Feeder Protection

Relay REX 521


Insert image
here

Insert image
here
© ABB AG -1-
REX 521
Feeder and Motor
Protection REX 521 Medium Range Products
„ Wide selection of single busbar
applications
„ Proven and reliable technology
„ Part of versatile product range
covering vast number of protection
applications

The enhanced REX 521 now offers a


number of new protection functions,
and supervision functions such as
motor protection and power quality
supervision.
© ABB AG -2-
REX 521
Feeder and Motor
Protection
Hardware
Four different variants of HW :
Basic, Medium, High and High with sensors
L1 L3
A
0 -
+
Q0
N
n

*) - I
a
da dn X4.1
+

All variants contain:


ACFail Mains 1
X1.1
27 VT4 U 31* * ) 2
100V
TempAlarm -
25
L1 L3 24 VT3
P1 S1 1 00 V U 23 5
22 IRF 4
21 VT2
100V U 12
S2 19 3

„ 9 Digital inputs
P2 18 100V
VT1 U0 8
16 7
S1 15 0,2A C T5
14 1A I 0B
13
12 1A
SO1 6
C T4
S2 11 5A I0 10
11
10

DI 9 can be used for time


9

„
1A
8 5A
C T3 I L3
7 SO2 9
6 1A
C T2 I L2 12
5 5A
13
4
3 1A

sync.
2 5A
C T1 I L1
1 PO1
14
15

PO2
17
18 +

PO3
„ 6 Digital outputs
X4.2

„ 4 power outputs
4
3
2

HSPO1

X4.2 TCS1 1 +
5 DI1
- 6
7

8
9
DI2

DI3
SERIAL BUS X3.2
„ 2 signal outputs
10 X3.3
DI4 SERIAL BUS

11 DI5
12
13
14 DI6

15 DI7
16
17
18 DI8

X3.1
1
© ABB AG -3-

DI9
2

*) Power flow direction


**) In H03 can also be connected to U12b
REX 521
Feeder and Motor
Protection
Hardware

X1.1
27
25
L1 L3 24
P1 S1
22
21
„ Basic
S2 19
P2 18 „ 4 CTs
16
S1 15
14
13
12 1A
CT4
S2 11 5A I0
10
9 1A
8 5A CT3 I L3
7
6 1A
CT2
5 5A I L2
4
3 1A
2 5A
CT1 I L1
1
© ABB AG -4-
REX 521
Feeder and Motor
Protection
Hardware

X1.1
27

P1
L1 L3
S1
25
24 „ Medium
22
21

P2
S2 19
18 VT1
„ 5 CTs
100V U0
16
S1 15
14
13
0,2A
1A
CT5 I 0B „ 1 VT
12 1A
CT4
S2 11 5A I0
10
9 1A
8 5A CT3 I L3
7
6 1A
CT2
5 5A I L2
4
3 1A
2 5A
CT1 I L1
1
© ABB AG -5-
REX 521
Feeder and Motor
Protection
Hardware

X1.1

L3
27
25
100V
VT4 U21 „ High
L1 24 VT3
P1 S1 100V U23
22
21
100V
VT2 U12
„ 5 CTs
S2 19
P2
S1
18

16
100V
VT1 U0
„ 4 VTs
15 0,2A
CT5
14 1A I 0B
13
12 1A
CT4
S2 11 5A I0
10
9 1A
8 5A CT3 I L3
7
6 1A
CT2
5 5A I L2
4
3 1A
2 5A
CT1 I L1
1
© ABB AG -6-
REX 521
Feeder and Motor
Protection
Hardware
X1.1
27
25
24
22
21

19
18 VT1
100V U0 *)
16
15 0,2A
CT5 I0B
„ High sensor
1A
14
13
12 1A
CT4
11 5A
I0
10
9
8
7 „ 6 sensors
6
5
4
3
2
1
„ 2 CTs
Sensor VD3
Voltage input, U3 X2.1
DIFF

Sensor VD2
„ 1 VT
Voltage input, U2 X2.2
DIFF

Sensor VD1
Voltage input, U1 X2.3
DIFF

Sensor RS3
Current input, IL3 X2.4
DIFF

Sensor RS2
Current input, IL2 X2.5
DIFF

Current input, IL1 Sensor RS1


X2.6
DIFF
© ABB AG -7-
REX 521
Feeder and Motor
Protection Application Example: B01/B02
„ Outgoing feeder of a single
busbar:
„ All network types (Solidly
earthed, etc.)
„ Overheadlines (AR in B02)
3
„ Supervision and condition
1
monitoring of primary
equipment for preventive
maintenance
„ Current measurements for
network supervision and
operations
„ Non-directional protections
© ABB AG -8-
REX 521
Feeder and Motor
Protection Application Example: M02
„ Outgoing feeder of a single
busbar:
„ All network types (Solidly
earthed, etc.)
„ Cables (Dir E/F) and
3 overheadlines (AR in M02)
1 „ Supervision and condition
monitoring of primary
equipment for preventive
maintenance
„ Current measurements for
network supervision and
operations
„ Thermal overload
protection for cable/line
© ABB AG -9-
REX 521
Feeder and Motor
Protection Application Example: H04
„ Outgoing feeder of a single
busbar:
„ All network types (Solidly
earthed, etc.)
„ Cables and overheadlines
3 „ Extensive supervision and
condition monitoring of primary
1
equipment for preventive
maintenance
„ Wide range of measurements
for network supervision and
operations
„ Directional and non-directional
earth-fault protection
„ Thermal overload protection for
cable or line
© ABB AG -10-
REX 521
Feeder and Motor
Protection Application Example: H07
„ Outgoing motor feeder:
„ For large and medium size
synchronous and
asynchronous AC motors
„ Thermal overload protection
3 for devices
1 „ Motor start-up supervision
(stall protection)
„ Extensive supervision and
condition monitoring for
preventive maintenance
„ Wide range of measurements
M for supervision and operation
© ABB AG -11-
REX 521
Feeder and Motor
Protection
Protection Functions
HW versions Basic Medium High
Standard B01 B02 M01 M02 H01 H02 H03 H04 H05 H06 H07 H08
configuration
Protection FB Name ANSI Code
functions „ Basic B01 & B02
3I> NOC3Low 51 x x x x x x x x x x x
3I>> NOC3High 50/51 x x x x x x x x x x x
3I>>> NOC3Inst 50/51 x x x x x x x x x x
Io>
Io>>
NEF1Low
NEF1High
51N
50/51N
x
x
x
x
x)
x)
x
x
x
x
x
x „ Medium M01 & M02
Io>>> NEF1Inst 50N x x x) x x
Io>--> DEF2Low 67N/51N x x x x x x x
Io>>--> DEF2High 67N x x x x x x x
Io>>>-->
3I>-->
DEF2Inst
DOC6Low
67N
67
x x x
x
x
x
x x
x
„ High H01 – H06 & H08
3I>>--> DOC6High 67 x x
3I>>>--> DOC6Inst 67
3U> OV3Low 59 x x x x
3U>> OV3High 59 x x x x „ Motor protection H07
3U< UV3Low 27 x x x x
3U<< UV3High 27 x x x x
3I2f> Inrush3 68 x x x x x x x x x x
Iub> CUB3Low 46 x x x x x x x x
3Ith> TOL3Cab 49F x x x x x x x x
O-->I AR5Func 79 x x x x x x
Uo> ROV1Low 59N x x x
Uo>> ROV1High 59N x x x
Uo>>> ROV1Inst 59N x x x
f1 Freq1St1 81U/81O x x x x
f2 Freq1St2 81U/81O x
SYNC SCVCSt1 25 x x
Is2t n< MotStart 48,14,66 x
3I() PREV3 46R x
I2> NPS3Low 46 x
I2>> NPS3High 46 x
3I< NUC3St1 37 x
© ABB AG -12-

FUSEF FuseFail 60 x
3Ithdev> Tol3Dev 49M x x
U1<U1U2> PSV3St1 27,47,59 x
REX 521
Feeder and Motor
Protection
Control Functions
Included control functionality decreases the amount of external
components

No extra auxiliary relays are


needed for interlockings or control

„ Control of one breaker


„ Pre-programmed interlocking
conditions
„ Operation by external push buttons,
through communication or via menus
© ABB AG -13-
REX 521
Feeder and Motor
Protection
Measurements
Enhanced measuring functions improve the supervision of the process!

„ REX 521 measures :


„ 3-phase current*
„ Neutral current
„ 3 phase voltage
„ Total harmonic distortion (THD) „ Residual voltage
„ Individual harmonics up to 13:th
„ Monitoring of each harmonic „ Active / reactive power*
„ Statistics of each harmonic
„ Supervision „ Energy
„ Separate alarm limits for each harmonic
„ Cos fi
„ Frequency
„ Harmonics for currents and
voltages

„ Disturbance recorder
© ABB AG -14-

* Also mean values


REX 521
Feeder and Motor
Protection
Conditon Monitoring
Coming errors/problems in auxiliary equipment can be foreseen with
condition monitoring
„ The monitored units are:
„ Current transformers
„ Voltage transformers
„ Trip circuit
„ Circuit breaker
„ Breaker wear
„ Counter
„ Inactive time
„ Travel time
„ Running time (motor
protection)
„ Relay
© ABB AG -15-
REX 521
Feeder and Motor
Protection Improving the Network

REX 521 combined with sensors:


„ Less engineering time as you
have two universal versions to
choose from
„ Human safety improved, through
low voltage levels
„ Accuracy at high current
„ Compact design, enabling easy
installation
© ABB AG -16-
REX 521
Feeder and Motor
Protection Communication Benefits
Information available through
communication:
„ Set values
„ Measured values
„ Registered values / events
„ Uploading of disturbance
recorder data
„ Control
„ Setting banks
© ABB AG -17-
REX 521
Feeder and Motor
Protection
Communication and System Integration
INBUILT PROTOCOLS IN REX 521
Rear port Rear port
Protocol
optical opto isolated RS-485
SPA X X
RS - 485
LON X
IEC 60870-5-103 X X
ModBus (RTU & ASCII) X X
DNP 3.0 X X

OPTICAL
WITH ADAPTER
Protocol ADAPTER
ProfiBus DPV1 SPA-ZC 302
IEC 61850-8-1 SPA-ZC 402

Note! Only one communication


port and protocol can be active at
a time (optical front connector can
be used simultaneously,
naturally).
© ABB AG -18-
REX 521
Feeder and Motor
Protection Saving Engineering Time

The REX 521 is suitable


for all kinds of switchgear
© ABB AG -19-
REX 521
Feeder and Motor
Protection Saving Engineering Time
Before After

Switchgear installation space


is reduced
© ABB AG -20-
REX 521
Feeder and Motor
Protection
Easy to Set with Graphical Setting Tool
New graphical setting tool in CAP 501 & CAP 505
© ABB AG -21-
REX 521
Feeder and Motor
Protection User Friendliness

Pre-tested in the factory providing ready


made test plans
© ABB AG -22-
REX 521
Feeder and Motor
Protection Ordering
When ordering REX 521 protection relays, specify the following:
„ Order number
„ Quantity
„ Additional language
© ABB AG -23-
REX 521
Feeder and Motor
Protection What It All Comes Down to Is…
„ Reduce the need for local
adaptations
„ Improve efficiency through data
information and prevent accidents
from happening
„ Engineering time is reduced thanks
to easy implementation
„ Reduce the need for advanced
training

We are there for you !


© ABB AG -24-