iQpump1000 AC Drive Page 1 of 4

Simplex Quick Start Procedure


Step Step Step Step
iQpump Model Connect Motor and Real-time Selecting Start/Stop and Speed Method
The following
1 Identification and Mounting 2 Line Power 3 Clock Setup 4
procedure is a To make sure you received the correct model, it is essential to Fig.1 & 2 below show the electrical connections for the input This step shows how to setup the This step shows how to connect control wiring and feedback signal to the iQpump. Before
verify the iQpump nameplate with your order and make sure iQpump real-time clock for first
supplement to the iQpump has the correct rating so it can be used with your
power and motor terminals for various iQpump models. Select
use.
making any control connections MAKE SURE POWER TO THE iQpump IS TURNED OFF!
the proper diagram for the model you are installing (see Step Next remove the terminal cover to gain access to the control terminals. (Step 1.)
other motor. Please check the nameplate information as shown in
1). WITH POWER OFF make the appropriate connections.
the example below. Note: If clock is not set the drive
documentation Make sure to follow good wiring practices and all applicable can still be programmed and SELECT START / STOP CONTROL METHOD b1-02
supplied with this Drive Model
Drive Spec Number codes. Ensure that the equipment is grounded properly as operated, but ALM light will flash
Number
CIMR-PW2A0021FAA shown in fig. 1 every 30s and showing Clock Not
equipment and Input Power CC : CIMR-PW2A0021FAA Set message. The iQpump is DEFAULT SETUP TO START/STOP FROM THE KEYPAD (digital operator).
Rating Normal
will guide the user Output Power
Duty Amps
! DANGER; LETHAL VOLTAGES ARE PRESENT- Before
If this is the preferred start/stop method then continue to the feedback signal connection
in properly wiring Rating Software
applying power to the iQpump, ensure that the terminal cover Power up the drive and set the section. Please refer to the wiring diagram below to start/stop the iQpump using an external
8000 Version
real-time Clock. The real-time switch or contact.
Weight 6W3050 - 2 - 100 is fastened and all wiring connections are secure. After the
the iQpump and J0073D207410100 power has been turned OFF, wait at least five minutes until
Clock setup screen will appear at
Serial
first power up. User Terminals User Terminals
motor. It will also Number
the charge indicator extinguishes completely before touching S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
show the user UL File
Number
any wiring, circuit boards or components. Press to set the clock.
how to configure WARNING DO NOT CONNECT ANY OF THE Run
FOLLOWING TERMINALS TO EARTH GROUND Note: After the real-time clock is Start Normally
(FWD) Link Link
the iQpump for a B1 B2 - +1 +2 +3 set the real-time clock setup Switch Open
· Check that the available power will meet the input power screen will not show again unless
simplex pump requirements. parameter o4-17 is set to “Set”.
application. · Ensure that the output power from the iQpump is Wiring Diagram: 2-Wire Control Stop Normally
compatible with the motor requirements. Switch Closed
Use for maintained contacts
· In the case of systems with more than one iQpump, follow Wiring Diagram: 3-Wire Control
DANGER! the above procedure for each iQpump and motor. Note: 3rd row of terminal board is shown here.
DC Bus terminals Use for momentary contacts
Improper wiring location varies by To use 3-Wire Control first Initialize the
Mounting the iQpump model.
can and will cause iQpump using parameter A1-03 = 3330
The mounting of the iQpump is extremely important (Refer to the Quick Start Guide
bodily harm as regarding environment and accessibility. Depending on your (T/L3)
(W/T3)
Real-time Clock Setup Screen TOEP YAIP1W 01)
(U/T1)
well as damage to system, there are various models available and the mounting (R/L1) (S/L2)
(V/T2)

FEEDBACK SIGNAL WIRING (TRANSDUCER)


dimensions (footprint) may be different. Because the
the equipment. mounting procedure is fairly extensive, it is beyond the scope
of this document; the user is referred to the iQpump Quick Note: 2nd row of terminal
board is shown here. Factory Installed (Factory Default)
Start Guide (Document No. TOEP YAIP1W 01) received with
When installing the iQpump, Section 2.2 Mechanical Installation. Match the To change 2-Wire, 4-20mA Transducer
Connect to chassis
the system be model that you received and follow the procedure described
Input
ground
direction of
motor rotation
swap any two
E(G) +V AC A1 A2 A3 FM AM AC RP AC 24V
in the manual to ensure a safe and functional installation. In
sure to follow cases where the system has more than one iQpump, refer to
Protection
(Fuse or Circuit
Breaker)
of the three
motor leads. SN A1 A3
good wiring the proper clearances required for adequate ventilation. V
Please pay particular attention to:
practices and all L1 L2 L3 Cable
Shield
Install link (AC-SN) when I
· The clearances to be maintained around the enclosure Connect
Black: Output
applicable codes. for adequate ventilation.
frame to
ground
4 – 20mA (2)
using transducer. A2
Use L1, L2 for Use L1, L2, L3 for 3Ø Induction Brown or Red: +Power (1)
Ensure that the · The environmental specifications such as avoiding 1Ø Input Power * 3Ø Input Power motor
mounting of the excessive dampness, extreme temperatures, chemical Fig. 1 Input Power and Output Motor Electrical Connections for
Models: 2_0004 - 2_0056, 4_0002 - 4_0044 and 5_0003 - 50011 Jumper located
exposure, corrosive areas, etc. to avoid damage to the DIN Cable
various equipment and to maintain safety. NOT USED Type Type inside the drive on
the terminal board
components are
Removing and Attaching the Terminal Cover
secure and that Improper removal of the iQpump terminal cover as well as
BUS TERMINALS: For use with 2-Wire, 4 – 20mA Transducer (Factory Default)
DO NOT CONNECT TO GROUND
the environment, front cover can cause extensive damage to the iQpump. To
avoid damage to these items, please pay particular attention Note: 2nd row of terminal
such as extreme to the iQpump Quick Start Guide, Document No. TOEP board is shown here.
dampness, poor YAIP1W 01, Section 3.5, Removing and Attaching the Use to move cursor to 3-Wire, 0-10V Transducer
Terminal Cover. E(G) +V AC A1 A2 A3 FM AM AC RP AC 24V Set Jumper to use 0 – 10V
ventilation etc. will Transducer
The left and to move
not cause system
degradation. cursor to the right
(U/T1) (W/T3)
(R/L1) (S/L2)
(T/L3) (V/T2) use to adjust. A1 A3
To change direction of motor
V
Please read this rotation swap any two of the
three motor leads.
When date and time are set
Connect to
cheat sheet and Input chassis
ground Blue or Black Common Signal (2)
I
Protection
press to save. A2
other NEMA 1
(Fuse or Circuit
Breaker)
Black or White Output 0 – 10V (3)
documentation Brown or Red: +Power (1)
provided with the L1 L2 L3 Jumper located
iQpump Connect inside the drive on
frame to For use with 3-Wire, 0 – 10V Transducer the terminal board
ground
thoroughly before Use L1, L2 for Use L1, L2, L3 for 3Ø Induction
1Ø Input Power * 3Ø Input Power motor ! Important Note: Signal colors and numbering may vary depending on
attempting any Fig. 2 Input Power and Output Motor Electrical Connections for feedback device used, please consult feedback device manual.
installation. Models: 2_0110 & Larger and 4_0058 & Larger Example: Jun 12th 2012, 7:35am
* Make sure the iQpump has been properly sized for single phase input
power. For best performance, the drive input supply voltage must be Note: Do NOT adjust sec per NOTE: It is beyond the scope of this document to program the iQpump drive for network communication control.
Open Chassis equal to or greater than the motor rated voltage. Please refer to the refer to the iQpump Quick Start Guide, (Document No. TOEP YAIP1W 01) for this selection.
month.

Yaskawa America, Inc., 2121 Norman Drive South, Waukegan, IL 60085, (800) YASKAWA (927-5292) Fax (847) 887-7310, DrivesHelpDesk@yaskawa.com, www.yaskawa.com, Document Number: TM.TM.iQp1000.01 03/25/2013 © Yaskawa America, Inc.
iQpump1000 Page 2 of 4
Simplex Quick Start Procedure
Step Step Step
Changing Parameters and
5 Monitoring the iQpump 6 Application Setup
7 iQpump Quick Setup Parameter Overview (Simplex)

This step shows how to access and modify an iQpump parameter This step shows how to configure the iQpump for a dedicated pump
as well as how to monitor iQpump signals such as output application. Parameter Value Description Reference Comments
frequency and motor current.
Make sure all protective covers have been re-attached and power is
Make sure all protective covers have been re-attached and power turned on. DO NOT RUN THE MOTOR. Dependent on
Application
A1-06 Initialization Displays selected applications, see Step 6. Read-only cannot be modified
is turned on. DO NOT RUN THE MOTOR. Selected
Mode
Available iQpump Application Macro’s:
Access Parameter Menu and Change Parameter Value Drive Size Motor Rated Cur- For submersible motors use service
E2-01 Set to the motor nameplate full load amps.
Dependent rent factor amps (SFA).
· 6008 Constant Pressure Mode (PSI) Default
· 6009 Pump Down Level Mode (Ft)
Press two times until the digital operator shows the parameter menu. Confirm number of poles
· 6010 Geothermal Mode The factory default is setup for Number of motor poles is used to show the correct
· 6011 VTC Pressure Control Mode constant pressure PSI, only change if 2 Pole Motor = 3600 RPM
· 7770 General Purpose Mode application different. Number of Motor motor RPM on the display
E2-04 2 4 Pole Motor = 1800 RPM
Poles Enter ’4’ for an 1800 RPM motor and ‘2’ for a 3600
6 Pole Motor = 1200 RPM
Select Application RPM motor.
8 Pole Motor = 900 RPM

System Scaling: Enter feedback device maximum:


2X Select Digit Press two times until the digital operator shows the parameter menu. Confirm feedback device scaling.
Feedback Device
P1-03 145 Example: Enter 200 for pressure transducer with a
Scaling (See Illustration 1)
maximum of 200 PSI at 20mA.

Q1-01 0 Setpoint 1 Set System Setpoint Set to system pressure


2X When the iQpump is turned On and the feedback

2X 2X Select Digit signal level (transducer) falls below this level, the It is mandatory to program the Start / Draw
pump system will start after the time specified in P1- Down Level in order to use the sleep func-
Inc./Dec. Selection Go to Next Digit Inc./Dec. Selection 05 (default 1 sec). tion.
Programming the Start Level as an Absolute (See Illustration 2 and 3)
Value. Start / Draw Down Level has to programmed
to a positive value in order for the Start / Draw Down
Level to be an absolute value. Example: Start /
Inc./Dec. Selection Switch to Edit Mode Select Application Draw Down Level P1-04 set to 50 PSI and delay
time P1-05 set to 5 sec. Pump system will start
Press to select.
when the pressure drops below 50 PSI for 5 sec.
Switch to Edit Mode Modify Value Save New Value
Start / Drawn
P1-04 0.0 PSI
Enter Application Parameters Down Level
Programming the Start Level as a Delta Level
Hold button for 3 sec. to go back to the main menu.
from the System Setpoint
Hold button for 3 sec. to go back to the main menu.
Monitor Motor Frequency and Motor Current Start / Draw Down Level has to programmed to a
negative value in order for the Start Level to be a
iQpump Digital Operator power-up state delta value from the setpoint.

Example: Start / Draw Down Level P1-04 set to –10 Use


Output Frequency and Transducer Feedback can be monitored PSI with a system setpoint of 50 PSI and a delay
3X
time P1-05 set to 5 sec. Pump system will start
simultaneously. Use and to select monitor signals. Select Parameter. when the pressure drops below 40 PSI (50 - 10) for
to change the sign.
5 sec.
Press simultaneously shows the monitor menu.
Minimum speed (Hz) the pump motor has to operate
Press to access monitor menu.
at. Example: Base pump motor speed is 3600 RPM, Minimum pump frequency should be set to
Minimum Pump
P1-06 40.0 Hz minimum speed is 2400 RPM. Set a value where the pump enters a no-flow
Use to select monitor. Speed
minimum pump frequency to 40.0 Hz. (2400 ÷ 3600 condition.

Switch to Edit Mode Modify Value Save New Value x 60 Hz = 40 Hz)

Auto Mode Opera- Stores the run status in the Auto mode when operat- Recommended for use when Start/Stop
Go Back to Main Menu P4-10
0 tor Run Power ing from digital operator (b1-02=0).
command is from the keypad.
Disabled Down 0: Disabled
Storage 1: Enabled (See Step 9)
Hold button for 3 sec. to go back to the main menu. Enables or disables the Hand Key on the digital op-
1 Hand Key erator. Hand Key on keypad.
Please refer to the iQpump Quick Start Guide, (Document No. P5-04
Enabled Enable / Disable 0: Disabled (See Step 10)
TOEP YAIP1W 01) on how to access other drive monitors. 1: Enabled

Yaskawa America, Inc., 2121 Norman Drive South, Waukegan, IL 60085, (800) YASKAWA (927-5292) Fax (847) 887-7310, DrivesHelpDesk@yaskawa.com, www.yaskawa.com, Document Number: TM.TM.iQp1000.01 03/25/2013 © Yaskawa America, Inc.
iQpump1000 Page 3 of 4
Simplex Quick Start Procedure
Step
iQpump Factory Defaults Overview (only adjust settings based on your application)
7
Parameter Value Description Reference Comments 3 SLEEP MODE (Example)
SYSTEM GOES TO SLEEP WHEN PUMP
60 Hz MOTOR SPEED DROPS BELOW 40 Hz
Sleep Delay Time (P2-03)
(2400 RPM for 3600 RPM Motor).

Output Frequency
Caution: can cause instability if (Example 5.0 sec.)
b5-03 3.0 sec. PI Integral Time Decrease integral time to make iQpump more responsive.
value is too low. Minimum Speed P1-06
(Example 40.0 Hz)
Select what to do when the feedback device (transducer) fails or gets disconnected. Output Frequency
0: Disabled, continue running no message is displayed NOTE: Disable parameter b5-12 (pump motor speed) Ramp or Coast to Stop, b1-02
2 PI Feedback Reference Missing
b5-12
(Fault) Detection Selection 1: Alarm, show warning on the keypad when the feedback device fails or is disconnected if no transducer is installed. 0
WAIT FOR PRESSURE TO FALL BELOW
2: Fault, stop pump system when the feedback fails or is disconnected
Pump Running Go to Sleep START / DRAW DOWN LEVEL (P1-04)
Time
20.0 sec. Time it takes to accelerate the pump motor from zero to maximum speed.
C1-01 Acceleration Time 1
See Note NOTE: Factory default with Thrust Mode enabled is 12.0 sec, 20.0 sec when disabled.
Adjusted depending on system 4 PUMP SYSTEM FAULT SETUP
performance The iQpump can display a ‘SSetpoint Not Met’ fault when the iQpump is unable to maintain the programmed system
10.0 sec. Time it takes to decelerate the pump motor from maximum speed to zero. setpoint due a problem with the pump system. Set P1-15 to the maximum allowed difference between setpoint and
C1-02 Deceleration Time 1
See Note NOTE: Factory default with Thrust Mode enabled is 5.0 sec, 10.0 sec when disabled.
feedback level.
FEEDBACK SIGNAL
 Overcurrent P1-11
Determines the number of times iQpump will perform an automatic restart on the faults listed
in the comments column. P1-15 Max Setpoint Diff
 Ground Fault
 Output Phase Loss
L5-01 5 Number of Restart Attempts iQpump System Protection Faults that can be setup to restart are Low Level Feedback, P1-11
High Level Feedback, Transducer Loss, Not Maintaining Setpoint, Loss of Prime,  Input Phase Loss
Pump Over Cycle. Refer to parameters P4-07 and P4-08. The number of restart attempts is Setpoint-LOP Tim P1-16
 iQpump Overload
set by L5-01. SETPOINT
 Motor Overload Time SET-POINT NOT MET
 Overtorque
 DC Bus Fuse Blown 5 LOW/HIGH FEEDBACK LEVEL DETECTION
If the restart fails (or is not attempted due to a continuing fault condition) iQpump waits the
L5-03 20 sec. Maximum Restart Time After Fault  DC Bus Undervoltage iQpump continuously monitors the system feedback signal. To display a ‘L
Low Feedback’ fault set the low feedback
Maximum Restart Time After Fault, before attempting another restart.
 DC Bus Overvoltage level parameter P1-08 to the minimum feedback level allowed for your system and to display a ‘H
High Feedback’ fault
set the high feedback level parameter P1-11 to the maximum feedback level allowed.
 Overheat

P1-06 should be set to the level


6 PRE-CHARGE OPERATION
Minimum speed (Hz) the pump motor has to operate at. This function is used when the pump system requires to be pre-charged before normal operation. Upon start the
where the pump can produce the iQpump will run at a fixed speed for a specified time or until the feedback signal reaches a programmed level after
P1-06 40.0 Hz Minimum Pump Frequency Example: Base pump motor speed is 3600 RPM, minimum speed is 2400 RPM. Set minimum
minimum pressure even at zero which it will switch to auto mode operation. Feedback
pump frequency to 40.0 Hz. (2400 ÷ 3600 x 60 Hz = 40 Hz)
flow.
Pre-Charge Lvl. P4-01
Pre-Charge Completed
Time it takes before the pump system goes to sleep when the selected signal level (P2-01) Adjust according to system
P2-03 5 sec. Sleep Delay Time
falls below the specified sleep level (P2-02) requirements.
Pre-Charge Freq. P4-02
Primarily used for submersible Output Auto Operation
Sets the frequency reference used when the thrust bearing function is active. A value of 0 pumps. Program P4-12 = 0.0 Hz Frequency
P4-12 30.0 Hz Thrust Bearing Frequency 0 Hz
disables this function. to disable function when iQpump is
P4-01 Pre-Charge Level: Specified feedback level to stop pre-charge operation
used with a centrifugal pump.
P4-02 Pre-Charge Frequency: Set desired pre-charge speed
Note: Only active when P4-10 is P4-03 Pre-Charge Time: Specified maximum pre-charge operation time
When utility power is restored and P4-10 is enabled (1), iQpump waits the time specified in enabled (1) and operation
P4-17 0.2 Min Utility Start Delay
P4-11 before auto operation becomes active. (start/stop) is from the
digital operator. 7 THRUST BEARING - SUBMERSIBLE MOTORS
When using a submersible motor in combination Turn Off Thrust Bearing Function

Output Frequency
with the iQpump, it is recommended to use the (Output Frequency Reached)
1 SYSTEM FEEDBACK UNIT / 2 START / DRAW DOWN LEVEL START / DRAW DOWN LEVEL
Example: Delta Level (Negative Start Level)
Thrust Bearing function to prevent excess motor
FEEDBACK DEVICE SCALING Example: Absolute Level (Positive Start Level) wear. To enable this function, enter the minimum
C1-01 Acceleration Time

e
motor frequency in parameter

m
P1-02 Feedback Unit SYSTEM STARTS WHEN SYSTEM STARTS WHEN

Ti
200 200

l.
P4-11. Example: Minimum motor speed 1800

ce
Start Level Delay (P1-05) PRESSURE SIGNAL FALLS Start Level Delay (P1-05) PRESSURE SIGNAL FALLS

Ac
PSI (Example 5.0 sec.) BELOW 100 PSI PSI (Example 5.0 sec.) BELOW 100 PSI Output Frequency
RPM, 1800 RPM ÷ 3600 RPM x 60.0 Hz = 30.0 Hz

4
-0
0: Inch of Water 8: Bar

P4
1: PSI 9: Pascal 150 150 Thrust Acceleration Time P4-11
2: GPM 10: Degrees Celsius (Example 1.0 sec.)
Pressure

Pressure

-50.0 PSI Time


3: Degrees Fahrenheit 11: Meter Thrust Bearing Frequency P4-12
4: CFM 12: Feet (Example 30.0 Hz) Thrust
Feedback Signal from pressure Feedback Signal from pressure Auto/Hand Operation
5: CMH 13: Liters per Minute transducer (4 – 20 mA) transducer (4 – 20 mA)
Bearing
6: Liters / Hr 14: cm per Minute
Start Start
7: Liters/Sec 15: Inch Hg
25: No Unit
0 WAIT
Delay Start Pump System WAIT
Delay Start Pump System 8 AUTO OPERATION – POWER DOWN STORAGE
P1-03 = 200.0 PSI Feedback Scaling Time Time Allows iQpump to automatically start after power failure when operated from keypad / digital operator. This function is
System Setpoint Feedback Scaling (P1-03) System Setpoint Feedback Scaling (P1-03) recommended for use when operating the iQpump in remote / unmanned areas. Use parameter P4-10 to enable.
(Example 150.0 PSI) (Example 200.0 PSI) (Example 150.0 PSI) (Example 200.0 PSI)
When the iQpump is powered down while running, an internal run
Feedback System Units (P1-02) Start / Draw Down Level (P1-04) System Units (P1-02) Start / Draw Down Level (P1-04)
Maximum (Example PSI) (Example 100.0 PSI) (Example PSI) (Example -50.0 PSI, (150.0 – 50.0) command will automatically be initiated upon power-up.
Yaskawa America, Inc., 2121 Norman Drive South, Waukegan, IL 60085, (800) YASKAWA (927-5292) Fax (847) 887-7310, DrivesHelpDesk@yaskawa.com, www.yaskawa.com, Document Number: TM.TM.iQp1000.01 03/25/2013 © Yaskawa America, Inc.
iQpump1000 Page 4 of 4
Simplex Quick Start Procedure
Step Step Step
Hand Mode Operation
8 Pump Rotation and Feedback Signal Check
9 Auto Mode Operation
10
In this step the motor is checked for proper direction and operation. This
test is to be performed solely from the digital operator. Apply power to the
AUTO MODE HAND MODE
iQpump after all the electrical connections have been made and protective The iQpump can be operated in AUTO mode when the following actions have been The iQpump can be operated in HAND mode when the following actions have been performed:
covers have been re-attached. At this point, DO NOT RUN THE MOTOR, performed: · All parameters are programmed
the Digital Operator should display as shown in Fig. 3. · All parameters are programmed · Motor direction has been checked
· Motor direction has been checked
· Auto Mode: Reference source selected in parameter b1-01 (See step 3)
· Auto Mode: Run source selected in parameter b1-02 (See Step 3)

No alarm active

LED is blinking
when AUTO mode
is active but AUTO
Run Command is Fig. 4: Digital Operator
Hand Mode Off
not active.

Auto Mode Off Fig. 3: Digital Operator

Motor Rotation Test


Press to access Hand Speed. Use to change Hand Speed value. Press
Next, push on the Digital Operator; the display should read
to save value.
Press the AUTO button to put the iQpump into AUTO mode.
Hand Speed from Analog Input (0 – 10V)
and the HAND LED should be ON. In AUTO mode the iQpump is capable of starting or stopping based on the Run Source
Selection setting parameter b1-02. (See Step 3 Select Start/Stop Control Method) The Set parameter P5-01 ‘Hand Mode Ref.’ to ‘0’ to adjust the hand mode reference from an external 0 – 10V signal
setpoint used in AUTO mode is based on the Reference Source Selection setting connected to terminal A3 and AC.
0 – 10V Connection
parameter b1-01. (See Step 3 Select Speed Method) +V AC A1 A2 A3 FM AM AC RP AC 24V
The motor should now be operating at in the correct direction of pump.
Push on the Digital Operator; the display should read as in Fig. 3. SET SYSTEM SETPOINT Cable
E(G)
Shield +
Next, press to access or modify the system setpoint that was entered using 0 ~ 10Vdc
Press to access Hand Speed. Use to change
parameter Q1-01 System Setpoint in the iQpump Quick Setup Menu
Hand Speed value. Press to save value. Sleep and Anti-No-Flow (ANF) Detection (P2-23, P2-24, P2-25)
Use to select the digit and to change the system setpoint.
NOTE: Before adjusting Anti-No-Flow operation ensure your system is regulating satisfactory while operating under
If the direction is not correct, then power down the iQpump and follow
Next press to store setpoint and press to return to the main normal running conditions.
Instructions below.
operation menu. If stable continue to Step 1 to verify no-flow/sleep operation. If unstable turn off the Anti-No-Flow function
! DANGER (P2-23 = 0.00%) and adjust the PI control parameters b5-02 and b5-03 to stabilize pump system. Refer to iQpump
Quick Start Guide (Document No.TOEP YAIP1W 01) for additional information. Once the system is stable, re-
After the power has been turned OFF, wait at least five minutes until the enable the Anti-No-Flow function by setting P2-23 to 0.40% and continue to Step 1 to verify no-flow/sleep
charge indicator extinguishes completely before touching any wiring, circuit operation.
boards or components. Next, press the AUTO
button to start the Step 1: Verify system holds pressure by creating a no-flow situation (e.g. close off discharge valve).
iQpump.
Use precaution, and refer to
Step 2: Press OFF button on the digital operator, wait 1 min. until system stabilizes and verify system pressure
Fig.1 or 2, swap any two of the Example: 80 PSI
feedback U1-91. If the pressure drops more than 3 PSI (U1-91) adjust P2-25 to the actual delta pressure drop plus
three output leads to the motor
1 PSI.
(U/T1, V/T2 and W/T3). After the
iQpump automatically starts in Auto Mode when the feedback signal level falls below
wiring change, repeat Step 8
the programmed level in parameter P1-04 for the specified time in P1-05. Example: Setpoint is 80 PSI, pressure feedback U1-91 shows 76 PSI, P2-25 should be 4 + 1 or 5 PSI.
and recheck motor direction. Note: This value should always be more than your start level (P1-04). If not, the system pressure is not holding and
Digital Operator this needs to be corrected, or the pump system will continue to cycle on and off.
145 PSI Start Level Delay (P1-05)
turned off.
(Example 5.0 sec.) Feedback signal from
pressure transducer Step 3: Run system in normal automatic operation with flow. Next check monitor
FEEDBACK SIGNAL CHECK (4 – 20 mA) U1-99 “ANF Timer” and verify that the value is incrementing and resetting back to zero continuously. If the value
Verify feedback on display (show keypad) matches mechanical pressure holds at 10 sec. (P2-24) increase P2-24 “Anti-No-Flow Detection Time” by increments of 5 sec. Repeat Step 3 each
Pressure

gauge. time P2-24 is adjusted.


Start / Draw Down
Refer to parameter P1-02 and P1-03, if the Level P1-04 Step 4: Create a no-flow situation (e.g. close discharge valve) and monitor that U1-99 “ANF Timer” increments and
feedback device scaling or system units are holds at P2-24 time (value set in Step 3). Once the Anti-No-Flow timer expires the speed will reduce gradually until
incorrect. Start System Setpoint it reaches minimum pump speed (P1-06) where it will hold for 5 sec. (P2-03) before going to sleep.
WAIT
Delay Start Pump System
0 (Example 80 PSI)
FEEDBACK SIGNAL LEVEL Step 5: Run system in normal automatic operation and verify sleep and wake-up operation until system performs
Refer to Illustration 2 on Page 3 of 4 for additional information on the Start Level Function.
satisfactory.

Yaskawa America, Inc., 2121 Norman Drive South, Waukegan, IL 60085, (800) YASKAWA (927-5292) Fax (847) 887-7310, DrivesHelpDesk@yaskawa.com, www.yaskawa.com, Document Number: TM.TM.iQp1000.01 03/25/2013 © Yaskawa America, Inc.