CONCRETE MIX DESIGN DATA

PROJECT : BPK Sunter


CONTRACTOR : PT. PAKUBUMI SEMESTA
SPECIFICATION : Class of Concrete : FC 25 MPa
Minimum compressive strength 25 MPa when tested at the age 28 days using
15 cm x 30 cm cylinder samples.
Slump on site 18.0 cm with the tolerance range of 2.0 cm.
Maximum size of coarse aggregate +/- 25 mm.

MATERIAL SPECIFIC GRAVITY


Fine Aggregate : Natural Sand ex Sumedang SSD 2.58
Coarse Aggregate : Crushed Stones ex Purwakarta SSD 2.60
Cement : Curah Ordinary Porland Cement ex Gresik 3.15
Flay Ash : Curah Ex Suralaya 2.10
Water : PAM 1.00
Additives : BASF 1.19

DESIGN CALCULATION
Water cement ratio 0,50
Free water required 190 kg/m3 190.00 dm3
Cement 323 kg/m3 102.54 dm3
Flay Ash 57 kg/m3 27.14 dm3
Additives 1 0.95 kg/m3 0.80 dm3
Additives 2 2.28 kg/m3 1.90 dm3

Pasta volume 319.68 dm3


Air content (1.0 %) 10.00 dm3
Aggregate volume 670.31 dm3
Fine Aggregate 0.49 x 670.31 x 2.58 = 848.67 kg
Coarse Aggregate 0.51 x 670.31 x 2.60 = 888.83 kg

Cikarang, November 05,2014

Approved By : Prepared By :

Sodri Firmansyah
Technical Manager Quality Control