Sie sind auf Seite 1von 5

A HIGH-PERFORMANCE, CONTROLLED CYCLOCONVERTER FOR TRACTION POWER APPLICATION

Ezzat B. Khalafalla, Senior Member S.C. Dun, Member


Stone & Webster Engineering Corporation Southeastern Pennsylvania Transportation Authority
3 Executive Campus, P.O. Box 5200 714 Market St.
Cherry Hill, New Jersey 08034 Philadelphia, Pennsylvania 19 106-2385

Absrract - This paper discusses the application and performance converter by phase-controlling the output of a double (reversing)
of a cycloconverter-type frequency converter as applied to traction converter to produce an alternative voltage (see Fig. 2). Traction
(railroad) power loads. The paper details 1) the basic theory and op- power used on SEPTA’S 11-kV commuter rail system is single-
eration of a cycloconverter and traction power, 2) ratings to meet phase, 25 Hz; therefore, one double converter is sufficient for trac-
performance requirements for traction application, 3) efficiency and tion power application (see Fig. 3). (Normally, three double convert-
power factors, 4) harmonic analysis, and 5) a summation, including ers are required to produce a 1200, phase-shifted, three-phase
the advantages of static frequency conversion equipment. The data cycloconverter system.) Since the cycloconverter output is derived
contained in this paper are based on corroborated experimental re- directly from the ac power system, the maximum output frequency is
sults from the field installation of a 3-15 MVA static frequency con- limited to a fraction (typically one-third) of the power system fre-
verter station. quency (e.g., 16 2/3 Hz for the 50-Hz systems used in Europe and
25 Hz for 60-Hz systems in the US.)to maintain an acceptable out-
Introduction put voltage waveform with low harmonic content. Output voltage con-
trol is also accomplished by phase-controlling the converters to pro-
During recent years, the development of thyristor switching de-
duce the desired voltage level of the output ac voltage wave. The
vices has opened up new fields of traction power application. These
cycloconverter operation continually transfers the load current from
devices are highly reliable and require little maintenance. For traction
one thyristor to another, and from positive to negative current flow,
applications, the most important characteristics of cycloconverters are
thus producing the shape and polarity of the output ac voltage. The
their high range of operation and high overload capability.
current-carrying capacity of the thyristor devices is based on this con-
This paper investigates line-side and load-side interaction for the tinual switching, which requires that certain output frequencies be
cycloconverter application in the traction power area. It is well known avoided to prevent excessive heating of a particular group of thyris-
that static converters may generate inductive power and harmonic tors. The most important frequencies to be avoided for continuous
power on both the line and load sides. For this investigation, funda- operation are 0, 30, 45, and 60 Hz [SI. Continuous operation at
mental inductive power on the load side (25 Hz) is assumed constant these frequencies may be possible at reduced load. For traction power
(0.8 pF). Harmonic power, which may cause additional losses, is application, the required output frequency is 25 Hz (the frequency
therefore a disadvantage. The power factor on the line side (60 Hz) utilized in the original electrification of U.S.railroads in the 1920s
ideally should be as close as possible to unity, since both reactive and and 1930s). The efficiency of the cycloconverter is high due to the
harmonic power contribute to additional losses and voltage distortion. use of static components such as thyristors. The no-load and full-load
losses are approximately 1 and 7 percent of rated kVA, respectively
With the rapid advance and acceptance of solid-state technology, [lo].
static power conversion equipment can be applied to replace existing
converter equipment on low-frequency traction power systems. A
number of such applications in Europe have successfully employed
thyristor switching equipment in traction power fields.

It should be recognized that the growing use of thyristor controls


requires increased attention to harmonic distortion for two reasons.
First, this equipment often introduces considerable amounts of har-
monic currents into the power system. Second, the equipment re-
quires high-quality voltage with low distortion for proper operation.

Basic Theorv of Ooeration

A cycloconverter consists of several phase-controlled rectifier cir-


cuits (thyristors) connected to an ac supply system which provides the
voltages necessary for delayed-phase commutation. The individual
circuits are controlled so a low-frequency output voltage waveform is
fabricated from segments of the polyphase input voltages [ 11.

A basic cycloconverter circuit which utilizes a three-phase bridge


thyristor converter is shown on Fig. 1. Note that the power conversion
circuits are connected to the ac power system through isolation trans-
formers, thus providing electrical isolation between the power system
and output phases of the cycloconverter. The transformers also pro-
vide correct voltage to the converter circuit as required. The basic Fig. 1. Three-phase to three-phase cycloconverter: (a) schematic
cycloconverter operation utilizes the technology of the dc thyristor diagram; (b) basic circuit.

CH3O4-9/91 /oooO-0133$1.oO 0 1991


133
able because the filter design can be guaranteed to stay within a rea-
sonable voltage limit despite changes in the 60-Hz network imped-
ance seen from the converter terminals [3].

A harmonic study of the entire system will determine the type and
location of potential harmonic problems within the system and the
i Inversion 1
remedial steps that should be taken.
]- Rectification -c- 4I

yniaue 0
- ine Characteristiq
0 '-curr.nr ".Call".
0
I"
OIOUP
The fact that traction load (25 Hz) is uncoupled from source
power (60 Hz) by the cycloconverter provides a number of unique
Fig. 2. Voltage and current waveforms for the positive group of operating characteristics.
a phase-controlled cycloconverter when feeding an in-
ductive load at 0.6 power factor. The system is defined as a static frequency converter (cyclocon-
verter), which operates as a source of current to the traction load.

The source power bus (60 Hz) does not "see" the traction load
(25 Hz) directly and vice versa. The traction load will not contribute
to short circuits on the 60-Hz bus; and 60-Hz bus disturbances, such
as unbalanced voltage, three-phase, phase-to-phase and ground fault
disturbances, will not disturb the traction load. The power transmis-
sion to the traction load is, of course, disrupted by the power 60-Hz
bus disruption.

Application of static frequency converter equipment to supply


power to traction loads requires recognition of the potentially adverse
60-Hz system operating characteristics and evaluation of the 60-Hz
system design to minimize their effects. The adverse characteristics
are the harmonic currents produced by line-commutated power con-
verters and the reduction-in-power factor associated with the phase-
control action of the cycloconverter.

The design and operation of the system should recognize these


unique operating characteristics and be optimized for highest effi-
ciency, power factor and reliability, and minimal harmonic effects.

Svstem Desien and Performancs

For traction load application, the system design can be optimized


to improve overall system performance. Performance criteria to con-
sider are as follows:

Cycloconverter rating
Fig. 3. Three-phase to single-phase cycloconverter: (a) schematic
diagram; (b) basic circuit; (c) actual circuit. System rating

Efficiency

Power factor
A major concem is the 60-Hz voltage waveshape, for which sev-
eral methods of reducing the harmonic content are available. Trans- Harmonics
formers or reactors insert impedance between the converter bridge Reliability/availability.
and the system. Capacitors tuned with a small inductance absorb har-
monic energy. Static harmonic filters and power factor correctors are Cvcloconverter Rating
used also.
The first consideration for traction application is selection of the
Whether or not harmonic filters are required for a particular ap- cycloconverter rating. For reasons not within the scope of this paper,
plication is determined by system impedances, magnitudes of the har- a 15-MVA cycloconverter unit with 200-percent emergency overload
monics, and other loads on the electrical system. rating capability was selected and sized to operate in parallel with two
other units [ 81.
The filters may be classified by their location, connection to the
main circuit, sharpness of tuning, and the number and frequencies of Svstem R a t i a
their resonances.
In the past, train-starting transients and voltage dips have been
The practical criterion for adequacy of ac filters would be an ac- major problems of electrical tractions. The new problem is not only
ceptable level of harmonics at the converter terminal, expressed in the transient conditions, but also the steady-state power harmonics
terms of harmonic current, harmonic voltage, or both. The criterion [ 61. The system design starts with the cycloconverter voltage, which is
based on harmonic voltage at the converter terminals is more favor- required at rated power.

134
banks happen to be resonant with the source at harmonic being gen-
erated, harmonic resonance occurs. The capacitor banks are in shunt
Determining cycloconverter system efficiency requires that the with the system impedance, which is usually inductive. The combina-
segregated losses of major components be determined as a function of tion forms a parallel resonant filter which results in increased harmon-
system operating variables such as voltage, current, and frequency. ic currents and voltages (a potential for high voltages is present). The
An evaluation of these losses will indicate the most efficient way to frequency of a resonance will be approximately:
operate the system over the power output range. The losses are identi-
fied in two categories, operating condition and harmonic, both of
h =-Mvasc
which must be adjusted from the losses at the base rating. Tables 1
Mvarc
and 2 identify the segregated losses for major components and define
the adjustments which apply for operating conditions and harmonics. where:

Table 1 - Transformers and Reactor Segregated Losses h = Harmonic of the fundamental


M V % ~Three-phase
= short-circuit duty of the bus in Mva
Loss Adiustment Mvar,= Mvar rating of the capacitor bank
Operating
kQss Condition The formula is also equivalent to:
Transformer

Excitation V None
PR I2 & temp. None
where:
Stray I2 & temp. PS = IiH
Eddy I2 & temp. Pe = IiH2 AV = Change in the voltage

Reactor For weak supply systems, the harmonic number can be in the
range of the second or third harmonic. It is not uncommon to find a
IR I2R & temp. None system tuned to the fifth harmonic.
Stray None Ps = IiH
Eddy None Pe = I;H2 From a capacitor bank application perspective, the amount of
harmonic on a high-voltage system may be divided into three catego-
Table 2 - Cycloconverter and Control Segregated Losses ries:

Loss 1. Harmonics exist, but not in enough magnitude to require any


special consideration.
Operating
Lpss Condition 2. Enough harmonics are present to cause problems only if reso-
nance occurs between the capacitors and system source.
Control Constant None
Cooling System Constant None 3. Harmonics are large enough to cause problems for capacitor
Bus P R 12 x K K = 1.1 banks or bus voltages, even in the absence of a resonant con-
Thyristor V(on-state)I None dition.
Filters Vf2 Pf = F(V2 ,f, a, p)
The location of the capacitor banks on the system will not be
discussed in detail here. Data to design a system for the harmonic
Note: requirements can be derived from the system distribution or transmis-
V(on-state) = Forward voltage drop of the thyristor
sion network impedances (see Fig. 4).
CY = Phase control angle
p = Commutating angle

Large installations of harmonic generating loads, such as


cycloconverters, on a weak high-voltage source may lead to badly
distorted bus voltages. In addition, if the high-voltage capacitor

BASE VALUES
KV = 230 KV
Mw 5 lOWMv8

Fig. 4. Schematic of simplified system network


To avoid harmonic resonance, an installation may be "detuned" interference is also possible, and lighting flicker may occur. Addi-
by tuning to a resonance below the fifth harmonic and using an un- tional problems such as heating in rotating equipment, transformer
grounded capacitor bank. The usual practice is to tune the capacitor overexcitation, and capacitor overvoltage have been known to occur.
with a reactor to about the 4.7th harmonic. This makes the capacitor Harmonic currents and voltages also tend to desensitize electrome-
resonant with the source substantially below the fifth harmonic, the chanical relays. To minimize the impact of harmonic voltage distor-
lowest harmonic generated in significant magnitude. Thus, the capaci- tion, one general approach is to design the power supply with low
tor bank cannot become resonant with the source at the fifth harmoic impedance (with a high short-circuit level) to allow currents to flow
or higher without removing a substantial number of capacitors from into the system without developing greater voltages than required.
the bank.
The harmonic currents injected by cycloconverters have a unique
The harmonic losses in the 60-Hz system (transformer, cables, type of spectrum. The characteristic harmonic frequencies can be
converter, filters, etc) are related to strand and circulating loss in the demonstrated by the following equation:
system. These harmonic losses can be reduced significantly by using
two separate transformer, phase-shifted 30 electrical degrees f = (pm f l)f f 6nfo
(12-pulse converter) filter banks. h
where:
hxedaml
fo= Output frequency of cycloconverter (25 Hz)
The 60-Hz ac supply currents are nonsinusoidal in a cycloconver-
ter installation, and a distinction must be made between the power f = Power frequency (60 Hz)
+
factor (A), displacement factor (cos ), and distortion factor (jl) . In
such cases, the power factor, A, is defined as the ratio of the real m and n = Constants 1, 2, 3, ...
input power in watts to the total apparent power in volt-amps. The
displacement factor, cos I$ , is the fundamental power factor, since p = pulse rectifier (12 pulse for this application)
4 is the phase displacement between the fundamental phase current
and the sinusoidal phase voltage. The distortion factor, p, is the ratio Because of load unbalance and asymmetries between the phase
of the fundamental Rh4S current to the total RMS current. These voltage and the firing angle, noncharacteristic harmonic frequencies
quantities are related as may be present which can be demonstrated by the following equation:

f = (pm&l)f k2nfo
A = jl cos I$ (1) h
The cycloconverter cannot transmit leading reactive power, and The above equation illustrates that the harmonic currents spec-
the lagging reactive power drawn from the supply is always greater trum ranges from 10 to 2000 Hz.
than that delivered to the load.
Because the output frequency, f,, is fixed (25 Hz) for traction
The power factor of interest to the user is the displacement power power application, the harmonic spectrum is fixed, unlike other appli-
factor seen at the 60-Hz primary isolation transformer. The power cations such as variable speed drive where output frequencies vary. As
factor of traction power is of interest only as it affects the efficiency a result of the fixed harmonic spectrum, tuned filters are effective and
and kVA rating of the cycloconverter and filter bank at the 25-Hz more practical. However, because of filter design limitations, a filter
side. The input displacement power factor is a function of the voltage for a subharmonic 10-Hz frequency may not be feasible or economi-
level at traction power. To a first approximation, the input displace- cal. The existence of a 10-Hz frequency may produce a flickering
ment power factor will decrease linearly with the traction power load voltage on the high-voltage network even though the total harmonic
voltage. distortion factor is within the acceptable level. To reduce the flicker-
ing voltage impact on the high-voltage network, the supply system-
m o n k and Svstem De- available short-circuit Mva should be at least 100 times the cyclocon-
verter output power.
The harmonics of major interest are those injected into the utility
power system network by the cycloconverter system. Static-power The magnitude of the harmonic current is a function of the mag-
converters generate currents which create harmonic voltage distortion nitude of the fundamental current and the phase-control angle of the
at the supply bus. By proper analysis and system design, the voltage source-side converter. In many cases, the magnitudes of harmonics
distortion can be kept within acceptable limits to ensure that other are known or calculated, but their phase angles are not known. For
equipment connected to the bus will operate satisfactorily (21. this reason, it is usually more practical to assume that the crests of all
harmonics occur simultaneously at least once per cycle.
The spectrum of currents at various frequencies indicates the
magnitudes expected at different load levels. These currents will be In practice, harmonic order above the twenty-fifth harmonic may
developed as a result of switching operations by the thyristors. The be neglected with very little error.
voltages produced will be the products of the current magnitudes flow-
ing into the system and encountering system impedances, which are Radio interference in the frequency range of 0.2 to 10 MHz is
presented to the current flow at the respective frequencies. These har- generated in the converter station due to rapid breakdown of the volt-
monic voltages may be of such magnitudes as to cause distortion of age between anodes and cathodes of the thyristor valves during the
the voltage waves. Distortion of the supply voltage waveform normally ignition period. These breakdowns cause steep current pulses to be
is objectionable, since it may cause overheating of power factor cor- injected into the system, resulting in radio noise. The noise can be
recting capacitors. At the harmonic frequencies, undesirable series reduced by proper electromagnetic screening of the thyristor valve
resonance also may occur between the power factor correcting capaci- cubicles in the converter station. No extra filtering measures should
tance and the transformer reactance. A certain amount of telephone be required.

136
. ‘i ing decisions for successful implementation of static frequency convert-
ers. The following fundamentals apply:
The reliability of the static-power conversion equipment, as ex-
pressed in terms of MTBF (mean time between failure), has been signifi- Employing a cycloconverter in a traction power application is
cantly improved by the use of thyristors, microprocessors, integrated-cir- feasible and practical provided the design recognizes all applica-
cuit technology, and improvements in manufacturing and quality control tion factors involved.
techniques. The calculated MTBF for a 12-pulse converter is 15,000 to
20,000 hours (approximately 2 years). These numbers are based on Harmonic analysis should be an integral part of the design or
conservative design practice for power and control circuits. The avail- expansion of any converter station containing several large
ability of the equipment, expressed by the probability that it will be oper- cycloconverters.
ating at any time, is 99.95 percent because of short repair time, which is
conservatively estimated to be 4 hours. The cycloconverter is equipped with tuned filter banks to sup-
press harmonics, generate reactive power, and support commu-
The reliabilitylavailability of the static frequency converter can be tation.
improved by maximizing the reliability of each of its major components -
the power system, cooling system, and control electronics. References
Power system reliability is maximized by increasing the thyristor reli- John M. D. Murphy. Thyristor Control of A X . Motors.
ability. The two key elements in determining thyristor reliability are New York: Pergamon Press, 1973.
working voltage and junction temperature.
The Institute of Electrical and Electronics Engineers, Inc.
Substantial derating must be applied to both the voltage rating and (IEEE). IEEE Standard 519-1981. Guide for Harmonic
the junction temperature to obtain a high level of reliability. Further Control and Reactive Compensation of Static Power Con-
significant improvement in reliability is achieved by adding one extra verters. New York, 1981.
thyristor device in series per string, which increases the voltage margin
and the ability of the converter to operate with one failed device without Edward Wilson Kimbark. Direct Current Transmission -
decreasing the reliability of the remaining devices. The combination of Volume 1. John Wiley and Sons, Inc., 1971.
voltage and junction temperature derating, plus the addition of an extra
Pennsylvania Power & Light Company (PP&L). Power Sys-
device per string such that no single power device can cause a converter
tem Harmonies - Establishment of Criteria and Method of
failure, results in an extremely high level of reliability in the converter
Analysis. PP&L System Planning Department Report
power system.
SPR-249. PP&L, Allentown, Pa., 1985.
The thyristor equipment is air-cooled. The ventilation system for the
Bimal K. Base. Adjustable Speed AC Drive Systems. New
converters employs a fan inside the converter cabinet as the moving
York: IEEE Press, 1980.
force for pulling outside air into the converter to cool the thyristors.
The Institute of Electrical and Electronics Engineers Work-
The control electronics, by the sheer number of components, is the
ing Group on Power System Harmonics. Power System Har-
determining factor in overall converter reliability. Control electronics re-
monics: An Overview. Vol. PAS-102, No. 8, August 1983.
liability is maximized by the following three steps:

1. Using the highest level of 100-percent tested components. Robert B. Fisher. Introduction of Static Frequency Convert-
er on SEPTA’S 25-Hz Commuter Rail System. Presented
2. Eliminating unreliable components. at ASME/IEEE Joint Railroad Conference, Chicago, Ill.,
April 17-19, 1990.
3. Bum-in of finished electronics package.
Tristan A. Kneschke. Static Frequency Converter for
Redundant control can be achieved to some degree, but its complex- SEPTA’S Wayne Junction Traction Substation. IEEE Trans.
ity can easily outweigh any advantages. A more favorable approach to on Industrial Application, vol. 1A-21, No. 2, MarchIApril
redundancy is the use of completely independent power/control systems 1985.
to operate the static converter. However, the increase in equipment size
and cost for redundant capability may not be justified. Stig A. Annestrand. Radio Interference from HVDC Con-
verter Stations. IEEE, PAS, 1971.
Redundant capability can be minimized by using “noninjurious”
temperature capability for these short-time emergency conditions or by Charlotte Hartelius. Frequency Converters for Wayne Junc-
applying any thermal margin originally specified for the equipment. In tion Substation. Internal engineering report, ASEA, 1986.
either case, the loss of equipment life would be insignificant.
Acknowledement
Conclusions
The authors wish to thank L. Nilsson (ABB Traction, Vasteras, Swe-
This paper has covered some of the basic principles of cycloconver- den), who provided technical contributions to this paper. The authors
ter theory, application in the traction power area, and system considera- also would like to acknowledge R. Fisher of SEPTA for his technical
tions. There is also a wealth of experience to guide an engineer in mak- direction and valuable comments regarding this paper.

137

Das könnte Ihnen auch gefallen