Technical Datasheet
True RMS Measurement Energy as per IEC 62053 Onsite Programmable Low Back Depth
Phase Reversal Indication LCD Display with Back-lit RS485, Limit or Pulse Output
Applications:
Energy billing
Electrical load monitoring
Sub-metering
Genset, Test Benches and Laboratories
Product Features:
True RMS measurement: User Configurable Features:
Measures distorted waveform up to 15th Harmonic. User can select any five or ten measurement
screens which will be shown on display. Also backlit
Energy as per IEC 62053: can be programmed to switched on or off.
Independent Import and Export Energy counter.
Active energy (kWh), Reactive energy (kVArh), LCD Display with Backlit:
Apparent energy (kVAh) measurement. LCD shows 3 Parameters at a glance.
Accuracy as per IEC 62053-21,IEC62053-23.
Parameter Screen recall:
THD Measurement: In case of power failure, the instrument memorizes
The instrument measures THD per phase voltage & the last displayed screen.
current up to 15th Harmonic.
Run Hour, ON Hour, Number of Interruptions:
Onsite programmable: Run Hour records the number of hours load is
Onsite Programmable System Configuration 3PH4W connected. ON Hour is the period for which the
/ 3PH3W / 1PH2W. auxiliary supply is ON. Number of Interruptions
Onsite Programmable CT ratios and PT ratios indicates the number of times the Auxiliary Supply
was interrupted.
Direct remote access(Optional):
Remote configuration of the Instrument via Onsite selection of Auto scroll / Fixed Screen
MODBUS. User can set the display in auto scrolling mode or
Remote access of measured parameters. fixed screen mode locally via front panel keys by
Programmable baud rates up to 38.4kbps. entering into Programming mode or remotely via
MODBUS (Rs485).
Limit (Alarm) or Pulse Relay Output(Optional):
Potential free, very fast acting relay contact. Enclosure Protection for dust and water:
Configurable as pulse output which can be used to Conforms to IP 50 (front face) as per IEC60529
drive an external counter for energy measurement.
Configurable as limit (alarm) switch. Compliance to International Safety standards
Compliance to International Safety standard
Low back depth: IEC 61010-1- 2010
The instrument has very low back depth (behind the EMC Compatibility
panel) of less than 35 mm. Compliance to International standard IEC 61326
Technical Specifications:
Dimensions Details: Input Voltage:
Nominal input voltage (AC RMS) Phase –Neutral Line-Line
96 mm 63.5 VL-N 110 VL-L
133 VL-N 230 VL-L
239.6 VL-N 415 VL-L
System PT primary values 100VLL to 1200kVLL programmable on site.
Max continuous input voltage 120% of nominal value
Input Current:
96mm
Technical Specifications:
Installation:
Overload Withstand:
Voltage 2 x rated value for 1 second, repeated 10 times
at 10 second intervals
Current 20x Imax for 0.5sec
Display update rate:
Easy Clip - in
mounting
Response time to step input 1 sec approx.
Applicable Standards:
EMC IEC 61326 - 1 : 2005
Immunity IEC 61000-4-3. 10V/m min – Level 3 industrial
Swivel screw
Low level
Safety IEC 61010-1-2010 , Permanently connected use
IP for water & dust IEC60529
Pollution degree: 2
Installation category: III
Isolation:
Protective Class 2
High Voltage Test
Input+Aux Vs Surface 4kV RMS, 50Hz,1min
Input Vs Remaining Circuit 2kV RMS,50Hz,1min
Environmental
Operating temperature -10 to +55°C
Optional Modbus/Pulse output pluggable module.
Storage temperature -20 to +65°C
Relative humidity 0... 90%RH (non condensing)
Electrical Connection: Warm up time Minimum 3 minute
Shock (As per IEC60068-2-27) Half sine wave,Peak acceleration
2 5 8 11 1 3 4 6 7 9 13 14
30gn (300 m/s^2),duration 18ms.
Vibration 10... 150...10 Hz, 0.15mm amplitude
L N Number of Sweep cycles 10 per axis
S1
L1
P1 S1
AUX SUPPLY
L Enclosure IP 50 (front face only)
L2 O
L3
P1 S1
P1
A Interfaces
N D
Impulse Led For Energy Calibration at front
3 Phase 4 wire Unbalanced load
Relay(Optional) 240 VAC ,5 A(Configured as limit or pulse output)
2 5 8 1 3 7 9 13 14 Modbus (Optional) RS485,max.1200m
Baud rate : 4.8k,9.6k,19.2k,38.4k bps
NOTE: Variation due to influence Quantity is 100% of class index for all other
L N
parameters except Energy.
S1
AUX SUPPLY
L1 L
L2
P1
S1
O PT Secondary Ranges for Various Input Voltage:
L3 A
P1 D
2 11 1 3 13 14 110V L-L (63.5V L-N) 100V – 125V L-L (57V – 72V L-N)
230V L-L (133V L-N) 126V – 250V L-L (73V – 144V L-N)
415V L-L (239.6V L-N) 251V – 480V L-L (145V – 277V L-N)
S1 L N
P1 AUX SUPPLY L
Input connections are made directly to screw-type terminals with indirect wire pressure.
L1 Numbering is clearly marked on the connector . Choice of cable should meet local regulations.
O
A Terminal for both Current and Voltage inputs will accept up to 4mm2 (12AWG) solid or 2.5 mm2
N D
1 Phase 2 Wire standard cable.
Note: It is recommended to use wire with lug for connection with meter.
!) )2
1. WH00-4385URP000000
RISH EM 1340, 3PH 3W/4W, 415VL-L, 5A / 1A, With RS 485, Pulse output
2. WH00-3335URP000000 %
RISH EM 1330, 1 Phase, 230VL-N, 5A / 1A, With RS 485, Pulse output