1 OVERVIEW
Motor protection and management shall be provided by a digital relay. Protective functions shall include:
• phase overload standard curves (51) • starts per hour and time between starts
• overload by custom programmable curve (51) • short circuit (50)
• I2t modeling (49) • ground fault (50G/50N 51G/51N)
• current unbalance / single phase detection (46) • mechanical jam / stall 2
Optional functions shall include:
• under / overvoltage (27/59) • power factor (55)
• phase reversal (47) • stator / bearing overtemperature with twelve (12) inde-
pendent RTD inputs (49/38)
• underpower (37)
• backspin detection
Management functions shall include:
• statistical data • a keypad with 40 character display
• pre-trip data (last 40 events) • flash memory
• ability to learn, display and integrate critical parame-
ters to maximize motor protection
The relay shall be capable of displaying important metering functions, including phase voltages, kilowatts, kvars, power fac-
tor, frequency and MWhr. In addition, undervoltage and low power factor alarm and trip levels shall be field programmable.
The communications interface shall include one front RS232 port and three independent rear RS485 ports with supporting
PC software, thus allowing easy setpoint programming, local retrieval of information and flexibility in communication with
SCADA and engineering workstations.
FEATURE OPTION
Modbus RTU Communications Protocol
Profibus DP rear communication port P
User Definable Baud Rate (1200-19200)
Flash Memory for easy firmware updates 2
Front RS232 communication port
Rear RS485 communication port
Rear fiber optic port F
RTD type is user definable R or RRTD
4 User Definable Analog Outputs M
(0 to 1 mA, 0 to 20 mA, 4 to 20 mA)
Windows based PC program for setting up
and monitoring
BACKUP
52 50 50G
OPTIONAL METERING (M)
BUS METERING
V, W, Var, VA, PF, Hz 55 4 ISOLATED
V V ANALOG
OUTPUTS
27 47 59
BREAKER
OR FUSED
CONTACTOR
74
METERING
3 50 51 37 66 46 A, Celsius
51G 50G
SPEED DEVICE
14 14
INPUTS 86
RTDs
RS232
DIFFERENTIAL
87 87 RS485
RELAY CONTACTS
RS485
RS485
BEARING
STATOR 49 38
AMBIENT
STATOR
BEARING
AMBIENT
840701B1.CDR
Figure 2–1: SINGLE LINE DIAGRAM
2.2.1 INPUTS
2.2.2 OUTPUTS
2.2.3 METERING
2.2.4 COMMUNICATIONS
2 Pickup Accuracy:
Dropout Level:
as per phase current inputs
96 to 98% of pickup
Time Delay:
Backup Delay:
0 to 255.00 s in steps of 0.01 s
0.01 to 255.00 s in steps of 0.01 s
Timing Accuracy: ±100 ms or ±2% of total trip time Timing Accuracy: +50 ms for delays <50 ms
±100 ms or ±0.5% of total trip time
THERMAL CAPACITY ALARM
Pickup Level: 1 to 100% TC in steps of 1 ACCELERATION TRIP
Pickup Accuracy: ±2% Pickup Level: motor start condition
Dropout Level: 96 to 98% of pickup Dropout Level: motor run, trip or stop condition
Timing Accuracy: ±100 ms Time Delay: 1.0 to 250.0 s in steps of 0.1
Timing Accuracy: ±100 ms or ±0.5% of total time
OVERLOAD ALARM
Pickup Level: 1.01 to 1.50 × FLA in steps of 0.01 38/49 RTD and RRTD PROTECTION
Pickup Accuracy: as per phase current inputs Pickup Level: 1 to 200°C or 34 to 392°F
Dropout Level: 96 to 98% of pickup Pickup Accuracy: ±2°C or ±4°F
Time Delay: 0.1 to 60.0 s in steps of 0.1 Dropout Level: 96 to 98% of pickup above 80°C
Timing Accuracy: ±100 ms or ±2% of total trip time Time Delay: <5 s
The 369 must be powered up at least once per year to prevent deterioration of electrolytic capacitors.
NOTE
2.2.9 APPROVALS / CERTIFICATION
DIELECTRIC STRENGTH
All high voltage inputs at 2 kV AC for 1 minute
CALIBRATION AND FUNCTIONALITY
100% hardware functionality tested
2
BURN IN 100% calibration of all metered quantities
8 hours @ 60°C sampling plan