
MIN.24x36 4'-0"
[1200mm]
MIN. 2-POSITION
TERMINAL UNIT
ELBOW
WITH REHEAT
S.S.
DUCT
TU
RH
~
WELDED S.S. DRAIN PAN HWS
~
HWR
STEAM HUMIDIFIER
~
LPS
~
LPR
~
D
INDIRECT WASTE
TO FLOOR DRAIN
LOCATED IN CORRIDOR
NOTES:
1.ALL DUCTWORK IS STAINLESS STEEL
DESIGNERS NOTES:
1.PROVIDE 2 FULL CROSS SECTIONS THRU EACH OR.
SCALE : NONE
ROUND OR OVAL
INLET COLLAR
MINIMUM 2"
VOLUME EXTENSION
DAMPER
NOTES:
INLET COLLAR
PLENUM
LINEAR
DIFFUSER
CEILING
SCALE : NONE
ELECTRICAL
CONDUIT GUIDE
WOOD NAILING
STRIP CURB CAP
NOTE:
1. SECURE CURB CAP TO WOOD NAILING STRIP WITH 3/8" [10mm] CADMIUM PLATED
LAG BOLTS NOT OVER 12" [300mm] ON CENTER.
2. SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION BOLTS
(CONCRETE ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR JOIST
ROOF).
3. RUN ELECTRICAL LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY DAMPER,
THEN THROUGH VENTILATOR ELECTRICAL CONDUIT GUIDE.
DESIGNERS NOTES:
1.PROVIDE A MOTORIZED DAMPER, IF APPLICABLE.
SCALE : NONE
SEE NOTE 1
SEE NOTE 2
CURB CAP
ROOF
SEE NOTE 2
GRAVITY BACKDRAFT
DAMPER.
TRANSITION DUCT TO
FULL SIZE OF DAMPER
DUCT (WHEN SHOWN)
SUPPLIED WITH HOOD
NOTE:
1. SECURE HOOD TO WOOD NAILING STRIP WITH 3/8" [10mm] CADMIUM PLATED LAG
BOLTS NOT OVER 12" [300mm] ON CENTER.
2. SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION BOLTS
(CONCRETE ROOF) OR RUST RESISTANT BOLTS (MENTAL DECK & BAR JOIST
ROOF).
DESIGNER'S NOTE:
1.PROVIDE A MOTORIZED DAMPER, WHERE APPLICABLE.
2.MINIMUM CURB HEIGHT SHALL BE 12" [300 MM]. INCREASE HEIGHT, IF REQUIRED,
TO OVER COME SNOW DRIFT
SCALE : NONE
SD233600-01.DWG
P
P
S
F
U
L
AIR FLOW
P
AIR FLOW
AIR FLOW
AIR FLOW
O
R
P
W
E
(CFM)
(CFM)
(CFM)
(CFM)
H
F
E
L
A
O
T
W
E
R
H
F
E
E
L
H
A
O
E
T
W
A
L
T
F
O
L
W
F
O
CV CV CV CV
O
W
CFM CFM CFM CFM
SP SP SP SP
ROOM TEMPERATURE (°F) ROOM TEMPERATURE (°F) ROOM TEMPERATURE (°F) ROOM TEMPERATURE (°F)
CV BOX CONTROL SEQUENCE CV BOX CONTROL SEQUENCE CV BOX CONTROL SEQUENCE CV BOX CONTROL SEQUENCE
NO DEADBAND
NO DEADBAND
W/DEADBAND W/DEADBAND
CONTROL DIAGRAM
MODULATE TO MAINTAIN SET POINT + VALVE V-1 HAS BEEN MODULATED OPEN MODULATE TO MAINTAIN SET POINT +
SCALE : NONE
TE REHEAT TERMINAL UNIT
OPEN ABOVE 30% (ADJ) V-2 SHALL
COIL UNIT THEN BE MODULATED TO MAINTAIN SET
TE REHEAT
POINT + .5° F. THE ADJUSTABLE
COIL
TOLERANCE OF .5° F HAS BEEN
SELECTED TO PREVENT VALVE HUNTING.
TU AIR D. THE REVERSE SHALL OCCUR ON RISE
FLOW IN SPACE TEMPERATURE.
RHC TU AIR
HWS
FLOW
HWR FE
RHC
V-1 HWS
HWR FE
V-1
PC
V-2
TE
HWR
ROOM THERMOSTAT/SENSOR ROOM THERMOSTAT/SENSOR
WALL MOUNTED TE
SUPPLEMENTAL WALL MOUNTED
48" [1200mm] AFF. HEAT 48" [1200mm] AFF.
S
100% U
U
100% P
P
W
P
P
O
W
E
O
L
O
R
F
L
H
F
L
L
L
E
R
AIR FLOW
AIR FLOW
E
L
F
O
F
E
H
AIR FLOW
R
W
O
H
R
(CFM)
AIR FLOW
(CFM)
T
R
E
R
(CFM)
A
A
A
E
A
I
I
(CFM)
T
F
T
H
A
A
V
L
E
A
O
F
F
A
V
V
W
L
T
A
A
O
V
W
SP SP SP SP
ROOM TEMPERATURE (°F) ROOM TEMPERATURE (°F) ROOM TEMPERATURE (°F) ROOM TEMPERATURE (°F)
VAV BOX CONTROL SEQUENCE VAV BOX CONTROL SEQUENCE VAV BOX CONTROL SEQUENCE VAV BOX CONTROL SEQUENCE
NO DEADBAND
W/DEADBAND NO DEADBAND
W/DEADBAND
VAV DAMPER WILL MODULATE TO MINIMUM COOLING 75°F (ADJ) VAV DAMPER WILL MODULATE TO MINIMUM COOLING 75°F (ADJ)
POSITION. HEATING 70°F(ADJ) POSITION. HEATING 70°F(ADJ)
B. UPON FURTHER DROP IN SPACE DEADBAND OF 5° F BETWEEN HEATING AND B. UPON FURTHER DROP IN SPACE DEADBAND OF 5° F BETWEEN HEATING AND
TEMPERATURE VALVE V-1 WILL MODULATE COOLING SET POINTS WILL BE MAINTAINED. TEMPERATURE VALVE V-1 WILL MODULATE COOLING SET POINTS WILL BE MAINTAINED.
TO MAINTAIN SET POINT + .5° F. THE B. UPON FALL IN SPACE TEMPERATURE THE TO MAINTAIN SET POINT + .5° F. THE B. UPON FALL IN SPACE TEMPERATURE THE
ADJUSTABLE TOLERANCE OF + .5° F HAS VAV DAMPER WILL MODULATE TO MINIMUM ADJUSTABLE TOLERANCE OF + .5° F HAS VAV DAMPER WILL MODULATE TO MINIMUM
BEEN SELECTED TO PREVENT VALVE POSITION. BEEN SELECTED TO PREVENT VALVE POSITION.
CONTROL DIAGRAM
HUNTING C. UPON FURTHER DROP IN SPACE HUNTING C. UPON FURTHER DROP IN SPACE
SCALE : NONE
HUNTING. THE REVERSE SHALL OCCUR ON AND VALVE V-1 HAS BEEN MODULATED
AIR
A RISE IN SPACE TEMPERATURE. OPEN ABOVE 30% (ADJ). VALVE V-2
TE REHEAT AIR TERMINAL SHALL MAINTAIN SET POINT + .5° F. THE
COIL TERMINAL UNIT ADJUSTABLE TOLERANCE OF + .5°F HAS
TE
UNIT REHEAT BEEN SELECTED TO PREVENT VALVE
COIL HUNTING.
E. THE REVERSE SHALL OCCUR ON THE RISE
TU AIR IN SPACE TEMPERATURE.
FLOW AIR
TU
RHC FLOW
HWS
HWR RHC
FE HWS
V-1 HWR FE
V-1
PC
ATU HWS ATU
PC
CONTROLLER CONTROLLER
V-2
ROOM THERMOSTAT/SENSOR HWR
TE
WALL MOUNTED
ROOM THERMOSTAT/SENSOR
48" [1200mm] AFF. SUPPLEMENTAL
TE WALL MOUNTED
PC M
FT
T SST
TT
FILTER
S/A FAN R/A OR
ROOM THERMOSTAT/SENSOR RECIRCULATED
WALL MOUNTED 48"
[1200 MM] AFF.
SOUND
HWR BAFFLE
HWS
NOTES:
A. TERMINAL UNIT SHALL OPERATE ON A SCHEDULE SET BY THE ECC.
THE SERIES FAN SHALL RUN CONTINUOUSLY DURING OCCUPIED HOURS.
SCALE : NONE
SOUND ATTENUATOR
SEE EQUIPMENT
SCHEDULE
SEE NOTE 1 REHEAT COIL
SEE NOTE 2
SEE NOTE 3
AIR TERMINAL UNIT
SEE NOTE 4
(CV OR VAV)
SEE SPECIFICATIONS FOR
SCALE : NONE
PRESSURE
GAUGE
DDC
TEMPERATURE
SENSOR TO ECC
FLOW SWITCH
FLEXIBLE
CONNECTORS
IF REQUIRED
TT TEST PLUGS TT
FS
CHR CHS
EVAPORATOR
DESIGNER NOTE:
SCALE : NONE
SCALE : NONE
5. FOR PIPING 6" AND BELOW,
MECHANICAL COUPLINGS ARE OPTIONAL.
ABOVE 6", WELDED PIPE WITH FLANGES
IS THE ONLY APPROVED JOINING
PIPING CONNECTIONS
DEVICE
SPECIFIED
FLOOR
6" [150mm] HIGH
DRAIN
COOLED CHILLER -
CONCRETE PAD
FLOOR
DRAIN
(TYP.)
CONDENSER END EVAPORATOR END
SD236400-02.DWG
EQUALIZING
HOT WATER PIPING
BASIN TYP
MANUAL BALANCING
VFD VFD VFD
VALVE FURNISHING
WITH TOWER TYP.
SCREEN
INLET
TYP.
WATER LEVEL
TO
MODULATING 3" OVERFLOW
LEVEL
COLD WATER
CONTROL LC
BASIN TYP.
VALVE
M M M M M M
PI
MIN. 2" BALL
VALVE N.C.
TO
SANITARY
SEWER
SCALE : NONE
CONDENSATE
WATER SUPPLY
CONDENSATE
(FROM TOWER)
WATER RETURN
TO PUMP SUCTION
PIPING CONNECTIONS
PROVIDED WITH ITS OWN SUMP AND ANTI-CAVITATION PLATE.
DESIGNERS NOTES:
1.IF TOWER IS INSTALLED MORE THAN 5 FT [1500 MM] ABOVE THE ROOF OR
GRADE PROVIDE A PLATFORM AROUND THE PERIMETER.
2.PROVIDE ACCESS FOR ALL ELEVATED VALVES AND CONTROL DEVICES AND TO
EACH FAN MOTOR.
3.SEE HVAC DESIGN MANUAL.
4.COORDINATE WITH ELECTRICAL ON BASIN HEATER.
SD236500-01.DWG
HS
TT ECC HS
EXHAUST AIR
PUMP
SUPPLY AIR
NOTES:
1.TO PREVENT ICING ON EXHAUST COIL MAINTAIN TEMPERATURE OF SOLUTION ENTERING
EXHAUST AIR COIL > 35° F BY MODULATING 3 WAY VALVE.
(ADJUSTABLE)
3.FOR SYSTEMS WITH WINTER DESIGN CONDITIONS < 32° F, PROVIDE APPROPRIATE
PROPYLENE GLYCOL SOLUTION.
SCALE : NONE
SD237300-01.DWG
VA STANDARD DETAILS.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
SCALE : NONE
ACCESS SECTION,
6 YES YES YES YES
MED-LARGE
* HEAT RECOVERY COIL 7 NO NO YES YES
ACCESS SECTION,
* 8 NO NO YES YES
MED-LARGE
* PRE-HEAT COIL 9 YES YES YES YES
INSPECTION
* 10 YES YES YES YES
SECTION,SMALL
HUMIDIFIER 11 YES YES YES YES
COOLING COIL 12 YES YES YES YES
FAN 13 YES YES YES YES
NOTE:
* DIFFUSER PLATE 14 NO NO NO YES
ACCESS
* 15 NO NO YES YES 1. ACCESS DOORS SHALL BE GASKETED AND HINGED TO OPEN
SECTION,MED-LARGE AGAINST FAN OPERATING PRESSURE TO PREVENT AIR LEAKAGE.
* HEPA FILTER 16 NO NO NO YES 2. MINIMUM ACCESS DOOR WIDTH SHALL BE 24" [600mm].
DISCHARGE PLENUM 3. ACCESS DOOR HEIGHT SHALL BE DETERMINED BY UNIT CASING
* 17 YES YES YES YES
(VERTICAL) BUT NOT TO EXCEED 6'-0" [1800mm].
* AS REQUIRED 4. ACCESS DOORS ON FAN SUCTION SHALL OPEN OUTWARD.
5. ACCESS DOORS ON FAN DISCHARGE SIZE SHALL OPEN INWARD.
DESIGNER'S NOTES:
1. ALL AHU SECTIONS SHOWN IN THIS DETAIL MAY NOT BE APPLICABLE TO EACH AIR HANDLING UNIT INCLUDED IN THE PROJECT.
2. SEE DETAIL FOR AIR INTAKE FOR MISSION CRITICAL FACILITIES.
3. USING THIS FORMAT, DESIGNER SHALL DEVELOP A SIMILAR VIEW OF EACH AHU INCLUDED IN THE PROJECT. SELECTION OF THE AHU
SECTIONS SHALL BE APPLICATION SPECIFIC. EACH VIEW SHALL INCLUDE OVERALL DIMENSIONS AND AVAILABLE ACCESS SPACE FOR
EACH AIR HANDLING UNIT. NOTE THAT THESE VIEWS DO NOT NEGATE THE NEED TO PROVIDE CROSS-SECTIONS/ELEVATIONS OF THE
MECHANICAL ROOMS, SHOWING EQUIPMENT SECTIONS AND DETAILS OF EACH AHU.
FAN COIL SEQUENCE OF OPERATION (COOLING ONLY)
1. FAN COIL UNIT SHALL OPERATE ON A SCHEDULE AS SET BY THE DCC.
2. MODULATE V-1 TO MAINTAIN SPACE SET POINT AND FAN SHALL CYCLE W/TEMPERATURE.
3. ALARM IF SPACE TEMPERATURE OUTSIDE OF RANGES.
COOLING COIL
RA
FAN
FILTER
V-1
CHR SST
HS
CHS
PC
SHARED ARRANGEMENT IF FEASIBLE
TT T-1
DESIGNER'S NOTE
1. MODIFY THE DETAIL IF DCC IS NOT USED.
SCALE : NONE
2. MODULATE V-1 TO MAINTAIN SPACE SET POINT AND FAN SHALL CYCLE W/TEMPERATURE.
3. ALARM IF SPACE TEMPERATURE OUTSIDE OF RANGES.
HEATING COIL
RA
FAN
FILTER
V-1
HWR SST
ZC HS
HWS
PC
SHARED ARRANGEMENT IF FEASIBLE
TT T-1
DESIGNER'S NOTE
MODIFY DETAIL IF DCC IS NOT USED.
SCALE : NONE
SET POINT WILL BE 70°-75° WITH 0.5° HEATING/COOLING OFFSETS. VALVE V-1 & V-2
WILL NOT BE OPEN SIMULTANEOUSLY. ROOM OCCUPANT WILL HAVE ABILITY OF ADJUSTING
ROOM TEMPERATURE BETWEEN 70°-75°.
FAN
RA
CS
FILTER TT
SST
HS
V-1 V-2
HWR CHR
HWS CHS
PC
T T-1
SCALE : NONE
UNIT FAILS TO RUN. THE ROOM TEMP SETPOINT WILL BE 74° (ADJ). THE HOT WATER
VALVE WILL BE ENABLED AS REQUIRED TO MAINTAIN SPACE TEMP SETPOINT. HI/LO/OFF
SWITCH WILL ALLOW LOCAL FAN SPEED ADJUSTMENT.
CABINET UNIT
HEATER
HEATING COIL
FAN
FILTER
120V
STT
HS
HI
LO
EMCS
ENABLE OFF FAN MOTOR PC
V-1
HWR
T
T-1
HWS
DESIGNER'S NOTES:
1. CONNECT TO ECC NETWORK IS OPTIONAL.
2. PROVIDE NON-DDC CLOSED LOOP AUTOMATIC TEMPERATURE CONTROLS FOR THE HOT WATER
CABINET UNIT HEATER. COORDINATE THE INTERFACE, IF ANY, WITH THE DDC SYSTEM FOR
APPLICATIONS SUCH AS ALARM INDICATION WITH PROJECT SCOPE OF WORK.
SCALE : NONE
HWR
HWS
SCALE : NONE
TYPICAL CONNECTIONS TO
HORIZONTAL HOT WATER UNIT HEATER
AUTOMATIC FLOW R
TE
CONTROL VALVE WA
T N
AIR VENT HO TUR R
R E TE
TEST PLUG, MV
WA
T Y
TYP. HO PPL
UNIT HEATER S U
SHUTOFF BALL
VALVE, TYP.
WYE STRAINER,
TYP.
TYPICAL CONNECTIONS TO
VERTICAL HOT WATER UNIT HEATER
SCALE : NONE