FEATURES
1. High accuracy
0.2% accuracy for all calibrated spans is a standard
feature for all AP models covering 1.6kPa {0.016bar} [ L-Type ] [ T-Type ]
range to 3000kPa {30bar} high pressure range. 0.1%
accuracy is available as option. Fuji’s micro-capacitance
silicon sensor assures this accuracy for all suppressed
calibration ranges without additional adjustment. SPECIFICATIONS
2. Minimum environmental influence
The “Advanced Floating Cell” design which protects Functional specifications
the pressure sensor against changes in temperature,
Service: Liquid, gas, or vapour
and overpressure substantially reduces total measure-
Span, range, and overrange limit:
ment error in actual field applications.
3. Fuji/HART® bilingual communications protocol
Span limit Overrange
FCX -AIII series transmitter offers bilingual communica- [kPa abs] {bar abs}
Range limit limit
[kPa abs]
tions to speak both Fuji proprietary protocol and HART®. Type
{bar abs}
[MPa]
{bar}
Any HART® compatible devices can communicate with Min. Max.
FCX -AIII. FKA 01 1.6 16 0 to +16 0.5
4. Application flexibility {0.016} {0.16} {0 to +0.16} {5}
Various options that render the FCX -AIII suitable for FKA 02 1.6 130 0 to +130 0.5
{0.016} {1.3} {0 to +1.3} {5}
almost any process applications include: FKA 03 5 500 0 to +500 1.5
– Full range of hazardous area approvals {0.05} {5} {0 to +5} {15}
FKA 04 30 3000 0 to +3000 9
– Built-in RFI filter and lightning arrester {0.3} {30} {0 to +30} {90}
– 5-digit LCD meter with engineering unit
– Stainless steel electronics housing Remark: To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
– Wide selection of materials
– The maximum span of each sensor can be converted
5. Burnout current flexibility (Under Scale: 3.2 to 4.0mA,
to different units using factors as below.
Over Scale: 20.0 to 22.5mA)
1MPa abs=103kPa abs=10bar abs=10.19716kgf/cm 2 abs
Burnout signal level is adjustable using Model FXW
=145.0377psi abs
Hand Held Communicator (HHC) to comply with
1kPa abs =10mbar abs=101.9716mmH2O abs
NAMUR NE43.
=4.01463inH2O abs=7.50062mmHg abs
6. Dry calibration without reference pressure
Output signal: 4 to 20mA DC with digital signal super
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance imposed on the 4 to 20mA signal.
electronics circuit (Electronics unit), reliability of dry Power supply: Transmitter operates on 10.5V to 45V
calibration without reference pressure is at equal level DC at transmitter terminals.
as wet calibration. 10.5V to 32V DC for the units with op-
tional arrester.
EDSX5-91g
Date Apr. 1, 2011
FKA...5
2
Performance specifications Process-wetted parts material:
l a i r e t aM
Reference conditions, silicone oil fill, 316SS isolating diaphragms, e d o c Wetted
t Process
i g i d h tcover
7( Diaphragm Vent/drain
4 to 20mA analog output in linear mode. sensor body
e d oC “ n i
Accuracy rating: (including linearity, hysteresis, and re- symbols”)
peatability). V 316 stainless 316L 316 316/316L
(Standard) steel (*1) stainless steel stainless steel stainless steel
For spans greater than 1/10 of URL: ±0.2% of span H 316 stainless Hastelloy-C Hastelloy-C 316/316L
steel (*1) lining stainless steel
For spans below 1/10 of URL:
( )
Note: (*1) SCS14A per JIS G 5121 (equivalent CF8M per ASTM
± 0.1 + 0.1 0.1 x URL % of span A351/A351M)
Span Remarks: Availability of above material design depends on ranges.
Refer to “Code symbols”.
(Option) (code: 21th digit H) Non-wetted parts material:
(Not available for Max span 16kPa abs, 130kPa abs) Electronics housing: Low copper die-cast
For spans greater than 1/10 of URL: ±0.1% of span aluminum alloy finished with polyester
For spans below 1/10 of URL: coating (standard), or 316 stainless
(
± 0.05 + 0.05 0.1 x URL % of span
Span
)
steel (ASTM CF8M), as specified.
Bolts and nut: Cr-Mo alloy (standard),
304 or 316 stainless steel
Stability: ±0.2% of upper range limit (URL) for 10 Fill fluid: Silicone oil
years. Mounting bracket: 304 or 316 stainless
Temperature effect: steel.
Effect per 28°C change between the Environmental protection:
limits of - 40°C and +85°C IEC IP67 and NEMA 6/6P
(
Zero shift: ± 0.125+0.1
URL
Span
% ) Mounting: On 60.5mm (JIS 50A) pipe using mounting
bracket, direct wall mounting, or direct
(
Total effect: ± 0.15+0.1 URL %
Span
) process mounting.
Mass{weight}: Transmitter approximately 2.9 to 3.4kg
without options.
Overrange effect: Zero shift; ±0.2% of URL for any overrange Add; 0.5kg for mounting bracket
to maximum limit 4.5kg for stainless steel housing
Supply voltage effect: option
Less than 0.005% of calibrated span per
1V Optional features
Update rate: 60 msec
Step response: Time constant: 0.08 s (at 23°C) Indicator: A plug-in analog indicator (2.5%
Dead time: 0.12 s accuracy)
(without electrical damping) An optional 5-digit LCD meter with
Mounting position effect: engineering unit is also available.
Zero shift, less than 0.1kPa{1mbar} for a Local configurator with LCD display:
10° tilt in any plane. An optional 5 digits LCD meter with 3
No effect on span. This error can be cor- push buttons can support items as using
rected by adjusting zero. communication with FXW.
Dielectric strength: Arrester: A built-in arrester protects the electronics
500V AC, 50/60Hz 1 min., between circuit from lightning surges.
and earth. Lightning surge immunity:
Insulation resistance: 4kV (1.2 × 50µs)
More than 100MΩ at 500V DC. Degreasing: Process-wetted parts are cleaned, but the
Internal resistance for external field indicator: fill fluid is standard silicone oil. Not for use
12Ω or less on oxygen or chlorine measurement.
NACE specification:
Metallic materials for all pressure bound-
Physical specifications ary parts comply with NACE MR-01-75.
304 stainless steel bolts and nuts, ASTM
Electrical connections: B7M or L7M bolts and 2HM nuts (Class
G 1 /2, 1 /2-14NPT, Pg13.5, or M20 x 1.5 II) are available.
conduit, as specified. Optional tagplate:
Process connections: An extra stainless steel tag for customer
1/4-18 NPT or Rc1/4 on 54mm centers, as
tag data is wired to the transmitter.
specified. Coating of cell: Cell’s surface is finished with epoxy/
polyurethane double coating. Specify if
environment is extremely corrosive.
3
FKA...5
4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 21 Digit No.
Digit Description Note F KA 0 5 of code
12 <Options>
Extra SS tag plate Stainless steel elec. housing Coating of cell
None None None Note2 Y
Yes None None B
None (*2) None Yes M
Yes None Yes N
None Yes Yes Note5 P
(*5) Q
Yes Yes Yes Note5
13 <Special applications and fill fluid>
Treatment Fill fluid
Standard Silicone oil Y
Degreasing Silicone oil G
NACE specification Silicone oil (7th digit code "T" and 15th digit code N
"A", "B" are not available)
14 <O-ring/Gasket and Teflon membrance>
Teflon (gasket) B
15 <Bolt/nut> (*3) Note 3
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut A
Cr-Mo alloy hexagon bolt/nut B
NACE bolt/nut (ASTM A193 B7M/A194 2HM) C
NECE bolt/nut (ASTM A320 L7M/A194 2HM) D
304 stainless steel bolt/304 stainless steel nut E
316 stainless steel bolt/316 stainless steel nut U
21 <Other options> (*4) Note 4
High accuracy type (*7) Instruction manual attached Note 7 H
Opposite Vent/Drain Plug Position Instruction manual attached C
Instruction manual unattached L
High accuracy type(*7) Instruction manual unattached Note 7 T
Opposite Vent/Drain Plug Position Instruction manual unattached P
Note2: (*2) Customer tag number can be engraved on standard stainless steel
name plate. If extra tag plate is required, select "Yes".
Note3: (*3) In case of tropical use, select stainless bolts and nuts.
Note4: (*4) If other option is not necessary, 21st digit code is blank.
In case of 21st digit code is blank, instruction manual attached.
Note5: (*5) Not available for 10th digit code “C”.
Note6: (*6) Available for 4th digit code "S".
Note7: (*7) Available for 6th digit code "3", "4".
Note8: (*8) Available for 4th digit code "6", "8", "T", "W".
Note9: (*9) Available for 4th digit code "6", "T".
5
FKA...5
8
(21)
10
EARTH TERMINAL
41
(11)
ZERO
110
φ81
100
SCS13
70
38
VENT/DRAIN PLUG
"B" CONDUIT CONN.
57 37
NOTE2)
(229) NOTE2)
H
φ15 SIDE VENT(OPTION)
2.5
226
8
41.3
F
E
L.P H.P
10 D
TABLE 1
+ −/CK− CK+
75
6
<AMP. case: L type>
VENT/DRAIN PLUG
(WHEN THE VENT/DRAIN PLUG ATTACHED
MTG. PIPE JIS 50A (2B) ON THE UPPER SIDE OF THE DETECTOR) NOTE3)
IN CASE OF 4TH DIGIT CODE "T"
10
41
41
103
φ81
103
70
φ81
120
RO
38
"B" CONDUIT CONN.
57 37
172 (21) WITH ANALOG IND.
(175) (11)
4 HOLES 9 DIA. 126
41 43
VENT/DRAIN PLUG
U-BOLT M8
WITH DIGITAL IND.
NOTE2)
EARTH TERMINAL
(201) NOTE2)
41.3
8
L.P
198
H.P
E
10 D 4-M8×12
SEE TABLE1 SEE TABLE1
TABLE 1
19
CONNECTION DIAGRAM <SS TAG PLATE>
17
83
"C" CONDUIT CONN.
G1/2
+ −/CK− CK+ CABLE GLAND
75
7
FKA...5
TABLE 2
ATEX Ex II 1 G ATEX Ex II 2 GD
Ex ia IIC T5 Tamb = –40°C to +50°C Ex d IIC T6 IP66/67 T85°C
Ex ia IIC T4 Tamb = –40°C to +70°C Tamb = −40°C to +65°C
Ex d IIC T5 IP66/67 T100°C
Entity Parameters: Tamb = −40°C to +85°C
Ui=28V, Ii=94.3mA, Pi=0.66W,
Factory Class I
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Mutual Div.1 Groups B, C, D
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
T6 Type 4X
Factory Class I II III Class II III
Mutual Div.1 Groups A, B, C, D, E, F, G Div.1 Groups E, F, G
T4 Entity Type 4X T6 Type 4X
Model code Tamb max = +60°C
Tamb
9th digit CSA Class I
A,B,D –40°C to +85°C Div.1 Groups C, D
L,P,1,2 –20°C to +80°C Class II
Q,S,4,5 –20°C to +60°C Div.1 Groups E, F, G
E,F,H –40°C to +60°C Class III
Entity Parameters: Div.1
Vmax=28V, Imax=94.3mA, Pi=0.66W,
Ci=35.98nF, Li=0.694mH Note) “Seal Not Required” enclosure is allowed.
TIIS Ex do IIB+H2 T4
CSA Class I
Tamb max = +60°C
Div.1 Groups A, B, C, D
Maximum process temp. = +120°C
Class II
Div.1 Groups E, F, G IECEx Ex d IIC T5 IP66/67
Class III Scheme Tamb = −40°C to +85°C
Div.1 Ex d IIC T6 IP66/67
Temp Code T5 Tamb max = +50°C Tamb = −40°C to +65°C
Temp Code T4 Tamb max = +70°C
NEPSI Ex d IIB+H2 T6
Entity Parameters:
Tamb = −40°C to +60°C
Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester),
Ci=36nF (With Arrester), Li=0.6mH (Without analog meter),
Type n
Li=0.7mH (With analog meter) Authorities Nonincendive
TIIS Ex ia IIC T4 ATEX Ex II 3 GD
Tamb max = +60°C EEx nL IIC T5 Tamb = –40°C to +50°C
Entity Parameters: EEx nL IIC T4 Tamb = –40°C to +70°C
Ui=28V, Ii=94.3mA, Pi=0.66W, Specific Parameters:
Ci=38.4nF, Li=0.694mH Model without arrester:
IECEx Ex ia IIC T4 Ui=42.4V, Ii=113mA, Pi=1W,
Scheme Tamb = –40°C to +70°C Ci=25.18nF, Li=0.694mH
Ex ia IIC T5 Model with arrester:
Tamb = –40°C to +50°C Ui=32V, Ii=113mA, Pi=1W,
Entity Parameters: Ci=35.98nF, Li=0.694mH
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), EEx nAL IIC T5 Tamb = –40°C to +50°C
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) EEx nAL IIC T4 Tamb = –40°C to +70°C
Specific Parameters:
NEPSI Ex ia IIC T4 Model without arrester:
Ex d IIB+H2 T6 / Ex ia IIC T4 Umax=42.4V, Imax=113mA, Pmax=1W
Model code Model with arrester:
Tamb Umax=32V, Imax=113mA, Pmax=1W
9th digit 13th digit
A,B,D Y,G,N –40°C to +85°C Factory Class I II III
L,P,1,2 Y,G,N –20°C to +80°C Mutual Div.2 Groups A, B, C, D, F, G
Q,S,4,5 Y,G,N –20°C to +60°C (pending) T4 Entity Type 4X
E,F,H Y,G,N –40°C to +60°C
Model code
Tamb
Entity Parameters: 9th digit
Ui=42.4V, Ii=113mA, Pi=1W, A,B,D –40°C to +85°C
Ci=35.98nF, Li=0.694mH L,P,1,2 –20°C to +80°C
Q,S,4,5 –20°C to +60°C
E,F,H –40°C to +60°C
CSA Class I
Div.2 Groups A, B, C, D
Class II
Div.2 Groups E, F, G
Class III
Div.2
Temp Code T5 Tamb max = +50°C
Temp Code T4 Tamb max = +70°C
Entity Parameters:
Vmax=28V, Ci=25.18nF (Without Arrester),
Ci=35.98nF (With Arrester), Li=0.694mH
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.