Beruflich Dokumente
Kultur Dokumente
Introduction
Pumps and fans move fluids in a wide variety of applications. Careful analysis can
improve the energy efficiency of most pump and fan systems. This chapter discusses
fundamentals of fluid flow systems, with an emphasis on energy-efficient design, retrofit
and operation.
where V is the volume flow rate, Ptotal is the total pressure rise created by the
pump/fan and Effpump/fan, Effdrive, and Effmotor are the efficiencies of the pump/fan,
drive and electrical motor. The energy balance equation shows that electrical power is
converted into fluid power in the form of a volume flow rate of fluid raised to a pressure
great enough to overcome friction and inlet/outlet requirements. In addition, some
electrical power is converted to heat rather than fluid work due to inefficiencies of the
pump/fan, drive and motor.
Thus, the energy balance equation is also a guide to improving the energy-efficiency of
fluid flow systems:
End Use
o Decrease elevation head
o Run pumps/fans slower and longer
Distribution
o Increase pipe/duct diameter
o Use smoother pipe/duct
o Use low friction fittings
o Reduce pipe/duct length and turns
Conversion
o Reduce entrance/exit head loss
o For fixed flow, control flow by trimming pump impellor or slowing fan
o For variable flow, control flow with VFD
o In VFD applications, reduce static pressure requirements during off-peak
periods
o In VFD applications, install control pressure sensor near the end of the
duct/piping system
o Select high efficiency pumps/fans, drives, motors, and size pumps/fans to
operate at near peak efficiency
Q
2
1
Wf
where Wf is the rate of work transmitted to the fluid, m is the mass flow rate, h is the
specific enthalpy, V is the velocity, g is the acceleration of gravity, z is the height above a
fixed reference and Q is the rate of heat loss from the system. From conservation of
mass and from the definition of enthalpy:
m1 = m2 = m
h = u + Pv.
where u is the specific internal energy, U is the internal energy, P is the pressure and v is
the specific volume. Assuming the density of the fluid does not change,
Substituting , m = V and v = 1/ gives:
where V is the volume flow rate. The term (Q + U2 – U1) represents the net energy
added to the fluid from friction with the pipe/duct walls. To be consistent with the other
terms, it is useful to write (Q + U2 – U1) in terms of pressure drop. Thus:
where hl is the “headloss” in units of specific energy (Btu/lb or J/kG) due to friction
between the fluid and pipes, ducts and fittings.
A number of interesting observations can be made about Equation 2. First, each of the
terms (P2 – P1), V22- V21), g(z2 – z1) and (hl) have units of pressure. Thus, the fluid
work necessary to propel the fluid can be written in terms of W = V P. The term (P2 –
The first three components of the total pressure loss (Pstatic , Pvelocity , Pelevation) refer
to differences between the inlet and outlet of the system. The forth component of the
total pressure loss, Pfriction, refers to irreversible friction losses in the pipes and ducts
and is always present (non-zero) in all real pump/fan applications. Thus, the total
pressure drop can also be written as:
where g is the acceleration of gravity, is the density of the fluid in the manometer, and
h is the height of the fluid column. When a pressure difference is characterized in
terms of h, it is frequently called head. Thus, when pressure loss due to friction in
pipes or ducts measured in terms of h, it is often called friction head or head loss.
Similarly, when the pressure required to lift a fluid against the force of gravity is
measured in terms of h, it is often called elevation head. When the fluid in the
manometer is water, the relationship between pressure and head is:
h = P / (g H20
In pump systems, head is often expressed as the difference in height, h, between
levels of a water-filled manometer in units of feet of water, ft-H20 or, equivalently, ft-
Wf = V Ptotal = V (g h)
Wf (hp) = V (gal/min) htotal (ft-H20) / 3,960 (gal-ft-H20/min-hp) [5]
The volume flow rate in this equation is the product of the mass flow rate and density of
the fluid. Thus, the pumping equation is easily modified for any fluid with a density
different than water at standard conditions by including term for the specific gravity of
the fluid, SGf. Specific gravity is the ratio of the density of the fluid to the density of
water at standard conditions.
SGf = fH20
Wf (hp) = V (gal/min) htotal (ft-H20) SGf / 3,960 (gal-ft-H20/min-hp) [6]
Example
Calculate the work added to the fluid (hp) by a pump pumping 100 gpm of water at
standard conditions if the pressure rise across a pump was 30 psi.
Fan Systems
In US units, a useful dimensional equation to calculate the fluid work, in horsepower, to
move air at standard conditions (density = 0.075 lbm/ft3) through ducts is:
Wf = V Ptotal = V (g z)
Wf (hp) = V (ft3/min) htotal (in-H20) / 6,356 (ft3-in/min-hp) [7]
Equation [5] is for air at standard conditions when the density of air is 0.075 lbm/ft 3.
This corresponds to air at sea level at about 65 F and 40% relative humidity or 70 F and
Example
Calculate the work added to the fluid (hp) by a fan moving 10,000 cfm of air at 300 F if
the pressure rise across a fan is 3.0 in-H20.
Open Systems
In open systems, such as the one shown below, fluid is pumped from one location to a
different location. In open systems the change between static, elevation and velocity
pressures between the inlet and outlet to the system must be considered; however,
careful definition of the inlet and outlet locations can minimize the complexity of the
calculations.
Open Tank 2
P-26
Open Tank 1
Static Pressure and Head: In an open system, it is frequently possible to define the inlet
and outlet locations so that the inlet, 1, and outlet, 2, of the system are surfaces of open
tanks. If so, both the inlet and outlet pressures, P1 and P2, are equal to atmospheric
pressure, and the change in static pressure is zero.
In some cases, however, the inlet and outlet pressures are different. In these cases, the
required static pressure or static head must be calculated.
If water is pumped from an open tank to a pressurized tank at 10 psig, then the required
static head is:
Pstatic = P2 – P1 = Ppres tank – Patm = (10 + 14.7) psia – 14.7 psia = 10 psi
hstatic = 10 psi x 2.31 ft-H20/psi = 23.1 ft-H20
Example
If air is pumped from an open tank to a pressurized tank at 10 psig, then the required
static head is:
Pstatic = P2 – P1 = Ppres tank – Patm = (10 + 14.7) psia – 14.7 psia = 10 psi
hstatic = 10 psi x 27.7 in-H20/psi = 277 in-H20
Velocity Pressure and Head: For internal incompressible flow, such as the flow of water
through a pipe, fluid velocity is inversely proportional to the square of the pipe
diameter. Thus, if the pipe diameter remains constant, the inlet and outlet velocities
are equal, and the change in velocity pressure is zero.
When the inlet and outlet velocities are different, the change in velocity pressure must
be calculated. Useful dimensional relationships to calculate velocity V from volume flow
rate, V, and pipe diameter, d, are:
Useful dimensional relations to calculate the velocity head associated with a velocity, V,
for water at standard conditions are:
Example
V1 (ft/s) = 0.4085 V (gpm) / [d (in)]2 = 0.4085 100 (gpm) / [4 (in)]2 = 2.55 ft/s
V2 (ft/s) = 0.4085 V (gpm) / [d (in)]2 = 0.4085 100 (gpm) / [2 (in)]2 = 10.2 ft/s
Example
If 1,000 cfm of air is pumped through a duct with an inlet diameter of 12 inches and
discharged from a duct with an outlet diameter of 8 inches, the required velocity head
is:
V1 = 183.35 V (cfm) / [d (in)]2 = 183.35 x 1,000 cfm / (12 in)2 = 1,273 ft/min
V2 = 183.35 V (cfm) / [d (in)]2 = 183.35 x 1,000 cfm / (8 in)2 = 2,865 ft/min
The change in elevation head, in terms of water filled manometer height, is:
If water at standard conditions is pumped from one open tank to another open tank
with a surface 10 feet higher than the first open tank, then the required elevation head
is:
helevation = 10 ft – 0 ft = 10 ft-H20
Example
If air at standard conditions is lifted through an elevation gain of 100 ft, the required
elevation head is:
helevation = 0.01445 x 100 (ft) = 1.445 in-H20
Similarly, the total friction loss, hfriction, as fluid flows through pipes is the sum of the
head loss from friction with the pipes, hp, and the head loss from friction through the
fittings, hf.
The next two sections describe how to calculate pressure loss due to friction through
pipes and fittings.
Re = V D / = fluid V D /
where is the kinematic viscosity (air at 60 F = 0.572 ft2/h and water at 60 F = 0.044 ft2/h),
and is the dynamic viscosity (air at 60 F = 0.043 lbm/h-ft andwater at 60 F = 2.71 lbm/h-ft).
The equivalent diameter, De, for a rectangular duct with dimensions L and W is:
Typical values for pipe roughness factors, e, are shown in the figure below.
Type e
Smooth (PVC plastic pipe) 0.0001 ft
Medium (Galvanized steel with spiral or longitudinal seams every 4 ft) 0.0003 ft
Average (Galvanized steel with longitudinal seams every 2.5 ft) 0.0005 ft
Medium Rough (Fiberous glass duct) 0.003 ft
Rough (Flexible duct) = 0.01 ft 0.01 ft
Source: ASHRAE Fundamentals 2005, Pg. 35.7
Example
Calculate the friction head loss (ft-H20) to pump 100 gpm of water through 100 ft of 3-in
diameter steel pipe using the friction-factor method and Churchill relation.
Calculate the friction head loss (in-H20) to convey 1,000 cfm of air through 100 ft of 12-
in diameter medium smooth duct using the friction-factor method and Churchill
relation.
Monograph Method
Alternately, head loss due to friction for water flow through pipes, hp, can be
determined from monographs such as shown below.
Similarly, head loss due to friction for air flow through ducts, hp, can be determined
from monographs such as shown below.
Calculate the friction head loss in ft-H20 for pumping 100 gpm of water through 200 ft of
3-in diameter steel pipe using the ASHRAE monographs.
From the monograph in Figure 6, the head loss for a flow rate of 100 gpm through a 3-in
diameter steel pipe is 2.5 ft-H20 per 100-ft pipe. Thus, the head loss through 200 ft of
pipe is:
Example
Calculate the friction head loss (in-H20) from moving 20,000 cfm of air through 200 ft of
34-inch diameter duct using the ASHRAE monograph.
From monograph, h/L at 20,000 cfm and 34-inch duct is 0.3 in-H20 per 100-ft duct.
Pf = kf fluid V2 / 2
In US units, this height is commonly measured in ft-H20 for pumping systems. For water
flow through pipe fittings, a useful dimensional relationship is:
A useful dimensional relationship to calculate velocity, V, from volume flow rate, V, and
pipe diameter, d, is:
In US units, this height is commonly measured in in-H20 for fan systems. For air flow
through duct fittings, a useful dimensional relationship is:
A useful dimensional relationship to calculate velocity, V, from volume flow rate, V, and
duct diameter, d, is:
Loss coefficient data, kf, for some pipe fittings are shown in the Tables below.
2
1
Wf
P2 = P1 because 1 and 2 are open the atmosphere.
V2= V1 because the area of duct at 1 and 2 are the same.
z2 = z1 because 1 and 2 are at the same elevation.
Thus:
hpres = hvel = helev = 0
htotal = hpres + hvel + helev + hp + hf = hp + hf
From monograph in Figure 6 at 100 gpm and 3-in diameter steel pipe, the friction head
loss through the pipe is:
hp = 2.5 ft-H20 per 100-ft pipe x 200 ft-pipe = 5.0 ft-H20
V (ft/s) = 0.4085 V (gpm) / [d (in)]2 = 0.4085 100 (gpm) / [3 (in)]2 = 4.54 ft/s
Values of loss coefficient, kf, for elbows in ducts are shown in the figure below, where
Vu is upstream velocity in ft/min. Note that kf, and hence pressure drop, varies by a
factor of more than 10 for the different types of elbows shown. This demonstrates the
importance of selecting low pressure-drop fittings when designing energy efficient
duct/fan systems.
Example
Find the fluid power, Wf, required to push 1,000 cfm of air through 200 ft of 12-inch
duct with four 5-gore elbows assuming that 1 and 2 are open to the atmosphere and at
the same elevation.
2
1
Wf
P2 = P1 because 1 and 2 are open the atmosphere.
V2= V1 because the area of duct at 1 and 2 are the same.
z2 = z1 because 1 and 2 are at the same elevation.
Thus:
hpres = hvel = helev = 0
htotal = hpres + hvel + helev + hp + hf = hp + hf
From the fittings chart, for a 12-inch 5-gore elbow, kf = 0.18. For four elbows, the total
head loss is:
Pressure-Gradient Diagrams
Diagrams of total pressure throughout the fan/duct system are often instructive and
useful for avoiding design mistakes. The total pressure, which is a measure of energy,
always decreases in the direction of flow due to friction and other losses. A total
pressure diagram for a typical system is shown below.
The total pressure drop is the sum of the static and velocity pressure drops:
Ptotal = Pstatic + Pvelocity
Although total pressure always decreases, the static and velocity pressures will vary if
duct diameter changes. The following pressure diagrams illustrate how static pressure
can be converted into velocity pressure, and vise versa, when duct diameter changes.
When a fitting’s inlet and outlet areas are different, the inlet and outlet velocity will be
different. Thus, the total pressure drop through the fitting must include the difference
in velocity pressures. If a fitting manufacturer only lists the static pressure drop across
the fitting, be sure to add the velocity pressure drop when computing total pressure
drop.
These design guidelines insures that the fluid velocity is low enough to avoid pipe
erosion and excess noise, and provide a reasonable balance between the cost of the
pipes/ducts and pump/fan energy costs. Using this as a starting place, subsequent
design iterations can identify economically optimum pipe/duct diameters. In many
cases, the economically optimum pipe/duct diameter will be larger than that suggested
by the design guideline.
A B C D A B C D
The configuration on the left is called direct return. In this configuration, the total
pressure drop for flow through leg A is less than the total pressure drop for flow through
leg D. Thus, if no balancing valves were installed, more fluid would flow through leg A
than D, and the total pressure drop across the pump would be set by the pressure drop
through leg D.
The configuration on the right is called indirect return. In this configuration, the
pressure drop and flow through all legs are equal. Thus, indirect return guarantees
equal flow through all legs in the absence of balancing or flow control valves.
Example
Consider the piping system shown below. The head loss though each cooling coil, CC, is
10 ft-H20 and head loss though the evaporator, E, is 20 ft-H20. The flow though each
cooling coil, CC, is 100 gpm. The length of pipe run A is 50 ft, pipe run B is 25 ft and pipe
run C is 25 ft. The distance between the supply and return headers is negligible. Piping
connections are flanged welded and elbows are long radius. The pump is 75% efficient
and the pump motor is 90% efficient. Using a design friction head loss of 3.0 ft-H20/100
ft, a) determine pipe diameters to the nearest nominal diameter, b) determine the total
head and flow required by the pump, c) determine the required size of the pump motor
to the nearest hp (round up!), and d) determine annual pumping electricity use
(kWh/year). Neglecting pressure losses through elbows and fittings, determine pipe
diameters.
A B C
a) Enter the monograph with the design friction loss of and volume flow rate to
determine pipe diameters, D.
DA (300 gpm at 3.0 ft-H20/100 ft) = 5 inches with actual dh = 1.7 ft-H20/100 ft
DB (200 gpm at 3.0 ft-H20/100 ft) = 4 inches with actual dh = 3.5 ft-H20/100 ft
DC (100 gpm at 3.0 ft-H20/100 ft) = 3 inches with actual dh = 2.5 ft-H20/100 ft
VA (ft/s) = 0.4085 V (gpm) / [d (in)]2 = 0.4085 x 300 (gpm) / [5 (in)]2 = 4.90 ft/s
VB (ft/s) = 0.4085 V (gpm) / [d (in)]2 = 0.4085 x 200 (gpm) / [4 (in)]2 = 5.11 ft/s
VC (ft/s) = 0.4085 V (gpm) / [d (in)]2 = 0.4085 x 100 (gpm) / [3 (in)]2 = 4.54 ft/s
Calculate the friction head loss across the pump as the head loss through the path with
the greatest resistance, which in this case is through path C .
htotal = [1.70 + 1.75 + 1.25 + 0.048 + 0.149 + 0.121 + 0.054 + 0.160 + 10 + 20] ft-H20
= 35.23 ft-H20
Specify pump:
Specify 4 hp motor
E = Wpump / Effmotor x dt
E = 3.56 hp / 0.90 x 0.75 kW/hp x 8,760 hours/year = 25,980 kWh/yr
Example
Consider the duct system shown below. The ducts can be sized to deliver the specified
volume flow rates using the Equal Friction or Equal Pressure method. For both
methods, assume a design friction head loss of 0.10 in-H20/100 ft. Neglect pressure
losses through elbows, fittings and inlet dampers and outlet dampers.
A B
LA = 40 ft LB = 200 ft
VA = 700 cfm VB = 500 cfm
C
LC = 20 ft
VC = 200 cfm
Equal Friction Method
Enter the monograph with the design friction loss of and volume flow rate to determine
duct diameters.
Calculate the head loss from the fan to the outlet of each duct using these duct
diameters.
hAB = hA + hB = (0.10 in-H20/100 ft x 40 ft) + (0.10 in-H20/100 ft x 200 ft)
hAB = hA + hB = 0.04 in-H20 + 0.20 in-H20 = 0.24 in-H20
Note that to deliver the required flow through duct A, the pressure at exit of the fan
must be equal to the maximum of these pressure drops. Thus, the pressure at exit of
the fan must be hAB = 0.24 in-H20. If so, then the pressure from the exit of the fan to
the exit of duct C would also be 0.24 in-H20. This pressure would cause a much higher
flow rate than the desired 200 cfm. Thus, a balancing valve must be added to the end of
duct C to generate the required flow.
The method then calculates the pressure drop through each branch duct using these
duct diameters.
As before, to deliver the required flows the pressure at the entrance to branch ducts
must be equal to the maximum of these pressure drops. Thus, the pressure at entrance
of the branch ducts must be h = hB = 0.20 in-H20. If so, then the pressure drop from
this point to the exit of duct C will also need to be 0.20 in-H20. Using this relation, the
required pressure drop per 100 feet of duct length can be found.
hB = hC
0.20 in-H20 = (X in-H20/100 ft x 20 ft)
X = 1.0 in-H20/100 ft
Finally, enter the monograph with this pressure drop and flow rate to determine the
required duct diameter.
Note that no balancing valve is required. The duct was sized to generate the required
flow.
Open Systems
Consider a pump operating between two open reservoirs with a total head loss of 23.1
ft-H20. The pressure rise to across the pump to compensate for this head loss is:
If the pump is placed near the inlet to the system, as shown below, then the minimum
pressure of the fluid is 0 psig.
P
P=0 psig P=0 psig
10
P(psig)
0
If the pump is placed near the outlet to the system, as shown below, then the minimum
fluid pressure is -10 psig. This low pressure may cause the fluid to cavitate.
P
P=0 psig P=0 psig
0
P(psig)
-10
Therefore, to avoid cavitation in open pumping systems, position the pump so it pushes
rather than pulls the fluid.
Closed-loop Systems
Most closed loop systems in which the fluid may undergo a large temperature change
employ an expansion tank to handle increased fluid volume with increased
temperature. The simplest expansion tank has a diaphragm with compressed air above.
The tank maintains the fluid pressure at the air pressure wherever the tank is located.
Consider a closed-loop system with an expansion tank set to 5 psig and a total friction
head loss of 23.1 ft-H20. The pressure rise to across the pump to compensate for this
head loss is:
P=5 psig
P=15 psig
If the expansion tank is placed before the pump, as shown below, then the minimum
fluid pressure is -5 psig. This low pressure may cause the fluid to cavitate.
P=5 psig
P=-5 psig
Pump Types
Pumping applications can generally be divided into two categories: “low flow at high
pressure” and “high flow at low pressure”. “Low flow at high pressure” applications
include hydraulic power systems and typically employ positive-displacement pumps.
The majority of fluid-flow applications are “high flow at low pressure” and use
centrifugal pumps.
In centrifugal pumps, the fluid enters along the centerline of the pump, is pushed
outward by the rotation of the impeller blades, and exits along the outside of the pump.
A schematic of a centrifugal pump is shown below.
Fan Types
The two most common types of fans are axial and centrifugal fans.
Axial fans, also called propeller fans, generate high flow rates but cannot generate the
high pressures required to push air through ducts. Thus, axial fans are generally used in
applications such as exhausting air through ceilings or walls, or destratifying air in rooms
with high ceilings.
Centrifugal fans are capable of generating the pressure required to force air through
ducts and are used almost exclusively in these applications. In centrifugal fans, the
shape of the blade (forward-curved, backward-curved or radial) changes the
relationship between pressure and flow. In general, backward-curved blades provide
the highest efficiency and are used in most HVAC applications.
Pump Curves
Pumps can generate high volume flow rates when pumping against low pressure or low
volume flow rates when pumping against high pressure. The possible combinations of
The power required to push the fluid through the pipe, Wfluid, is the product of the
volume flow rate and system pressure drop.
Graphically, fluid work is represented by the area under the rectangle defined by the
operating point on a pump performance chart.
Typically, the efficiency of the pump at converting the power supplied to the pump into
kinetic energy of the fluid is also plotted on the pump performance chart. Pump
efficiencies typically range from about 50% to 80%. Power that is not converted into
kinetic energy is lost as heat. The power required by the pump, which is called the
“shaft work” or “brake horsepower”. Pump efficiency is the ratio of fluid work to shaft
work. , can be calculated from the flow rate, total pressure, and efficiency values from
the pump curve, using the following equation.
A useful dimensional version of this equation for pumping water at standard conditions
is:
Many pump performance graphs, including those shown above, also plot curves
showing the work required by the pump to produce a specific flow and pressure. Note
that these curves show work required by the pump including the efficiency of the pump.
Calculating the work supplied to the pump using the preceding equation and comparing
it to the value indicated on a pump performance graph is a useful exercise.
Fan Curves
Similarly, the volume flow rate generated by a fan depends on the total system pressure
drop. Fans can generate high volume flow rates at low system pressure drops or low
volume flow rates at high system pressure drops. A fan curve shows the relationship
between total pressure drop and volume flow rate for a specific fan.
It is common for fan manufacturers to publish fan performance data in terms of “static
pressure” versus flow. The “static pressure’ in performance data is actually the
difference between the static pressure at the fan outlet and the total pressure at the fan
inlet.
All fan performance calculations should be performed using total pressure. For
example, the methods to calculate pressure loss through ducts and fittings, calculate
total pressure loss. In addition, the power requirement of a fan is a function of total
pressure loss, not static pressure loss. Thus, for fan calculations, it is important to add
the velocity pressure of the air leaving the fan outlet to the static pressure reported in
fan performance data to determine the relationship between total pressure and flow for
the fan. In some cases manufactures list outlet velocity for the fan. In other cases,
outlet velocity can be calculated from outlet dimensions of the fan and airflow. The
total pressure of the fan is then:
To determine the form of a system curve, consider the equation for total pressure in a
piping system. The total pressure caused by a piping system is the sum of the pressure
due to inlet and outlet conditions and the pressure required to overcome friction
through the pipes and fittings.
Inlet/Outlet Pressure
The inlet/outlet pressure that the pump must overcome is the sum of the static, velocity
and elevation pressures between the inlet and outlet of the piping system. For closed
loop piping systems, the inlet and outlet are at the same location; hence, the static,
velocity and elevation pressure differences are all zero. For open systems, the
differences in static, velocity and elevation pressures must be calculated.
In many pumping applications, the velocity pressure difference between the inlet and
outlet is zero or negligible, and inlet/outlet pressure is simply the sum of the static and
elevation heads. In these cases, the inlet/outlet pressure is independent of flow and is
represented on a pump performance chart as the pressure at zero flow.
Pf = kf fluid V2 / 2
These equations clearly show that for a given pipe system, the pressure drop is
proportional to the square of the velocity, and hence the square of the volume flow
rate.
Pfriction = C1 V2 = C2 V2
This quadratic relationship can be plotted on the pump curve to show the “system
curve”.
A system curve for a closed-loop piping system with no inlet/outlet pressure difference
is shown below. The curve is a parabola of the form hheadloss = C2 V2. The curve passes
through the origin because the inlet/outlet pressure difference, sometimes called the
static head, is zero. The coefficient C2 can be determined if the operating point is known
by substituting the known pressure drop and flow rate into the equation and solving for
C2. The fluid work required to push the fluid through the pipe is the product of the
volume flow rate and system pressure drop and is represented graphically by the area
under the rectangle defined by the operating point.
System Curve
System curve for closed-loop piping system with no inlet/outlet pressure difference. Source of original
pump curve: Kreider and Rabl, 1996.
A system curve for an open-loop piping system with a “static” or “inlet/outlet” pressure
of 40 ft is shown below. This system curve is of the form hheadloss = A + C2 V2; where A
is the “static” or “inlet/outlet” pressure drop. As before, the coefficient C 2 can be
determined if the operating point and inlet/outlet pressure are known by substituting
the known values into the equation and solving for C2.
System curve for open-loop piping system with 40 ft-H20 inlet/outlet pressure difference
Source of original pump curve: Kreider and Rabl, 1996.
When two pumps are operated in parallel, they perform like a single pump with twice
the flow rate at the same pressure drop. The figure below shows the pump curve of a
single pump A, two pumps operating in parallel B, and the system curve C.
The system curve C describes the relationship of pressure drop and flow rate for the
given piping system with no static head. Because head loss varies with the square of
flow rate, the equation of the system curve can be estimated by fitting a quadratic
equation through the origin and the design operating point:
where V is the flow rate in gpm. The equation for curve B can be estimated by the
fitting a regression equation through the data points on the curve:
The operating point of curve B for two pumps in parallel can be found from Equations 1
and 2 to be about:
Note that the total volume flow rate of two pumps operating in parallel is less than
twice the flow rate of a single pump operating alone (at the intersection of C and A).
Similarly, two to six diameters of duct are generally required for the airflow leaving a fan
to become fully developed. Branch lines, elbows and other ductwork installed before
the flow is fully developed increase pressure drop and reduce airflow.
Improper air inlet and outlet conditions can dramatically increase the total pressure
drop across the fan. The increased pressure drop due to fan inlet and outlet conditions
is called the “system effect”. The system effect frequently causes fans to operate at a
higher pressure and lower flow rate, A, than would be anticipated based on the system
curve from the duct system B. To maximize energy-efficiency, it is important to
minimize these losses by proper design of fan inlet and outlet conditions.
Wmotor Wdrive
100 90 Wpump
83
Wfluid
58
For example, if the efficiency of the motor at converting electrical energy to motor shaft
work is 90%, the efficiency of belt drives at transferring motor shaft work to pump is
92%, and the efficiency of a pump at converting pump shaft work to fluid work is 75%,
the electrical energy use required by the motor would be 73% greater than the required
fluid work.
As shown in the section of system curves, friction head loss is proportional to the square
of the volume flow rate.
Pfriction = C1 V2 = C2 V2
Wf = V Pfriction = V C2 V2 = C2 V3
This relation shows that a small reduction in the volume flow rate results in a large
reduction in the fluid work. For example, reducing the volume flow rate by one half
reduces fluid work by 88%!
Another useful relation can be derived from the relationship between volume flow rate
V and the rotational speed of the pump fan. In centrifugal pumps and fans, the volume
flow rate is proportional to the rotational speed of the pump fan.
V = C RPM
(V / RPM)1 = C = (V / RPM)2
V2 = V1 (RPM2 / RPM1)
The fluid work equation shows that energy required by fan/pump systems is a function
of the volume flow rate, inlet/outlet conditions, and system friction.
Example
A pump lifts 100 gpm of water 120 feet to fill an elevated reservoir. Determine the electrical
power savings if the level of the reservoir could be reduced by 20 feet. The pump is 70%
efficient and the pump motor is 90% efficient.
PE1 = 100 gpm x 120 ft-H20 / [3,960 gpm-ft-H20/hp x 0.70 x 0.90] x 0.75 kW/hp = 3.61 kW
PE2 = 100 gpm x 100 ft-H20 / [3,960 gpm-ft-H20/hp x 0.70 x 0.90] x 0.75 kW/hp = 3.01 kW
Pp = f L V2 / (2 D)
The velocity V is the quotient of volume flow rate V and area A, thus
Pp = f L (V / A)2 / (2 D) = f L (V / D2 )2 / (2 D) = f L V2 / (2 2 D5 )
Thus, friction pressure loss through pipes/ducts is inversely proportional to the fifth
power of the diameter
This means that doubling the pipe/duct diameter reduces friction pressure loss by about
97%!
Example
Calculate the percentage reduction in friction head loss if pumping 4 gpm of water
through 0.5-inch and 1-inch diameter schedule 40 steel pipes.
h 0.5-inch = 17 ft-H20/100 ft
h1-inch = 1.3 ft-H20/100 ft
The percent reduction in friction head loss from doubling the diameter of the pipe
would be about:
Optimum pipe diameter is often calculated based on the net present value of the cost of
the pipe plus pumping energy costs. Using this method in the figure below (Larson and
Nilsson, 1991) optimum pipe diameter was found to be 200 mm. When the cost of the
pump was also included in the analysis, the optimum diameter was found to be 250 mm
and energy use was reduced by 50%. This illustrates the importance of considering the
whole system.
Piping Examples:
Using long radius elbows instead of standard elbows reduces friction head through a 2-
inch welded elbow by:
(h,std –h,long) / h,std = (kf,,std –kf,,long) / kf,,std = ( 0.38 – 0.30 ) / 0.38 = 21%
Using gate valves instead of globe valves reduces friction head through a 2-inch welded
valve by:
Thus, it is important to reduce the diameter of the pump impellor, or slow the pump/fan
so that the volume flow rate remains the same as it was in the high friction in order to
realize energy savings. The following examples demonstrate this importance of
modifying the pump to realize savings from reducing piping system pressure drop.
The power required by the pump, Wp, is the fluid power requirements divided by the
pump efficiency.
Thus, decreasing system pressure drop without altering the pump impellor or speed
would cause the pump to consume more energy, not less.
h = C V2
The coefficient, C, for the new system curve can be found by substituting the values of
pressure drop and volume flow rate for point B.
Thus, the pressure drop through the new duct system at 235 gpm would be about:
The flow rate of 235 gpm and 71 ft-H20 defines point C, which would be the operating
point of the pump with a 5.5-in impeller. At this operating point, the pump would be
about 65% efficient, and the pump power draw would be about:
Thus, the savings from reducing the pressure drop in the pipe system, if the pump
impeller diameter were reduced, would be about:
This example demonstrates the importance of modifying the pump to realize savings
from reducing system friction loss.
The figure below shows fan performance at various speeds and a system curve. Assume
the fan is operated at 1,550 rpm on the system curve at point A. The volume flow rate
would be about 10,500 cfm and the system pressure drop would be about 8.4 in-H20.
From the chart, the required power to the fan would be about 20 hp.
If the pressure drop were reduced to 5.8 in-H20 at point B by increasing duct diameter,
opening dampers or using low-pressure drop fittings, the operating point would shift
down the fan curve. The volume flow rate would increase to about 18,000 cfm and the
required power to the fan would increase to about 25 hp. Thus, reducing pressure drop
without slowing the fan would increase energy use!
To realize energy savings from reducing pressure drop, it is necessary to slow the fan
speed. To determine the fan speed required to deliver the initial air flow of 10,500 cfm
with the new lower pressure drop duct system, it is necessary to develop a system curve
for the new duct system. Pressure drop always varies with the square of flow rate.
Thus, the equation for a system curve can be written as:
h = C V2
The coefficient, C, for the new system curve can be found by substituting the values of
pressure drop and volume flow rate for point B.
Thus the pressure drop through the new duct system at 10,500 cfm would be about:
According to the fan curves, the fan would deliver 10,500 cfm at 2.0 in-H20 if the fan
speed were slowed to about 900 rpm at point C. At this operating point, the fan would
20 hp – 5 hp = 15 hp
This example demonstrates the importance of slowing the fan to realize savings from
reducing system friction loss.
Once the required flow is determined, it is necessary to determine how the flow is
currently controlled and consider more energy-efficient options. Inefficient methods of
flow control, in order of worst to better, are:
Bypass
Throttling / Outlet dampers
Fan variable inlet vanes
Intermittent pump operation
dP
VFD
Typical relationships between power and flow for outlet damper control, variable-inlet
vane control and speed control via variable frequency drives are shown in the figure
below.
Example
Two pumps operate in parallel to lift water 40 vertical feet and generate 5,800 gpm at
140 ft H20 as shown in the figure below. One pump operating alone would generate
5,200 gpm at 123 ft H20. The pumps are 75% efficient and the pump motors are 90%
efficient. When operating in parallel, the pumps operate 10 hours per day. Determine
the energy savings from “pumping slow, pumping long” and running one pump longer to
generate the same daily flow rate.
160
B
120
dh (ft H20)
80 A
C
40
0
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000
V (gpm )
The electrical power and energy required to pump this quantity of water using two
pumps in parallel is:
P2 Pumps = 5,700 gpm x 140 ft-H20 / (3,960 gpm-ft-H20/hp x 0.75 x 0.90) x 0.75 kW/hp
P2 Pumps = 223.9 kW
E2 Pumps = 223.9 kW x 10 hours/day = 2,239 kWh/day
The time required to generate the same daily flow rate while operating only one pump
is:
The energy required to pump this quantity of water using one pumps is:
P1 Pump = 5,200 gpm x 123 ft-H20 / (3,960 gpm-ft-H20/hp x 0.75 x 0.90) x 0.75 kW/hp
P1 Pump = 179.5 kW
E1 Pump = 179.5 kW x 10.96 hours/day = 1,967 kWh/day
Wn = -0.042487 + 3.6573 x Vn -6.4957 x Vn2 + 3.8760 x Vn3 (Vn >= 50%) (1)
Wn = 0.589 + 0.116 x Vn (Vn < 50%) (2)
Where Vn is the fraction of full-load flow rate and Wn is the fraction of full-load power.
The power draw of the blower motor with VIV control is:
W = Wfl x Wn (3)
Example
At full flow, a blower powered by an 800-hp motor draws 466 kW of power when
delivering 25,000 cfm at full flow. Flow is controlled using variable inlet vanes. The flow
rate is 18,000 cfm for 80% of the time, 20,000 cfm for 10% of the time and 16,000 cfm
for 10% of the time. Based on these data and Equations 2 and 3, the average power
draw of the blowers during blast mode is about:
The figure below shows a set of pump curves for different impellor diameters. The
pump is equipped with a 7-inch impellor. At design conditions, the pump would operate
at point A. The system curve extends from the origin to A, which means this is a closed-
loop piping system with no inlet/outlet pressure difference to overcome.
The power required to pump a fluid is the product of the volume flow rate and pressure
drop; hence, the areas enclosed by the rectangles defined by the vertical and horizontal
axes and each operating point represent the fluid power requirements, W fA , WfB, , and
WfC,. Comparison of these rectangles clearly indicates that reducing flow by trimming
the pump impellor uses much less energy than reducing flow by throttling.
The power required by the pump at A, WPA, is the fluid power requirement divided by
the pump efficiency.
The power required by the pump for throttled flow at B, WPB, is the fluid power
requirement divided by the pump efficiency.
To determine the pump impellor size required to deliver a flow of 235 gpm with a
trimmed impellor, it is necessary to develop the design system curve with the throttling
valve wide open and the pump operating at A. Pressure drop through piping systems
h = C V2
The coefficient, C, for the new system curve can be found by substituting the values of
pressure drop and volume flow rate for point A.
The flow rate of 235 gpm and 71 ft-H20 defines point C. This indicates that the pump
impellor should be trimmed to a diameter of 5.5-inches. At this operating point, the
pump would be about 65% efficient, and the pump power draw would be about:
Thus, the savings from controlling flow by trimming the pump impellor rather than
throttling flow would be about:
Alternately, power savings from reducing the volume flow rate can be estimated from
the pump affinity laws. Theoretically, pump work varies with the cube of volume flow
rate. Use of the cubic relationship would predict:
The 6.0 hp predicted by the pump-affinity law is less than the 6.5 hp predicted by the
pump curve. This example demonstrates how use of the cubic relationship typically
exaggerates savings. In practice, the efficiencies of the VSD, pump and motor typically
decline as flow rate decreases, resulting in slightly less savings than would be predicted
using this ‘cubic’ relationship. Thus, we estimate that pump/fan work varies with the
2.5 power of flow rather than the cube of flow. Using this relationship, if P A is 16.7 hp at
330 gpm, PC at 235 gpm would be about:
WPC = WPA (VC/VA)2.5 = 16.7 hp x (235 gpm / 330 gpm) 2.5 = 7.1 hp
The figure below shows a set of pump curves for different impellor diameters. The
pump is equipped with a 7-inch impellor. At design conditions, the pump operates at
point A. The system curve extends from an inlet/outlet pressure difference of 40 ft H20
from lifting water over an elevation change of 40 ft in an open system.
The actual flow required was less than the design flow. Thus, flow was reduced by a
throttling valve to operating point B. A more energy efficient method of reducing flow is
to open the throttling valve, and trim the impellor to a smaller diameter. This would
cause the pump to operate at point C.
The power required to pump a fluid is the product of the volume flow rate and pressure
drop; hence, the areas enclosed by the rectangles defined by the vertical and horizontal
axes and each operating point represent the fluid power requirements, W fA , WfB, , and
WfC,. Comparison of these rectangles clearly indicates that reducing flow by trimming
the pump impellor uses much less energy than reducing flow by throttling.
The power required by the pump at A, WPA, is the fluid power requirement divided by
the pump efficiency.
The power required by the pump for throttled flow at B, WPB, is the fluid power
requirement divided by the pump efficiency.
To determine the pump impellor size required to deliver a flow of 235 gpm with a
trimmed impellor, it is necessary to develop the design system curve with the throttling
valve wide open and the pump operating at A. Pressure drop through piping systems
varies with the square of flow rate. Thus, the equation for a system curve that passes
through the origin can be written as:
h = h0 + C V2
Where h0 is the pump head at zero flow. The coefficient, C, for the new system curve
can be found by substituting the values of pressure drop and volume flow rate for point
A.
Thus, the pressure drop through the new duct system at 235 gpm would be about:
The flow rate of 235 gpm and 91 ft-H20 defines point C. This indicates that the pump
impellor should be trimmed to a diameter of 5.75-inches. At this operating point, the
pump would be about 69% efficient, and the pump power draw would be about:
Thus, the savings from controlling flow by trimming the pump impellor rather than
throttling flow would be about:
Alternately, power savings from reducing the volume flow rate can be estimated from
the pump affinity laws. However the cubic relationship between pump work and
volume flow rate applies only to the friction head, not the inlet/outlet head. Thus, the
component of total power due to friction must be calculated. The component of total
power due to friction is the difference between the total power and the inlet/outlet
power.
Theoretically, pump work varies with the cube of volume flow rate. In practice, the
efficiencies of the VSD, pump and motor typically decline as flow rate decreases,
resulting in slightly less savings than would be predicted using this ‘cubic’ relationship.
Thus, we estimate that pump/fan work varies with the 2.5 power of flow rather than the
cube of flow. Using this relationship, the component of power at C due to reduced
friction at 235 gpm would be about:
WPCF = WPAF (VC/VA)2.5 = 11.9 hp x (235 gpm / 330 gpm) 2.5 = 5.1 hp
This estimate of savings incorporates the reduction in motor efficiency, and power loss
by the VSD.
The figure below shows pump performance at various speeds and a system curve. At
design conditions, the pump operates at 1,200 RPM at point A. The system curve
extends from the origin to A, which means this is a closed-loop piping system with no
inlet/outlet pressure difference to overcome.
At A, the volume flow rate is 1,200 gpm, the total head is 55 ft-H20 and the pump
efficiency is 74%. According to the chart, the required power to the pump at this
operating point is about 23 hp. Alternately, the required pump input power could be
calculated as:
If the flow were reduced to 900 gpm with a flow-control valve, the operating point
would move along the pump curve to point B at 900 gpm, 62 ft-H20 with pump
efficiency of 70%. According to the chart, the required power to the pump at this
operating point is about 20 hp. Alternately, the required pump input power could be
calculated as:
Thus, the pump power savings from reducing flow from 1,200 gpm to 900 gpm with a
flow-control valve would be about:
h = C V2
The coefficient, C, for the new system curve can be found by substituting the values of
pressure drop and volume flow rate for point A.
C = h / V2 = 55 / 1,2002 = 0.000038194
The flow rate of 900 gpm and 31 ft-H20 defines point C. This indicates that the pump
speed should be reduced to 900. At this operating point, the pump would be about 67%
efficient, and the required pump input power would be:
Alternately, the power required by the pump at point C, PC, can be read from the chart
to be about 10 hp.
Alternately, power savings from reducing the volume flow rate can be estimated from
the pump affinity laws. Theoretically, pump work varies with the cube of volume flow
rate. Use of the cubic relationship would predict:
The 9.5 hp predicted by the pump-affinity law is less than the 10.5 hp predicted by the
pump curve. This example demonstrates how use of the cubic relationship typically
exaggerates savings. In practice, the efficiencies of the VSD, pump and motor typically
decline as flow rate decreases, resulting in slightly less savings than would be predicted
using this ‘cubic’ relationship. Thus, we estimate that pump/fan work varies with the
2.5 power of flow rather than the cube of flow. Using this relationship, the required
pump input power at 900 gpm would be:
This estimate of savings incorporates the reduction in motor efficiency, and power loss
by the VSD.
The figure below shows pump performance at various speeds and a system curve. At
design conditions, the pump operates at 1,200 RPM at point A. The system curve
extends from an inlet/outlet pressure difference of 20 ft H20. This inlet/outlet head can
result from lifting water over an elevation change of 20 ft in an open system, or as the
required head between the supply and return pipes for controlling a variable speed
drive.
B
A
At A, the volume flow rate is 1,200 gpm, the total head is 55 ft-H20 and the pump
efficiency is 74%. According to the chart, the required power to the pump at this
If the flow were reduced to 900 gpm with a flow-control valve, the operating point
would move along the pump curve to point B at 900 gpm, 62 ft-H20 with pump
efficiency of 70%. According to the chart, the required power to the pump at this
operating point is about 20 hp. Alternately, the required pump input power could be
calculated as:
Thus, the pump power savings from reducing flow from 1,200 gpm to 900 gpm with a
flow-control valve would be about:
To determine the pump speed required to deliver a flow of 900 gpm, it is necessary to
develop the design system curve with the flow-control valve wide open and the pump
operating at A. Pressure drop through piping systems varies with the square of flow
rate. Thus, the equation for a system curve that passes through the origin can be
written as:
h = h0 + C V2
Where h0 is the pump head at zero flow. The coefficient, C, for the new system curve
can be found by substituting the values of pressure drop and volume flow rate for point
A.
Thus, the pressure drop through the new duct system at 235 gpm would be about:
The flow rate of 900 gpm and 40 ft-H20 defines point C. This indicates that the pump
speed should be reduced to 900. At this operating point, the pump would be about 70%
efficient, and the required pump input power would be about:
Alternately, the power required by the pump at point C, PC, can be read from the chart
to be about 13 hp. Pump power savings are the difference between WPA and WPC.
Alternately, power savings from reducing the volume flow rate can be estimated from
the pump affinity laws. However the cubic relationship between pump work and
volume flow rate applies only to the friction head, not the inlet/outlet head. Thus, the
component of total power due to friction must be calculated. The component of total
power due to friction is the difference between the total power and the inlet/outlet
power.
Theoretically, pump work varies with the cube of volume flow rate. In practice, the
efficiencies of the VSD, pump and motor typically decline as flow rate decreases,
resulting in slightly less savings than would be predicted using this ‘cubic’ relationship.
Thus, we estimate that pump/fan work varies with the 2.5 power of flow rather than the
cube of flow. Using this relationship, the component of power at C due to reduced
friction PCF at 235 gpm would be about:
WPCF = WPAF (VC/VA)2.5 = 14.3 hp x (900 gpm / 1,200 gpm) 2.5 = 7.0 hp
This estimate of savings incorporates the reduction in motor efficiency, and power loss
by the VSD.
The figure below shows fan performance at various speeds and a system curve.
Reducing the fan speed from 1,550 rpm to 1,050 rpm on the system curve would reduce
the volume flow rate from 10,500 cfm to 7,000 cfm. The reduced volume flow rate
would also generate less friction, and the system pressure drop would be reduced from
8.4 to 3.9 in-H20. The power required to push the air is the product of the volume flow
rate and pressure drop; hence, the areas enclosed by the rectangles defined by each
operating point represent the fluid power requirements, WA and WB, at the different
flow rates.
The fluid work calculated above does not take into account fan efficiency. Taking into
account fan efficiency, the shaft power required by the fan, which is plotted on the
chart, accounts for fan efficiency. From the chart, shaft power is:
PA = 20 hp
PB = 6.3 hp
Alternately, power savings from reducing the volume flow rate can be estimated using
the fan affinity laws. Theoretically, fan work varies with the cube of volume flow rate.
Use of the cubic relationship would predict:
PA – PB = 20 hp – 5.9 hp = 14.1 hp
The small discrepancy is due to the fact that the fan affinity method does not take into
account the slight decrease in fan efficiency at the lower speed. In practice, the
efficiencies of the VSD, pump and motor typically decline as flow rate decreases,
resulting in slightly less savings than would be predicted using this ‘cubic’ relationship.
Thus, we estimate that pump/fan work varies with the 2.5 power of flow rather than the
cube of flow. Using this relationship, if we measured PA to be 20.0 hp at 10,500 cfm, we
would estimate PB at 7,000 cfm to be about:
This slightly lower estimate of savings incorporates the reduction in motor efficiency,
and power use by the VSD.
VSDs subject motors to voltage spikes and fast voltage rise and fall times. These voltage
spikes can “punch” through traditional winding insulation. Because of this, VSDs should
only be coupled to motors that the manufacturer specifies as suitable for PWM VSDs. If
In some applications, it may be possible to simply reduce the flow to a fixed rate rather
than vary it continuously. In these cases, slowing the pump by increasing the diameter
of the pump pulley or decreasing the diameter or the motor pulley would generate the
same savings.
Because VSDs work best with premium efficiency motors, the motor may need to be
upgraded if it is not a premium efficiency motor. Typical installed costs of VSDs are
shown below.
w/o
Horsepower w/bypass w/o bypass Wiring Installation Controls w/bypass bypass
5 $1,653 $500 $400 $2,000 $4,553
10 $2,008 $1,515 $579 $463 $2,000 $5,050 $4,557
15 $2,233 $1,771 $658 $526 $2,000 $5,417 $4,955
20 $2,458 $2,028 $737 $589 $2,000 $5,784 $5,354
25 $2,772 $2,332 $816 $653 $2,000 $6,240 $5,800
50 $4,344 $3,854 $1,211 $968 $2,000 $8,523 $8,033
100 $7,021 $6,049 $2,000 $1,600 $2,000 $12,621 $11,649
Typical 2006 costs with 25% contractor markup on drives assuming existing motor is
suitable for inverter use.
If these procedures are followed, the inlet-outlet head across the pump approaches the
differential-pressure between the supply and return headers as flow decreases. For
example, if the differential-pressure between the supply and return headers were set to
20 ft-H20, the system curve would run from 20 ft-H20 at zero flow through C to A in the
figure below. Thus, when modeling energy savings in VSD applications, use the
procedure demonstrated in “Example: Slow Pump Speed with Inlet/Outlet Head”. In
B
A
bypass /
pressure
cooling relief
tower valve
dP
cooling
7.5 hp water to
pump process
loads
city water
make-up 25 hp
pump
reservoir
Condenser Primary
(Cooling Tower) Chilled Water
Pumps Pumps
Close-ups of a typical piping configuration at the air handler cooling coils in a constant-
flow chilled-water supply system are shown below. The three-way valves direct chilled
water either through the cooling coil or around the cooling coil via the bypass loop. The
flow of chilled water through the cooling coils is varied to maintain the temperature of
the air leaving the cooling coils at a constant temperature. In a VSD retrofit, the bypass
valves would be closed, and a differential-pressure sensor would be installed between
the supply and return headers at the air handler located farthest from the pump. In
some cases, it may be necessary to replace the three-way valves with two-way valves if
the three-way valves were not designed to handle larger pressure drops in a VSD
situation.
Manual
2-Way Valve
Tsa
Automatic
3-Way Valve
Cooling Coil
Manual
2-Way Valve
Tsa
Automatic
3-Way Valve
The greatest pump energy savings come from changing the secondary chilled-water
loop from constant to variable flow. This is done by:
A typical variable flow secondary chilled water loop system is shown below.
Condenser Primary
(Cooling Tower) Chilled Water
Pumps Pumps
Source: Taylor, S., 2002, “Primary-Only vs. Primary Secondary Variable Flow Systems”,
ASHRAE Journal, February, 2002, pgs 25-29.
The figure below shows an all variable-speed cooling plant (Erpelding, Ben, 2008,
“Monitoring Chiller Plant Performance”, ASHRAE Journal, April, pp. 48-52.) The plant
was converted from a primary-secondary constant speed plant to the variable-speed
plant because of low dT (significant mixing), inefficient constant speed operation and
low-load instability
The following figures show measured performance of the system. The two sets of
values show differences between two independent measurement systems. During the
monitoring period, the 300-ton chiller never operated. The data show total cooling
plant power varying from about 0.5 kW/ton at high loads to about 0.3 kW/ton at low
loads. In comparison, constant flow cooling plants have higher specific power
requirements at full load, with constant or increasing specific power requirements as
the low decreases.
Source: “Monitoring Chiller Plant Performance”, ASHRAE Journal, April, pp. 48-52.
References
ASHRAE Handbook: Fundamentals, 1977, 1985, 1996, 2005, ASHRAE.
Bernier and Bourret, 1999, “Pumping Energy and Variable Frequency Drives”, ASHRAE
Journal, December.
Incropera and DeWitt, 1985, Fundamentals of Heat and Mass Transfer, John Wiley and
Sons.
Kreider and Rabl, 1994, Heating and Cooling of Buildings, McGraw-Hill Inc.
Larson, E.D. and Nilsson, L.J., 1991, “Electricity Use and Efficiency in Pumping and Air
Handling Systems, ASHRAE Transactions, pgs. 363-377.
McQuiston and Parker, 1994, Heating Ventilating and Air Conditioning, John Wiley and
Sons, Inc.
Nadel, S., Shepard, M., Greenberg, S., Katz, G., and Almeida, A., 1991, “Energy Efficient
Motor Systems”, American Counsel for an Energy Efficient Economy, Washington D.C.
Taylor, S., 2002, “Primary-Only vs. Primary Secondary Variable Flow Systems”, ASHRAE
Journal, February, 2002, pgs 25-29.
Tutterow, 199x, Energy Efficient Fan Systems, Industrial Energy Technology Conference,
Houston, TX
U.S. Department of Energy, 2002m “Pumping Systems Field Monitoring and Application
of the Pumping System Assessment Tool PSAT”,