NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETERS AND ALL


ELEVATIONS ARE IN METERS UNLESS OTHERWISE
NOTED.

PLANT NORTH
TRUE NORTH
2. ALL LIGHTNING PROTECTION COMPONENTS SHALL BE
UL LISTED OR LABELED IN ACCORDANCE WITH UL96

OF
H

29¡ AND INSTALLATION SHALL BE IN ACCORDANCE WITH


KA

CONSENT
NFPA 780 AS SPECIFIED IN SAES-P-111.
K
MA

3. SUPPORT AND FASTEN OF DOWN CONDUCTOR AND


HORIZONTALL CONDUCTOR EVERY 0.9 M.

4. AIR TERMINALS MOUNTED ON BUILDINGS ROOF TO BE

TTEN
MOUNTED WITHIN 0.6 M OF ROOF EDGE AT LOCATIONS
AS HOWN ON DRAWING.

WRI
5. DOWN CONDUCTOR SHALL BE PROTECTED FOR A
MINIMUM DISTANCE OF 1.8 M ABOVE GRADE LEVEL.

THE
6. STRIKE TERMINATION DEVICES 0.6 M OR MORE

THOUT
ABOVE THE OBJECT OR AREA TO BE PROTECTED
SHALL BE PREMITTED TO BE PLACED AT INTERVALS
NOT EXCEEDING 7.5 M.

WI
7. CONNECT DOWN CONDUCTORS AND HORIZONTAL

NG
CONDUCTORS ON ROOF WITH EXOTHERMIC WELD.

DRAWI
8. THE MAIN GROUND GRID POSITION IS INDICATED ONLY,
DETAILED GROUND GRID POSITION REFER
A29-P-CBL-VA-241364-002.

S
THI
FROM
LEGEND

NED
1 3 4 7 10 13

OBTAI
77400
EQUIPMENT CONNECTION

GROUND GRID 19000 19200 19200 GROUND GRID 19200 GROUND GRID

BE
AIR TERMINAL
800

PART,SHALL
GROUND GRID GROUND ROD (DIA=20MM, L=4800MM)

2
70MM INTERCONNECTION CONDUCTOR,
A
BARE COPPER

7600 MAX.

N
2

I
70MM DOWN CONDUCTOR,
(TYP.) PVC INSULATED COPPER WIRE

FULL,OR
38400 01A

CADWELD CONNECTION POINT

(T TYPE)
7500

CADWELD CONNECTION POINT

N
I
LP02 (CROSS TYPE)
TYP. 5

ON
REPRODUCTI
-

CONDUCTOR CHANGE ELEVATION


15600

15000 MAX.
(TYP.)

SAUDIARAMCO.NO
REFERENCE DRAWINGS
DWG. CONTROL FOR J.O.
7500

SS GROUNDING LAYOUT (SS-329) A29-P-CBL-VA-241364-002

LIGHTNING PROTECTION CALCULATION A00-P-DOC-VE-240498

LIGHTNING INSTALLATION DETAILS A00-B-HAZ-VA-240472-001


LP03
TYP. 26
-

KEY PLAN

OF
E

PROPERTY
SOLE
GROUND GRID GROUND GRID GROUND GRID GROUND GRID

THE
SS-329
SS-329 LIGHTNING PROTECTION LAYOUT

ARE
SCALE 1:100

N
HEREI
0 1.0 2.0 3.0 4.0 5.0 10.0

METERS

NED
1 : 100M
SCALE:

CONTAI
REVISION VALIDATION

THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION


REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

ON
10-01525-0004-006

NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

LC.CHEN B.ANDERS
03/30/16 03/30/16

REV.NO. DATE REVISION DESCRIPTION

I
00 03/30/16 ISSUED FOR CONSTRUCTION

THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
10-01525-0004 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY

AND
DRAWING TYPE

LIGHTNING PROT LAYOUT/ DETAILS HAZ

NG
SS-329

DRAWI
ELECTRICAL POWER DISTRIBUTION & INT

JAZAN SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
A29 B VA-240392 001 00
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-05