Sie sind auf Seite 1von 1

MATERIAL LIST

NOTE 4 ITEM DESCRIPTION QTY


IMC567 1/2"T x 1/2"NPT Male Connector, 316 SS 2
IMC568 1/2"T x 3/4"NPT Male Connector, 316 SS 2
SIT493 1/2" OD x 0.049" WT Tubing, A269 Gr.TP316, Smls, Fully Annealed 40 ft

IMC567 IMC567

H L

SLOPE DOWN 1" PER FOOT MIN.

IMC568

SIT493 SIT493

TIME: 10:17:43
IMC568

GENERATED DATE: 20-Jan-11


BY PIPING 3
BY INSTRUMENTS CLASS 150, 300 & 600
NOTES
INSTRUMENT INSTALLATION DETAIL
1. SEE INSTRUMENT NOTES AND LEGEND DRAWING #166000-000-DG-IC04-0001.
2. FOR TAGS ASSIGNED TO THIS DETAIL SEE INSTRUMENT INDEX.
3 ISSUED FOR CONSTRUCTION GC DS GN 28-Jan-11
PRESSURE DIFFERENTIAL TRANSMITTER

HOOK-UP: PDT-STD-001
3. INSTRUMENT TUBING TO BE FIELD ROUTED AND SUPPORTED 2 ISSUED FOR CONSTRUCTION GC DS GN 31-Mar-10 GAS ABOVE REMOTE MOUNT
AS REQUIRED.
4. MANIFOLD & MOUNTING BRACKET TO BE SUPPLIED WITH TRANSMITTER. 1 REVISED AS NOTED KRF PMB COMM 09-Feb-09 CARTAGENA EXPANSION PROJECT
5. FIELD TO VERIFY HIGH PRESSURE AND LOW PRESSURE PROCESS CONNECTIONS.
0 ISSUED FOR DESIGN KRF PMB COMM 24-Aug-09
THIS DOCUMENT IS THE PROPERTY OF CHICAGO BRIDGE & IRON COMPANY ("CB&I"). IT MAY CONTAIN INFORMATION DESCRIBING TECHNOLOGY
OWNED BY CB&I AND DEEMED TO BE COMMERCIALLY SENSITIVE. IT IS TO BE USED ONLY IN CONNECTION WITH WORK PERFORMED BY CB&I.
REPRODUCTION IN WHOLE OR IN PART FOR ANY PURPOSE OTHER THAN WORK PERFORMED BY CB&I IS FORBIDDEN EXCEPT BY EXPRESS WRITTEN
PERMISSION OF CB&I. IT IS TO BE SAFEGUARDED AGAINST BOTH DELIBERATE AND INADVERTENT DISCLOSURE TO ANY THIRD PARTY.
FOR: Refineria de Cartagena S.A.
DRAWN: CK'D: APPD: DATE: SCALE:
NO. REVISION DRAWN CK'D APPD DATE
PMB RSB COMM 18-Aug-09 N/A PROJ NO: 166000 DWG NO: 000-DG-IC04-0027 REV: 3