Pressure sensors
Grundfos Direct Sensors™
Pressure sensors

1. Product overview 4
Table of contents

2. Product introduction 5

3. Relative Pressure transmitters, Industry (RPI and RPI+T) 6


General data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
RPI and RPI+T, 0 - 0.6 bar (0 - 8.7 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
RPI and RPI+T, 0 - 1.0 bar (0 - 14.5 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
RPI and RPI+T, 0 - 1.6 bar (0 - 23.2 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
RPI and RPI+T, 0 - 2.5 bar (0 - 36.3 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
RPI and RPI+T, 0 - 4.0 bar (0 - 58.0 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
RPI and RPI+T, 0 - 6.0 bar (0 - 87.0 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
RPI and RPI+T, 0 - 10.0 bar (0 - 145.0 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
RPI and RPI+T, 0 - 16.0 bar (0 - 232.1 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
RPI+T2, 0 - 16.0 bar (0 - 232.1 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
RPI and RPI+T, 0 - 25.0 bar (0 - 362.6 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

4. Differential Pressure transmitter, Industry (DPI I) 18


General data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
DPI, 0 - 0.6 bar (0 - 8.7 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
DPI, 0 - 1.0 bar (0 - 14.5 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
DPI, 0 - 1.2 bar (0 - 17.4 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
DPI, 0 - 1.6 bar (0 - 23.2 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
DPI, 0 - 2.5 bar (0 - 36.3 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
DPI, 0 - 4.0 bar (0 - 58.0 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
DPI, 0 - 6.0 bar (0 - 87.0 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
DPI, 0 - 10.0 bar (0 - 145.0 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

5. Differential Pressure transmitter, Industry (DPI II and DPI II+T) 27


General data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
DPI II and DPI II+T, 0 - 0.6 bar (0 - 8.7 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
DPI II and DPI II+T, 0 - 1.0 bar (0 - 14.5 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
DPI II and DPI II+T, 0 - 1.6 bar (0 - 23.2 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
DPI II and DPI II+T, 0 - 2.5 bar (0 - 36.3 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
DPI II and DPI II+T, 0 - 4.0 bar (0 - 58.0 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
DPI II and DPI II+T, 0 - 6.0 bar (0 - 87.0 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
DPI II and DPI II+T, 0 - 10.0 bar (0 - 145.0 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
DPI II and DPI II+T, 0 - 16.0 bar (0 - 232.1 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

6. Relative Pressure sensor Standard, RPS 37


General data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
RPS, 0 - 0.6 bar (0 - 8.7 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
RPS, 0 - 1.0 bar (0 - 14.5 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
RPS, 0 - 1.6 bar (0 - 23.2 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
RPS, 0 - 2.5 bar (0 - 36.3 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
RPS, 0 - 4.0 bar (0 - 58.0 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
RPS, 0 - 6.0 bar (0 - 87.0 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
RPS, 0 - 10.0 bar (0 - 145.0 psig) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
RPS, 0 - 16.0 bar (0 - 232.1 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

7. Differential Pressure sensor Standard, DPS 47


General data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
DPS, 0 - 0.6 bar (0 - 8.7 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
DPS, 0 - 1.0 bar (0 - 14.5 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
DPS, 0 - 1.6 bar (0 - 23.2 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
DPS, 0 - 2.5 bar (0 - 36.3 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
DPS, 0 - 4.0 bar (0 - 58.0 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
DPS, 0 - 6.0 bar (0 - 87.0 psid) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

8. Product range 55
RPI transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
DPI II and DPI II+T transmitter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
DPI I transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
RPS and DPS sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

2
Pressure sensors

9. Accessories 58

Table of contents
SI power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
M12 cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Capillary tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Adapter for Grundfos CR pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Snap-on cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
SI converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

10. Appendix 60
Installation of RPI and DPI II transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

11. Grundfos Product Center 61

3
Pressure sensors
1

1. Product overview
Product overview

This data booklet is for the latest version of Grundfos Direct Sensors™. Customers already buying Grundfos Direct
Sensors™ might be buying a sensor with another specification

Variant Description Technical data

RPI
Pressure range: 0 - 0.6 to 25 bar (0 - 8.7 to 363 psig)
System pressure range: Maximum 30 bar (453 psig)
Relative Pressure transmitter, Industry System temperature: -30 to +120 °C (-22 to +248 °F)
• stainless-steel housing. Signal: 4-20 mA (2-wire)
Power supply: 12.5 - 30 VDC
Enclosure class: IP67

RPI+T Pressure range: 0 - 0.6 to 25 bar (0 - 8.7 to 363 psig)


Temperature range: 0-120 °C (32-248 °F)
Relative Pressure transmitter, Industry System pressure: Maximum 30 bar (453 psig)
• combined pressure and temperature measurement System temperature: -30 to +120 °C (-22 to +248 °F)
• stainless-steel housing. Signal: 2 x 0-10 VDC (4-wire)
Power supply: 16.6 - 30 VDC
Enclosure class: IP67

DPI
Differential pressure range: 0 - 0.6 to 10 bar (0 - 8.7 to 145 psid)
System pressure: Maximum 30 bar (453 psig)
Differential Pressure transmitter, Industry
System temperature: -10 to +70 °C (14 to 158 °F)
• conventional sensor with two capillaries
Signal: 4-20 mA (3-wire)
• stainless-steel and composite housing.
Power supply: 12-30 VDC
Enclosure class: IP55

DPI II
Differential pressure range: 0 - 0.6 to 16 bar (0 - 8.7 to 232 psid)
System pressure: Maximum 30 bar (453 psig)
Differential Pressure transmitter, Industry
System temperature: -30 to +120 °C (-22 to +248 °F)
• G 1/2 connection and one capillary
Signal: 4-20 mA (2-wire)
• stainless-steel housing.
Power supply: 12.5 - 30 VDC
Enclosure class: IP67

DPI II+T Differential pressure range: 0 - 0.6 to 16 bar (0 - 8.7 to 232 psid)
Temperature range: 0-120 °C (32-248 °F)
Differential Pressure transmitter, Industry
System pressure: Maximum 30 bar (453 psig)
• G 1/2 connection and one capillary
System temperature: -30 to +120 °C (-22 to +248 °F)
• combined pressure and temperature measurement
Signal: 2 x 0-10 VDC (4-wire)
• stainless-steel housing.
Power supply: 12.5 - 30 VDC
Enclosure class: IP67

RPS Pressure range: 0 - 0.6 to 16 bar (0 - 8.7 to 232 psig)


Temperature range: 0-120 °C (32-248 °F)
Relative Pressure sensor, Standard System pressure: Maximum 24 bar (348 psig)
• combined pressure and temperature measurement System temperature: 0-120 °C (32-248 °F)
• composite transmitter. Signal: 2 x 0.5 - 3.5 VDC (4-wire)
Power supply: 5 VDC (PELV)
Enclosure class: IP44 (with connected cable)

DPS Pressure range: 0 - 0.6 to 6 bar (0 - 8.7 to 87 psid)


Temperature range: 0-120 °C (32-248 °F)
Differential Pressure sensor, Standard System pressure: Maximum 24 bar (348 psig)
• combined pressure and temperature measurement System temperature: 0-120 °C (32-248 °F)
• composite transmitter. Signal: 2 x 0.5 - 4.5 VDC (4-wire)
Power supply: 5 VDC (PELV)
Enclosure class: IP44 (with connected cable)

4
Pressure sensors
2

2. Product introduction

Product introduction
This data booklet describes these Grundfos products: Differential-pressure sensor
• industrial relative- and differential-pressure sensors The central part of a differential-pressure sensor is a
• standard relative- and differential-pressure sensors. chip which transforms the differential pressure into
electrical signals. The difference between the two
system pressures on either side of the chip, called the
differential pressure, causes the chip to warp. This is
registered as a change of resistance in the strain
gauges of a Wheatstone bridge. The change in

TM04 5034 2409 - TM04 7865 2410


TM04 7866 2410 - TM05 4752 2512
resistance is converted into an analog output signal.
The sensors incorporating temperature measurement
also transform the temperature of the liquid into
electrical signals.

Fig. 1 Grundfos pressure sensors

Three different types of pressure are used in pressure


measurement:
• Absolute pressure: the measured value is zero-
referenced against vacuum.

TM03 4055 1406


• Relative pressure: the measured value is zero-
referenced against the ambient pressure.
• Differential pressure: the measured value is the
difference between two pressures.
The Grundfos pressure sensor ranges contain relative- Fig. 2 Schematic view of how the chip is affected by
and differential-pressure sensors as well as relative- pressure on both sides
and differential-pressure sensors combined with
temperature measurement capable of measuring Sensor chip
temperatures from 0 to 100 °C (32 to 212 °F). This The steady-state properties of silicon protect the chip
makes Grundfos sensorsTM suitable for a wide range against wear and tear. Lifelong nano-coating
of applications. protection enables direct measurement (wet-wet) in a
cost-effective packaging for aqueous media. The
Relative-pressure sensor secret is a metal-glass alloy coating, Silicoat ®, which is
The central part of a relative-pressure sensor is a chip extremely resistant to corrosion. Compared to
which transforms the pressure into electrical signals. conventional sensor technologies, which encapsulate
The difference between the ambient air pressure and the unprotected measuring cell to protect it from the
the system pressure causes the chip to warp which is liquid, Silicoat® ensures protection of the chip from
registered as a change of resistance in the strain aqueous media (pH2 - pH11) at temperatures up to
gauges of a Wheatstone bridge. The change in 120 °C (248 °F) through the entire life of the product.
resistance is converted into an analog output signal.
The sensors incorporating temperature measurement Definitions
also transform the temperature of the liquid into
Burst Pressure
electrical signals.
The signals are linearised and compensated for the The maximum allowable pressure (relative to ambient)
influence of temperature variations. in a system, which will not destroy the sensor or
transmitter. Measured in [bar].
Maximum System Pressure
Maximum allowable static pressure (relative to ambient
pressure) in a system, where the flow is zero.

5
Pressure sensors
3

3. Relative Pressure transmitters, Industry (RPI and RPI+T)


Relative Pressure transmitters, Industry (RPI and RPI+T)

General data Pressure range


Pressure range

[bar] [psig]
0 - 0.6 0 - 8.7
0 - 1.0 0 - 14.5
0 - 1.6 0 - 23.2

TM04 7865 2510


0 - 2.5 0 - 36.3
0 - 4.0 0 - 58.0
0 - 6.0 0 - 87.0
0 - 10.0 0 - 145.0
0 - 16.0* 0 - 232.1
Fig. 3 RPI, RPI+T transmitter 0 - 25.0 0 - 362.6

* RPI+T2 is a special 0-16.0 bar Relative Pressure Transmitter,


Technical overview Industry measuring up to 120 C at 10 V intended for Magna3 and
TPE3.
The RPI relative-pressure transmitter from Grundfos
Direct Sensors™ is designed for industrial Approvals (w/EPDM O-rings)
applications. The transmitter is designed to be
• WRAS
mounted direct on a unit, for example a pump.
• KTW
The RPI transmitter is fully compatible with aqueous
media. The transmitter is based on MEMS sensing • A4020
technology in combination with the corrosion-resistant • ACS.
Silicoat® coating technology on the transmitter chip.
This makes the RPI transmitter very robust and ideal Certificates
for pump integration and monitoring in harsh
environments.The RPI+T transmitter offers a two-in-
one solution with combined pressure and temperature
measurement. + 75
CE C, CSA, US EAC

Applications
• Pump control
• HVAC systems
• temperature control and chiller systems
• renewable energies such as heat pumps, solar
thermals, fresh water and micro-CHP systems
• monitoring and control systems
• water treatment plants
• water utility and distribution systems
• HPC and IT cooling systems.

Features and benefits


• Pressure and temperature measurement in one
transmitter (two-in-one solution) for easy and cost-
efficient installation (RPI+T)
• MEMS technology
• direct contact with the aqueous media resulting in a
fast response time
• plug and play for quick setup
• smart system solution with Grundfos pump controls
• compact and robust design
• compatible with aggressive aqueous medias
• suitable for a wide temperature range.
• suitable for a wide range of applications.

6
Pressure sensors
3
Electrical connections

Relative Pressure transmitters, Industry (RPI and RPI+T)


2 1
3 4

TM06 1070 1514


Fig. 4 Electrical connections

RPI
Signal condition: 2-wire (loop-powered)
Pin 1 2 3 4

Wire colour Brown White Blue Black


Power Not Pressure signal
I/O Not used
supply used 4-20 mA

RPI+T
Signal condition: 4-wire
Pin 1 2 3 4

Wire colour Brown White Blue Black


Power Pressure signal Temperature
I/O GND*
supply 0-10 V signal 0-10 V

* Common ground for pressure and temperature signals.


Power supply, screened cable: SELV or PELV.

Directives
The Grundfos Direct Sensors™ are in conformity
with these council directives on the approximation of
the laws of the EC member states:
• • Low Voltage Directive (2014/35/EU)
– Standards used: EN 61010-1:2010
• EMC Directive (2014/30/EU).
– Standards used: EN 61326-1:2013 and EN
61326-2-3:2013
The GRUNDFOS Direct Sensors™ are exempted from
the Pressure Equipment Directive (PED) according to
Article 4, paragraph 3 in the PED 2014/68/EU.

7
Pressure sensors
3
RPI and RPI+T, 0 - 0.6 bar (0 - 8.7 Specifications
Relative Pressure transmitters, Industry (RPI and RPI+T)

psig) Pressure
Measuring range 0 - 0.6 bar (0 - 8.7 psig)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Less than 100 ms
Response time
(typically 50 ms)

TM04 9240 3510


Resolution 1/1000 FS
Temperature, RPI+T with temperature output
Measuring range 0-100 °C (32-212 °F)
Accuracy (± 1 σ),
±1K
0-80 °C (32-176 °F)
Fig. 5 RPI and RPI+T transmitter Accuracy (± 1 σ),
±2K
0-100 °C (32-212 °F)
Dimensions Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation,
-30 to +120 °C (-22 to +248 °F)
not freezing
B

Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)


Storage temperature -55 to +70 °C (-67 to +158 °F)
Humidity 0-95 % RH, non-condensing
TM04 9237 3510

C Maximum system pressure 30 bar (435 psig)


Burst pressure 40 bar (580 psig)
Electrical data, RPI without temperature output
A
Power supply, RPI 12.5 - 30 VDC
Fig. 6 Dimensions, RPI and RPI+T Output signals 4-20 mA
– Signal cut off 21 mA
Maximum power consumption 660 mW
A B C 60 Ω at 12.5 VDC
mm 36.95 110 100 Ω at 13.3 VDC
ISO 228/1 - G 1/2 Maximum load impedance
600 Ω at 24 VDC
in 1.45 4.33
900 Ω at 30 VDC
Output signals Maximum cable length 30 m (98 ft)
Electrical data, RPI+T with temperature output
Power supply, RPI+T 16.6 - 30 VDC
Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
Minimum load impedance 10 kΩ
TM06 3358 1716

Maximum cable length 30 m (98 ft)


Materials
Sensing element Silicon-based MEMS
P max Sealing EPDM or FKM
Fig. 7 Pressure response, RPI Housing Stainless steel 1.4404 (AISI 316 L)
Corrosion-resistant coating
Wetted materials EPDM or FKM
Stainless steel 1.4404 (AISI 316 L)

10V
Environmental standards
Enclosure class IP67, cable-connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 8 Pressure and temperature response, RPI+T

8
Pressure sensors
3
RPI and RPI+T, 0 - 1.0 bar (0 - 14.5 Specifications

Relative Pressure transmitters, Industry (RPI and RPI+T)


psig) Pressure
Measuring range 0 - 1.0 bar (0 - 14.5 psig)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Less than 100 ms
Response time
(typically 50 ms)

TM04 9240 3510


Resolution 1/1000 FS
Temperature, RPI with temperature output
Measuring range 0-100 °C (32-212 °F)
Accuracy (± 1 σ),
±1K
0-80 °C (32-176 °F)
Fig. 9 RPI and RPI+T transmitter Accuracy (± 1 σ),
±2K
0-100 °C (32-212 °F)
Dimensions Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)
B

Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
Storage temperature -55 to +70 °C (-67 to +158 °F)
TM04 9237 3510

Humidity 0-95 % RH, non-condensing


C
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)

A Electrical data, RPI without temperature output


Power supply, RPI 12.5 - 30 VDC
Fig. 10 Dimensions, RPI and RPI+T Output signals 4-20 mA
– Signal cut off 21 mA
A B C Maximum power consumption 660 mW
60 Ω at 12.5 VDC
mm 36.95 110
ISO 228/1 - G 1/2 100 Ω at 13.3 VDC
in 1.45 4.33 Maximum load impedance
600 Ω at 24 VDC
900 Ω at 30 VDC
Output signals Maximum cable length 30 m (98 ft)
Electrical data, RPI+T with temperature output
Power supply, RPI+T 16.6 - 30 VDC
Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
Minimum load impedance 10 kΩ
Maximum cable length 30 m (98 ft)
TM06 3358 1716

Materials
Sensing element Silicon-based MEMS
Sealing EPDM or FKM
Housing Stainless steel 1.4404 (AISI 316 L)
P max
Corrosion-resistant coating
Fig. 11 Pressure response, RPI Wetted materials EPDM or FKM
Stainless steel 1.4404 (AISI 316 L)
Environmental standards
Enclosure class IP67, cable connected
10V Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 12 Pressure and temperature response, RPI+T

9
Pressure sensors
3
RPI and RPI+T, 0 - 1.6 bar (0 - 23.2 Specifications
Relative Pressure transmitters, Industry (RPI and RPI+T)

psig) Pressure
Measuring range 0 - 1.6 bar (0 - 23.2 psig)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Less than 100 ms
Response time
(typically 50 ms)

TM04 9240 3510


Resolution 1/1000 FS
Temperature, RPI with temperature output
Measuring range 0-100 °C (32-212 °F)
Accuracy (± 1 σ),
±1K
0-80 °C (32-176 °F)
Fig. 13 RPI and RPI+T transmitter Accuracy (± 1 σ),
±2K
0-100 °C (32-212 °F)
Dimensions Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)
B

Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
Storage temperature -55 to +70 °C (-67 -to +158 °F)
TM04 9237 3510

Humidity 0-95 % RH, non-condensing


C Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)

A Electrical data, RPI without temperature output


Power supply, RPI 12.5 - 30 VDC
Fig. 14 Dimensions, RPI and RPI+T Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
A B C
Maximum power consumption 660 mW
mm 36.95 110 60 Ω at 12.5 VDC
ISO 228/1 - G 1/2
in 1.45 4.33 100 Ω at 13.3 VDC
Maximum load impedance
600 Ω at 24 VDC
Output signals 900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Electrical data, RPI+T with temperature output
Power supply, RPI+T 16.6 - 30 VDC
Output signals 0-10 VDC
– Signal cut off 11 VDC
Power consumption Maximum 270 mW
Load impedance Minimum 10 kΩ
Maximum cable length 30 m (98 ft)
TM06 3358 1716

Materials
Sensing element Silicon-based MEMS
Sealing EPDM or FKM
Housing Stainless steel 1.4404 (AISI 316 L)
P max
Corrosion-resistant coating
Fig. 15 Pressure response, RPI Wetted materials EPDM or FKM
Stainless steel 1.4404 (AISI 316 L)
Environmental standards
Enclosure class IP67, cable connected
10V Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 16 Pressure and temperature response, RPI+T

10
Pressure sensors
3
RPI and RPI+T, 0 - 2.5 bar (0 - 36.3 Specifications

Relative Pressure transmitters, Industry (RPI and RPI+T)


psig) Pressure
Measuring range 0 - 2.5 bar (0 - 36.3 psig)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Less than 100 ms
Response time
(typically 50 ms)

TM04 9240 3510


Resolution 1/1000 FS
Temperature, RPI with temperature output
Measuring range 0-100 °C (32-212 °F)
Accuracy (± 1 σ),
±1K
0-80 °C (32-176 °F)
Fig. 17 RPI and RPI+T transmitter Accuracy (± 1 σ),
±2K
0-100 °C (32-212 °F)
Dimensions Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)
B

Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)


Storage temperature -55 to +70 °C (-67 to +158 °F)
Humidity 0-95 % RH, non-condensing
TM04 9237 3510

Maximum system pressure 30 bar (435 psig)


C
Burst pressure 40 bar (580 psig)
Electrical data, RPI without temperature output
A Power supply, RPI 12.5 - 30 VDC
Output signals 4-20 mA
Fig. 18 Dimensions, RPI and RPI+T – Signal cut off 21 mA
Maximum power consumption 660 mW
A B C 60 Ω at 12.5 VDC
100 Ω at 13.3 VDC
mm 36.95 110 Maximum load impedance
ISO 228/1 - G 1/2 600 Ω at 24 VDC
in 1.45 4.33 900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Output signals
Electrical data, RPI+T with temperature output
Power supply, RPI+T 16.6 - 30 VDC
Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
Minimum load impedance 10 kΩ
Maximum cable length 30 m (98 ft)
Materials
TM06 3358 1716

Sensing element Silicon-based MEMS


Sealing EPDM or FKM
Housing Stainless steel 1.4404 (AISI 316 L)
P max Corrosion-resistant coating
Wetted materials EPDM or FKM
Fig. 19 Pressure response, RPI Stainless steel 1.4404 (AISI 316 L)
Environmental standards
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
10V Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 20 Pressure and temperature response, RPI+T

11
Pressure sensors
3
RPI and RPI+T, 0 - 4.0 bar (0 - 58.0 Specifications
Relative Pressure transmitters, Industry (RPI and RPI+T)

psig) Pressure
Measuring range 0 - 4.0 bar (0 - 58.0 psig)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Less than 100 ms
Response time
(typically 50 ms)

TM04 9240 3510


Resolution 1/1000 FS
Temperature, RPI with temperature output
Measuring range 0-100 °C (32-212 °F)
Accuracy (± 1 σ),
±1K
0-80 °C (32-176 °F)
Fig. 21 RPI and RPI+T transmitter Accuracy (± 1 σ),
±2K
0-100 °C (32-212 °F)
Dimensions Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)
B

Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)


Storage temperature -55 to +70 °C (-67 to +158 °F)
Humidity 0-95 % RH, non-condensing
TM04 9237 3510

Maximum system pressure 30 bar (435 psig)


C
Burst pressure 40 bar (580 psig)
Electrical data, RPI without temperature output
A Power supply, RPI 12.5 - 30 VDC
Output signals 4-20 mA
Fig. 22 Dimensions, RPI and RPI+T – Signal cut off 21 mA
Maximum power consumption 660 mW
A B C 60 Ω at 12.5 VDC
100 Ω at 13.3 VDC
mm 36.95 110 Maximum load impedance
ISO 228/1 - G 1/2 600 Ω at 24 VDC
in 1.45 4.33 900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Output signals
Electrical data, RPI+T with temperature output
Power supply, RPI+T 16.6 - 30 VDC
Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
Minimum load impedance 10 kΩ
Maximum cable length 30 m (98 ft)
Materials
TM06 3358 1716

Sensing element Silicon-based MEMS


Sealing EPDM or FKM
Housing Stainless steel 1.4404 (AISI 316 L)
Corrosion-resistant coating
P max
Wetted materials EPDM or FKM
Fig. 23 Pressure response, RPI Stainless steel 1.4404 (AISI 316 L)
Environmental standards
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
10V Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 24 Pressure and temperature response, RPI+T

12
Pressure sensors
3
RPI and RPI+T, 0 - 6.0 bar (0 - 87.0 Specifications

Relative Pressure transmitters, Industry (RPI and RPI+T)


psig) Pressure
Measuring range 0 - 6.0 bar (0 - 87.0 psig)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Less than 100 ms
Response time
(typically 50 ms)

TM04 9240 3510


Resolution 1/1000 FS
Temperature, RPI with temperature output
Measuring range 0-100 °C (32-212 °F)
Accuracy (± 1 σ),
±1K
0-80 °C (32-176 °F)
Fig. 25 RPI and RPI+T transmitter Accuracy (± 1 σ),
±2K
0-100 °C (32-212 °F)
Dimensions Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)
B

Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
Storage temperature -55 to +70 °C (-67 to +158 °F)
TM04 9237 3510

Humidity 0-95 % RH, non-condensing


C Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Electrical data, RPI without temperature output
A
Power supply, RPI 12.5 - 30 VDC
Fig. 26 Dimensions, RPI and RPI+T Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
A B C
Maximum power consumption 660 mW
mm 36.95 110 660 Ω at 12.5 VDC
ISO 228/1 - G 1/2
in 1.45 4.33 100 Ω at 13.3 VDC
Maximum load impedance
600 Ω at 24 VDC
Output signals 900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Electrical data, RPI+T with temperature output
Power supply, RPI+T 16.6 - 30 VDC
Output signals 0-10 VDC
– Signal cut off 11 VDC
Maximum power consumption 270 mW
Minimum load impedance 10 kΩ
Maximum cable length 30 m (98 ft)
TM06 3358 1716

Materials
Sensing element Silicon-based MEMS
Sealing EPDM or FKM
Housing Stainless steel 1.4404 (AISI 316 L)
P max Corrosion-resistant coating
Fig. 27 Pressure response, RPI Wetted materials EPDM or FKM
Stainless steel 1.4404 (AISI 316 L)
Environmental standards
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
10V
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 28 Pressure and temperature response, RPI+T

13
Pressure sensors
3
RPI and RPI+T, 0 - 10.0 bar (0 - Specifications
Relative Pressure transmitters, Industry (RPI and RPI+T)

145.0 psig) Pressure


Measuring range 0 - 10.0 bar (0 - 145.0 psig)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Less than 100 ms
Response time
(typically 50 ms)

TM04 9240 3510


Resolution 1/1000 FS
Temperature, RPI with temperature output
Measuring range 0-100 °C (32-212 °F)
Accuracy (± 1 σ),
±1K
0-80 °C (32-176 °F)
Fig. 29 RPI and RPI+T transmitter Accuracy (± 1 σ),
±2K
0-100 °C (32-212 °F)
Dimensions Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)
B

Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
Storage temperature -55 to +70 °C (-67 to +158 °F)
TM04 9237 3510

Humidity 0-95 % RH, non-condensing


C Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Electrical data, RPI without temperature output
A
Power supply, RPI 12.5 - 30 VDC
Fig. 30 Dimensions, RPI and RPI+T Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
A B C
Maximum power consumption 660 mW
mm 36.95 110 660 Ω at 12.5 VDC
ISO 228/1 - G 1/2
in 1.45 4.33 100 Ω at 13.3 VDC
Maximum load impedance
600 Ω at 24 VDC
Output signals 900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Electrical data, RPI+T with temperature output
Power supply, RPI+T 16.6 - 30 VDC
Output signals 0-10 VDC
– Signal cut off 11 VDC
Maximum power consumption 270 mW
Minimum load impedance 10 kΩ
Maximum cable length 30 m (98 ft)
TM06 3358 1716

Materials
Sensing element Silicon-based MEMS
Sealing EPDM or FKM
Housing Stainless steel 1.4404 (AISI 316 L)
P max Corrosion-resistant coating
Fig. 31 Pressure response, RPI Wetted materials EPDM or FKM
Stainless steel 1.4404 (AISI 316 L)
Environmental standards
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
10V
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 32 Pressure and temperature response, RPI+T

14
Pressure sensors
3
RPI and RPI+T, 0 - 16.0 bar (0 - Specifications

Relative Pressure transmitters, Industry (RPI and RPI+T)


232.1 psig) Pressure
Measuring range 0 - 16.0 bar (0 - 232.1 psig)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Less than 100 ms
Response time
(typically 50 ms)

TM04 9240 3510


Resolution 1/1000 FS
Temperature, RPI with temperature output
Measuring range 0-100 °C (32-212 °F)
Accuracy (± 1 σ),
±1K
0-80 °C (32-176 °F)
Fig. 33 RPI and RPI+T transmitter Accuracy (± 1 σ),
±2K
0-100 °C (32-212 °F)
Dimensions Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)
B

Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
Storage temperature -55 to +70 °C (-67 to +158 °F)
TM04 9237 3510

Humidity 0-95 % RH, non-condensing


C Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Electrical data, RPI without temperature output
A
Power supply, RPI 12.5 - 30 VDC
Fig. 34 Dimensions, RPI and RPI+T Output signals 4-20 mA
– Signal cut off 21 mA
Maximum power consumption 660 mW
A B C
660 Ω at 12.5 VDC
mm 36.95 110 100 Ω at 13.3 VDC
ISO 228/1 - G 1/2 Maximum load impedance
in 1.45 4.33 600 Ω at 24 VDC
900 Ω at 30 VDC
Output signals Maximum cable length 30 m (98 ft)
Electrical data, RPI+T with temperature output
Power supply, RPI+T 16.6 - 30 VDC
Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
Minimum load impedance 10 kΩ
Maximum cable length 30 m (98 ft)
TM06 3358 1716

Materials
Sensing element Silicon-based MEMS
Sealing EPDM or FKM
Housing Stainless steel 1.4404 (AISI 316 L)
P max
Corrosion-resistant coating
Fig. 35 Pressure response, RPI Wetted materials EPDM or FKM
Stainless steel 1.4404 (AISI 316 L)
Environmental standards
Enclosure class IP67, cable connected
10V Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 36 Pressure and temperature response, RPI+T

15
Pressure sensors
3
RPI+T2, 0 - 16.0 bar (0 - 232.1 psig) Specifications
Relative Pressure transmitters, Industry (RPI and RPI+T)

Pressure
Measuring range 0 - 16.0 bar (0 - 232.1 psig)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +120 °C (-22 to +248 °F)
Less than 100 ms

TM04 9240 3510


Response time
(typically 50 ms)
Resolution 1/1000 FS
Temperature, RPI with temperature output
Measuring range -10 to +120 °C (14 to +248 °F)
Fig. 37 RPI+T transmitter Accuracy (± 1 σ),
±1K
-10 - 15 and 90-120 °C
Dimensions Accuracy (± 1 σ),
± 0.5 K
15-90 °C
Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
B

Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)


Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
TM04 9237 3510

C Storage temperature -55 to +70 °C (-67 to +158 °F)


Humidity 0-95 % RH, non-condensing
Maximum system pressure 30 bar (435 psig)
A Burst pressure 40 bar (580 psig)
Electrical data, RPI+T with temperature output
Fig. 38 Dimensions, RPI+T transmitter
Power supply, RPI+T 16.6 - 30 VDC
Output signals 0-10 VDC
A B C (0 V at -10 °C, 10 V at 120 °C)
mm 36.95 110 – Signal cut off 11 VDC
ISO 228/1 - G 1/2
in 1.45 4.33 Maximum power consumption 270 mW
Minimum load impedance 10 kΩ
Output signals Maximum cable length 30 m (98 ft)
Materials
Sensing element Silicon-based MEMS
10V Sealing EPDM
Housing Stainless steel 1.4404 (AISI 316 L)
Corrosion-resistant coating
Wetted materials EPDM
Stainless steel 1.4404 (AISI 316 L)
Environmental standards
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
TM07 2422 3518

Vibration, non-destructive 20-2000 Hz, 10 G, 4 h


Electromagnetic compatibility EN 61326-1
0
P min P max
T min T max

Fig. 39 Pressure and temperature response, RPI+T


TM07 2415 3518

Fig. 40 MAGNA3 and TPE3 with RPI+T2 transmitter

16
Pressure sensors
3
RPI and RPI+T, 0 - 25.0 bar (0 - Specifications

Relative Pressure transmitters, Industry (RPI and RPI+T)


362.6 psig) Pressure
Measuring range 0 - 25.0 bar (0 - 362.6 psig)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Less than 100 ms
Response time
(typically 50 ms)

TM04 9240 3510


Resolution 1/1000 FS
Temperature, RPI with temperature output
Measuring range 0-100 °C (32-212 °F)
Accuracy (± 1 σ),
±1K
0-80 °C (32-176 °F)
Fig. 41 RPI and RPI+T transmitter Accuracy (± 1 σ),
±2K
0-100 °C (32-212 °F)
Dimensions Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)
B

Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
Storage temperature -55 to +70 °C (-67 to +158 °F)
TM04 9237 3510

Humidity 0-95 % RH, non-condensing


C Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)

A Electrical data, RPI without temperature output


Power supply, RPI 12.5 - 30 VDC
Fig. 42 Dimensions, RPI and RPI+T Output signals 4-20 mA
– Signal cut off 21 mA
A B C Maximum power consumption 660 mW
60 Ω at 12.5 VDC
mm 36.95 110 100 Ω at 13.3 VDC
ISO 228/1 - G 1/2 Maximum load impedance
in 1.45 4.33 600 Ω at 24 VDC
900 Ω at 30 VDC
Output signals Maximum cable length 30 m (98 ft)
Electrical data, RPI+T with temperature output
Power supply, RPI+T 16.6 - 30 VDC
Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
Minimum load impedance 10 kΩ
Maximum cable length 30 m (98 ft)
TM06 3358 1716

Materials
Sensing element Silicon-based MEMS
Sealing EPDM or FKM
Housing Stainless steel 1.4404 (AISI 316 L)
P max
Corrosion-resistant coating
Fig. 43 Pressure response, RPI Wetted materials EPDM or FKM
Stainless steel 1.4404 (AISI 316 L)
Environmental standards
Enclosure class IP67, cable connected
10V Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 44 Pressure and temperature response, RPI+T

17
Pressure sensors
4

4. Differential Pressure transmitter, Industry (DPI I)


Differential Pressure transmitter, Industry (DPI I)

General data Certificates

+ 75
CE C, CSA, US EAC

TM04 4738 0509


Electrical connections

Fig. 45 DPI sensor

Technical overview
The DPI differential-pressure transmitter from
Grundfos Direct Sensors™ is designed for industrial
purposes.
The DPI transmitter is fully compatible with aqueous
media. The sensor is based on MEMS sensing
technology in combination with the corrosion-resistant
Silicoat® coating technology on the sensor chip.
This makes the DPI transmitter very robust and ideal
for pump integration and monitoring in harsh
environments.

Applications
• Pump control
• HVAC systems

TM03 2225 3905


• temperature control and chiller systems
• renewable energies such as heat pumps, solar
thermals, fresh water and micro-CHP systems
• monitoring and control systems
• water treatment plants Fig. 46 Electrical connections
• water utility and distribution systems
• HPC and IT cooling systems. Pin Description Colour
1 12-30 V supply voltage Brown
Features and benefits 2 GND (earth conductor) Yellow
3 Signal conductor Green
• MEMS technology
Test conductor
• No wear and tear The conductor can be cut off during mounting.
4 White
• plug and play for quick setup The conductor must not be connected to the
power supply.
• smart system solution with Grundfos pump controls
• compact and robust design Directives
• compatible with aqueous media The Grundfos Direct Sensors™ are in conformity with
• suitable for a wide range of applications. these council directives on the approximation of the
laws of the EC member states:
Pressure range • Low Voltage Directive (2014/35/EU)
Pressure range
– Standards used: EN 61010-1:2010
• EMC Directive (2014/30/EU).
[bar] [psid]
0 - 0.6 0 - 8.7
– Standards used: EN 61326-1:2013 and EN
0 - 1.0 0 - 14.5 61326-2-3:2013
0 - 1.2 0 - 17.4 The GRUNDFOS Direct Sensors™ are exempted from
0 - 1.6 0 - 23.2 the Pressure Equipment Directive (PED) according to
0 - 2.5 0 - 36.3 Article 4, paragraph 3 in the PED 2014/68/EU.
0 - 4.0 0 - 58.0
For outside usage, the DPI I is IP55, and may only be
0 - 6.0 0 - 87.0
0 - 10.0 0 - 145.0
used outside in it's 0.9 m. variants powered by a
Grundfos pump or the SI power supply (See
Accessories on page 58).

18
Pressure sensors
4
DPI, 0 - 0.6 bar (0 - 8.7 psid) Specifications

Differential Pressure transmitter, Industry (DPI I)


Pressure
Measuring range 0 - 0.6 bar (0 - 8.7 psid)
Accuracy (IEC 61298-2) 3.5 % FS
Response time Less than 0.5 s
System pressure deviation 6 mbar/bar (0.09 psid/psig)
System conditions and environment

TM04 5034 2409


Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -10 to +70 °C (14 to 158 °F)
Liquid temperature, peak Up to 80 °C (176 °F)
Ambient temperature -40 to +70 °C (-40 to +158 °F)
Fig. 47 DPI transmitter Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
Dimensions
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
Maximum p2-p1 pressure 10 bar (145 psid)
Electrical data
Power supply, 12-30 VDC
Output signals 4-20 mA
– Signal cut off 21 mA
F 500 kΩ at 24 V
Maximum load impedance 200 kΩ at 16 V
100 kΩ at 12 V
D

P2
E

Maximum cable length 30 m (98 ft)


TM03 2059 3505

Materials
P1
Sensing element Silicon-based MEMS
O-ring FKM
C
Housing Stainless steel 1.4305 (AISI 303)
A B Wetted materials FKM, PPS and 1.4305
Fig. 48 Dimensions, DPI Environmental standards
Enclosure class IP55
A B C D E F Temperature cycling IEC 68-2-14
7/16 - 20 Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
mm 14 6 ∅45 77 Immunity EN 61000-6-2
UNF
SW 14
0.25" Emission EN 61000-6-3
in 0.55 0.24 ∅1.77 3.03
flare Weight 550 g (1.21 lbs)

Output signals
TM06 3358 1716

P max
Fig. 49 Differential-pressure response, DPI

19
Pressure sensors
4
DPI, 0 - 1.0 bar (0 - 14.5 psid) Specifications
Differential Pressure transmitter, Industry (DPI I)

Pressure
Measuring range 0 - 1.0 bar (0 - 14.5 psid)
Accuracy (IEC 61298-2) 2 % FS
Response time Less than 0.5 s
System pressure deviation 6 mbar/bar (0.09 psid/psig)
System conditions and environment

TM04 5034 2409


Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -10 to +70 °C (14 to 158 °F)
Liquid temperature, peak Up to 80 °C (176 °F)
Ambient temperature -40 to +70 °C (-40 to +158 °F)
Fig. 50 DPI transmitter
Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
Dimensions
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
Maximum p2-p1 pressure 10 bar (145 psid)
Electrical data
Power supply 12-30 VDC
Output signals 4-20 mA
– Signal cut off 21 mA
F
500 kΩ at 24 V
Maximum load impedance 200 kΩ at 16 V
100 kΩ at 12 V
D

P2
E

Maximum cable length 30 m (98 ft)


TM03 2059 3505

Materials
P1
Sensing element Silicon-based MEMS
C
O-ring FKM
Housing Stainless steel 1.4305 (AISI 303)
A B
Wetted materials FKM, PPS and 1.4305
Fig. 51 Dimensions, DPI Environmental standards
Enclosure class IP55
A B C D E F Temperature cycling IEC 68-2-14
7/16 - 20 Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
mm 14 6 ∅45 77
UNF Immunity EN 61000-6-2
SW 14
0.25" Emission EN 61000-6-3
in 0.55 0.24 ∅1.77 3.03
flare Weight 550 g (1.21 lbs)

Output signals
TM06 3358 1716

P max
Fig. 52 Differential-pressure response, DPI

20
Pressure sensors
4
DPI, 0 - 1.2 bar (0 - 17.4 psid) Specifications

Differential Pressure transmitter, Industry (DPI I)


Pressure
Measuring range 0 - 1.2 bar (0 - 17.4 psid)
Accuracy (IEC 61298-2) 2 % FS
Response time Less than 0.5 s
System pressure deviation 6 mbar/bar (0.09 psid/psig)
System conditions and environment

TM04 5034 2409


Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -10 to +70 °C (14 to 158 °F)
Liquid temperature, peak Up to 80 °C (176 °F)
Ambient temperature -40 to +70 °C (-40 to +158 °F)
Fig. 53 DPI transmitter
Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 % non-condensing
Dimensions
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
Maximum p2-p1 pressure 10 bar (145 psid)
Electrical data
Power supply 12-30 VDC
Output signals 4-20 mA
– Signal cut off 21 mA
F
500 kΩ at 24 V
Maximum load impedance 200 kΩ at 16 V
100 kΩ at 12 V
D

P2
E

Maximum cable length 30 m (98 ft)


TM03 2059 3505

Materials
P1
Sensing element Silicon-based MEMS
C O-ring FKM
Housing Stainless steel 1.4305 (AISI 303)
A B
Wetted materials FKM, PPS and 1.4305
Fig. 54 Dimensions, DPI Environmental standards
Enclosure class IP55
A B C D E F Temperature cycling IEC 68-2-14
7/16 - 20 Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
mm 14 6 ∅45 77
UNF Immunity EN 61000-6-2
SW 14
0.25" Emission EN 61000-6-3
in 0.55 0.24 ∅1.77 3.03
flare Weight 550 g (1.21 lbs)
Output signals
TM06 3358 1716

P max
Fig. 55 Differential-pressure response, DPI

21
Pressure sensors
4
DPI, 0 - 1.6 bar (0 - 23.2 psid) Specifications
Differential Pressure transmitter, Industry (DPI I)

Pressure
Measuring range 0 - 1.6 bar (0 - 23.2 psid)
Accuracy (IEC 61298-2) 2 % FS
Response time Less than 0.5 s
System pressure deviation 6 mbar/bar (0.09 psid/psig)
System conditions and environment

TM04 5034 2409


Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -10 to +70 °C (14 to 158 °F)
Liquid temperature, peak Up to 80 °C (176 °F)
Ambient temperature -40 to +70 °C (-40 to +158 °F)
Fig. 56 DPI transmitter
Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
Dimensions
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
Maximum p2-p1 pressure 10 bar (145 psid)
Electrical data
Power supply 12-30 VDC
Output signals 4-20 mA
– Signal cut off 21 mA
F
500 kΩ at 24 V
Maximum load impedance 200 kΩ at 16 V
100 kΩ at 12 V
D

P2
E

Maximum cable length 30 m (98 ft)


TM03 2059 3505

Materials
P1
Sensing element Silicon-based MEMS
C
O-ring FKM
Housing Stainless steel 1.4305 (AISI 303)
A B
Wetted materials FKM, PPS and 1.4305
Fig. 57 Dimensions, DPI Environmental standards
Enclosure class IP55
A B C D E F Temperature cycling IEC 68-2-14
7/16 - 20 Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
mm 14 6 ∅45 77
UNF Immunity EN 61000-6-2
SW 14
0.25" Emission EN 61000-6-3
in 0.55 0.24 ∅1.77 3.03
flare Weight 550 g (1.21 lbs)

Output signals
TM06 3358 1716

P max
Fig. 58 Differential-pressure response, DPI

22
Pressure sensors
4
DPI, 0 - 2.5 bar (0 - 36.3 psid) Specifications

Differential Pressure transmitter, Industry (DPI I)


Pressure
Measuring range 0 - 2.5 bar (0 - 36.3 psid)
Accuracy (IEC 61298-2) 2 % FS
Response time Less than 0.5 s
System pressure deviation 6 mbar/bar (0.09 psid/psig)
System conditions and environment

TM04 5034 2409


Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -10 to +70 °C (14 to 158 °F)
Liquid temperature, peak Up to 80 °C (176 °F)
Ambient temperature -40 to +70 °C (-40 to +158 °F)
Fig. 59 DPI transmitter
Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
Dimensions
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
Maximum p2-p1 pressure 10 bar (145 psid)
Electrical data
Power supply 12-30 VDC
Output signals 4-20 mA
– Signal cut off 21 mA
F 500 kΩ at 24 V
Maximum load impedance 200 kΩ at 16 V
100 kΩ at 12 V
D

P2
E

Maximum cable length 30 m (98 ft)


TM03 2059 3505

Materials
P1
Sensing element Silicon-based MEMS
O-ring FKM
C
Housing Stainless steel 1.4305 (AISI 303)
A B Wetted materials FKM, PPS and 1.4305
Fig. 60 Dimensions, DPI Environmental standards
Enclosure class IP55
A B C D E F Temperature cycling IEC 68-2-14
7/16 - 20 Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
mm 14 6 ∅45 77
UNF Immunity EN 61000-6-2
SW 14
0.25" Emission EN 61000-6-3
in 0.55 0.24 ∅1.77 3.03
flare Weight 550 g (1.21 lbs)

Output signals
TM06 3358 1716

P max
Fig. 61 Differential-pressure response, DPI

23
Pressure sensors
4
DPI, 0 - 4.0 bar (0 - 58.0 psid) Specifications
Differential Pressure transmitter, Industry (DPI I)

Pressure
Measuring range 0 - 4.0 bar (0 - 58.0 psid)
Accuracy (IEC 61298-2) 2 % FS
Response time Less than 0.5 s
System pressure deviation 6 mbar/bar (0.09 psid/psig)
System conditions and environment

TM04 5034 2409


Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -10 to +70 °C (14 to 158 °F)
Liquid temperature, peak Up to 80 °C (176 °F)
Ambient temperature -40 to +70 °C (-40 to +158 °F)
Fig. 62 DPI transmitter
Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity 0-95 %, non-condensing
Dimensions
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
Maximum p2-p1 pressure 10 bar (145 psid)
Electrical data
Power supply 12-30 VDC
Output signals 4-20 mA
– Signal cut off 21 mA
F
500 kΩ at 24 V
Maximum load impedance 200 kΩ at 16 V
100 kΩ at 12 V
D

P2
E

Maximum cable length 30 m (98 ft)


TM03 2059 3505

Materials
P1
Sensing element Silicon-based MEMS
C
O-ring FKM
Housing Stainless steel 1.4305 (AISI 303)
A B
Wetted materials FKM, PPS and 1.4305
Fig. 63 Dimensions, DPI Environmental standards
Enclosure class IP55
A B C D E F Temperature cycling IEC 68-2-14
7/16 - 20 Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
mm 14 6 ∅45 77 Immunity EN 61000-6-2
UNF
SW 14
0.25" Emission EN 61000-6-3
in 0.55 0.24 ∅1.77 3.03
flare Weight 550 g (1.21 lbs)

Output signals
TM06 3358 1716

P max
Fig. 64 Differential-pressure response, DPI

24
Pressure sensors
4
DPI, 0 - 6.0 bar (0 - 87.0 psid) Specifications

Differential Pressure transmitter, Industry (DPI I)


Pressure
Measuring range 0 - 6.0 bar (0 - 87.0 psid)
Accuracy (IEC 61298-2) 2 % FS
Response time Less than 0.5 s
System pressure deviation 6 mbar/bar (0.09 psid/psig)
System conditions and environment

TM04 5034 2409


Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -10 to +70 °C (14 to 158 °F)
Liquid temperature, peak Up to 80 °C (176 °F)
Ambient temperature -40 to +70 °C (-40 to +158 °F)
Fig. 65 DPI transmitter
Ambient temperature, peak -55 to- +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
Dimensions
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
Maximum p2-p1 pressure 10 bar (145 psid)
Electrical data
Power supply 12-30 VDC
Output signals 4-20 mA
– Signal cut off 21 mA
F
500 kΩ at 24 V
Maximum load impedance 200 kΩ at 16 V
100 kΩ at 12 V
D

P2
E

Maximum cable length 30 m (98 ft)


TM03 2059 3505

Materials
P1
Sensing element Silicon-based MEMS
C
O-ring FKM
Housing Stainless steel 1.4305 (AISI 303)
A B
Wetted materials FKM, PPS and 1.4305
Fig. 66 Dimensions, DPI Environmental standards
Enclosure class IP55
A B C D E F Temperature cycling IEC 68-2-14
7/16 - 20 Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
mm 14 6 ∅45 77
UNF Immunity EN 61000-6-2
SW 14
0.25" Emission EN 61000-6-3
in 0.55 0.24 ∅1.77 3.03
flare Weight 550 g (1.21 lbs)

Output signals
TM06 3358 1716

P max
Fig. 67 Differential-pressure response, DPI

25
Pressure sensors
4
DPI, 0 - 10.0 bar (0 - 145.0 psid) Specifications
Differential Pressure transmitter, Industry (DPI I)

Pressure
Measuring range 0 - 10.0 bar (0 - 145.0 psid)
Accuracy (IEC 61298-2) 2 % FS
Response time Less than 0.5 s
System pressure deviation 6 mbar/bar (0.09 psid/psig)

TM04 5034 2409


System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation -10 to +70 °C (14 to 158 °F)
Liquid temperature, peak Up to 80 °C (176 °F)
Ambient temperature -40 to +70 °C (-40 to +158 °F)
Fig. 68 DPI transmitter
Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Dimensions Humidity, relative 0-95 %, non-condensing
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
Maximum p2-p1 pressure 10 bar (145 psid)
Electrical data
Power supply 12-30 VDC
Output signals 4-20 mA
– Signal cut off 21 mA
F
500 kΩ at 24 V
Maximum load impedance 200 kΩ at 16 V
100 kΩ at 12 V
D

P2
E

Maximum cable length 30 m (98 ft)


TM03 2059 3505

Materials
P1
Sensing element Silicon-based MEMS
C O-ring FKM
Housing Stainless steel 1.4305 (AISI 303)
A B
Wetted materials FKM, PPS and 1.4305
Fig. 69 Dimensions, DPI Environmental standards
Enclosure class IP55
A B C D E F Temperature cycling IEC 68-2-14
7/16 - 20 Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
mm 14 6 ∅45 77
UNF Immunity EN 61000-6-2
SW 14
0.25" Emission EN 61000-6-3
in 0.55 0.24 ∅1.77 3.03
flare Weight 550 g (1.21 lbs)
Output signals
TM06 3358 1716

P max
Fig. 70 Differential-pressure response, DPI

26
Pressure sensors
5

5. Differential Pressure transmitter, Industry

Differential Pressure transmitter, Industry


(DPI II and DPI II+T)
General data Pressure range
Pressure range

[bar] [psid]
0 - 0.6 0 - 8.7
0 - 1.0 0 - 14.5
0 - 1.6 0 - 23.2
0 - 2.5 0 - 36.3
0 - 4.0 0 - 58.0

TM04 7866 2510


0 - 6.0 0 - 87.0
0 - 10.0 0 - 145.0
0 - 16.0 0 - 232.1

Approvals (w/EPDM O-rings)


Fig. 71 DPI II transmitter
• WRAS
Technical overview • KTW
The DPI II+T combined differential-pressure and • AS 4020
temperature transmitter (two-in-one) from Grundfos • ACS.
Direct Sensors™ is designed for industrial
applications. Certificates
The capillary tube makes it possible to measure the
differential pressure.
The DPI II+T transmitter is fully compatible with
aqueous media. The transmitter is based on MEMS + 75
CE C, CSA, US EAC
sensing technology in combination with the corrosion-
resistant Silicoat® coating technology on the
transmitter chip.
This makes the DPI I+T transmitter very robust and
ideal for pump integration and monitoring in harsh
environments.

Applications
• Pump control
• HVAC systems
• temperature control and chiller systems
• renewable energies such as heat pumps, solar
thermals, fresh water and micro-CHP systems
• monitoring and control systems
• water treatment plants
• water utility and distribution systems
• HPC and IT cooling systems.

Features and benefits


• Differential pressure and temperature measurement
in one transmitter (two-in-one solution) for easy and
cost-efficient installation (DPI II+T)
• MEMS technology.
• direct contact with the aqueous media resulting in a
fast response time
• plug and play for quick setup
• smart system solution with Grundfos pump controls
• compact and robust design
• compatible with aqueous media
• suitable for a wide temperature range
• suitable for a wide range of applications.

27
Pressure sensors
5
Electrical connections
Differential Pressure transmitter, Industry

2 1
3 4

TM06 1070 1514


Fig. 72 Electrical connections

DPI II
Signal condition: 2-wire (loop-powered)
Pin 1 2 3 4

Wire colour Brown White Blue Black


Pressure
Power
I/O Not used signal Not used
supply
4-20 mA

DPI II+T
Signal condition: 4-wire
Pin 1 2 3 4

Wire colour Brown White Blue Black


Pressure Temperature
Power
I/O signal GND* signal
supply
0-10 V 0-10 V

* Common ground for pressure and temperature signals. Power


supply, screened cable: SELV or PELV.

Directives
The Grundfos Direct Sensors™ are in conformity
with these council directives on the approximation of
the laws of the EC member states:
• Low Voltage Directive (2014/35/EU)
– Standards used: EN 61010-1:2010
• EMC Directive (2014/30/EU).
– Standards used: EN 61326-1:2013 and EN
61326-2-3:2013
The GRUNDFOS Direct Sensors™ are exempted from
the Pressure Equipment Directive (PED) according to
Article 4, paragraph 3 in the PED 2014/68/EU.

28
Pressure sensors
5
DPI II and DPI II+T, 0 - 0.6 bar (0 - Specifications

Differential Pressure transmitter, Industry


8.7 psid) Pressure
Measuring range 0 - 0.6 bar (0 - 8.7 psid)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Response time Less than 100 ms (typically 50 ms)
System pressure deviation 6 mbar/bar (0.09 psid/psig)

TM04 9239 3510


Resolution 1/1000 FS
Temperature, DPI II+T with temperature output
Measuring range 0-100 °C (32-212 °F)
Accuracy (± 1 σ),
±1K
Fig. 73 DPI II and DPI II+T transmitter 0-80 °C (32-176 °F)
Accuracy (± 1 σ),
±2K
0-100 °C (32-212 °F)
Dimensions
Response time for sensor
Less than 100 ms (typically 50 ms)
electronics
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
B

Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)


D Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
Storage temperature -55 to +70 °C (-67 to +158 °F)
Humidity, relative 0-95 % RH, non-condensing
TM04 9238 0415

Maximum system pressure 30 bar (435 psig)


C
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
A Maximum p2-p1 pressure 10 bar (145 psid)
Electrical data, DPI II without temperature output
Fig. 74 Dimensions, DPI II and DPI II+T
Power supply, DPI II 12.5 - 30 VDC
Output signals 4-20 mA
A B C D – Signal cut off 21 mA
mm 36.95 110 ISO 228/1 - 7/16 - 20 UNF Maximum power consumption 660 mW
in 1.45 4.33 G 1/2 0.25" flare 60 Ω at 12.5 VDC
100 Ω at 13.3 VDC
Maximum load impedance
Output signals 600 Ω at 24 VDC
900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Electrical data, DPI II+T with temperature output
Power supply, DPI II+T 16.6 - 30 VDC
Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
Minimum load impedance 10 kΩ
TM06 3358 1716

Maximum cable length 30 m (98 ft)


Materials
Sensing element Silicon-based MEMS
P max O-ring EPDM or FKM
Housing Stainless steel 1.4404 (AISI 316 L)
Fig. 75 Pressure response, DPI II Corrosion-resistant coating
Wetted materials EPDM or FKM
Stainless steel 1.4404 (AISI 316 L)
Environmental standards
10V Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 76 Pressure and temperature response, DPI II+T

29
Pressure sensors
5
DPI II and DPI II+T, 0 - 1.0 bar (0 - Specifications
Differential Pressure transmitter, Industry

14.5 psid) Pressure


Measuring range 0 - 1.0 bar (0 - 14.5 psid)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Response time Less than 100 ms (typically 50 ms)
System pressure deviation 6 mbar/bar (0.09 psid/psig)

TM04 9239 3510


Resolution 1/1000 FS
Temperature, DPI II+T with temperature output
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
±1K
Fig. 77 DPI II and DPI II+T transmitter 0-80 °C (32-176 °F)
Accuracy (± 1 σ),
±2K
Dimensions 0-120 °C (32-248 °F)
Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
B

Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)


D
Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
Storage temperature -55 to +70 °C (-67 to +158 °F)
TM04 9238 0415

Humidity, relative 0-95 % RH, non-condensing


C Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
A
Maximum p2-p1 pressure 10 bar (145 psid)
Fig. 78 Dimensions, DPI II and DPI II+T Electrical data, DPI II without temperature output
Power supply, DPI II 12.5 - 30 VDC
A B C D Output signals 4-20 mA
– Signal cut off 21 mA
mm 36.95 110 ISO 228/1 - 7/16 - 20 UNF
Maximum power consumption 660 mW
in 1.45 4.33 G 1/2 0.25" flare
60 Ω at 12.5 VDC
100 Ω at 13.3 VDC
Output signals Maximum load impedance
600 Ω at 24 VDC
900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Electrical data, DPI II+T with temperature output
Power supply, DPI II+T 16.6 - 30 VDC
Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
TM06 3358 1716

Minimum load impedance 10 kΩ


Maximum cable length 30 m (98 ft)
Materials
Sensing element Silicon-based MEMS
P max
O-ring EPDM or FKM
Fig. 79 Pressure response, DPI II Housing Stainless steel 1.4404 (AISI 316 L)
Corrosion-resistant coating
Wetted materials EPDM or FKM
Stainless steel 1.4404 (AISI 316 L)
Environmental standards
10V
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 80 Pressure and temperature response, DPI II+T

30
Pressure sensors
5
DPI II and DPI II+T, 0 - 1.6 bar (0 - Specifications

Differential Pressure transmitter, Industry


23.2 psid) Pressure
Measuring range 0 - 1.6 bar (0 - 23.2 psid)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Response time Less than 100 ms (typically 50 ms)
System pressure deviation 6 mbar/bar (0.09 psid/psig)

TM04 9239 3510


Resolution 1/1000 FS
Temperature, DPI II+T with temperature output
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
±1K
Fig. 81 DPI II and DPI II+T transmitter 0-80 °C (32-176 °F)
Accuracy (± 1 σ),
±2K
0-120 °C (32-248 °F)
Dimensions
Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
B

Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)


D Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
Storage temperature -55 to +70 °C (-67 to +158 °F)
TM04 9238 0415

Humidity, relative 0-95 % RH, non-condensing


Maximum system pressure 30 bar (435 psig)
C
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
A Maximum p2-p1 pressure 10 bar (145 psid)
Fig. 82 Dimensions, DPI II and DPI II+T Electrical data, DPI II without temperature output
Power supply, DPI II 12.5 - 30 VDC
A B C D Output signals 4-20 mA
– Signal cut off 21 mA
mm 36.95 110 ISO 228/1 - 7/16 - 20 UNF Maximum power consumption 660 mW
in 1.45 4.33 G 1/2 0.25" flare 60 Ω at 12.5 VDC
100 Ω at 13.3 VDC
Output signals Maximum load impedance
600 Ω at 24 VDC
900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Electrical data, DPI II+T with temperature output
Power supply, DPI II+T 16.6 - 30 VDC
Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
Minimum load impedance 10 kΩ
TM06 3358 1716

Maximum cable length 30 m (98 ft)


Materials
Sensing element Silicon-based MEMS
P max O-ring EPDM or FKM
Fig. 83 Pressure response, DPI II Housing Stainless steel 1.4404 (AISI 316 L)
Corrosion-resistant coating
Wetted materials EPDM or FKM
Stainless steel 1.4404 (AISI 316 L)
Environmental standards
10V
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 84 Pressure and temperature response, DPI II+T

31
Pressure sensors
5
DPI II and DPI II+T, 0 - 2.5 bar (0 - Specifications
Differential Pressure transmitter, Industry

36.3 psid) Pressure


Measuring range 0 - 2.5 bar (0 - 36.3 psid)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Response time Less than 100 ms (typically 50 ms)

TM04 9239 3510


System pressure deviation 6 mbar/bar (0.09 psid/psig)
Resolution 1/1000 FS
Temperature, DPI II+T with temperature output
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
±1K
Fig. 85 DPI II and DPI II+T transmitter 0-80 °C (32-176 °F)
Accuracy (± 1 σ),
±2K
Dimensions 0-120 °C (32-248 °F)
Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
B

Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)


D
Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
Storage temperature -55 to +70 °C (-67 to +158 °F)
TM04 9238 0415

Humidity, relative 0-95 % RH, non-condensing


C Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
A
Maximum p2-p1 pressure 10 bar (145 psid)
Fig. 86 Dimensions, DPI II and DPI II+T Electrical data, DPI II without temperature output
Power supply, DPI II 12.5 - 30 VDC
A B C D Output signals 4-20 mA
– Signal cut off 21 mA
mm 36.95 110 ISO 228/1 - 7/16 - 20 UNF
Maximum power consumption 660 mW
in 1.45 4.33 G 1/2 0.25" flare
60 Ω at 12.5 VDC
100 Ω at 13.3 VDC
Output signals Maximum load impedance
600 Ω at 24 VDC
900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Electrical data, DPI II+T with temperature output
Power supply, DPI II+T 16.6 - 30 VDC
Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
TM06 3358 1716

Minimum load impedance 10 kΩ


Maximum cable length 30 m (98 ft)
Materials
Sensing element Silicon-based MEMS
P max
O-ring EPDM or FKM
Fig. 87 Pressure response, DPI II Housing Stainless steel 1.4404 (AISI 316 L)
Corrosion-resistant coating
Wetted materials EPDM or FKM
Stainless steel 1.4404 (AISI 316 L)
Environmental standards
10V
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 88 Pressure and temperature response, DPI II+T

32
Pressure sensors
5
DPI II and DPI II+T, 0 - 4.0 bar (0 - Specifications

Differential Pressure transmitter, Industry


58.0 psid) Pressure
Measuring range 0 - 4.0 bar (0 - 58.0 psid)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Response time Less than 100 ms (typically 50 ms)
System pressure deviation 6 mbar/bar (0.09 psid/psig)

TM04 9239 3510


Resolution 1/1000 FS
Temperature, DPI II+T with temperature output
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
±1K
Fig. 89 DPI II and DPI II+T transmitter 0-80 °C (32-176 °F)
Accuracy (± 1 σ),
±2K
0-120 °C (32-248 °F)
Dimensions
Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
B

Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)


D
Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
Storage temperature -55 to +70 °C (-67 to +158 °F)
TM04 9238 0415

Humidity, relative 0-95 % RH, non-condensing


C
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
A Maximum p2-p1 pressure 10 bar (145 psid)
Fig. 90 Dimensions, DPI II and DPI II+T Electrical data, DPI II without temperature output
Power supply, DPI II 12.5 - 30 VDC
A B C D Output signals 4-20 mA
– Signal cut off 21 mA
mm 36.95 110 ISO 228/1 - 7/16 - 20 UNF
Maximum power consumption 660 mW
in 1.45 4.33 G 1/2 0.25" flare
60 Ω at 12.5 VDC
100 Ω at 13.3 VDC
Output signals Maximum load impedance
600 Ω at 24 VDC
900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Electrical data, DPI II+T with temperature output
Power supply, DPI II+T 16.6 - 30 VDC
Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
TM06 3358 1716

Minimum load impedance 10 kΩ


Maximum cable length 30 m (98 ft)
Materials
Sensing element Silicon-based MEMS
P max O-ring EPDM or FKM
Fig. 91 Pressure response, DPI II Housing Stainless steel 1.4404 (AISI 316 L)
Corrosion-resistant coating
Wetted materials EPDM or FKM
Stainless steel 1.4404 (AISI 316 L)
Environmental standards
10V
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 92 Pressure and temperature response, DPI II+T

33
Pressure sensors
5
DPI II and DPI II+T, 0 - 6.0 bar (0 - Specifications
Differential Pressure transmitter, Industry

87.0 psid) Pressure


Measuring range 0 - 6.0 bar (0 - 87.0 psid)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Response time Less than 100 ms (typically 50 ms)
System pressure deviation 6 mbar/bar (0.09 psid/psig)

TM04 9239 3510


Resolution 1/1000 FS
Temperature, DPI II+T with temperature output
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
±1K
Fig. 93 DPI II and DPI II+T transmitter 0-80 °C (32-176 °F)
Accuracy (± 1 σ),
±2K
0-120 °C (32-248 °F)
Dimensions
Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
B

Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)


D
Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
Storage temperature -55 to +70 °C (-67 to +158 °F)
TM04 9238 0415

Humidity, relative 0-95 % RH, non-condensing


C
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
A Maximum p2-p1 pressure 10 bar (145 psid)
Fig. 94 Dimensions, DPI II and DPI II+T Electrical data, DPI II without temperature output
Power supply, DPI II 12.5 - 30 VDC
A B C D Output signals 4-20 mA
– Signal cut off 21 mA
mm 36.95 110 ISO 228/1 - 7/16 - 20 UNF
Maximum power consumption 660 mW
in 1.45 4.33 G 1/2 0.25" flare
60 Ω at 12.5 VDC
100 Ω at 13.3 VDC
Output signals Maximum load impedance
600 Ω at 24 VDC
900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Electrical data, DPI II+T with temperature output
Power supply, DPI II+T 16.6 - 30 VDC
Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
TM06 3358 1716

Minimum load impedance 10 kΩ


Maximum cable length 30 m (98 ft)
Materials
Sensing element Silicon-based MEMS
P max O-ring EPDM or FKM
Fig. 95 Pressure response, DPI II Housing Stainless steel 1.4404 (AISI 316 L)
Corrosion-resistant coating
Wetted materials EPDM or FKM
Stainless steel 1.4404 (AISI 316 L)
Environmental standards
10V
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 96 Pressure and temperature response, DPI II+T

34
Pressure sensors
5
DPI II and DPI II+T, 0 - 10.0 bar (0 - Specifications

Differential Pressure transmitter, Industry


145.0 psid) Pressure
Measuring range 0 - 10.0 bar (0 - 145.0 psid)
Accuracy (± 1 σ),
± 2 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 2.5 % FS
-30 to +100 °C (-22 to +212 °F)
Response time Less than 100 ms (typically 50 ms)
System pressure deviation 6 mbar/bar (0.09 psid/psig)

TM04 9239 3510


Resolution 1/1000 FS
Temperature, DPI II+T with temperature output
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
±1K
Fig. 97 DPI II and DPI II+T transmitter 0-80 °C (32-176 °F)
Accuracy (± 1 σ),
±2K
Dimensions 0-120 °C (32-248 °F)
Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
B

Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)


D
Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
Storage temperature -55 to +70 °C (-67 to +158 °F)
TM04 9238 0415

Humidity, relative 0-95 % RH, non-condensing


C Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
A
Maximum p2-p1 pressure 10 bar (145 psid)
Fig. 98 Dimensions, DPI II and DPI II+T Electrical data, DPI II without temperature output
Power supply, DPI II 12.5 - 30 VDC
A B C D Output signals 4-20 mA
– Signal cut off 21 mA
mm 36.95 110 ISO 228/1 - 7/16 - 20 UNF
Maximum power consumption 660 mW
in 1.45 4.33 G 1/2 0.25" flare
60 Ω at 12.5 VDC
100 Ω at 13.3 VDC
Output signals Maximum load impedance
600 Ω at 24 VDC
900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Electrical data, DPI II+T with temperature output
Power supply, DPI II+T 16.6 - 30 VDC
Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
TM06 3358 1716

Minimum load impedance 10 kΩ


Maximum cable length 30 m (98 ft)
Materials
Sensing element Silicon-based MEMS
P max
O-ring EPDM or FKM
Fig. 99 Pressure response, DPI II Housing Stainless steel 1.4404 (AISI 316 L)
Corrosion-resistant coating
Wetted materials EPDM or FKM
Stainless steel 1.4404 (AISI 316 L)
Environmental standards
10V
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 100 Pressure and temperature response, DPI II+T

35
Pressure sensors
5
DPI II and DPI II+T, 0 - 16.0 bar (0 - Specifications
Differential Pressure transmitter, Industry

232.1 psid) Pressure


Measuring range 0 - 16.0 bar (0 - 232.1 psid)
Accuracy (± 1 σ),
± 2.5 % FS
0-80 °C (32-176 °F)
Accuracy (± 1 σ),
± 3 % FS
-30 to +100 °C (-22 to +212 °F)
Response time Less than 100 ms (typically 50 ms)
System pressure deviation 6 mbar/bar (0.09 psid/psig)

TM04 9239 3510


Resolution 1/1000 FS
Temperature, DPI II+T with temperature output
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
±1K
Fig. 101 DPI II and DPI II+T transmitter 0-80 °C (32-176 °F)
Accuracy (± 1 σ),
±2K
0-120 °C (32-248 °F)
Dimensions
Response time for sensor Less than 100 ms
electronics (typically 50 ms)
Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
B

Liquid temperature, operation -30 to +120 °C (-22 to +248 °F)


D Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
Storage temperature -55 to +70 °C (-67 to +158 °F)
TM04 9238 0415

Humidity, relative 0-95 % RH, non-condensing


Maximum system pressure 30 bar (435 psig)
C
Burst pressure 40 bar (580 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
A Maximum p2-p1 pressure 10 bar (145 psid)
Fig. 102 Dimensions, DPI II and DPI II+T Electrical data, DPI II without temperature output
Power supply, DPI II 12.5 - 30 VDC
A B C D Output signals 4-20 mA
– Signal cut off 21 mA
mm 36.95 110 ISO 228/1 - 7/16 - 20 UNF Maximum power consumption 660 mW
in 1.45 4.33 G 1/2 0.25" flare 60 Ω at 12.5 VDC
100 Ω at 13.3 VDC
Output signals Maximum load impedance
600 Ω at 24 VDC
900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Electrical data, DPI II+T with temperature output
Power supply, DPI II+T 16.6 - 30 VDC
Output signals 0-10 VDC
(0 V at 0 °C, 10 V at 100 °C)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
Minimum load impedance 10 kΩ
TM06 3358 1716

Maximum cable length 30 m (98 ft)


Materials
Sensing element Silicon-based MEMS
P max O-ring EPDM or FKM
Fig. 103 Pressure response, DPI II Housing Stainless steel 1.4404 (AISI 316 L)
Corrosion-resistant coating
Wetted materials EPDM or FKM
Stainless steel 1.4404 (AISI 316 L)
Environmental standards
10V
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
TM06 3359 1716

0
0 P max
T max

Fig. 104 Pressure and temperature response, DPI II+T

36
Pressure sensors
6

6. Relative Pressure sensor Standard, RPS

Relative Pressure sensor Standard, RPS


General data Pressure range
Pressure range

[bar] [psig]
0 - 0.6 0 - 8.7
0 - 1.0 0 - 14.5
0 - 1.6 0 - 23.2

TM06 1286 2214


TM06 1287 2214
0 - 2.5 0 - 36.3
0 - 4.0 0 - 58.0
0 - 6.0 0 - 87.0
0 - 10.0 0 - 145.0
0 - 16.0 0 - 232.0
Fig. 105 RPS sensor
Approvals (w/EPDM O-rings)
Technical overview
• WRAS
The RPS is a combined pressure and temperature
• KTW
sensor (two-in-one) from Grundfos Direct Sensors™.
• AS 4020
The RPS sensor is fully compatible with wet, aqueous
media. The sensor is based on MEMS sensing • ACS.
technology in combination with the corrosion-resistant
Silicoat® coating technology on the sensor chip. Certificates

Applications
• Pump control + 75
• HVAC systems CE C, CSA, US EAC
• temperature control and chiller systems
• renewable energies such as heat pumps, solar
thermals, fresh water and micro-CHP systems
• monitoring and control systems
• water treatment plants
• water utility and distribution systems
• HPC and IT cooling systems.

Features and benefits


• Pressure and temperature measurement in one
sensor (two-in-one solution) for easy and cost-
efficient installation
• MEMS technology.
• direct contact with the aqueous media resulting in a
fast response time
• plug and play for quick setup
• smart system solution with Grundfos pump controls
• compact and robust design
• compatible with aqueous media
• suitable for a wide temperature range
• suitable for a wide range of applications.

37
Pressure sensors
6
Electrical connections
Relative Pressure sensor Standard, RPS

Analogue signal Digital signal

Electrical
connector

1 2 3 4 Pin No 1 2 3 4

Temperature signal

V Pressure signal 3Y

V 5Y

TM04 7156 1610


Pipe system

PE PE

Fig. 106 Electrical connections

Description Description
Pin Colour
Analogue signal Digital signal
1 Temperature signal Rx Yellow
2 Pressure signal Tx White
3 GND, 0 V PELV GND, 0 V PELV Green
4 Voltage supply, +5 VDC Power supply, +5 VDC Brown

Power supply requirements


• VDC +/- 5 % PELV (Ratiometric)
• The sensor must be separated from hazardous live
circuitry by double or reinforced insulation
• Max 10 mV ripple, 50 Hz
• Min output current 25 mA
• Grounding of sensor supply is required

Options
TM06 6670 2016
TM06 6671 2016

Fig. 107 Sensor options

Description
1/2'' nipple, stainless steel (316L)

Differential Temperature
The differential temperature is between two standard
Direct SensorsTM from GRUNDFOS.

Directives
The Grundfos Direct Sensors™ are in conformity
with these council directives on the approximation of
the laws of the EC member states:
• Low Voltage Directive (2014/35/EU)
– Standards used: EN 61010-1:2010
• EMC Directive (2014/30/EU).
– Standards used: EN 61326-1:2013 and EN
61326-2-3:2013
The GRUNDFOS Direct Sensors™ are exempted from
the Pressure Equipment Directive (PED) according to
Article 4, paragraph 3 in the PED 2014/68/EU.

38
Pressure sensors
6
RPS, 0 - 0.6 bar (0 - 8.7 psig) Specifications

Relative Pressure sensor Standard, RPS


Pressure
Measuring range 0 - 0.6 bar (0 - 8.7 psig)
Accuracy (± 1 σ), in water,
± 1.5 % FS
15-90 °C (59-194 °F)
Accuracy (± 1 σ), in water,
± 2 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 1 s
Resolution 0.6 mbar (0.009 psig)
Temperature
Measuring range 0-120 °C (32-248 °F)

TM06 1287 2214


Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Response time for sensor
250 ms
electronics
Fig. 108 RPS sensor Resolution 0.008 K

Dimensions Differential Temperature


Accuracy 15-90 °C (59-194 °F) 0.3 K
D E Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
C

Liquid temperature, operation 0-120 °C (32-248 °F)


-25 to +120 °C (-13 to +248 °F),
B

Liquid temperature, peak


non-freezing
Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
TM05 4669 2512

Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)


Humidity, relative 0-95 %, non-condensing
A F Maximum system pressure 24 bar (348 psig)
Burst Pressure 30 bar (435 psig)
G
Electrical data
Fig. 109 Dimensions, RPS
5 VDC (± 5 %), PELV
Power supply Grounding of sensor supply
A B C D E F G required.
Output signals Ratiometric
mm 4.5 53.7 27 20 39.9 10.2 14.8
Digital output signals Grundfos open data protocol
in 0.18 2.11 1.06 0.79 1.57 0.40 0.58
0.5-3.5 V for pressure
(zero at 0.5 V)
Analog output signals
Output signals 0.5-4.1 V for temperature
(zero at 0.5 V and 100 °C at 3.5 V)
[V] Power consumption Appr. 75 mW
Load impedance > 47 kΩ
Pressure output signal

Maximum cable length 3 m (9.10 ft)


Materials
Sensor Silicon-based MEMS
TM06 3360 5214

EPDM O-rings, FKM O-rings or


Sealing EPDM sealing cap with FKM O-
rings
Housing Composite, PPS
Corrosion-resistant coating, PPS,
P max
EPDM or FKM
Wetted materials
Fig. 110 Pressure response in Analogue mode Adapter ISO 7/1 - R1/2" and NPT 1/
2", EN 1.4408 (AISI 316)
Environmental standards
[V]
Temperature output signal

4.5 Enclosure class IP44


4.0 Temperature cycling IEC 68-2-14
3.5 Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
3.0
Electromagnetic compatibility EN 61326-1
2.5
2.0
1.5
1.0
TM06 3354 5214

0.5
0.0
0 120
T max =
peak temperature

Fig. 111 Temperature response in Analogue mode

39
Pressure sensors
6
RPS, 0 - 1.0 bar (0 - 14.5 psig) Specifications
Relative Pressure sensor Standard, RPS

Pressure
Measuring range 0 - 1.0 bar (0 - 14.5 psig)
Accuracy (± 1 σ),
± 1.5 % FS
15-90°C (59-194°F)
Accuracy (± 1 σ),
± 2 % FS
0-120 °C (32-248 °F)
Response time Less than 1 s
Resolution 0.6 mbar (0.009 psig)
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)

TM06 1287 2214


Response time for sensor
250 ms
electronics
Resolution 0.008 K
Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
Fig. 112 RPS sensor Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
Dimensions Aqueous media compatible with
Liquid types
wetted materials
D E Liquid temperature, operation 0-120 °C (32-248 °F)
-25 to +120 °C (-13 to +248 °F),
Liquid temperature, peak
non-freezing
Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
C

Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)


Humidity, relative 0-95 %, non-condensing
B

Maximum system pressure 24 bar (348 psig)


Burst pressure 30 bar (435 psig)
TM05 4669 2512

Electrical data
5 VDC (± 5 %), PELV
A F Power supply Grounding of sensor supply
required.
G
Output signals Ratiometric
Fig. 113 Dimensions, RPS Digital output signals Grundfos open data protocol
0.5-3.5 V for pressure
(zero at 0.5 V)
A B C D E F G Analog output signals
0.5-4.1 V for temperature
mm 4.5 53.7 27 20 39.9 10.2 14.8 (zero at 0.5 V and 100 °C at 3.5 V)
in 0.18 2.11 1.06 0.79 1.57 0.40 0.58 Power consumption Appr. 75 mW
Load impedance > 47 kΩ
Output signals Maximum cable length 3 m (9.10 ft)
Materials
[V] Sensor Silicon-based MEMS
EPDM O-rings, FKM O-rings or
Pressure output signal

Sealing EPDM sealing cap with FKM O-


rings
Housing Composite (PPS)
Corrosion-resistant coating, PPS,
TM06 3360 5214

EPDM or FKM
Wetted materials
Adapter ISO 7/1 - R1/2" and NPT 1/
2" EN 1.4408 (AISI 316)
Environmental standards
P max
Enclosure class IP44, cable connected
Fig. 114 Pressure response in Analogue mode Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
[V] Electromagnetic compatibility EN 61326-1
Temperature output signal

4.5
4.0
3.5
3.0
2.5
2.0
1.5
TM06 3354 5214

1.0
0.5
0.0
0 120
T max =
peak temperature
Fig. 115 Temperature response in Analogue mode

40
Pressure sensors
6
RPS, 0 - 1.6 bar (0 - 23.2 psig) Specifications

Relative Pressure sensor Standard, RPS


Pressure
Measuring range 0 - 1.6 bar (0 - 23.2 psig)
Accuracy (± 1 σ),
± 1 % FS
15-90°C (59-194°F)
Accuracy (± 1 σ),
± 1.5 % FS
0-120 °C (32-248 °F)
Response time Less than 1 s
Resolution 0.6 mbar (0.009 psig)
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)

TM06 1287 2214


Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Response time for sensor
250 ms
electronics
Resolution 0.008 K
Fig. 116 RPS sensor Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
Dimensions Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
D E
Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation 0-120 °C (32-248 °F)
-25 to +120 °C (-13 to +248 °F),
C

Liquid temperature, peak


non-freezing
B

Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)


Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
TM05 4669 2512

Maximum system pressure 24 bar (348 psig)


Burst Pressure 30 bar (435 psig)
A F Electrical data
G 5 VDC (± 5 %), PELV
Power supply Grounding of sensor supply
Fig. 117 Dimensions, RPS required.
Output signals Ratiometric
A B C D E F G Digital output signals Grundfos open data protocol
mm 4.5 53.7 27 20 39.9 10.2 14.8 0.5-3.5 V for pressure
(zero at 0.5 V)
in 0.18 2.11 1.06 0.79 1.57 0.40 0.58 Analog output signals
0.5-4.1 V for temperature
(zero at 0.5 V and 100 °C at 3.5 V)
Output signals Power consumption Appr. 75 mW
Load impedance > 47 kΩ
[V] Maximum cable length 3 m (9.10 ft)
Materials
Pressure output signal

Sensor Silicon-based MEMS


EPDM O-rings, FKM O-rings or
Sealing EPDM sealing cap with FKM O-
rings
TM06 3360 5214

Housing Composite, PPS


Corrosion-resistant coating, PPS,
EPDM or FKM
Wetted materials
Adapter ISO 7/1 - R1/2" and NPT
P max 1/2", EN 1.4408 (AISI 316)
Fig. 118 Pressure response in Analogue mode Environmental standards
Enclosure class IP44, cable connected
[V] Temperature cycling IEC 68-2-14
Temperature output signal

4.5 Vibration, non-destructive 20-2000 Hz, 10 G, 4 h


4.0 Electromagnetic compatibility EN 61326-1
3.5
3.0
2.5
2.0
1.5
1.0
TM06 3354 5214

0.5
0.0
0 120
T max =
peak temperature

Fig. 119 Temperature response in Analogue mode

41
Pressure sensors
6
RPS, 0 - 2.5 bar (0 - 36.3 psig) Specifications
Relative Pressure sensor Standard, RPS

Pressure
Measuring range 0 - 2.5 bar (0 - 36.3 psig)
Accuracy (± 1 σ),
± 1 % FS
15-90°C (59-194°F)
Accuracy (± 1 σ),
± 1.5 % FS
0-120 °C (32-248 °F)
Response time Less than 1 s
Resolution 0.6 mbar (0.009 psig)
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)

TM06 1287 2214


Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Response time for sensor
250 ms
electronics
Resolution 0.008 K

Fig. 120 RPS sensor Differential Temperature


Accuracy 15-90 °C (59-194 °F) 0.3 K
Dimensions Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
D E Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation 0-120 °C (32-248 °F)
-25 to +120 °C (-13 to +248 °F),
Liquid temperature, peak
non-freezing
C

Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)


B

Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)


Humidity, relative 0-95 %, non-condensing
Maximum system pressure 24 bar (348 psig)
TM05 4669 2512

Burst Pressure 30 bar (435 psig)

A Electrical data
F
5 VDC (± 5 %), PELV
G Power supply Grounding of sensor supply
required.
Fig. 121 Dimensions, RPS Output signals Ratiometric
Digital output signals Grundfos open data protocol
0.5-3.5 V for pressure
A B C D E F G
(zero at 0.5 V)
Analog output signals
mm 4.5 53.7 27 20 39.9 10.2 14.8 0.5-4.1 V for temperature
in 0.18 2.11 1.06 0.79 1.57 0.40 0.58 (zero at 0.5 V and 100 °C at 3.5 V)
Power consumption Appr. 75 mW
Output signals Load impedance > 47 kΩ
Maximum cable length 3 m (9.10 ft)
[V] Materials
Sensor Silicon-based MEMS
Pressure output signal

EPDM O-rings, FKM O-rings or


Sealing EPDM sealing cap with FKM O-
rings
Housing Composite, PPS
TM06 3360 5214

Corrosion-resistant coating, PPS,


EPDM or FKM
Wetted materials
Adapter ISO 7/1 - R1/2" and NPT 1/
2", EN 1.4408 (AISI 316)
P max Environmental standards
Fig. 122 Pressure response in Analogue mode Enclosure class IP44, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
[V]
Temperature output signal

Electromagnetic compatibility EN 61326-1


4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
TM06 3354 5214

0.5
0.0
0 120
T max =
peak temperature

Fig. 123 Temperature response in Analogue mode

42
Pressure sensors
6
RPS, 0 - 4.0 bar (0 - 58.0 psig) Specifications

Relative Pressure sensor Standard, RPS


Pressure
Measuring range 0 - 4.0 bar (0 - 58.0 psig)
Accuracy (± 1 σ),
± 1 % FS
15-90°C (59-194°F)
Accuracy (± 1 σ),
± 1.5 % FS
0-120 °C (32-248 °F)
Response time Less than 1 s
Resolution 0.6 mbar (0.009 psig)
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)

TM06 1287 2214


Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Response time for sensor
250 ms
electronics
Resolution 0.008 K

Fig. 124 RPS sensor Differential Temperature


Accuracy 15-90 °C (59-194 °F) 0.3 K
Dimensions Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
D E Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation 0-120 °C (32-248 °F)
-25 to +120 °C (-13 to +248 °F),
Liquid temperature, peak
non-freezing
C

Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)


B

Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)


Humidity, relative 0-95 %, non-condensing
Maximum system pressure 24 bar (348 psig)
TM05 4669 2512

Burst Pressure 30 bar (435 psig)


Electrical data
A F
5 VDC (± 5 %), PELV
G Power supply Grounding of sensor supply
required.
Fig. 125 Dimensions, RPS Output signals Ratiometric
Digital output signals Grundfos open data protocol
0.5-3.5 V for pressure
A B C D E F G (zero at 0.5 V)
Analog output signals
mm 4.5 53.7 27 20 39.9 10.2 14.8 0.5-4.1 V for temperature
in 0.18 2.11 1.06 0.79 1.57 0.40 0.58 (zero at 0.5 V and 100 °C at 3.5 V)
Power consumption Appr. 75 mW
Output signals Load impedance > 47 kΩ
Maximum cable length 3 m (9.10 ft)
[V] Materials
Sensor Silicon-based MEMS
Pressure output signal

EPDM O-rings, FKM O-rings or


Sealing EPDM sealing cap with FKM O-
rings
Housing Composite, PPS
TM06 3360 5214

Corrosion-resistant coating, PPS,


EPDM or FKM
Wetted materials
Adapter ISO 7/1 - R1/2" and NPT 1/
2" EN 1.4408 (AISI 316)
P max Environmental standards
Fig. 126 Pressure response in Analogue mode Enclosure class IP44, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
[V]
Electromagnetic compatibility EN 61326-1
Temperature output signal

4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
TM06 3354 5214

0.5
0.0
0 120
T max =
peak temperature

Fig. 127 Temperature response in Analogue mode

43
Pressure sensors
6
RPS, 0 - 6.0 bar (0 - 87.0 psig) Specifications
Relative Pressure sensor Standard, RPS

Pressure
Measuring range 0 - 6.0 bar (0 - 87.0 psig)
Accuracy (± 1 σ),
± 1 % FS
15-90°C (59-194°F)
Accuracy (± 1 σ),
± 1.5 % FS
0-120 °C (32-248 °F)
Response time Less than 1 s
Resolution 0.6 mbar (0.009 psig)
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)

TM06 1287 2214


Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Response time for sensor
250 ms
electronics
Resolution 0.008 K

Fig. 128 RPS sensor Differential Temperature


Accuracy 15-90 °C (59-194 °F) 0.3 K
Dimensions Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
D E Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation 0-120 °C (32-248 °F)
-25 to +120 °C (-13 to +248 °F), non-
Liquid temperature, peak
freezing
C

Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)


B

Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)


Humidity, relative 0-95 %, non-condensing
Maximum system pressure 24 bar (348 psig)
TM05 4669 2512

Burst Pressure 30 bar (435 psig)

A Electrical data
F
5 VDC (± 5 %), PELV
G Power supply Grounding of sensor supply
required.
Fig. 129 Dimensions, RPS Output signals Ratiometric
Digital output signals Grundfos open data protocol
0.5-3.5 V for pressure (zero at 0.5 V)
A B C D E F G
Analog output signals 0.5-4.1 V for temperature
mm 4.5 53.7 27 20 39.9 10.2 14.8 (zero at 0.5 V and 100 °C at 3.5 V)
in 0.18 2.11 1.06 0.79 1.57 0.40 0.58 Power consumption Appr. 75 mW
Load impedance > 47 kΩ
Output signals Maximum cable length 3 m (9.10 ft)
Materials
[V]
Sensor Silicon-based MEMS
EPDM O-rings, FKM O-rings or
Sealing
Pressure output signal

EPDM sealing cap with FKM O-rings


Housing Composite (PPS)
Corrosion-resistant coating, PPS,
EPDM or FKM
TM06 3360 5214

Wetted materials
Adapter ISO 7/1 - R1/2" and NPT 1/
2" EN 1.4408 (AISI 316)
Environmental standards

P max
Enclosure class IP44, cable connected
Temperature cycling IEC 68-2-14
Fig. 130 Pressure response in Analogue mode Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
[V]
Temperature output signal

4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
TM06 3354 5214

0.5
0.0
0 120
T max =
peak temperature

Fig. 131 Temperature response in Analogue mode

44
Pressure sensors
6
RPS, 0 - 10.0 bar (0 - 145.0 psig) Specifications

Relative Pressure sensor Standard, RPS


Pressure
Measuring range 0 - 10.0 bar (0 - 145.0 psig)
Accuracy (± 1 σ),
± 1 % FS
15-90°C (59-194°F)
Accuracy (± 1 σ),
± 1.5 % FS
0-120 °C (32-248 °F)
Response time Less than 1 s
Resolution 0.6 mbar (0.009 psig)
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)

TM06 1287 2214


Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Response time for sensor
250 ms
electronics
Resolution 0.008 K

Fig. 132 RPS sensor Differential Temperature


Accuracy 15-90 °C (59-194 °F) 0.3 K
Dimensions Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
D E Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation 0-120 °C (32-248 °F)
-25 to +120 °C (-13 to +248 °F),
Liquid temperature, peak
non-freezing
C

Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)


B

Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)


Humidity, relative 0-95 %, non-condensing
Maximum system pressure 24 bar (348 psig)
TM05 4669 2512

Burst Pressure 30 bar (435 psig)

A Electrical data
F
5 VDC (± 5 %), PELV
G Power supply
Grounding of sensor supply required.
Output signals Ratiometric
Fig. 133 Dimensions, RPS Digital output signals Grundfos open data protocol
0.5-3.5 V for pressure (zero at 0.5 V)
Analog output signals 0.5-4.1 V for temperature
A B C D E F G
(zero at 0.5 V and 100 °C at 3.5 V)
mm 4.5 53.7 27 20 39.9 10.2 14.8 Power consumption Appr. 75 mW
in 0.18 2.11 1.06 0.79 1.57 0.40 0.58 Load impedance > 47 kΩ
Maximum cable length 3 m (9.10 ft)
Output signals
Materials
[V] Sensor Silicon-based MEMS
EPDM O-rings, FKM O-rings or
Sealing
Pressure output signal

EPDM sealing cap with FKM O-rings


Housing Composite, PPS
Corrosion-resistant coating, PPS,
EPDM or FKM
Wetted materials
TM06 3360 5214

Adapter ISO 7/1 - R1/2" and NPT 1/


2" EN 1.4408 (AISI 316)
Environmental standards
Enclosure class IP44, cable connected
P max
Temperature cycling IEC 68-2-14
Fig. 134 Pressure response in Analogue mode Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
[V]
Temperature output signal

4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
TM06 3354 5214

0.5
0.0
0 120
T max =
peak temperature

Fig. 135 Temperature response in Analogue mode

45
Pressure sensors
6
RPS, 0 - 16.0 bar (0 - 232.1 psid) Specifications
Relative Pressure sensor Standard, RPS

Pressure
Measuring range 0 - 16.0 bar (0 - 232.1 psid)
Accuracy (± 1 σ),
± 1 % FS
15-90°C (59-194°F)
Accuracy (± 1 σ),
± 1.5 % FS
0-120 °C (32-248 °F)
Response time Less than 1 s
Resolution 0.6 mbar (0.009 psig)
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)

TM06 1287 2214


Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Response time for sensor
250 ms
electronics
Resolution 0.008 K
Fig. 136 RPS sensor Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
Dimensions Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
D E
Aqueous media compatible with
Liquid types
wetted materials
Liquid temperature, operation 0-120 °C (32-248 °F)
-25 to +120 °C (-13 to +248 °F),
C

Liquid temperature, peak


non-freezing
B

Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)


Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
TM05 4669 2512

Maximum system pressure 24 bar (348 psig)


Burst Pressure 30 bar (435 psig)
A F
Electrical data
G 5 VDC (± 5 %), PELV
Power supply
Grounding of sensor supply required.
Fig. 137 Dimensions, RPS Output signals Ratiometric
Digital output signals Grundfos open data protocol
A B C D E F G 0.5-3.5 V for pressure (zero at 0.5 V)
Analog output signals 0.5-4.1 V for temperature
mm 4.5 53.7 27 20 39.9 10.2 14.8
(zero at 0.5 V and 100 °C at 3.5 V)
in 0.18 2.11 1.06 0.79 1.57 0.40 0.58
Power consumption Appr. 75 mW
Load impedance > 47 kΩ
Output signals Maximum cable length 3 m (9.10 ft)
Materials
[V]
Sensor Silicon-based MEMS
EPDM O-rings, FKM O-rings or
Pressure output signal

Sealing
EPDM sealing cap with FKM O-rings
Housing Composite, PPS
Corrosion-resistant coating, PPS,
TM06 3360 5214

EPDM or FKM
Wetted materials
Adapter ISO 7/1 - R1/2" and NPT 1/
2" EN 1.4408 (AISI 316)
Environmental standards
P max Enclosure class IP44, cable connected
Fig. 138 Pressure response in Analogue mode Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Electromagnetic compatibility EN 61326-1
[V]
Temperature output signal

4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
TM06 3354 5214

0.5
0.0
0 120
T max =
peak temperature

Fig. 139 Temperature response in Analogue mode

46
Pressure sensors
7

7. Differential Pressure sensor Standard, DPS

Differential Pressure sensor Standard, DPS


General data Approvals (w/EPDM O-rings)
• WRAS
• KTW
• ACS.

Certificates

TM06 1682 2614


+ 75
Fig. 140 DPS sensor CE C, CSA, US EAC

Technical overview Electrical connections


The DPS is a combined differential-pressure and Analogue signal Digital signal
temperature sensor (two-in-one) from Grundfos Direct
Electrical
Sensors™. connector
The DPS sensor is fully compatible with aqueous
1 2 3 4 1 2 3 4
media. The sensor is based on MEMS sensing Pin No
technology in combination with the corrosion-resistant Temperature signal
Silicoat® coating technology on the sensor chip.
V Pressure signal 3Y
Applications V 5Y

TM04 7156 1610


Pipe system
• Pump control
• HVAC systems
• temperature control and chiller systems PE PE

• renewable energies such as heat pumps, solar Fig. 141 Electrical connections
thermals, fresh water and micro-CHP systems
• monitoring and control systems Description Description
Pin Colour
• water treatment plants Analogue signal Digital signal

• water utility and distribution systems 1 Temperature signal Rx Yellow


2 Pressure signal Tx White
• HPC and IT cooling systems.
3 GND, 0 V PELV GND, 0 V PELV Green
4 Voltage supply, +5 VDC Power supply, +5 VDC Brown
Features and benefits
• Differential pressure and temperature measurement Power supply requirements
in one sensor (two-in-one solution) for easy and • VDC +/- 5 % PELV (Ratiometric)
cost-efficient installation • The sensor must be separated from hazardous live
• MEMS technology circuitry by double or reinforced insulation
• direct contact with the aqueous media resulting in a • Max 10 mV ripple, 50 Hz
fast response time • Min output current 25 mA
• plug and play for quick setup • Grounding of sensor supply is required
• smart system solution with Grundfos pump controls
• compact and robust design
• compatible with aqueous media
• suitable for a wide temperature range
• suitable for a wide range of applications.

Pressure range
Pressure range

[bar] [psid]
0 - 0.6 0 - 8.7
0 - 1.0 0 - 14.5
0 - 1.6 0 - 23.2
0 - 2.5 0 - 36.3
0 - 4.0 0 - 58.0
0 - 6.0 0 - 87.0

47
Pressure sensors
7
Options
Differential Pressure sensor Standard, DPS

Part

Stainless steel adapter

Fitting, 6 mm (0.23")
Tube fitting
Fitting, 8 mm (0.31")
1.4408
(AISI 316)
Fitting, 6 mm (0.23") Compression
Fitting, 8 mm (0.31") fitting

Wall bracket for DPS


with stainless steel
adapter

Differential Temperature
The differential temperature is between two standard
Direct SensorsTM from Grundfos.

Directives
The Grundfos Direct Sensors™ are in conformity
with these council directives on the approximation of
the laws of the EC member states:
• Low Voltage Directive (2014/35/EU)
– Standards used: EN 61010-1:2010
• EMC Directive (2014/30/EU).
– Standards used: EN 61326-1:2013 and
EN 61326-2-3:2013
The GRUNDFOS Direct Sensors™ are exempted from
the Pressure Equipment Directive (PED) according to
Article 4, paragraph 3 in the PED 2014/68/EU.

48
Pressure sensors
7
DPS, 0 - 0.6 bar (0 - 8.7 psid) Specifications

Differential Pressure sensor Standard, DPS


Pressure
Measuring range 0 - 0.6 bar (0 - 8.7 psid)
Accuracy (± 1 σ), in water,
± 1.5 % FS
15-90 °C (59-194 °F)
Accuracy (± 1 σ), in water,
± 2 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 1 s
System pressure deviation 6 mbar/bar (0.09 psid/psig)

TM06 1682 2614


Resolution 1.2 mbar (0.02 psid)
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
Fig. 142 DPS sensor 15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Dimensions
Response time for sensor
250 ms
electronics
A D
Resolution 0.008 K
Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
B

Accuracy 0-120 °C (32-248 °F) 0.5 K


System conditions and environment
2xH Aqueous media compatible with
G

Liquid types
wetted materials
Liquid temperature, operation 0-120 °C (32-248 °F)
TM06 3455 0115

-25 to +120 °C (-13 to +248 °F),


Liquid temperature, peak
non-freezing
Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
C F
Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
E
Humidity, relative 0-95 %, non-condensing
Fig. 143 Dimensions, DPS 24 bar (348 psig)
Maximum system pressure 16 bar (232 psig) at 70 °C (158 °F)
12 bar (145 psig) at 100 °C (212 °F)
A B C D E F G H Burst Pressure 30 bar (435 psig)
mm 20 29.9 40 39.9 35 32.9 57.9 1/8 - 27 Maximum p1-p2 pressure 16 bar (232 psid)
in 0.79 1.18 1.57 1.57 1.38 1.30 2.28 NPT Maximum p2-p1 pressure 10 bar (145 psid)
Electrical data
Output signals 5 VDC (± 5 %), PELV.
Power supply Grounding of sensor supply
[V] required.
Output signals Ratiometric
Pressure output signal

Digital output signals Grundfos open data protocol


0.5-3.5 V for pressure
(zero at 0.5 V)
Analog output signals
0.5-4.1 V for temperature
TM06 3360 5214

(zero at 0.5 V and 100 °C at 3.5 V)


Power consumption Appr. 75 mW
Load impedance > 47 kΩ
Maximum cable length 3 m (9.10 ft)
P max Materials
Fig. 144 Pressure response in Analogue mode Sensing element Silicon-based MEMS
Sealing cap EPDM
[V] Housing Composite (PPS)
Temperature output signal

4.5 Corrosion-resistant coating, PPS,


Wetted materials
4.0 EPDM or FKM,
3.5 Environmental standards
3.0
2.5 Enclosure class IP44, cable connected
2.0 Temperature cycling IEC 68-2-14
1.5 Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
1.0
TM06 3354 5214

0.5 Electromagnetic compatibility EN 61326-1


0.0
0 120
T max =
peak temperature

Fig. 145 Temperature response in Analogue mode

49
Pressure sensors
7
DPS, 0 - 1.0 bar (0 - 14.5 psid) Specifications
Differential Pressure sensor Standard, DPS

Pressure
Measuring range 0 - 1.0 bar (0 - 14.5 psid)
Accuracy (± 1 σ), in water,
± 1.5 % FS
15-90 °C (59-194 °F)
Accuracy (± 1 σ), in water,
± 2 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 1 s
System pressure deviation 6 mbar/bar (0.09 psid/psig)
Resolution 1.2 mbar (0.02 psid)
Temperature

TM06 1682 2614


Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Fig. 146 DPS sensor Response time for sensor
250 ms
electronics
Dimensions Resolution 0.008 K
Differential Temperature
A D Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
Aqueous media compatible with
Liquid types
B

wetted materials
Liquid temperature, operation 0-120 °C (32-248 °F)
-25 to +120 °C (-13 to +248 °F),
Liquid temperature, peak
non-freezing
2xH
G

Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)


Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
24 bar (348 psig)
TM06 3455 0115

Maximum system pressure 16 bar (232 psig) at 70 °C (158 °F)


12 bar (145 psig) at 100 °C (212 °F)
C F Burst Pressure 30 bar (435 psig)
E Maximum p1-p2 pressure 16 bar (232 psid)
Maximum p2-p1 pressure 10 bar (145 psid)
Fig. 147 Dimensions, DPS
Electrical data
5 VDC (± 5 %), PELV.
A B C D E F G H Power supply Grounding of sensor supply
mm 20 29.9 40 39.9 35 32.9 57.9 required.
1/8 - 27
in 0.79 1.18 1.57 1.57 1.38 1.30 2.28 NPT Output signals Ratiometric
Digital output signals Grundfos open data protocol
0.5-3.5 V for pressure
Output signals (zero at 0.5 V)
Analog output signals
0.5-4.1 V for temperature
[V] (zero at 0.5 V and 100 °C at 3.5 V)
Power consumption Appr. 75 mW
Pressure output signal

Load impedance > 47 kΩ


Maximum cable length 3 m (9.10 ft)
Materials
TM06 3360 5214

Sensing element Silicon-based MEMS


Sealing cap EPDM
Housing Composite (PPS)
Corrosion-resistant coating, PPS,
Wetted materials
P max EPDM or FKM,
Fig. 148 Pressure response in Analogue mode Environmental standards
Enclosure class IP44, cable connected
[V]
Temperature cycling IEC 68-2-14
Temperature output signal

4.5 Vibration, non-destructive 20-2000 Hz, 10 G, 4 h


4.0 Electromagnetic compatibility EN 61326-1
3.5
3.0
2.5
2.0
1.5
TM06 3354 5214

1.0
0.5
0.0
0 120
T max =
peak temperature
Fig. 149 Temperature response in Analogue mode

50
Pressure sensors
7
DPS, 0 - 1.6 bar (0 - 23.2 psid) Specifications

Differential Pressure sensor Standard, DPS


Pressure
Measuring range 0 - 1.6 bar (0 - 23.2 psid)
Accuracy (± 1 σ), in water,
± 1.5 % FS
15-90 °C (59-194 °F)
Accuracy (± 1 σ), in water,
± 2 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 1 s
System pressure deviation 6 mbar/bar (0.09 psid/psig)
Resolution 1.2 mbar (0.02 psid)
Temperature

TM06 1682 2614


Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Fig. 150 DPS sensor Response time for sensor
250 ms
electronics
Dimensions Resolution 0.008 K
Differential Temperature
A D Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
Aqueous media compatible with
Liquid types
B

wetted materials
Liquid temperature, operation 0-120 °C (32-248 °F)
-25 to +120 °C (-13 to +248 °F),
Liquid temperature, peak
non-freezing
2xH
G

Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)


Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
TM06 3455 0115

24 bar (348 psig)


Maximum system pressure 16 bar (232 psig) at 70 °C (158 °F)
12 bar (145 psig) at 100 °C (212 °F)
C F Burst Pressure 30 bar (435 psig)
E Maximum p1-p2 pressure 16 bar (232 psid)
Maximum p2-p1 pressure 10 bar (145 psid)
Fig. 151 Dimensions, DPS
Electrical data
5 VDC (± 5 %), PELV.
A B C D E F G H Power supply Grounding of sensor supply
mm 20 29.9 40 39.9 35 32.9 57.9 required.
1/8 - 27
in 0.79 1.18 1.57 1.57 1.38 1.30 2.28 NPT Output signals Ratiometric
Digital output signals Grundfos open data protocol
Output signals 0.5-3.5 V for pressure
(zero at 0.5 V)
Analog output signals
0.5-4.1 V for temperature
[V] (zero at 0.5 V and 100 °C at 3.5 V)
Power consumption Appr. 75 mW
Pressure output signal

Load impedance > 47 kΩ


Maximum cable length 3 m (9.10 ft)
Materials
TM06 3360 5214

Sensing element Silicon-based MEMS


Sealing cap EPDM
Housing Composite (PPS)
Corrosion-resistant coating, PPS,
P max
Wetted materials
EPDM or FKM,
Fig. 152 Pressure response in Analogue mode Environmental standards
Enclosure class IP44, cable connected
[V] Temperature cycling IEC 68-2-14
Temperature output signal

4.5 Vibration, non-destructive 20-2000 Hz, 10 G, 4 h


4.0 Electromagnetic compatibility EN 61326-1
3.5
3.0
2.5
2.0
1.5
1.0
TM06 3354 5214

0.5
0.0
0 120
T max =
peak temperature

Fig. 153 Temperature response in Analogue mode

51
Pressure sensors
7
DPS, 0 - 2.5 bar (0 - 36.3 psid) Specifications
Differential Pressure sensor Standard, DPS

Pressure
Measuring range 0 - 2.5 bar (0 - 36.3 psid)
Accuracy (± 1 σ), in water,
± 1.5 % FS
15-90 °C (59-194 °F)
Accuracy (± 1 σ), in water,
± 2 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 1 s
System pressure deviation 6 mbar/bar (0.09 psid/psig)
Resolution 1.2 mbar (0.02 psid)
Temperature

TM06 1682 2614


Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Fig. 154 DPS sensor Response time for sensor
250 ms
electronics
Dimensions Resolution 0.008 K
Differential Temperature
A D Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
Aqueous media compatible with
Liquid types
B

wetted materials
Liquid temperature, operation 0-120 °C (32-248 °F)
-25 to +120 °C (-13 to +248 °F),
Liquid temperature, peak
non-freezing
2xH
G

Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)


Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
24 bar (348 psig)
TM06 3455 0115

Maximum system pressure 16 bar (232 psig) at 70 °C (158 °F)


12 bar (145 psig) at 100 °C (212 °F)
C F Burst Pressure 30 bar (435 psig)
E Maximum p1-p2 pressure 16 bar (232 psid)
Maximum p2-p1 pressure 10 bar (145 psid)
Fig. 155 Dimensions, DPS Electrical data
5 VDC (± 5 %), PELV.
A B C D E F G H Power supply Grounding of sensor supply
required.
mm 20 29.9 40 39.9 35 32.9 57.9 1/8 - 27
NPT Output signals Ratiometric
in 0.79 1.18 1.57 1.57 1.38 1.30 2.28
Digital output signals Grundfos open data protocol
0.5-3.5 V for pressure
Output signals (zero at 0.5 V)
Analog output signals
0.5-4.1 V for temperature
[V] (zero at 0.5 V and 100 °C at 3.5 V)
Power consumption Appr. 75 mW
Pressure output signal

Load impedance > 47 kΩ


Maximum cable length 3 m (9.10 ft)
Materials
TM06 3360 5214

Sensing element Silicon-based MEMS


Sealing cap EPDM
Housing Composite (PPS)
Corrosion-resistant coating, PPS,
Wetted materials
P max EPDM or FKM,

Fig. 156 Pressure response in Analogue mode Environmental standards


Enclosure class IP44, cable connected
Temperature cycling IEC 68-2-14
[V]
Temperature output signal

Vibration, non-destructive 20-2000 Hz, 10 G, 4 h


4.5
4.0 Electromagnetic compatibility EN 61326-1
3.5
3.0
2.5
2.0
1.5
1.0
TM06 3354 5214

0.5
0.0
0 120
T max =
peak temperature

Fig. 157 Temperature response in Analogue mode

52
Pressure sensors
7
DPS, 0 - 4.0 bar (0 - 58.0 psid) Specifications

Differential Pressure sensor Standard, DPS


Pressure
Measuring range 0 - 4.0 bar (0 - 58.0 psid)
Accuracy (± 1 σ), in water,
± 1.5 % FS
15-90 °C (59-194 °F)
Accuracy (± 1 σ), in water,
± 2 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 1 s
System pressure deviation 6 mbar/bar (0.09 psid/psig)
Resolution 1.2 mbar (0.02 psid)
Temperature

TM06 1682 2614


Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Fig. 158 DPS sensor Response time for sensor
250 ms
electronics
Dimensions Resolution 0.008 K
Differential Temperature
A D Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
Aqueous media compatible with
Liquid types
wetted materials
B

Liquid temperature, operation 0-120 °C (32-248 °F)


-25 to +120 °C (-13 to +248 °F),
Liquid temperature, peak
non-freezing
2xH
G

Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)


Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
24 bar (348 psig)
TM06 3455 0115

Maximum system pressure 16 bar (232 psig) at 70 °C (158 °F)


12 bar (145 psig) at 100 °C (212 °F)
C F Burst Pressure 30 bar (435 psig)
Maximum p1-p2 pressure 16 bar (232 psid)
E
Maximum p2-p1 pressure 10 bar (145 psid)
Fig. 159 Dimensions, DPS Electrical data
5 VDC (± 5 %), PELV.
A B C D E F G H Power supply Grounding of sensor supply
required.
mm 20 29.9 40 39.9 35 32.9 57.9 1/8 - 27
Output signals Ratiometric
in 0.79 1.18 1.57 1.57 1.38 1.30 2.28 NPT
Digital output signals Grundfos open data protocol
0.5-3.5 V for pressure
Output signals (zero at 0.5 V)
Analog output signals
0.5-4.1 V for temperature
[V] (zero at 0.5 V and 100 °C at 3.5 V)
Power consumption Appr. 75 mW
Pressure output signal

Load impedance > 47 kΩ


Maximum cable length 3 m (9.10 ft)
Materials
TM06 3360 5214

Sensing element Silicon-based MEMS


Sealing cap EPDM
Housing Composite (PPS)
Corrosion-resistant coating, PPS,
Wetted materials
P max EPDM or FKM,

Fig. 160 Pressure response in Analogue mode Environmental standards


Enclosure class IP44, cable connected
Temperature cycling IEC 68-2-14
[V]
Vibration, non-destructive 20-2000 Hz, 10 G, 4 h
Temperature output signal

4.5
4.0 Electromagnetic compatibility EN 61326-1
3.5
3.0
2.5
2.0
1.5
1.0
TM06 3354 5214

0.5
0.0
0 120
T max =
peak temperature

Fig. 161 Temperature response in Analogue mode

53
Pressure sensors
7
DPS, 0 - 6.0 bar (0 - 87.0 psid) Specifications
Differential Pressure sensor Standard, DPS

Pressure
Measuring range 0 - 6.0 bar (0 - 87.0 psid)
Accuracy (± 1 σ), in water,
± 1.5 % FS
15-90 °C (59-194 °F)
Accuracy (± 1 σ), in water,
± 2 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 1 s
System pressure deviation 6 mbar/bar (0.09 psid/psig)
Resolution 1.2 mbar (0.02 psid)
Temperature

TM06 1682 2614


Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Fig. 162 DPS sensor Response time for sensor
250 ms
electronics
Dimensions Resolution 0.008 K
Differential Temperature
A D Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
Aqueous media compatible with
Liquid types
B

wetted materials
Liquid temperature, operation 0-120 °C (32-248 °F)
-25 to +120 °C (-13 to +248 °F),
Liquid temperature, peak
non-freezing
2xH
G

Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)


Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
24 bar (348 psig)
TM06 3455 0115

Maximum system pressure 16 bar (232 psig) at 70 °C (158 °F)


12 bar (145 psig) at 100 °C (212 °F)
C F Burst Pressure 30 bar (435 psig)
E Maximum p1-p2 pressure 16 bar (232 psid)
Maximum p2-p1 pressure 10 bar (145 psid)
Fig. 163 Dimensions, DPS
Electrical data
5 VDC (± 5 %), PELV.
A B C D E F G H Power supply Grounding of sensor supply
mm 20 29.9 40 39.9 35 32.9 57.9 required.
1/8 - 27
in 0.79 1.18 1.57 1.57 1.38 1.30 2.28 NPT Output signals Ratiometric
Digital output signals Grundfos open data protocol
0.5-3.5 V for pressure
Output signals (zero at 0.5 V)
Analog output signals
0.5-4.1 V for temperature
[V] (zero at 0.5 V and 100 °C at 3.5 V)
Power consumption Appr. 75 mW
Pressure output signal

Load impedance > 47 kΩ


Maximum cable length 3 m (9.10 ft)
Materials
TM06 3360 5214

Sensing element Silicon-based MEMS


Sealing cap EPDM
Housing Composite (PPS)
Corrosion-resistant coating, PPS,
Wetted materials
P max EPDM or FKM,
Fig. 164 Pressure response in Analogue mode Environmental standards
Enclosure class IP44, cable connected
[V]
Temperature cycling IEC 68-2-14
Temperature output signal

4.5 Vibration, non-destructive 20-2000 Hz, 10 G, 4 h


4.0 Electromagnetic compatibility EN 61326-1
3.5
3.0
2.5
2.0
1.5
1.0
TM06 3354 5214

0.5
0.0
0 120
T max =
peak temperature

Fig. 165 Temperature response in Analogue mode

54
Pressure sensors
8

8. Product range

Product range
RPI transmitter
Scope of delivery:
• RPI transmitter
• 2 m (6.5 ft) cable
• quick guide.

Temperature O-ring
Complete product range Pressure range Thread Outside usage
measurement EPDM FKM
RPI/--0-0.6b/1/C/M2.00-X/EG6/--/03P/SD-1 ● ●
RPI/--0-0.6b/1/C/M2.00-X/VG6/--/03P/SD-1 0 - 0.6 bar ● ●
G 1/2
RPI/--0-0.6b/1/F/M2.00-X/EG6/--/03P/SD-1 (0 - 8.7 psig) ● ● ●
RPI/--0-0.6b/1/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●
RPI/--0-1.0b/1/C/M2.00-X/EG6/--/03P/SD-1 ● ●
RPI/--0-1.0b/1/C/M2.00-X/VG6/--/03P/SD-1 0 - 1.0 bar ● ●
G 1/2
RPI/--0-1.0b/1/F/M2.00-X/EG6/--/03P/SD-1 (0 - 14.5 psig) ● ● ●
RPI/--0-1.0b/1/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●
RPI/--0-1.6b/1/C/M2.00-X/EG6/--/03P/SD-1 ● ●
RPI/--0-1.6b/1/C/M2.00-X/VG6/--/03P/SD-1 0 - 1.6 bar ● ●
G 1/2
RPI/--0-1.6b/1/F/M2.00-X/EG6/--/03P/SD-1 (0 - 23.2 psig) ● ● ●
RPI/--0-1.6b/1/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●
RPI/--0-2.5b/1/C/M2.00-X/EG6/--/03P/SD-1 ● ●
RPI/--0-2.5b/1/C/M2.00-X/VG6/--/03P/SD-1 0 - 2.5 bar ● ●
G 1/2
RPI/--0-2.5b/1/F/M2.00-X/EG6/--/03P/SD-1 (0 - 36.3 psig) ● ● ●
RPI/--0-2.5b/1/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●
RPI/--0-4.0b/1/C/M2.00-X/EG6/--/03P/SD-1 ● ●
RPI/--0-4.0b/1/C/M2.00-X/VG6/--/03P/SD-1 0 - 4.0 bar ● ●
G 1/2
RPI/--0-4.0b/1/F/M2.00-X/EG6/--/03P/SD-1 (0 - 58.0 psig) ● ● ●
RPI/--0-4.0b/1/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●
RPI/--0-6.0b/1/C/M2.00-X/EG6/--/03P/SD-1 ● ●
RPI/--0-6.0b/1/C/M2.00-X/VG6/--/03P/SD-1 0 - 6.0 bar ● ●
G 1/2
RPI/--0-6.0b/1/F/M2.00-X/EG6/--/03P/SD-1 (0 - 87.0 psig) ● ● ●
RPI/--0-6.0b/1/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●
RPI/---0-10b/1/C/M2.00-X/EG6/--/03P/SD-1 ● ●
RPI/---0-10b/1/C/M2.00-X/VG6/--/03P/SD-1 0 - 10.0 bar ● ●
G 1/2
RPI/---0-10b/1/F/M2.00-X/EG6/--/03P/SD-1 (0 - 145.0 psig) ● ● ●
RPI/---0-10b/1/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●
RPI/---0-16b/1/C/M2.00-X/EG6/--/03P/SD-1 ● ●
RPI/---0-16b/1/C/M2.00-X/VG6/--/03P/SD-1 0 - 16.0 bar ● ●
G 1/2
RPI/---0-16b/1/F/M2.00-X/EG6/--/03P/SD-1 (0 - 232.1 psig) ● ● ●
RPI/---0-16b/1/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●
RPI/---0-25b/1/C/M2.00-X/EG6/--/03P/SD-1 ● ●
RPI/---0-25b/1/C/M2.00-X/VG6/--/03P/SD-1 0 - 25.0 bar ● ●
G 1/2
RPI/---0-25b/1/F/M2.00-X/EG6/--/03P/SD-1 (0 - 362.6 psig) ● ● ●
RPI/---0-25b/1/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●

55
Pressure sensors
8
DPI II and DPI II+T transmitter
Product range

Scope of delivery:
• DPI II and DPI II+T transmitter
• 2 m (6.5 ft) cable
• capillary tube with fitting
• quick guide.

Temperature O-ring
Complete product range Pressure range Thread Outside usage
measurement EPDM FKM
DPI/--0-0.6b/2/C/M2.00-X/EG6/--/03P/SD-1 ● ●
DPI/--0-0.6b/2/C/M2.00-X/VG6/--/03P/SD-1 0 - 0.6 bar ● ●
G 1/2
DPI/--0-0.6b/2/F/M2.00-X/EG6/--/03P/SD-1 (0 - 8.7 psid) ● ● ●
DPI/--0-0.6b/2/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●
DPI/--0-1.0b/2/C/M2.00-X/EG6/--/03P/SD-1 ● ●
DPI/--0-1.0b/2/C/M2.00-X/VG6/--/03P/SD-1 0 - 1.0 bar ● ●
G 1/2
DPI/--0-1.0b/2/F/M2.00-X/EG6/--/03P/SD-1 (0 - 14.5 psid) ● ● ●
DPI/--0-1.0b/2/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●
DPI/--0-1.6b/2/C/M2.00-X/EG6/--/03P/SD-1 ● ●
DPI/--0-1.6b/2/C/M2.00-X/VG6/--/03P/SD-1 0 - 1.6 bar ● ●
G 1/2
DPI/--0-1.6b/2/F/M2.00-X/EG6/--/03P/SD-1 (0 - 23.2 psid) ● ● ●
DPI/--0-1.6b/2/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●
DPI/--0-2.5b/2/C/M2.00-X/EG6/--/03P/SD-1 ● ●
DPI/--0-2.5b/2/C/M2.00-X/VG6/--/03P/SD-1 0 - 2.5 bar ● ●
G 1/2
DPI/--0-2.5b/2/F/M2.00-X/EG6/--/03P/SD-1 (0 - 36.3 psid) ● ● ●
DPI/--0-2.5b/2/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●
DPI/--0-4.0b/2/C/M2.00-X/EG6/--/03P/SD-1 ● ●
DPI/--0-4.0b/2/C/M2.00-X/VG6/--/03P/SD-1 0 - 4.0 bar ● ●
G 1/2
DPI/--0-4.0b/2/F/M2.00-X/EG6/--/03P/SD-1 (0 - 58.0 psid) ● ● ●
DPI/--0-4.0b/2/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●
DPI/--0-6.0b/2/C/M2.00-X/EG6/--/03P/SD-1 ● ●
DPI/--0-6.0b/2/C/M2.00-X/VG6/--/03P/SD-1 0 - 6.0 bar ● ●
G 1/2
DPI/--0-6.0b/2/F/M2.00-X/EG6/--/03P/SD-1 (0 - 87.0 psid) ● ● ●
DPI/--0-6.0b/2/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●
DPI/---0-10b/2/C/M2.00-X/EG6/--/03P/SD-1 ● ●
DPI/---0-10b/2/C/M2.00-X/VG6/--/03P/SD-1 0 - 10.0 bar ● ●
G 1/2
DPI/---0-10b/2/F/M2.00-X/EG6/--/03P/SD-1 (0 - 145.0 psid) ● ● ●
DPI/---0-10b/2/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●
DPI/---0-16b/2/C/M2.00-X/EG6/--/03P/SD-1 ● ●
DPI/---0-16b/2/C/M2.00-X/VG6/--/03P/SD-1 0 - 16.0 bar ● ●
G 1/2
DPI/---0-16b/2/F/M2.00-X/EG6/--/03P/SD-1 (0 - 232.1 psid) ● ● ●
DPI/---0-16b/2/F/M2.00-X/VG6/--/03P/SD-1 ● ● ●

56
Pressure sensors
8
DPI I transmitter

Product range
The DPI I transmitter is available as an individual packaged transmitter as well as in sets with capillary tubes.
As standard, the scope of delivery includes: (for outside usage only powered by Grundfos pump or the SI power
supply. See accessory section for more information.)
• DPI I transmitter
• cable with bracket
• installation and operating instructions.
See table below for sets with special parts.
Reducing
Pressure Cable Wall Motor Capillary piece Service Outside
Product description
range length bracket bracket tube 7/16-20 UNF instructions usage
- R 1/4
0 - 0.6 bar 0.9 m
DPI/--0-0.6b/1/G/D.900-B/V-5/--/---/VC-1 ● ●
(0 - 8.7 psid) (2.9 ft)
0 - 1.0 bar 0.9 m
DPI/--0-1.0b/1/G/D.900-B/V-5/--/---/VC-1 ● ●
(0 - 14.5 psid) (2.9 ft)
0 - 1.6 bar 0.9 m
DPI/--0-1.6b/1/G/D.900-B/V-5/--/---/VC-1 ● ●
(0 - 23.2 psid) (2.9 ft)
0 - 2.5 bar 0.9 m
DPI/--0-2.5b/1/G/D.900-B/V-5/--/---/VC-1 ● ●
(0 - 36.3 psid) (2.9 ft)
0 - 4.0 bar 0.9 m
DPI/--0-4.0b/1/G/D.900-B/V-5/--/---/VC-1 ● ●
(0 - 58.0 psid) (2.9 ft)
0 - 6.0 bar 0.9 m
DPI/--0-6.0b/1/G/D.900-B/V-5/--/---/VC-1 ● ●
(0 - 87.0 psid) (2.9 ft)
0 - 10.0 bar 0.9 m
DPI/---0-10b/1/G/D.900-B/V-5/--/---/VC-1 ● ●
(0 - 145.0 psid) (2.9 ft)
0 - 0.6 bar 0.9 m
DPI/--0-0.6b/1/G/D.900-B/V-5/-B/02B/SD-1 ● ● ● ● ● ●
(0 - 8.7 psid) (2.9 ft)
0 - 1.0 bar 0.9 m
DPI/--0-1.0b/1/G/D.900-B/V-5/-B/02B/SD-1 ● ● ● ● ● ●
(0 - 14.5 psid) (2.9 ft)
0 - 1.6 bar 0.9 m
DPI/--0-1.6b/1/G/D.900-B/V-5/-B/02B/SD-1 ● ● ● ● ● ●
(0 - 23.2 psid) (2.9 ft)
0 - 2.5 bar 0.9 m
DPI/--0-2.5b/1/G/D.900-B/V-5/-B/02B/SD-1 ● ● ● ● ● ●
(0 - 36.3 psid) (2.9 ft)
0 - 4.0 bar 0.9 m
DPI/--0-4.0b/1/G/D.900-B/V-5/-B/02B/SD-1 ● ● ● ● ● ●
(0 - 58.0 psid) (2.9 ft)
0 - 6.0 bar 0.9 m
DPI/--0-6.0b/1/G/D.900-B/V-5/-B/02B/SD-1 ● ● ● ● ● ●
(0 - 87.0 psid) (2.9 ft)
0 - 10.0 bar 0.9 m
DPI/---0-10b/1/G/D.900-B/V-5/-B/02B/SD-1 ● ● ● ● ● ●
(0 - 145.0 psid) (2.9 ft)
0 - 1.2 bar 5m
DPI/--0-1.2b/1/G/D5.00-B/V-5/-B/02B/TD-1 ● ● ●
(0 - 17.4 psid) (16.4 ft)
0 - 2.5 bar 5m
DPI/--0-2.5b/1/G/D5.00-B/V-5/-B/02B/TD-1 ● ● ●
(0 - 36.3 psid) (16.4 ft)
0 - 4.0 bar 5m
DPI/--0-4.0b/1/G/D5.00-B/V-5/-B/02B/TD-1 ● ● ●
(0 - 58.0 psid) (16.4 ft)
0 - 6.0 bar 5m
DPI/--0-6.0b/1/G/D5.00-B/V-5/-B/02B/TD-1 ● ● ●
(0 - 87.0 psid) (16.4 ft)
0 - 10.0 bar 5m
DPI/---0-10b/1/G/D5.00-B/V-5/-B/02B/TD-1 ● ● ●
(0 - 145.0 psid) (16.4 ft)

RPS and DPS sensors


Grundfos offers a wide range of custom-built RPS and DPS sensors.
The RPS and DPS sensors can be customised depending on the application.
Therefore, contact Grundfos Direct Sensors™ when proceeding to selection.

57
Pressure sensors
9

9. Accessories
Accessories

SI power supply Adapter


The SI power supply from Grundfos Direct Sensors™ Use the adapter together with the capillary tube. The
is an external power supply for the DPI I transmitter. adapter enables the connection of the tube to the
Use the external power supply where the distance system.
between the sensor and the controller is longer than
Description
30 m (98 ft).

Fitting, G 1/4 - 7/16, 20 UNF

TM04 4194 0809


Adapter for Grundfos CR pumps
This adapter is required when fitting the RPI, RPI+T or
DPI II, DPI II+T on Grundfos CR pumps.

Fig. 166 SI power supply Grundfos CR pump size


Pump type
1 3 5 10 15 20 32 45 64 90 120 150
Specifications:
CR, CRE - - - - ❍ ❍ ❍ ● ● ● ● ●
• Voltage range: 110-400 VAC.
• Frequency: 50-60 Hz. CRI, CRIE - - - - ❍ ❍ ● ● ● ● ● ●

• Ambient temperature: -20 to +50 °C (-4 to +122 °F). CRN, CRNE - - - - ❍ ❍ ❍ ● ● ● ● ●


• Enclosure class: IP54.
- An adapter is not required.
Part ❍ An adapter is required if the sensor and coupling guard are in
direct contact. This will create unnecessary acoustic noise.
SI power supply ● An adapter is always required.

Description
M12 cable
4-wire screened cable with M12 connector in the
sensor end and open end in the equipment end. Use Adapter for RPI, RPI+T and DPI II and DPI II+T
the cable for the industrial sensor series such as RPI,
DPI II and VFI.

Description Length
Snap-on cable
Cable, industry, M2.000X 2 m (6.6 ft) Cable with snap-on connection in the sensor end and
different variants in the equipment end, such as open
end, ferrules and various types of connectors.
Cable, industry, M5.000X 5 m (16.4 ft)
Use the cable for the standard sensor series such as
VFS, RPS and DPS.
The cable is available in various lengths, mainly 1.2 m
Capillary tube and 2.9 m.
Use the capillary tube together with the DPI I, DPI II
and DPI II+T to connect the transmitter to the low- Description Length [mm]
pressure side of the equipment. Ferrules, 1.2 m 1.200
The capillaries are available in copper and stainless
steel as well as in various lengths. Ferrules, 2.9 m 2.900

Description

Capillary tube, 7/16 - 20 UNF

58
Pressure sensors
9
SI converter

Accessories
The SI converter from Grundfos Direct Sensors™ is an
external power supply, signal amplifier and signal
converter for Grundfos standard sensors: RPS, VFS
and DPS.
The SI converter has built-in precision resistors
enabling the sensor to transmit 4-20 mA, 1-5 V and
2-10 V output signals.
Use the SI converter in applications incorporating
sensors from the standard product range. The sensor
interface delivers a 4-20 mA input signal to external
controllers.

TM04 4882 2209

Fig. 167 SI converter

Specifications:
• Voltage range: 115-230 VAC ± 10 % or 24 VDC.
• Frequency: 50-60 Hz.
• Power consumption: Maximum 2.5 W.
• Ambient temperature: -20 to +50 °C (-4 to +122 °F).
• Enclosure class: IP20.
Part
SI converter, IP20

59
Pressure sensors
10

10. Appendix
Appendix

Installation of RPI and DPI II transmitters

TM07 2421 3518

60
Pressure sensors
11

11. Grundfos Product Center

Grundfos Product Center


Online search and sizing tool to help you
make the right choice.

http://product-selection.grundfos.com

SIZING enables you to REPLACEMENT enables you to find a


size a pump based on replacement product.
entered data and Search results will include information on
selection choices.
• the lowest purchase price
• the lowest energy consumption
• the lowest total life cycle cost.

CATALOGUE gives you LIQUIDS enables you to find pumps


access to the Grundfos and sensors designed for aqueous
product catalogue. media or other special liquids.

All the information you need in one place Downloads


Performance curves, technical specifications, pictures, dimensional drawings, motor On the product pages, you can download
curves, wiring diagrams, spare parts, service kits, 3D drawings, documents, system parts. installation and operating instructions, data
The Product Center displays any recent and saved items - including complete projects - booklets, service instructions, etc. in PDF format.
right on the main page.

61
ECM: XX
97790251 0818

GRUNDFOS A/S

www.grundfos.com
Telephone: +45 87 50 14 00
DK-8850 Bjerringbro . Denmark
The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide. © Copyright Grundfos Holding A/S