Canteen QV internal inspection

Inspection Date : Jan 18 2018

Inspection Time : 10h30 to 11h30

Person of Attendance : 1. Mr. Tuan

2. Mr. Van Anh

3. Mr. Quang
Canteen QV renovation work internal inspection

Photo No. : 1 Before After

Location : Canteen

Contents :

1. Cleaning all lighting before


inspection with OVC
2. Illumination Tesr report
Finish before inspection with OVC

Photo No. : 2 Before After

Location : Canteen

Contents :
1. Update new layout of canteen in
the switch map and install it before
inspection with OVC
2. Take out nilon sheet and cleaning
before inspection with OVC

Photo No. : 3 Before After

Location : L-CAN-1

Contents :
Cable terminal have no good
conection, pls repair it.
When repair pls take care and
make sure already no power.

Photo No. : 4 Before After

Location : L-CAN-1

Contents :
We should be confirm by marking
after tightening.
Canteen QV renovation work internal inspection

Photo No. : 5 Before After

Location : L-CAN-1

Contents :
(only consider for next time design)
Pls check current of Lighting circuit
I think no need use 4sqmm size
only 2.5sqmm is ok, you can reduce
cost.

Photo No. : 6 Before After

Location : L-CAN-1

Contents :
Should be use grounding terminal cap
and add cable tag also.

Photo No. : 7 Before After

Location : M-CAN-2-2

Contents :
Additional cable tag for main
grounding cable

Photo No. : 8 Before After

Location : M-CAN-2-2

Contents :
Additional your confirmed color of
re-tightening marking
Canteen QV renovation work internal inspection

Photo No. : 9 Before After

Location : M-CAN-5-1

Contents :
make Current, Leak Current Testing
report of Mechanical Equipment
before inspection with OVC

Photo No. : 10 Before After

Location : M-CAN-2-2

Contents :
1. Not yet install grounding cable for
cable rack.
2. Grounding cable conection to panel
you install inside cable rack, this point
very far with Panel, pls next time
consider connection point easy check
easy for explain

Photo No. : 11 Before After

Location : M-CAN-5-1

Contents :
1.add grounding cable tag

Photo No. : 12 Before After

Location : M-CAN-5-1

Contents :
Have some point dirty in panel
pls cleaning it.