Beruflich Dokumente
Kultur Dokumente
Powerhouse 1 to MTCP – 1
10.12
%Voltage Drop = 460𝑉 𝑥 100% = 2.20%
Powerhouse 1 to MTCP – 2
13.11𝑉
%Voltage Drop = 𝑥 100% = 2.85%
460𝑉
Powerhouse 1 to MTCP – 3
13.99𝑉
%Voltage Drop = 𝑥 100% = 3.04%
460𝑉
Powerhouse 1 to MTCP – 4
13.11𝑉
%Voltage Drop = 𝑥 100% = 2.85%
460𝑉
Powerhouse 1 to MTCP – 5
15.21𝑉
%Voltage Drop = 𝑥 100% = 3.31%
460𝑉
Powerhouse 1 to MTCP – 6
17.44𝑉
%Voltage Drop = 𝑥 100% = 3.79%
460𝑉
Powerhouse 1 to FP- 1
10.36𝑉
%Voltage Drop = 𝑥 100% = 2.25%
460𝑉
Powerhouse 1 to FP- 2
13.43𝑉
%Voltage Drop = 𝑥 100% = 2.92%
460𝑉
Powerhouse 1 to FP- 3
14.33𝑉
%Voltage Drop = 𝑥 100% = 3.12%
460𝑉
Powerhouse 1 to FP- 4
13.43𝑉
%Voltage Drop = 𝑥 100% = 2.92%
460𝑉
Powerhouse 1 to FP- 5
15.57𝑉
%Voltage Drop = 𝑥 100% = 3.39%
460𝑉
Powerhouse 1 to FP- 6
17.86𝑉
%Voltage Drop = 𝑥 100% = 3.88%
460𝑉
Powerhouse 1 to DP - 1
√3 𝑥 0.2 𝑥 90 𝑥 36.71
Voltage Drop3Φ = = 3.75𝑉
305𝑚
3.75𝑉
%Voltage Drop = 230𝑉 𝑥 100% = 1.63%
Powerhouse 1 to AP - 1
10.40𝑉
%Voltage Drop = 𝑥 100% = 4.52%
230𝑉
Powerhouse 1 to Guardhouse
6.40𝑉
%Voltage Drop = 230𝑉 𝑥 100% = 2.78%
Powerhouse 2 to MTCP - 7
9.92𝑉
%Voltage Drop = 460𝑉 𝑥 100% = 2.16%
Powerhouse 2 to MTCP - 8
12.92𝑉
%Voltage Drop = 𝑥 100% = 2.81%
460𝑉
Powerhouse 2 to MTCP - 9
15.91𝑉
%Voltage Drop = 𝑥 100% = 3.46%
460𝑉
Powerhouse 2 to MTCP - 10
9.92𝑉
%Voltage Drop = 460𝑉 𝑥 100% = 2.16%
Powerhouse 2 to MTCP - 11
12.92𝑉
%Voltage Drop = 𝑥 100% = 2.81%
460𝑉
Powerhouse 2 to MTCP - 12
15.91𝑉
%Voltage Drop = 𝑥 100% = 3.46%
460𝑉
Powerhouse 2 to FP- 7
10.16𝑉
%Voltage Drop = 𝑥 100% = 3.22%
460𝑉
Powerhouse 2 to FP- 8
13.23𝑉
%Voltage Drop = 𝑥 100% = 2.88%
460𝑉
Powerhouse 2 to FP- 9
16.29𝑉
%Voltage Drop = 𝑥 100% = 3.54%
460𝑉
Powerhouse 2 to FP- 10
10.16𝑉
%Voltage Drop = 𝑥 100% = 3.22%
460𝑉
Powerhouse 2 to FP- 11
13.23𝑉
%Voltage Drop = 𝑥 100% = 2.88%
460𝑉
Powerhouse 2 to FP- 12
16.29𝑉
%Voltage Drop = 𝑥 100% = 3.54%
460𝑉
Powerhouse 2 to DP - 2
√3 𝑥 0.2 𝑥 90 𝑥 36.41
Voltage Drop3Φ = = 3.72𝑉
305𝑚
3.72𝑉
%Voltage Drop = 230𝑉 𝑥 100% = 1.62%
Powerhouse 2 to AP - 2
11.23𝑉
%Voltage Drop = 𝑥 100% = 4.88%
230𝑉
Powerhouse 2 to GP - 2
6.91𝑉
%Voltage Drop = 230𝑉 𝑥 100% = 3.01%
Powerhouse 3 to MTCP - 13
9.92𝑉
%Voltage Drop = 460𝑉 𝑥 100% = 2.16%
Powerhouse 3 to MTCP - 14
12.92𝑉
%Voltage Drop = 𝑥 100% = 2.81%
460𝑉
Powerhouse 3 to MTCP - 15
15.91𝑉
%Voltage Drop = 𝑥 100% = 3.46%
460𝑉
Powerhouse 3 to MTCP - 16
9.92𝑉
%Voltage Drop = 460𝑉 𝑥 100% = 2.16%
Powerhouse 3 to MTCP - 17
12.92𝑉
%Voltage Drop = 𝑥 100% = 2.81%
460𝑉
Powerhouse 3 to MTCP - 18
15.91𝑉
%Voltage Drop = 𝑥 100% = 3.46%
460𝑉
Powerhouse 3 to FP- 13
10.16𝑉
%Voltage Drop = 𝑥 100% = 3.22%
460𝑉
Powerhouse 3 to FP- 14
13.23𝑉
%Voltage Drop = 𝑥 100% = 2.88%
460𝑉
Powerhouse 3 to FP- 15
16.29𝑉
%Voltage Drop = 𝑥 100% = 3.54%
460𝑉
Powerhouse 3 to FP- 16
10.16𝑉
%Voltage Drop = 𝑥 100% = 3.22%
460𝑉
Powerhouse 3 to FP- 17
13.23𝑉
%Voltage Drop = 𝑥 100% = 2.88%
460𝑉
Powerhouse 3 to FP- 18
16.29𝑉
%Voltage Drop = 𝑥 100% = 3.54%
460𝑉
Powerhouse 4 to DP - 3
√3 𝑥 0.2 𝑥 90 𝑥 36.41
Voltage Drop3Φ = = 3.72𝑉
305𝑚
3.72𝑉
%Voltage Drop = 230𝑉 𝑥 100% = 1.62%
Powerhouse 4 to AP - 3
11.23𝑉
%Voltage Drop = 𝑥 100% = 4.88%
230𝑉
Powerhouse 4 to GP - 3
6.91𝑉
%Voltage Drop = 230𝑉 𝑥 100% = 3.01%
Powerhouse 4 to MTCP - 19
9.92𝑉
%Voltage Drop = 460𝑉 𝑥 100% = 2.16%
Powerhouse 4 to MTCP - 20
12.92𝑉
%Voltage Drop = 𝑥 100% = 2.81%
460𝑉
Powerhouse 4 to MTCP - 21
15.91𝑉
%Voltage Drop = 𝑥 100% = 3.46%
460𝑉
Powerhouse 4 to MTCP - 22
9.92𝑉
%Voltage Drop = 460𝑉 𝑥 100% = 2.16%
Powerhouse 4 to MTCP - 23
12.92𝑉
%Voltage Drop = 𝑥 100% = 2.81%
460𝑉
Powerhouse 4 to MTCP - 24
15.91𝑉
%Voltage Drop = 𝑥 100% = 3.46%
460𝑉
Powerhouse 4 to FP- 19
10.16𝑉
%Voltage Drop = 𝑥 100% = 3.22%
460𝑉
Powerhouse 4 to FP- 20
13.23𝑉
%Voltage Drop = 𝑥 100% = 2.88%
460𝑉
Powerhouse 4 to FP- 21
16.29𝑉
%Voltage Drop = 𝑥 100% = 3.54%
460𝑉
Powerhouse 4 to FP- 22
10.16𝑉
%Voltage Drop = 𝑥 100% = 3.22%
460𝑉
Powerhouse 4 to FP- 23
13.23𝑉
%Voltage Drop = 𝑥 100% = 2.88%
460𝑉
Powerhouse 4 to FP- 24
16.29𝑉
%Voltage Drop = 𝑥 100% = 3.54%
460𝑉
Powerhouse 4 to DP - 4
√3 𝑥 0.2 𝑥 90 𝑥 36.41
Voltage Drop3Φ = = 3.72𝑉
305𝑚
3.72𝑉
%Voltage Drop = 230𝑉 𝑥 100% = 1.62%
Powerhouse 4 to AP - 4
11.23𝑉
%Voltage Drop = 𝑥 100% = 4.88%
230𝑉
Powerhouse 4 to GP - 4
6.91𝑉
%Voltage Drop = 230𝑉 𝑥 100% = 3.01%
Powerhouse 4 to MAP - 1
√3 𝑥 0.094 𝑥 50.87 𝑥 131.65
Voltage Drop3Φ = = 11.27𝑉
305𝑚
11.27𝑉
%Voltage Drop = 𝑥 100% = 4.90%
230𝑉
Powerhouse 4 to TP - 1
11.37𝑉
%Voltage Drop = 𝑥 100% = 4.94%
230𝑉
Fermentation Powerhouse 1 to FP - 1
7.88𝑉
%Voltage Drop = 230𝑉 𝑥 100% = 1.71%
Fermentation Powerhouse 1 to FP - 2
6.34𝑉
%Voltage Drop = 230𝑉 𝑥 100% = 1.38%
Fermentation Powerhouse 1 to FP - 4
8.32𝑉
%Voltage Drop = 230𝑉 𝑥 100% = 1.81%
Fermentation Powerhouse 2 to FP - 1
7.88𝑉
%Voltage Drop = 230𝑉 𝑥 100% = 1.71%
Fermentation Powerhouse 2 to FP - 2
6.34𝑉
%Voltage Drop = 230𝑉 𝑥 100% = 1.38%
Fermentation Powerhouse 2 to FP - 4
8.32𝑉
%Voltage Drop = 230𝑉 𝑥 100% = 1.81%
0.551
%Voltage Drop = 13200𝑉 𝑥 100% = 0.0038%
1.12
%Voltage Drop = 13200𝑉 𝑥 100% = 0.0084%
0.73𝑉
%Voltage Drop = 13200𝑉 𝑥 100% = 0.0055%
Sub Main 2 to Phase 1
1.47𝑉
%Voltage Drop = 13200𝑉 𝑥 100% = 0.0112%
1.32𝑉
%Voltage Drop = 13200𝑉 𝑥 100% = 0.0100%
0.74𝑉
%Voltage Drop = 13200𝑉 𝑥 100% = 0.0056%