Sie sind auf Seite 1von 2

ERRATA

ACI 350.3-06
Seismic Design of Liquid-Containing Concrete Structures
and Commentary (ACI 350.3-06)
Reported by ACI Committee 350
3rd and 4th printings

Table 4.1.1(b), page 20, last footnote revised as:


‡Unanchored, uncontained tanks shall not be built in locations where SDS ≥ SS ≥
0.75.

Section R5.3.1, page 24, last paragraph revised as:


…and the dynamic force on the trailing half of the tank will reduce the effects of the
hydrodynamic hydrostatic force on the wall.

Section R9.2.4, page 36, SI equation for k revised as:

3 3
Ec  t w  Ec  t w 
4  106  h  4  103  h 
[k = in the SI system]

Section 9.4.1, page 39, revised as:

Ci shall be determined as follows:

For TI Ti ≤ TS…

Section 9.5, page 40, 2nd paragraph, revised as:

For periods less than or equal to…..spectra at a period of 2 0.2 seconds…

--`,````,,,,``,``````,,,,,,,,```-`-`,,`,,`,`,,`---

Copyright American Concrete Institute


Provided by IHS under license with ACI Licensee=Fluor Corp no FPPPV per administrator /2110503106, User=Henriquez, Ser
No reproduction or networking permitted without license from IHS Not for Resale, 02/09/2012 05:16:50 MST
Section B.3, page 59, Eq. (B-7) and (B-8) revised as:

Ci I Ci I
Pr  W r Pr  W (B-7)
Ri Ri r

Ci I Ci I
Pi  Wi Pi  W (B-8)
Ri Ri i

Updated 11-10-08, 9:53 a.m.


--`,````,,,,``,``````,,,,,,,,```-`-`,,`,,`,`,,`---

Copyright American Concrete Institute


Provided by IHS under license with ACI Licensee=Fluor Corp no FPPPV per administrator /2110503106, User=Henriquez, Ser
No reproduction or networking permitted without license from IHS Not for Resale, 02/09/2012 05:16:50 MST