Sie sind auf Seite 1von 1

Escala:

Solar power Solar Domestic hot


pannels
66 kWth water
94.5 kWth
SANKEY DIAGRAM NEW SUPPLY SYSTEM Appendix A
Water heaters PLAN A.3
Heat losses
0.3 kWth
Electricity
28.8 kWe Excess heat
12.04 MWth
Heat losses
1.32 MWth Cooling energy
5.4 MWch
Air cooler Natural gas
5.28 MWth 2.6 MWth Natural gas
Co
7 MWth
nd Heat losses
bo ens 0.36 MWth
ile atio
rs n 2.8 MW Heating
Refrigeration
th
energy Electricity
Cooling
5.28 MWth 4.1 MWth 36 kWe
towers
Absorption
Heat losses Flue gas
HR boiler + burner chillers
Diesel oil Engines Flue gas 6.64 MWth
1.18 MWth 8 MWth
23 MWth 8 MWth
Electricity
90 kWe

Heat losses
1.36 MWth

Electricity Electricity
8.4 MWe 2.6 MWe
Energy
generation
consumption
Airport's 2.7 MWe
consumption Compression Excess heat
4.3 MWe chillers 9.6 MWth

Other, reserve
capacity
1.4 MWe

Cooling energy
7 MWch

Das könnte Ihnen auch gefallen