CLIENT PROJECT: 114070

SPEC Nº:

DATE: 10/02/2015
DONE: ABC
Sharm el-Sheikh (EGYPT) SHARM EL-SHEIKH POWER PLANT CHECKED: APR
DATA SHEET APPROVED: JQV
DATA SHEET Nº: 114070-30-MEC-HD-0028-00
TANK CATHODIC PROTECTION SYSTEM
SHEET: 3 of 3
GENERAL
Equipment: Well water break tank
P&ID: 114070-30-PRC-DI-0005
Ambient temperature: +0 / +55 ºC
Ambient relative humidity: 60 %
Tank foundation type: According attached tank CIVIL WORKS foundation drawing
Tank material: Carbon steel S-275-JR
Tank diameter: 8000 mm
Tank cylindrical height: 6000 mm
* API-651: cathodic protection of aboveground storage tanks.
* NACE-RP-0572: design, installation, operation and maintenance of impressed current deep groundbeds.
Design codes * NACE-RP-0388: impressed current cathodic protection of internal submerged surfaces of steel water storage tanks.
* NACE-RP-0193: external cathodic protection of on-grade metallic storage tank bottoms.
* NACE-RP-0196: galvanic anode cathodic protection of internal submerged surfaces of steel water storage tanks.
Sea water
pH: 7,1
TDS Total Disolved Solids: - ppm
Fluid (Note 3) Hardness (CaCO3): - ppm
Silica (SiO2): - ppm
Chlorides: - ppm
Conductivity: - ђS/cm
1DWLYHVRLOFXVKLRQ
&OHDQVDQGFXVKLRQ QRWRLOHG
&UXVKHGOLPHVWRQH DFF$3,FKDSWHU
Soil (Note 3)
pH: -
Chlorides: - ppm
Resistivity (Note 5): - ohm x m
INTERNAL CATHODIC PROTECTION BY MEANS OF SACRIFICIAL ANODES
Required: <HV 1R
Anodes type: =Q 0J
Anodes number: By Supplier
Anodes location: By Supplier
Anodes clamps to tank type: :HOGHG 7KUHDGHG
Anodes clamps to tank material: By Supplier
Reference electrode: &X62&X $J$J&O ZKHQVDOLQHHQYLURQPHQWV
Test electrode: Tank same material
AISI-316 (IP-65). Free-standing freme, including anchor bolts.
Panels/junction boxes ventilation (by Supplier, acc. Local ambient conditions): $LUFRROHG +9$&V\VWHP
Standard test sockets.
Local electrical/control panel and Output voltage (local adjustment voltage setting value).
junction boxes: Local & remote monitoring of (Note 4):
Reference electrode potentials.
Feed/electrical battery limit at main panel: 400 V - 50 Hz - 3 Ph (no neutral). Cables entry by means of armoured glands. All cabling in between main panel and
electrodes (including intermediate junction boxes) shall be included within SoS. Earthing lugs. Supplier to state overall power consumption.
Portable multifunction multimeter <HV 1R
INTERNAL CATHODIC PROTECTION BY MEANS OF IMPRESSED CURRENT
Required: <HV 1R
Anodes type: =Q 0J
Anodes number: By Supplier
Anodes location: By Supplier
Anodes clamps to tank type: :HOGHG 7KUHDGHG
Anodes clamps to tank material: By Supplier
Reference electrode: &X62&X $J$J&O ZKHQVDOLQHHQYLURQPHQWV
Test electrode: Tank same material
AISI-316 (IP-65). Free-standing freme, including anchor bolts.
Panels/junction boxes ventilation (by Supplier, acc. Local ambient conditions): $LUFRROHG +9$&V\VWHP
Including transformer-rectifier.
Standard test sockets.
Equipment nominal power shall be 40% higher (oversized) than the one calculated.
Rectifier shall always work at 70% of its capacity.
Windings shall be made of Cu, insulation class "H".
Local electrical/control panel and Rectifier allowable ripple factor shall be lower than 5% RMS at mid load.
junction boxes: Circuit breaker.
Voltimeter/data logger.
Electronic timer and ON/OFF switch.
Output voltage (local adjustment voltage setting value).
Local & remote monitoring of (Note 4): Current (local adjustmen min. current value).
Reference electrode potentials.
Feed/electrical battery limit at main panel: 400 V - 50 Hz - 3 Ph (no neutral). Cables entry by means of armoured glands. All cabling in between main panel and
electrodes (including intermediate junction boxes) shall be included within SoS. Earthing lugs. Supplier to state overall power consumption.
Portable multifunction multimeter <HV 1R
EXTERNAL CATHODIC PROTECTION BY MEANS OF IMPRESSED CURRENT
Required: <HV 1R
Anodes type: 7DQNVXUURXQGLQJEXULHGDFWLYDWHGWLWDQLXP 0020L[HG0HWDO2[LGHV 7DQNXQGHUQHDWKEXULHGWLWDQLXPVWULSV
Backfill: 1DWXUDOJUDSKLWHJUDQXOHV &DOFLQHGSHWFRNH SHWUROHXPFRNH
Anodes number: By Supplier
External current shield (Note 6): By Supplier (e.g. polyethylene film)
Reference electrode: &X62&X $J$J&O ZKHQVDOLQHHQYLURQPHQWV
Test electrode: Tank same material
AISI-316 (IP-65). Free-standing freme, including anchor bolts.
Panels/junction boxes ventilation (by Supplier, acc. Local ambient conditions): $LUFRROHG +9$&V\VWHP
Including transformer-rectifier.
Standard test sockets.
Equipment nominal power shall be 40% higher (oversized) than the one calculated.
Rectifier shall always work at 70% of its capacity.
Windings shall be made of Cu, insulation class "H".
Local electrical/control panel and Rectifier allowable ripple factor shall be lower than 5% RMS at mid load.
junction boxes: Circuit breaker.
Voltimeter/data logger.
Electronic timer and ON/OFF switch.
Output voltage (local adjustment voltage setting value).
Local & remote monitoring of (Note 4): Current (local adjustmen min. current value).
Reference electrode potentials.
Feed/electrical battery limit at main panel: 400 V - 50 Hz - 3 Ph (no neutral). Cables entry by means of armoured glands. All cabling in between main panel and
electrodes (including intermediate junction boxes) shall be included within SoS. Earthing lugs. Supplier to state overall power consumption.
Portable multifunction multimeter <HV 1R
ACCESSORIES
All accessories/tools/componentes necessary for erection and commissioning shall be included within SoS.
NOTES
1.- Supplier to fill-in blank spaces/cells.
2.- Min. quality required. Vendor may propose different materials (these shall be approved by Buyer).
3.- Supplier to carry out his own on-site study/assessment.
4.- Supplier to take into account signal shall be sent to power plant DCS Distributed Control System.
5.- According site geoelectrical resistivity study.
6.- Supplier to carry out eventual current flow perturbations study (e.g. surrounding errant currents).
7.- Supplier shall issue complete commissioning procedures and O&M Operation & Maintenance manuals.
8.- Supplier shall include all special tools required for maintenance purposes (e.g. plates removal and cleaning).
9.- Equipments shall include a nameplate (AISI-316; 3 mm thickness).
10.- All equipment components/items submitted to pressure shall be certified according EN-10204-3.1 (rest of the components shall be certified according EN-10204-2.2).
11.- Supplier shall be certified according quality management systems ISO-9001.
12.- Supplier shall quote as an OPTIONAL a complete/detailed recommended spare parts list.
13.- Bidder shall include TSK’s “EXCEPTIONS & DEVIATIONS FORM” properly filled in; no exception/deviation (to applicable documentation) shall be taken into account if it is not clearly stated within this
excel form.
14.- Equipment shall be designed for a lifetime of 25 years. SELLER shall warrant that the supply is free from any defect of manufacture, design, materials and workmanship for a period of 24 months
from plant commercial operation starting date. Therefore it undertakes to promptly replace or repair wherever necessary (at site or in workshop), and without any cost for BUYER, any parts that do not
comply with the required characteristics and/or which for any defect is detected during the warranty period.
15.- Wind conditions: speed 50 m/s (ASCE 7-05 / IBC 09).
16.- Seismic conditions (ASCE 7/05):
Basic acceleration: 0,25g.
Max. acceleration: 0,6g.