Sie sind auf Seite 1von 2

Foundation Design for 9m High Spun Pole DABS/003-ICB (Design, Supply and Installation of Distribution Plant for

Baghlan and Kunduz Distribution Networks Afghanistan)

Foundation Design Computations


1) General Data
Power Pole Description LV Line S/C Pole
Power Pole Height m 9
Pole base dia m 0.305
No. of Circuits loaded [S/C or D/C] S/C Single Circuit
No. of wires loaded by Pole 3
Max line angle θ Degrees 0.0
Wind Span m 60.0
Weight Span m 80.0
Dead/Self Weight of the Pole kg 816 Refer to Design Report of the Pole
Max Working lateral load on the Pole kg 320 ---do---
Wind pressure kg/m2 70.8 Refer to Sag tension Calculations criteria
Embedment Depth of Pole m 1.7 Refer to design drawing of the Pole (S-02)

2) Conductor Data
Conductor Type ABC 3x95mm2+1x70mm2
Unit Weight of conductor kg/m 1.245
Diameter of the Conductor m 0.0116
Conductor working Tension @ T kg 450 0.315*70 = 22.05kN, Where 0.315 is UTS of the cable
and 70 is X-Sectional area of Aluminium Alloy
3) Load Calculations on the Pole
3.1) Vertical Load
Weight of the Conductors kg 298.80
Weight of the Insulators kg 90.00 3 Phases (Wt of each insulator considered =30kg)
Total Vertical Load on the pole kg 1204.80
kN 11.82
3.2) Lateral Load
3.2.1) Due to Wind
Wind load on Conductors kg 147.8
3.1.2) Due to Conductor Pull
Angle Pull 2T Sin(θ/2) kg 0.0

9m 0-15deg Soil Type B Design Calculations (Page 1 of 2)


Foundation Design for 9m High Spun Pole DABS/003-ICB (Design, Supply and Installation of Distribution Plant for
Baghlan and Kunduz Distribution Networks Afghanistan)

4) Final Loads [ Service ]


Shear at ground line [Hz load] kg 320.0
kN 3.14
Axial force kN 11.82 Downward (Compression)

5) Footing data
Pole base dia m 0.31 Equal to dia of the embedded pole
Pad size m 0.31 Equal to dia of the embedded pole
Thickness of pad m 0.00 Direct embedment of pole
Exposed height above Ground line m 0.20
Foundation Depth below NSL m 2.25 Min depth of footing 1.8 m

6) Soil data
Soil Type Type B 5001kg/m2<ABC <10000kg/m2
Unit weight of Backfilled soil γ KN/m3 15.70 Where ABC means "Allowable Bearing Capacity"
Angle of internal friction φ degree 20
Coeff of passive earth pressure Kp 2.04
Net Allowable Bearing Capacity of soil kg/m2 5000
kN/m2 49.1
COMPUTATIONS
7-1)Footing Embedment depth as per IBC-2009 (1807.3.2.1)
d=0.5A (1+(1+(4.36h/A)^(1/2)))) m 2.25 < 2.25 Ok
where, A = 2.34P/S1 b 2.05 = 2.34x3.14/(11.75*0.305)
b = Diagonal dimension of square footing m 0.31
h = Distance from ground surface to point of application m 0.20
P = Applied lateral force as given above kN 3.14
S1 = Allowable lateral soil bearing pressure kN/m2 11.75 100*0.157*2.245/3

RESULT
As per IBC-2009, the minimum depth to be directly embedded required 2.25 m

9m 0-15deg Soil Type B Design Calculations (Page 2 of 2)