COLUMN DESIGN CALCULATIONS

Project Name :

Client Name :

Engineer Name :

Design File :

Analysis File :

Analysis Last Modified :

Definitions Of Terms:

All forces in units kN and m

All reinforcement details like area, spacing in mm

Neutral axis angle for resultant design moment is with respect to local major axis.

1 βdns = Ratio to account for reduction of stiffness of columns

due to sustained axial loads

2 δns = Moment magnification factor for frames not braced

against sidesway

3 Δo = First-order relative deflection between the top and

bottom of the story due to Vu in mm

4 ∑Pu =

Total factored vertical load in the story

corresponding to the lateral loading case for which

∑Pu is greatest, kN (Clause 10.10.5)

5 δu = Design displacement in mm

6 λ = Modification factor reflecting the reduced

mechanical properties of lightweight concrete

7 Φ = Strength reduction factor

8 ac = Coefficient defining the relative contribution of

concrete strength to nominal wall shear strength

9 Ach =

Cross-sectional area of a structural member


measured to the outside edges of transverse

reinforcement in sqmm

10 Acv =

Gross area of concrete section bounded by web

thickness and length of section in the direction of

shear force considered in sqmm

11 Aj =

Effective cross-sectional area within a joint in a

plane parallel to plane of reinforcement generating

shear in the joint in sqmm

12 As = Area of non-prestressed longitudinal tension

reinforcement in sqmm

13 Avmin = Minimum area of shear reinforcement within

spacing 's' in sqmm

14 B = Width of column/ wall in mm

15 B' = width of beam along B / column width in mm

16 bc =

Cross-sectional dimension of member core

measured to the outside edges of the transverse

reinforcement composing area Ash in mm

17 c =

Distance from extreme compression fiber to neutral

axis in mm

18 Cc

= Clear cover of reinforcement in mm

19 Cm

= Factor relating actual moment diagram to an

equivalent uniform moment diagram

20
D

= Depth / diameter of column in mm

21 D'

22

= Distance from extreme compression fiber to centroid

of longitudinal tension reinforcement in mm

23 d'

= Distance from extreme compression fiber to centroid

of longitudinal compression reinforcement,mm

24 Ec

= Modulus of elasticity of concrete in N/sqmm

25 EI

= Flexural stiffness of compression member in

N-sqmm

26 f'c

= Specified strength of concrete cylinder in N/sqmm

27 fy

= Specified yield strength of reinforcement in

N/sqmm

28 fyt

= Specified yield strength fy of transverse

reinforcement in N/sqmm

29 hw

Height of entire wall from base to top, or clear

height of wall segment or wall pier considered in

mm
30

= Effective length factor for compression member

31 lc

= Length of compression member in a frame in mm

32 lg

= Moment of inertia of gross concrete section about

centroidal axis neglecting reinforcement in mm4

33 lw

= Length of entire wall in mm

34 lux

= Un-supported length for compression member

along D in mm

35 luy

= Un-supported length for compression member

along B in mm

36 MCap

= Moment capacity of section for NA angle at design

Pu in kNm

37 MRes

= Resultant design moment at angle to local major axis

in kNm

38 Mc

Factored moment amplified for the effects of

member curvature used for design of compression

member in kNm

39 mm

= Factored moment modified to account for effect of


axial compression in kNm

40 Mux

= Factored moment at section along D in kNm (From

Analysis)

41 Muy

= Factored moment at section along B in kNm (From

Analysis)

42 M1

= Smaller factored end moment on a compression

member in kNm

43 M1ns

Factored end moment on a compression member at

the end at which M1 acts, due to loads that cause no

appreciable sidesway in kNm

44 M1s

Factored end moment on compression member at

the end at which M1 acts, due to loads that cause

appreciable sidesway in kNm

45 M1sldr

= Smaller factored end moment on a compression

member due to slenderness effect in kNm

46 M2

= Larger factored end moment on compression

member in kNm

47 M2min

= Minimum value of M2

48 M2ns
=

Factored end moment on compression member at

the end at which M2 acts, due to loads that cause no

appreciable sidesway in kNm

49 M2s

Factored end moment on compression member at

the end at which M2 acts, due to loads that cause

appreciable sidesway in kNm

50 M2sldr

= Largest factored end moment on a compression

member due to slenderness effect in kNm

51 Mnb

= Flexure Capacity for Beam

52 Mnc

= Flexure Capacity for Column

53 Mnty

= Flexure strength at top along column depth, kNm

54 Mnby

= Flexure strength at bottom along column depth,

kNm

55 Mntx

= Flexure strength at top along column width, kNm

56 Mnbx

= Flexure strength at bottom along column width,

kNm

57 Nu

= Factored axial force normal to cross section

occurring simultaneously with Vu in kN


58 Pc

= Critical buckling load in kN

59 pt

Ratio of area of distributed transverse reinforcement

to gross concrete area perpendicular to that

reinforcement

60 Pω

= Ratio of As to B x d

61

= Stability index for storey

62

= Radius of gyration of cross section of a compression

member in mm

63 Vc

= Nominal shear strength provided by concrete in kN

64 Vj

= Shear Force acting at the joint in kN

65 Vn

= Nominal shear strength in kN

66 Vn'

= Nominal shear strength in kN

67 Vus

= Factored horizontal shear in a storey of section in

kN

68 Vux

= Factored shear at section along D in kN (From


Analysis)

69 Vux1

= Shear induced due to column flexural capacity along

width, kN

70 Vux2

Shear due to enhanced earthquake factor along

width, kN

71 Vuy = Factored shear at section along B in kN (From

Analysis)

72 Vuy1 = Shear induced due to column flexural capacity along

depth, kN

73 Vuy2 = Shear due to enhanced earthquake factor along

depth, kN

74 β = It is a Neutral Axis angle corresponding to load

angle to find out MCap

75 φ = Strength Reduction Factor

Code References:

ACI 318M-2011

Sr.No Element Clause / table

1 Minimum area of longitudinal

reinforcement for column : 21.6.3

2 Maximum area of longitudinal

reinforcement for column : 21.6.3

3 Minimum longitudinal and transverse

reinforcement for wall : 21.9.2.1

4 Minimum diameter of transverse ties : 7.10.5

5 Minimum spacing of transverse ties : 7.10.5

6 Maximum spacing of longitudinal and


transverse reinforcement for wall : 21.9.2.1

7 Applicability of boundary element : 21.9.6

8 Area and spacing of special confining

reinforcement : 21.6.4

9 Slenderness Moments : 10.10

10 Shear Strength provided by concrete for

column : 11.2

11 Design of shear for non-ductile wall : 11.9

12 Design of shear for ductile wall : 21.9.4

13 Minimum Flexural Strength of Columns : 21.6.2.2

14 Shear Check at Column Joint : 21.7.4.1

15 Shear Strength of Column : 21.3.3 & 21.5.4

Sway Calculation (Stability Index)

For Global-X Direction

Level Load

Name

Story

Height (m)

Gravity

Load P (kN)

Relative

Displacements

(mm)

Story

Shear (kN)

Stability

Index

Sway

Condition
ABCD

B x C / (A x

D)

0m to

1.5m

LOAD 1:

SX 1.5 2797.067 2.015 331.964 0.011 Non Sway

1.5m to

5m

LOAD 1:

SX 3.5 2320.301 11.814 311.245 0.025 Non Sway

5m to 8m LOAD 1:

SX 3 625.72 7.433 120.211 0.013 Non Sway

For Global-Y Direction

Level Load

Name

Story

Height (m)

Gravity

Load P (kN)

Relative

Displacements

(mm)

Story

Shear (kN)

Stability

Index

Sway

Condition
A B C D B x C / (A x

D)

0m to

1.5m

LOAD 2:

SZ 1.5 2797.067 1.668 331.964 0.009 Non Sway

1.5m to

5m

LOAD 2:

SZ 3.5 2320.301 9.836 311.245 0.021 Non Sway

5m to 8m LOAD 2:

SZ 3 625.72 6.189 120.211 0.011 Non Sway

General Data

Column No. : C1

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 1


Critical Analysis Load Combination : 9

Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 2:

SZ)

Critical Location = Bottom Joint

Put = 130.94 kN

Muxt = 1.82 kNm

Muyt = 16.75 kNm

Vuxt = -14.14 kN

Vuyt = -5.12 kN

Pub = 136.14 kN

Muxb = -5.86 kNm

Muyb = 37.96 kNm

Vuxb = -14.14 kN

Vuyb = -5.12 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x Depth)

Beam 2

(Length x

Width x Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x


350 No Beam 16.373 - 6.71

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x Depth)

Beam 2

(Length x

Width x Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x

350 No Beam 16.373 - 6.71

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)
Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 101.04 mm

Kluy /r = 9.9

M1 = 1.82 kNm

M2 = -5.86 kNm

34 - 12 x (M1/M2) = 37.73

9.9 < 37.73, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 9.9

M1 = 16.75 kNm

M2 = 37.96 kNm

34 - 12 x (M1/M2) = 28.7

9.9 < 28.7, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 1.82 - 1.82

Major Axis Mux (bottom) -5.86 - -5.86

Minor Axis Muy (top) 16.75 - 16.75


Minor Axis Muy (bottom) 37.96 - 37.96

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 136.14 kN

Mux = -5.86 kNm

Muy = 37.96 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 81.22 deg

MRes = 38.41 kNm

( φ ) MCap = 74.77 kNm

Capacity Ratio = MRes/ MCap

= 0.514 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 136.14 kN

Luy = 1150 mm

Mnty = 74.23 kNm

Mnby = 74.23 kNm

Vuy1 = 129.1 kN

Shear from Load combinations with


Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 53.63 kN

Critical Analysis Load Combination : 8

Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 189.78 kN

Muy = 39.59 kNm

Vuy = -19.5909 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 129.1 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 13.54 kNm

Vcy Permissible = 89.12 kN

Vuy > Vcy Permissible

Link For Shear Design Along D are required

Vs = Vu - Vcy

= 39.98 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 28.96

Area of shear reinforcement

required, Asv-D = 479.65 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm


Design for shear along B

Shear from Moment Capacity:

Pu = 136.14 kN

Lux = 1150 mm

Mntx = 74.23 kNm

Mnbx = 74.23 kNm

Vux1 = 129.1 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 52.1851 kN

Critical Analysis Load Combination : 10

Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 2: SZ) kN

Nu = 183.57 kN

Mux = 40.15 kNm

Vux = 19.0206 kN

Design Shear = max(Vux, Vux1, Vux2)

= 129.1 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 14.95 kNm

Vcx Permissible = 88.96 kN

Vux > Vcx Permissible

Link For Shear Design Along B are required

Vs = Vu - Vcx
= 40.14 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 28.91

Area of shear reinforcement

required, Asv-B = 481.6 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10


Spacing 175 --- 125 175 125

General Data

Column No. : C1

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 45

Critical Analysis Load Combination : 10

Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 2:

SZ)

Critical Location = Top Joint

Put = 132.6 kN

Muxt = 7.74 kNm

Muyt = 40.48 kNm

Vuxt = 22.09 kN

Vuyt = -2.98 kN

Pub = 144.72 kN

Muxb = -2.68 kNm


Muyb = -36.81 kNm

Vuxb = 22.09 kN

Vuyb = -2.98 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 4000 x 200 x

350 No Beam 16.373 - 6.71

Top 32.746 4000 x 250 x

400 No Beam 30.551 - 2.328

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness
Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 4000 x 200 x

350 No Beam 16.373 - 6.71

Top 32.746 4000 x 250 x

400 No Beam 30.551 - 2.328

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 1

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check
Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 30.68

M1 = -2.68 kNm

M2 = 7.74 kNm

34 - 12 x (M1/M2) = 38.15

30.68 < 38.15, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K=1

r = 101.04 mm

Klux /r = 30.68

M1 = -36.81 kNm

M2 = 40.48 kNm

34 - 12 x (M1/M2) = 44.91

30.68 < 44.91, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 7.74 - 7.74

Major Axis Mux (bottom) -2.68 - -2.68

Minor Axis Muy (top) 40.48 - 40.48

Minor Axis Muy (bottom) -36.81 - -36.81

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))


Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 132.6 kN

Mux = 7.74 kNm

Muy = 40.48 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 79.18 deg

MRes = 41.21 kNm

( φ ) MCap = 74.55 kNm

Capacity Ratio = MRes/ MCap

= 0.553 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 132.6 kN

Luy = 3100 mm

Mnty = 75.3 kNm

Mnby = 75.3 kNm

Vuy1 = 48.58 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 51.88 kN

Critical Analysis Load Combination : 10


Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 2: SZ) kN

Nu = 144.72 kN

Muy = 2.68 kNm

Vuy = -2.9764 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 56.44 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 17.19 kNm

Vcy Permissible = 162.76 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 132.6 kN

Lux = 3100 mm

Mntx = 75.3 kNm

Mnbx = 75.3 kNm

Vux1 = 48.58 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 56.4356 kN

Critical Analysis Load Combination : 6

Critical Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4:


LL) kN

Nu = 120.39 kN

Mux = 12.08 kNm

Vux = 5.2517 kN

Design Shear = max(Vux, Vux1, Vux2)

= 51.88 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 4.44 kNm

Vcx Permissible = 159.23 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm
Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C1

Level : 5m To 8m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 2700 mm

Clear Floor Height @ luy = 2700 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 89

Critical Analysis Load Combination : 8

Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 42.36 kN
Muxt = 15.71 kNm

Muyt = 6.78 kNm

Vuxt = 6.3 kN

Vuyt = -10.57 kN

Pub = 52.76 kN

Muxb = -16 kNm

Muyb = -12.11 kNm

Vuxb = 6.3 kN

Vuyb = -10.57 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x

400 No Beam 30.551 - 2.328

Top 38.204 4000 x 200 x

300 No Beam 10.311 - 3.705

Sway Condition (as per Stability


Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x

400 No Beam 30.551 - 2.328

Top 38.204 4000 x 200 x

300 No Beam 10.311 - 3.705

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 1

Check For Stability Index

Along D

Q = 0.013

0.013< 0.05, Column shall be designed as non-sway frame


(Braced)

Along B

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 26.72

M1 = 15.71 kNm

M2 = -16 kNm

34 - 12 x (M1/M2) = 45.78

26.72 < 45.78, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K=1

r = 101.04 mm

Klux /r = 26.72

M1 = 6.78 kNm

M2 = -12.11 kNm

34 - 12 x (M1/M2) = 40.72

26.72 < 40.72, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 15.71 - 15.71

Major Axis Mux (bottom) -16 - -16


Minor Axis Muy (top) 6.78 - 6.78

Minor Axis Muy (bottom) -12.11 - -12.11

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 52.76 kN

Mux = -16 kNm

Muy = -12.11 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 37.12 deg

MRes = 20.06 kNm

( φ ) MCap = 67.86 kNm

Capacity Ratio = MRes/ MCap

= 0.296 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 52.76 kN

Luy = 2700 mm

Mnty = 63.83 kNm

Mnby = 63.83 kNm

Vuy1 = 47.28 kN
Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 20.48 kN

Critical Analysis Load Combination : 6

Critical Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4:

LL) kN

Nu = 37.26 kN

Muy = 6.15 kNm

Vuy = -5.8494 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 47.28 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 1.04 kNm

Vcy Permissible = 104.88 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 52.76 kN

Lux = 2700 mm

Mntx = 63.83 kNm

Mnbx = 63.83 kNm

Vux1 = 47.28 kN

Shear from Load combinations with


Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 16.6134 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 32.17 kN

Mux = 5.34 kNm

Vux = 5.6377 kN

Design Shear = max(Vux, Vux1, Vux2)

= 47.28 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 0.92 kNm

Vcx Permissible = 109.07 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm


Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C2

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data
Analysis Reference No. = 2

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 232.97 kN

Muxt = 6.25 kNm

Muyt = 1.18 kNm

Vuxt = 0.68 kN

Vuyt = 23.86 kN

Pub = 238.17 kN

Muxb = 42.03 kNm

Muyb = 0.17 kNm

Vuxb = 0.68 kN

Vuyb = 23.86 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2
N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x

350

4000 x 200 x

350 16.373 16.373 3.331

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x Depth)

Beam 2

(Length x

Width x Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x

350 No Beam 16.373 - 6.71

Sway Condition (as per Stability

Index)

= Non Sway

Effective Length Factor along Minor


axis = 0.87

Check For Stability Index

Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 101.04 mm

Kluy /r = 9.9

M1 = 6.25 kNm

M2 = 42.03 kNm

34 - 12 x (M1/M2) = 32.21

9.9 < 32.21, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 9.9

M1 = 0.17 kNm

M2 = 1.18 kNm

34 - 12 x (M1/M2) = 32.29

9.9 < 32.29, Column not slender along B


Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 6.25 - 6.25

Major Axis Mux (bottom) 42.03 - 42.03

Minor Axis Muy (top) 1.18 - 1.18

Minor Axis Muy (bottom) 0.17 - 0.17

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 238.17 kN

Mux = 42.03 kNm

Muy = 0.17 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 0.23 deg

MRes = 42.03 kNm

( φ ) MCap = 86.37 kNm

Capacity Ratio = MRes/ MCap

= 0.487 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:


Pu = 238.17 kN

Luy = 1150 mm

Mnty = 86.35 kNm

Mnby = 86.35 kNm

Vuy1 = 150.17 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 71.16 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 238.17 kN

Muy = 42.03 kNm

Vuy = 23.8601 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 150.17 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 9.34 kNm

Vcy Permissible = 90.23 kN

Vuy > Vcy Permissible

Link For Shear Design Along D are required

Vs = Vu - Vcy

= 59.94 kN

Vcx Permissible = 0.5 x Vcx x 0.65


= 29.32

Area of shear reinforcement

required, Asv-D = 719.12 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design for shear along B

Shear from Moment Capacity:

Pu = 238.17 kN

Lux = 1150 mm

Mntx = 86.35 kNm

Mnbx = 86.35 kNm

Vux1 = 150.17 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 46.218 kN

Critical Analysis Load Combination : 10

Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 2: SZ) kN

Nu = 263.61 kN

Mux = 36.73 kNm

Vux = 16.076 kN

Design Shear = max(Vux, Vux1, Vux2)

= 150.17 kN

λ=1

φ = 0.65

deff = 302 mm
ρw = 0.007

mm = 0.55 kNm

Vcx Permissible = 92.07 kN

Vux > Vcx Permissible

Link For Shear Design Along B are required

Vs = Vu - Vcx

= 58.1 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 29.92

Area of shear reinforcement

required, Asv-B = 697.05 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm
Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C2

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 46

Critical Analysis Load Combination : 8

Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 1:

SX)

Critical Location = Top Joint

Put = 181.13 kN
Muxt = 38.77 kNm

Muyt = 16.04 kNm

Vuxt = 6.97 kN

Vuyt = -21.68 kN

Pub = 193.26 kN

Muxb = -37.08 kNm

Muyb = -8.35 kNm

Vuxb = 6.97 kN

Vuyb = -21.68 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 4000 x 200 x

350

4000 x 200 x

350 16.373 16.373 3.331

Top 32.746 30.551 30.551 1.16


4000 x 250 x

400

4000 x 250 x

400

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 4000 x 200 x

350 No Beam 16.373 - 6.71

Top 32.746 4000 x 250 x

400 No Beam 30.551 - 2.328

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor


axis = 1

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 30.68

M1 = -37.08 kNm

M2 = 38.77 kNm

34 - 12 x (M1/M2) = 45.48

30.68 < 45.48, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K=1

r = 101.04 mm

Klux /r = 30.68

M1 = -8.35 kNm

M2 = 16.04 kNm

34 - 12 x (M1/M2) = 40.24

30.68 < 40.24, Column not slender along B


Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 38.77 - 38.77

Major Axis Mux (bottom) -37.08 - -37.08

Minor Axis Muy (top) 16.04 - 16.04

Minor Axis Muy (bottom) -8.35 - -8.35

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 181.13 kN

Mux = 38.77 kNm

Muy = 16.04 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 22.47 deg

MRes = 41.96 kNm

( φ ) MCap = 77.55 kNm

Capacity Ratio = MRes/ MCap

= 0.541 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:


Pu = 181.13 kN

Luy = 3100 mm

Mnty = 81.2 kNm

Mnby = 81.2 kNm

Vuy1 = 52.39 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 65.25 kN

Critical Analysis Load Combination : 10

Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 2: SZ) kN

Nu = 198.49 kN

Muy = 3.96 kNm

Vuy = 2.371 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 55.41 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 23.28 kNm

Vcy Permissible = 170.3 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 181.13 kN
Lux = 3100 mm

Mntx = 81.2 kNm

Mnbx = 81.2 kNm

Vux1 = 52.39 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 55.4085 kN

Critical Analysis Load Combination : 5

Critical Load Combination = [1] : 1.4 (LOAD 3: DL) kN

Nu = 207.23 kN

Mux = 8.17 kNm

Vux = 6.6677 kN

Design Shear = max(Vux, Vux1, Vux2)

= 65.25 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 20.27 kNm

Vcx Permissible = 171.5 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4


= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C2

Level : 5m To 8m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 2700 mm


Clear Floor Height @ luy = 2700 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 90

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 47.35 kN

Muxt = -19.85 kNm

Muyt = 6.74 kNm

Vuxt = 7.77 kN

Vuyt = 13.54 kN

Pub = 57.74 kN

Muxb = 20.77 kNm

Muyb = -16.58 kNm

Vuxb = 7.77 kN

Vuyb = 13.54 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2
(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x

400

4000 x 250 x

400 30.551 30.551 1.16

Top 38.204 4000 x 200 x

300

4000 x 200 x

300 10.311 10.311 1.853

Sway Condition (as per Stability

Index) = Non Sway

=1

Effective Length Factor along Major

Axis

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x
Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x

400 No Beam 30.551 - 2.328

Top 38.204 4000 x 200 x

300 No Beam 10.311 - 3.705

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 1

Check For Stability Index

Along D

Q = 0.013

0.013< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 26.72

M1 = -19.85 kNm

M2 = 20.77 kNm

34 - 12 x (M1/M2) = 45.46
26.72 < 45.46, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K=1

r = 101.04 mm

Klux /r = 26.72

M1 = 6.74 kNm

M2 = -16.58 kNm

34 - 12 x (M1/M2) = 38.88

26.72 < 38.88, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) -19.85 - -19.85

Major Axis Mux (bottom) 20.77 - 20.77

Minor Axis Muy (top) 6.74 - 6.74

Minor Axis Muy (bottom) -16.58 - -16.58

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 57.74 kN

Mux = 20.77 kNm

Muy = -16.58 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31
Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 38.59 deg

MRes = 26.58 kNm

( φ ) MCap = 68.13 kNm

Capacity Ratio = MRes/ MCap

= 0.39 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 57.74 kN

Luy = 2700 mm

Mnty = 64.46 kNm

Mnby = 64.46 kNm

Vuy1 = 47.74 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 39.12 kN

Critical Analysis Load Combination : 8

Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 47.44 kN

Muy = 17.91 kNm

Vuy = -12.0282 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 47.74 kN

λ=1
φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 11.4 kNm

Vcy Permissible = 87 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 57.74 kN

Lux = 2700 mm

Mntx = 64.46 kNm

Mnbx = 64.46 kNm

Vux1 = 47.74 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 16.6241 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 47.35 kN

Mux = 6.74 kNm

Vux = 7.7732 kN

Design Shear = max(Vux, Vux1, Vux2)

= 47.74 kN

λ=1

φ = 0.65
deff = 302 mm

ρw = 0.007

mm = 0.24 kNm

Vcx Permissible = 102.76 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data
Column No. : C3

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 3

Critical Analysis Load Combination : 8

Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 126.82 kN

Muxt = -15.56 kNm

Muyt = 3.06 kNm

Vuxt = 1.73 kN

Vuyt = -14.38 kN

Pub = 132.02 kN

Muxb = -37.12 kNm

Muyb = 0.47 kNm

Vuxb = 1.73 kN
Vuyb = -14.38 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x Depth)

Beam 2

(Length x

Width x Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 No Beam 4000 x 200 x

350 - 16.373 6.71

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1 Beam 2

Beam 1

(Length x

Width x Depth)
Beam 2

(Length x

Width x Depth)

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x

350 No Beam 16.373 - 6.71

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 101.04 mm

Kluy /r = 9.9

M1 = -15.56 kNm

M2 = -37.12 kNm

34 - 12 x (M1/M2) = 28.97
9.9 < 28.97, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 9.9

M1 = 0.47 kNm

M2 = 3.06 kNm

34 - 12 x (M1/M2) = 32.17

9.9 < 32.17, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) -15.56 - -15.56

Major Axis Mux (bottom) -37.12 - -37.12

Minor Axis Muy (top) 3.06 - 3.06

Minor Axis Muy (bottom) 0.47 - 0.47

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 132.02 kN

Mux = -37.12 kNm

Muy = 0.47 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31
Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 0.72 deg

MRes = 37.12 kNm

( φ ) MCap = 73.8 kNm

Capacity Ratio = MRes/ MCap

= 0.503 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 132.02 kN

Luy = 1150 mm

Mnty = 73.07 kNm

Mnby = 73.07 kNm

Vuy1 = 127.08 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 53.46 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX)

kN

Nu = 190.59 kN

Muy = 39.99 kNm

Vuy = 19.5404 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 127.08 kN
λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 13.83 kNm

Vcy Permissible = 88.82 kN

Vuy > Vcy Permissible

Link For Shear Design Along D are required

Vs = Vu - Vcy

= 38.26 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 28.87

Area of shear reinforcement

required, Asv-D = 458.97 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design for shear along B

Shear from Moment Capacity:

Pu = 132.02 kN

Lux = 1150 mm

Mntx = 73.07 kNm

Mnbx = 73.07 kNm

Vux1 = 127.08 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 43.0585 kN
Critical Analysis Load Combination : 10

Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 2: SZ) kN

Nu = 182.64 kN

Mux = 10.74 kNm

Vux = 15.9323 kN

Design Shear = max(Vux, Vux1, Vux2)

= 127.08 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 14.33 kNm

Vcx Permissible = 168.12 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm


24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C3

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 47

Critical Analysis Load Combination : 10

Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 2:

SZ)
Critical Location = Top Joint

Put = 135.82 kN

Muxt = -12.83 kNm

Muyt = 37.07 kNm

Vuxt = 20.24 kN

Vuyt = 6.32 kN

Pub = 147.95 kN

Muxb = 9.28 kNm

Muyb = -33.74 kNm

Vuxb = 20.24 kN

Vuyb = 6.32 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 No Beam 4000 x 200 x

350 - 16.373 6.71

Top 32.746 No Beam 4000 x 250 x


400 - 30.551 2.328

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis

=1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 4000 x 200 x

350 No Beam 16.373 - 6.71

Top 32.746 4000 x 250 x

400 No Beam 30.551 - 2.328

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 1

Check For Stability Index


Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 30.68

M1 = 9.28 kNm

M2 = -12.83 kNm

34 - 12 x (M1/M2) = 42.68

30.68 < 42.68, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K=1

r = 101.04 mm

Klux /r = 30.68

M1 = -33.74 kNm

M2 = 37.07 kNm

34 - 12 x (M1/M2) = 44.92

30.68 < 44.92, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final


ABC

Major Axis Mux (top) -12.83 - -12.83

Major Axis Mux (bottom) 9.28 - 9.28

Minor Axis Muy (top) 37.07 - 37.07

Minor Axis Muy (bottom) -33.74 - -33.74

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 135.82 kN

Mux = -12.83 kNm

Muy = 37.07 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 70.91 deg

MRes = 39.22 kNm

( φ ) MCap = 74.78 kNm

Capacity Ratio = MRes/ MCap

= 0.525 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 135.82 kN

Luy = 3100 mm
Mnty = 75.71 kNm

Mnby = 75.71 kNm

Vuy1 = 48.84 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 52.08 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 98.7 kN

Muy = 7.36 kNm

Vuy = 3.0163 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 50.79 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 6.19 kNm

Vcy Permissible = 156.02 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 135.82 kN

Lux = 3100 mm

Mntx = 75.71 kNm


Mnbx = 75.71 kNm

Vux1 = 48.84 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 50.7859 kN

Critical Analysis Load Combination : 6

Critical Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4:

LL) kN

Nu = 121.73 kN

Mux = 11.78 kNm

Vux = 5.2902 kN

Design Shear = max(Vux, Vux1, Vux2)

= 52.08 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 4.93 kNm

Vcx Permissible = 159.43 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm
Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C3

Level : 5m To 8m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 2700 mm

Clear Floor Height @ luy = 2700 mm


No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 91

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 43.07 kN

Muxt = -16.58 kNm

Muyt = 7.19 kNm

Vuxt = 6.59 kN

Vuyt = 11.61 kN

Pub = 53.46 kN

Muxb = 18.23 kNm

Muyb = -12.57 kNm

Vuxb = 6.59 kN

Vuyb = 11.61 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x
Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 No Beam 4000 x 250 x

400 - 30.551 2.328

Top 38.204 No Beam 4000 x 200 x

300 - 10.311 3.705

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x

400 No Beam 30.551 - 2.328

Top 38.204 4000 x 200 x


300 No Beam 10.311 - 3.705

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 1

Check For Stability Index

Along D

Q = 0.013

0.013< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 26.72

M1 = -16.58 kNm

M2 = 18.23 kNm

34 - 12 x (M1/M2) = 44.91

26.72 < 44.91, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K=1

r = 101.04 mm

Klux /r = 26.72
M1 = 7.19 kNm

M2 = -12.57 kNm

34 - 12 x (M1/M2) = 40.86

26.72 < 40.86, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) -16.58 - -16.58

Major Axis Mux (bottom) 18.23 - 18.23

Minor Axis Muy (top) 7.19 - 7.19

Minor Axis Muy (bottom) -12.57 - -12.57

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 53.46 kN

Mux = 18.23 kNm

Muy = -12.57 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 34.59 deg

MRes = 22.15 kNm

( φ ) MCap = 67.76 kNm

Capacity Ratio = MRes/ MCap


= 0.327 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 53.46 kN

Luy = 2700 mm

Mnty = 63.92 kNm

Mnby = 63.92 kNm

Vuy1 = 47.35 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 21.57 kN

Critical Analysis Load Combination : 8

Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 43.43 kN

Muy = 7.44 kNm

Vuy = 1.648 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 47.35 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 1.48 kNm

Vcy Permissible = 100.17 kN

Vuy < Vcy Permissible


Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 53.46 kN

Lux = 2700 mm

Mntx = 63.92 kNm

Mnbx = 63.92 kNm

Vux1 = 47.35 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 13.3063 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 44.35 kN

Mux = 11.98 kNm

Vux = 3.9105 kN

Design Shear = max(Vux, Vux1, Vux2)

= 47.35 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 5.89 kNm

Vcx Permissible = 91.58 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required


Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C4

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes


Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 4

Critical Analysis Load Combination : 9

Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 2:

SZ)

Critical Location = Bottom Joint

Put = 174.32 kN

Muxt = 2.82 kNm

Muyt = 4.69 kNm

Vuxt = -25.9 kN

Vuyt = -4.01 kN

Pub = 179.51 kN

Muxb = -3.2 kNm

Muyb = 43.53 kNm

Vuxb = -25.9 kN

Vuyb = -4.01 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta


Beam 1

(Length x

Width x Depth)

Beam 2

(Length x

Width x Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x

350 No Beam 16.373 - 6.71

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M


Bottom 76.408 No Beam No Beam - - 1

Top 76.408 3000 x 200 x

350

4000 x 200 x

350

21.831 16.373 2.853

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 101.04 mm

Kluy /r = 9.9

M1 = 2.82 kNm

M2 = -3.2 kNm

34 - 12 x (M1/M2) = 44.59

9.9 < 44.59, Column not slender along D


Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 9.9

M1 = 4.69 kNm

M2 = 43.53 kNm

34 - 12 x (M1/M2) = 32.71

9.9 < 32.71, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 2.82 - 2.82

Major Axis Mux (bottom) -3.2 - -3.2

Minor Axis Muy (top) 4.69 - 4.69

Minor Axis Muy (bottom) 43.53 - 43.53

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 179.51 kN

Mux = -3.2 kNm

Muy = 43.53 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16


Load Angle = Tan-1(Muy/Mux)

= 85.8 deg

MRes = 43.64 kNm

( φ ) MCap = 79.56 kNm

Capacity Ratio = MRes/ MCap

= 0.549 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 179.51 kN

Luy = 1150 mm

Mnty = 79.62 kNm

Mnby = 79.62 kNm

Vuy1 = 138.47 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 56.95 kN

Critical Analysis Load Combination : 8

Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 224.55 kN

Muy = 42 kNm

Vuy = -20.9703 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 138.47 kN

λ=1

φ = 0.65
deff = 302 mm

ρw = 0.007

mm = 11.18 kNm

Vcy Permissible = 89.25 kN

Vuy > Vcy Permissible

Link For Shear Design Along D are required

Vs = Vu - Vcy

= 49.22 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 29.01

Area of shear reinforcement

required, Asv-D = 590.59 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design for shear along B

Shear from Moment Capacity:

Pu = 179.51 kN

Lux = 1150 mm

Mntx = 79.62 kNm

Mnbx = 79.62 kNm

Vux1 = 138.47 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 77.4761 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:


LL) +(LOAD 2: SZ) kN

Nu = 179.51 kN

Mux = 43.53 kNm

Vux = -25.8956 kN

Design Shear = max(Vux, Vux1, Vux2)

= 138.47 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 18.89 kNm

Vcx Permissible = 88.83 kN

Vux > Vcx Permissible

Link For Shear Design Along B are required

Vs = Vu - Vcx

= 49.64 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 28.87

Area of shear reinforcement

required, Asv-B = 595.52 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm
Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C4

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm


No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 48

Critical Analysis Load Combination : 9

Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 2:

SZ)

Critical Location = Top Joint

Put = 130.46 kN

Muxt = 11.29 kNm

Muyt = -51.04 kNm

Vuxt = -27.5 kN

Vuyt = -5.15 kN

Pub = 142.59 kN

Muxb = -6.71 kNm

Muyb = 45.19 kNm

Vuxb = -27.5 kN

Vuyb = -5.15 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x
Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 No Beam 16.373 - 6.71

4000 x 200 x

350

Top 32.746 4000 x 250 x

400 No Beam 30.551 - 2.328

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 3000 x 200 x

350
4000 x 200 x

350 21.831 16.373 2.853

Top 32.746 3000 x 250 x

400

4000 x 250 x

400 40.734 30.551 0.996

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 30.68

M1 = -6.71 kNm

M2 = 11.29 kNm

34 - 12 x (M1/M2) = 41.13

30.68 < 41.13, Column not slender along D


Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 26.69

M1 = 45.19 kNm

M2 = -51.04 kNm

34 - 12 x (M1/M2) = 44.63

26.69 < 44.63, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 11.29 - 11.29

Major Axis Mux (bottom) -6.71 - -6.71

Minor Axis Muy (top) -51.04 - -51.04

Minor Axis Muy (bottom) 45.19 - 45.19

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 130.46 kN

Mux = 11.29 kNm

Muy = -51.04 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16


Load Angle = Tan-1(Muy/Mux)

= 77.52 deg

MRes = 52.27 kNm

( φ ) MCap = 74.42 kNm

Capacity Ratio = MRes/ MCap

= 0.702 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 130.46 kN

Luy = 3100 mm

Mnty = 75.04 kNm

Mnby = 75.04 kNm

Vuy1 = 48.41 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 54.97 kN

Critical Analysis Load Combination : 5

Critical Load Combination = [1] : 1.4 (LOAD 3: DL) kN

Nu = 168.77 kN

Muy = 5.87 kNm

Vuy = -4.635 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 75.91 kN

λ=1

φ = 0.65

deff = 302 mm
ρw = 0.007

mm = 17.29 kNm

Vcy Permissible = 166.18 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 130.46 kN

Lux = 3100 mm

Mntx = 75.04 kNm

Mnbx = 75.04 kNm

Vux1 = 48.41 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 75.908 kN

Critical Analysis Load Combination : 8

Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 173.76 kN

Mux = 1.02 kNm

Vux = -1.4855 kN

Design Shear = max(Vux, Vux1, Vux2)

= 54.97 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007
mm = 22.83 kNm

Vcx Permissible = 166.88 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C4

Level : 5m To 8m
Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 2700 mm

Clear Floor Height @ luy = 2700 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 92

Critical Analysis Load Combination : 9

Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 2:

SZ)

Critical Location = Bottom Joint

Put = 42.17 kN

Muxt = 6.53 kNm

Muyt = -22.71 kNm

Vuxt = -16.46 kN

Vuyt = -5.69 kN

Pub = 52.57 kN

Muxb = -10.55 kNm

Muyb = 26.67 kNm

Vuxb = -16.46 kN

Vuyb = -5.69 kN

Effective Length Calculation


Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x

400 No Beam 30.551 - 2.328

Top 38.204 4000 x 200 x

300 No Beam 10.311 - 3.705

= Non Sway

Sway Condition (as per Stability

Index)

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x
Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 3000 x 250 x

400

4000 x 250 x

400 40.734 30.551 0.996

Top 38.204 3000 x 200 x

300

4000 x 200 x

300 13.748 10.311 1.588

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.013

0.013< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)
Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 26.72

M1 = 6.53 kNm

M2 = -10.55 kNm

34 - 12 x (M1/M2) = 41.43

26.72 < 41.43, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 23.25

M1 = -22.71 kNm

M2 = 26.67 kNm

34 - 12 x (M1/M2) = 44.22

23.25 < 44.22, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 6.53 - 6.53

Major Axis Mux (bottom) -10.55 - -10.55

Minor Axis Muy (top) -22.71 - -22.71

Minor Axis Muy (bottom) 26.67 - 26.67

Where

A = Moments from analysis

B = Moment due to slenderness effect


C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 52.57 kN

Mux = -10.55 kNm

Muy = 26.67 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 68.42 deg

MRes = 28.68 kNm

( φ ) MCap = 66.29 kNm

Capacity Ratio = MRes/ MCap

= 0.433 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 52.57 kN

Luy = 2700 mm

Mnty = 63.81 kNm

Mnby = 63.81 kNm

Vuy1 = 47.27 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 21.22 kN
Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 49.92 kN

Muy = 4.52 kNm

Vuy = -0.1053 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 47.27 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 2.33 kNm

Vcy Permissible = 148.54 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 52.57 kN

Lux = 2700 mm

Mntx = 63.81 kNm

Mnbx = 63.81 kNm

Vux1 = 47.27 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 40.977 kN

Critical Analysis Load Combination : 8


Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 60.42 kN

Mux = 7.53 kNm

Vux = -3.2728 kN

Design Shear = max(Vux, Vux1, Vux2)

= 47.27 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 0.76 kNm

Vcx Permissible = 150.18 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm


B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C5

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 5

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Bottom Joint


Put = 273.7 kN

Muxt = 2.02 kNm

Muyt = -1.46 kNm

Vuxt = -1.9 kN

Vuyt = 29.82 kN

Pub = 278.89 kN

Muxb = 46.73 kNm

Muyb = 1.39 kNm

Vuxb = -1.9 kN

Vuyb = 29.82 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x

350

4000 x 200 x
350 16.373 16.373 3.331

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 3000 x 200 x

350

4000 x 200 x

350 21.831 16.373 2.853

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index


Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 101.04 mm

Kluy /r = 9.9

M1 = 2.02 kNm

M2 = 46.73 kNm

34 - 12 x (M1/M2) = 33.48

9.9 < 33.48, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 9.9

M1 = 1.39 kNm

M2 = -1.46 kNm

34 - 12 x (M1/M2) = 45.42

9.9 < 45.42, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final


ABC

Major Axis Mux (top) 2.02 - 2.02

Major Axis Mux (bottom) 46.73 - 46.73

Minor Axis Muy (top) -1.46 - -1.46

Minor Axis Muy (bottom) 1.39 - 1.39

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 278.89 kN

Mux = 46.73 kNm

Muy = 1.39 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 1.7 deg

MRes = 46.75 kNm

( φ ) MCap = 91.05 kNm

Capacity Ratio = MRes/ MCap

= 0.514 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 278.89 kN

Luy = 1150 mm
Mnty = 91.02 kNm

Mnby = 91.02 kNm

Vuy1 = 158.29 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 80.07 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 278.89 kN

Muy = 46.73 kNm

Vuy = 29.8174 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 158.29 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 8.46 kNm

Vcy Permissible = 89.57 kN

Vuy > Vcy Permissible

Link For Shear Design Along D are required

Vs = Vu - Vcy

= 68.72 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 29.11

Area of shear reinforcement


required, Asv-D = 824.47 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design for shear along B

Shear from Moment Capacity:

Pu = 278.89 kN

Lux = 1150 mm

Mntx = 91.02 kNm

Mnbx = 91.02 kNm

Vux1 = 158.29 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 72.51 kN

Critical Analysis Load Combination : 9

Critical Load Combination = kN

[5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ)

Nu = 264.01 kN

Mux = 41.03 kNm

Vux = -25.1289 kN

Design Shear = max(Vux, Vux1, Vux2)

= 158.29 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007
mm = 4.79 kNm

Vcx Permissible = 91.25 kN

Vux > Vcx Permissible

Link For Shear Design Along B are required

Vs = Vu - Vcx

= 67.04 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 29.66

Area of shear reinforcement

required, Asv-B = 804.33 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm
Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C5

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 49

Critical Analysis Load Combination : 9

Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 2:

SZ)

Critical Location = Top Joint

Put = 217.98 kN

Muxt = 4.66 kNm


Muyt = -50.93 kNm

Vuxt = -27.17 kN

Vuyt = -1.57 kN

Pub = 230.11 kN

Muxb = -0.84 kNm

Muyb = 44.15 kNm

Vuxb = -27.17 kN

Vuyb = -1.57 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 4000 x 200 x

350

4000 x 200 x

350 16.373 16.373 3.331

Top 32.746 4000 x 250 x

400
4000 x 250 x

400 30.551 30.551 1.16

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 3000 x 200 x

350

4000 x 200 x

350 21.831 16.373 2.853

Top 32.746 3000 x 250 x

400

4000 x 250 x

400 40.734 30.551 0.996

Sway Condition (as per Stability


Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 30.68

M1 = -0.84 kNm

M2 = 4.66 kNm

34 - 12 x (M1/M2) = 36.17

30.68 < 36.17, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 26.69

M1 = 44.15 kNm

M2 = -50.93 kNm
34 - 12 x (M1/M2) = 44.4

26.69 < 44.4, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 4.66 - 4.66

Major Axis Mux (bottom) -0.84 - -0.84

Minor Axis Muy (top) -50.93 - -50.93

Minor Axis Muy (bottom) 44.15 - 44.15

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 217.98 kN

Mux = 4.66 kNm

Muy = -50.93 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 84.77 deg

MRes = 51.14 kNm

( φ ) MCap = 84.11 kNm

Capacity Ratio = MRes/ MCap

= 0.608 < 1

Design Of Shear
Design for shear along D

Shear from Moment Capacity:

Pu = 217.98 kN

Luy = 3100 mm

Mnty = 85.42 kNm

Mnby = 85.42 kNm

Vuy1 = 55.11 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 69.78 kN

Critical Analysis Load Combination : 5

Critical Load Combination = [1] : 1.4 (LOAD 3: DL) kN

Nu = 254.71 kN

Muy = 1.33 kNm

Vuy = -0.2498 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 72.87 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 33.62 kNm

Vcy Permissible = 177.85 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:


Pu = 217.98 kN

Lux = 3100 mm

Mntx = 85.42 kNm

Mnbx = 85.42 kNm

Vux1 = 55.11 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 72.8708 kN

Critical Analysis Load Combination : 5

Critical Load Combination = [1] : 1.4 (LOAD 3: DL) kN

Nu = 254.71 kN

Mux = 5.43 kNm

Vux = -4.1649 kN

Design Shear = max(Vux, Vux1, Vux2)

= 69.78 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 29.53 kNm

Vcx Permissible = 177.85 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm
> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C5

Level : 5m To 8m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm
Clear Floor Height @ lux = 2700 mm

Clear Floor Height @ luy = 2700 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 93

Critical Analysis Load Combination : 9

Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 2:

SZ)

Critical Location = Bottom Joint

Put = 52.1 kN

Muxt = 0.35 kNm

Muyt = -20.85 kNm

Vuxt = -15.73 kN

Vuyt = -1.17 kN

Pub = 62.5 kN

Muxb = -3.16 kNm

Muyb = 26.32 kNm

Vuxb = -15.73 kN

Vuyb = -1.17 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)
Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x

400

4000 x 250 x

400 30.551 30.551 1.16

Top 38.204 4000 x 200 x

300

4000 x 200 x

300 10.311 10.311 1.853

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x
Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 3000 x 250 x

400

4000 x 250 x

400 40.734 30.551 0.996

Top 38.204 3000 x 200 x

300

4000 x 200 x

300 13.748 10.311 1.588

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.013

0.013< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm
Kluy /r = 26.72

M1 = 0.35 kNm

M2 = -3.16 kNm

34 - 12 x (M1/M2) = 35.33

26.72 < 35.33, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 23.25

M1 = -20.85 kNm

M2 = 26.32 kNm

34 - 12 x (M1/M2) = 43.51

23.25 < 43.51, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 0.35 - 0.35

Major Axis Mux (bottom) -3.16 - -3.16

Minor Axis Muy (top) -20.85 - -20.85

Minor Axis Muy (bottom) 26.32 - 26.32

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 62.5 kN

Mux = -3.16 kNm


Muy = 26.32 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 83.16 deg

MRes = 26.5 kNm

( φ ) MCap = 65.66 kNm

Capacity Ratio = MRes/ MCap

= 0.404 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 62.5 kN

Luy = 2700 mm

Mnty = 65.05 kNm

Mnby = 65.05 kNm

Vuy1 = 48.18 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 40.93 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 62.5 kN

Muy = 3.16 kNm


Vuy = -1.1682 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 48.18 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 5.42 kNm

Vcy Permissible = 150.5 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 62.5 kN

Lux = 2700 mm

Mntx = 65.05 kNm

Mnbx = 65.05 kNm

Vux1 = 48.18 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 37.8005 kN

Critical Analysis Load Combination : 8

Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 65.21 kN

Mux = 10.33 kNm

Vux = -4.5916 kN
Design Shear = max(Vux, Vux1, Vux2)

= 48.18 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 1.38 kNm

Vcx Permissible = 94.12 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C6

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 6

Critical Analysis Load Combination : 8

Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 191.33 kN

Muxt = -12.7 kNm

Muyt = -1.85 kNm

Vuxt = -3.05 kN

Vuyt = -18.88 kN
Pub = 196.53 kN

Muxb = -41.01 kNm

Muyb = 2.73 kNm

Vuxb = -3.05 kN

Vuyb = -18.88 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x Depth)

Beam 2

(Length x

Width x Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 No Beam 4000 x 200 x

350 - 16.373 6.71

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta


Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 3000 x 200 x

350

4000 x 200 x

350 21.831 16.373 2.853

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check
Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 101.04 mm

Kluy /r = 9.9

M1 = -12.7 kNm

M2 = -41.01 kNm

34 - 12 x (M1/M2) = 30.28

9.9 < 30.28, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 9.9

M1 = -1.85 kNm

M2 = 2.73 kNm

34 - 12 x (M1/M2) = 42.11

9.9 < 42.11, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) -12.7 - -12.7

Major Axis Mux (bottom) -41.01 - -41.01

Minor Axis Muy (top) -1.85 - -1.85

Minor Axis Muy (bottom) 2.73 - 2.73

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))


Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 196.53 kN

Mux = -41.01 kNm

Muy = 2.73 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 3.81 deg

MRes = 41.1 kNm

( φ ) MCap = 81.56 kNm

Capacity Ratio = MRes/ MCap

= 0.504 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 196.53 kN

Luy = 1150 mm

Mnty = 81.57 kNm

Mnby = 81.57 kNm

Vuy1 = 141.87 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 53.65 kN

Critical Analysis Load Combination : 8


Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 196.53 kN

Muy = 41.01 kNm

Vuy = -18.8799 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 141.87 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 14.04 kNm

Vcy Permissible = 89.82 kN

Vuy > Vcy Permissible

Link For Shear Design Along D are required

Vs = Vu - Vcy

= 52.05 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 29.19

Area of shear reinforcement

required, Asv-D = 624.36 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design for shear along B

Shear from Moment Capacity:

Pu = 196.53 kN

Lux = 1150 mm

Mntx = 81.57 kNm


Mnbx = 81.57 kNm

Vux1 = 141.87 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 66.5918 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 209 kN

Mux = 38.1 kNm

Vux = -23.4702 kN

Design Shear = max(Vux, Vux1, Vux2)

= 141.87 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 9.42 kNm

Vcx Permissible = 90.77 kN

Vux > Vcx Permissible

Link For Shear Design Along B are required

Vs = Vu - Vcx

= 51.1 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 29.5

Area of shear reinforcement

required, Asv-B = 613.06 mm^2/m


Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C6

Level : 1.5m To 5m

Design Code = ACI 318M - 2011


Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 50

Critical Analysis Load Combination : 9

Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 2:

SZ)

Critical Location = Top Joint

Put = 169.41 kN

Muxt = -8.82 kNm

Muyt = -40.53 kNm

Vuxt = -22.37 kN

Vuyt = 3.58 kN

Pub = 181.54 kN

Muxb = 3.7 kNm

Muyb = 37.73 kNm

Vuxb = -22.37 kN

Vuyb = 3.58 kN

Effective Length Calculation

Calculation Along Major Axis Of Column


Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 No Beam 4000 x 200 x

350 - 16.373 6.71

Top 32.746 No Beam 4000 x 250 x

400 - 30.551 2.328

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)
Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 3000 x 200 x

350

4000 x 200 x

350 21.831 16.373 2.853

Top 32.746 3000 x 250 x

400

4000 x 250 x

400 40.734 30.551 0.996

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D


Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 30.68

M1 = 3.7 kNm

M2 = -8.82 kNm

34 - 12 x (M1/M2) = 39.04

30.68 < 39.04, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 26.69

M1 = 37.73 kNm

M2 = -40.53 kNm

34 - 12 x (M1/M2) = 45.17

26.69 < 45.17, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) -8.82 - -8.82

Major Axis Mux (bottom) 3.7 - 3.7

Minor Axis Muy (top) -40.53 - -40.53

Minor Axis Muy (bottom) 37.73 - 37.73

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending

Pu = 169.41 kN

Mux = -8.82 kNm

Muy = -40.53 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 77.72 deg

MRes = 41.48 kNm

( φ ) MCap = 78.69 kNm

Capacity Ratio = MRes/ MCap

= 0.527 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 169.41 kN

Luy = 3100 mm

Mnty = 79.85 kNm

Mnby = 79.85 kNm

Vuy1 = 51.52 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 57.75 kN

Critical Analysis Load Combination : 5

Critical Load Combination = [1] : 1.4 (LOAD 3: DL) kN


Nu = 206.82 kN

Muy = 4.8 kNm

Vuy = 4.016 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 65.42 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 23.59 kNm

Vcy Permissible = 171.44 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 169.41 kN

Lux = 3100 mm

Mntx = 79.85 kNm

Mnbx = 79.85 kNm

Vux1 = 51.52 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 65.4207 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 212.49 kN
Mux = 0.54 kNm

Vux = 0.1549 kN

Design Shear = max(Vux, Vux1, Vux2)

= 57.75 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 28.62 kNm

Vcx Permissible = 172.21 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm


Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C6

Level : 5m To 8m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 2700 mm

Clear Floor Height @ luy = 2700 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 94

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 50.69 kN

Muxt = -17.67 kNm

Muyt = -0.96 kNm


Vuxt = -0.85 kN

Vuyt = 13.11 kN

Pub = 61.09 kN

Muxb = 21.65 kNm

Muyb = 1.58 kNm

Vuxb = -0.85 kN

Vuyb = 13.11 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 No Beam 4000 x 250 x

400 - 30.551 2.328

Top 38.204 No Beam 4000 x 200 x

300 - 10.311 3.705

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major


Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 3000 x 250 x

400

4000 x 250 x

400 40.734 30.551 0.996

Top 38.204 3000 x 200 x

300

4000 x 200 x

300 13.748 10.311 1.588

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D
Q = 0.013

0.013< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 26.72

M1 = -17.67 kNm

M2 = 21.65 kNm

34 - 12 x (M1/M2) = 43.8

26.72 < 43.8, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 23.25

M1 = -0.96 kNm

M2 = 1.58 kNm

34 - 12 x (M1/M2) = 41.27

23.25 < 41.27, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC
Major Axis Mux (top) -17.67 - -17.67

Major Axis Mux (bottom) 21.65 - 21.65

Minor Axis Muy (top) -0.96 - -0.96

Minor Axis Muy (bottom) 1.58 - 1.58

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 61.09 kN

Mux = 21.65 kNm

Muy = 1.58 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 4.19 deg

MRes = 21.71 kNm

( φ ) MCap = 65.11 kNm

Capacity Ratio = MRes/ MCap

= 0.333 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 61.09 kN

Luy = 2700 mm

Mnty = 64.87 kNm


Mnby = 64.87 kNm

Vuy1 = 48.05 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 25.27 kN

Critical Analysis Load Combination : 8

Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 40.21 kN

Muy = 2.85 kNm

Vuy = 0.9474 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 48.05 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 2.67 kNm

Vcy Permissible = 147 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 61.09 kN

Lux = 2700 mm

Mntx = 64.87 kNm

Mnbx = 64.87 kNm


Vux1 = 48.05 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 31.0057 kN

Critical Analysis Load Combination : 8

Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 40.21 kN

Mux = 2.94 kNm

Vux = -1.9803 kN

Design Shear = max(Vux, Vux1, Vux2)

= 48.05 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 2.58 kNm

Vcx Permissible = 147 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links


Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C7

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1
No Of Columns In Group = 1

Load Data

Analysis Reference No. = 7

Critical Analysis Load Combination : 10

Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 2:

SZ)

Critical Location = Bottom Joint

Put = 173.04 kN

Muxt = 3.38 kNm

Muyt = -4.27 kNm

Vuxt = 26.19 kN

Vuyt = -2.99 kN

Pub = 178.23 kN

Muxb = -1.1 kNm

Muyb = -43.54 kNm

Vuxb = 26.19 kN

Vuyb = -2.99 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x Depth)

Beam 2

(Length x

Width x Depth)

Beam 1 Beam 2
N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x

350 No Beam 16.373 - 6.71

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x

350

3000 x 200 x

350 16.373 21.831 2.853

Sway Condition (as per Stability

Index) = Non Sway


Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 101.04 mm

Kluy /r = 9.9

M1 = -1.1 kNm

M2 = 3.38 kNm

34 - 12 x (M1/M2) = 37.89

9.9 < 37.89, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 9.9

M1 = -4.27 kNm

M2 = -43.54 kNm

34 - 12 x (M1/M2) = 32.82
9.9 < 32.82, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 3.38 - 3.38

Major Axis Mux (bottom) -1.1 - -1.1

Minor Axis Muy (top) -4.27 - -4.27

Minor Axis Muy (bottom) -43.54 - -43.54

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 178.23 kN

Mux = -1.1 kNm

Muy = -43.54 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 88.56 deg

MRes = 43.56 kNm

( φ ) MCap = 79.44 kNm

Capacity Ratio = MRes/ MCap

= 0.548 < 1

Design Of Shear

Design for shear along D


Shear from Moment Capacity:

Pu = 178.23 kN

Luy = 1150 mm

Mnty = 79.47 kNm

Mnby = 79.47 kNm

Vuy1 = 138.22 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 58.93 kN

Critical Analysis Load Combination : 8

Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 223.79 kN

Muy = 43.63 kNm

Vuy = -21.6039 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 138.22 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 12.91 kNm

Vcy Permissible = 88.79 kN

Vuy > Vcy Permissible

Link For Shear Design Along D are required

Vs = Vu - Vcy

= 49.43 kN
Vcx Permissible = 0.5 x Vcx x 0.65

= 28.86

Area of shear reinforcement

required, Asv-D = 593.02 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design for shear along B

Shear from Moment Capacity:

Pu = 178.23 kN

Lux = 1150 mm

Mntx = 79.47 kNm

Mnbx = 79.47 kNm

Vux1 = 138.22 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 77.8211 kN

Critical Analysis Load Combination : 10

Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 2: SZ) kN

Nu = 178.23 kN

Mux = 43.54 kNm

Vux = 26.1902 kN

Design Shear = max(Vux, Vux1, Vux2)

= 138.22 kN

λ=1

φ = 0.65
deff = 302 mm

ρw = 0.007

mm = 19.08 kNm

Vcx Permissible = 88.81 kN

Vux > Vcx Permissible

Link For Shear Design Along B are required

Vs = Vu - Vcx

= 49.41 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 28.86

Area of shear reinforcement

required, Asv-B = 592.75 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm


B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C7

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 51

Critical Analysis Load Combination : 10

Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 2:

SZ)

Critical Location = Top Joint


Put = 129.72 kN

Muxt = 10 kNm

Muyt = 50.62 kNm

Vuxt = 27.14 kN

Vuyt = -4.31 kN

Pub = 141.85 kN

Muxb = -5.1 kNm

Muyb = -44.34 kNm

Vuxb = 27.14 kN

Vuyb = -4.31 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 4000 x 200 x

350 No Beam 16.373 - 6.71

Top 32.746 4000 x 250 x

400 No Beam 30.551 - 2.328


Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 4000 x 200 x

350

3000 x 200 x

350 16.373 21.831 2.853

Top 32.746 4000 x 250 x

400

3000 x 250 x

400 30.551 40.734 0.996

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor


axis = 0.87

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 30.68

M1 = -5.1 kNm

M2 = 10 kNm

34 - 12 x (M1/M2) = 40.12

30.68 < 40.12, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 26.69

M1 = -44.34 kNm

M2 = 50.62 kNm

34 - 12 x (M1/M2) = 44.51

26.69 < 44.51, Column not slender along B


Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 10 - 10

Major Axis Mux (bottom) -5.1 - -5.1

Minor Axis Muy (top) 50.62 - 50.62

Minor Axis Muy (bottom) -44.34 - -44.34

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 129.72 kN

Mux = 10 kNm

Muy = 50.62 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 78.83 deg

MRes = 51.6 kNm

( φ ) MCap = 74.26 kNm

Capacity Ratio = MRes/ MCap

= 0.695 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:


Pu = 129.72 kN

Luy = 3100 mm

Mnty = 74.94 kNm

Mnby = 74.94 kNm

Vuy1 = 48.35 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 57.27 kN

Critical Analysis Load Combination : 5

Critical Load Combination = [1] : 1.4 (LOAD 3: DL) kN

Nu = 169.1 kN

Muy = 5.62 kNm

Vuy = -4.5492 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 75.47 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 17.59 kNm

Vcy Permissible = 166.22 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 129.72 kN

Lux = 3100 mm
Mntx = 74.94 kNm

Mnbx = 74.94 kNm

Vux1 = 48.35 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 75.4716 kN

Critical Analysis Load Combination : 8

Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 173.57 kN

Mux = 6.34 kNm

Vux = 4.7862 kN

Design Shear = max(Vux, Vux1, Vux2)

= 57.27 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 17.49 kNm

Vcx Permissible = 166.85 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4


= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C7

Level : 5m To 8m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 2700 mm


Clear Floor Height @ luy = 2700 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 95

Critical Analysis Load Combination : 10

Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 2:

SZ)

Critical Location = Bottom Joint

Put = 42.05 kN

Muxt = 5.9 kNm

Muyt = 21.31 kNm

Vuxt = 15.29 kN

Vuyt = -5.34 kN

Pub = 52.44 kN

Muxb = -10.12 kNm

Muyb = -24.55 kNm

Vuxb = 15.29 kN

Vuyb = -5.34 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2
(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x

400 No Beam 30.551 - 2.328

Top 38.204 4000 x 200 x

300 No Beam 10.311 - 3.705

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x

400
3000 x 250 x

400 30.551 40.734 0.996

Top 38.204 4000 x 200 x

300

3000 x 200 x

300 10.311 13.748 1.588

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.013

0.013< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 26.72

M1 = 5.9 kNm

M2 = -10.12 kNm

34 - 12 x (M1/M2) = 41

26.72 < 41, Column not slender along D


Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 23.25

M1 = 21.31 kNm

M2 = -24.55 kNm

34 - 12 x (M1/M2) = 44.42

23.25 < 44.42, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 5.9 - 5.9

Major Axis Mux (bottom) -10.12 - -10.12

Minor Axis Muy (top) 21.31 - 21.31

Minor Axis Muy (bottom) -24.55 - -24.55

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 52.44 kN

Mux = -10.12 kNm

Muy = -24.55 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16


Load Angle = Tan-1(Muy/Mux)

= 67.6 deg

MRes = 26.55 kNm

( φ ) MCap = 66.34 kNm

Capacity Ratio = MRes/ MCap

= 0.4 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 52.44 kN

Luy = 2700 mm

Mnty = 63.79 kNm

Mnby = 63.79 kNm

Vuy1 = 47.26 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 21.68 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 50.25 kN

Muy = 4.16 kNm

Vuy = 0.192 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 47.26 kN

λ=1

φ = 0.65
deff = 302 mm

ρw = 0.007

mm = 2.73 kNm

Vcy Permissible = 148.59 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 52.44 kN

Lux = 2700 mm

Mntx = 63.79 kNm

Mnbx = 63.79 kNm

Vux1 = 47.26 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 39.7546 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 50.25 kN

Mux = 5.5 kNm

Vux = 2.1286 kN

Design Shear = max(Vux, Vux1, Vux2)

= 47.26 kN

λ=1

φ = 0.65

deff = 302 mm
ρw = 0.007

mm = 1.4 kNm

Vcx Permissible = 148.59 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C8
Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 8

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 273.72 kN

Muxt = 6.52 kNm

Muyt = -1.94 kNm

Vuxt = -2.37 kN

Vuyt = 26.81 kN

Pub = 278.92 kN

Muxb = 46.72 kNm

Muyb = 1.61 kNm

Vuxb = -2.37 kN

Vuyb = 26.81 kN
Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x

350

4000 x 200 x

350 16.373 16.373 3.331

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1
(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x

350

3000 x 200 x

350 16.373 21.831 2.853

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D


Slenderness Check along D

K = 0.87

r = 101.04 mm

Kluy /r = 9.9

M1 = 6.52 kNm

M2 = 46.72 kNm

34 - 12 x (M1/M2) = 32.33

9.9 < 32.33, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 9.9

M1 = 1.61 kNm

M2 = -1.94 kNm

34 - 12 x (M1/M2) = 43.96

9.9 < 43.96, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 6.52 - 6.52

Major Axis Mux (bottom) 46.72 - 46.72

Minor Axis Muy (top) -1.94 - -1.94

Minor Axis Muy (bottom) 1.61 - 1.61

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending

Pu = 278.92 kN

Mux = 46.72 kNm

Muy = 1.61 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 1.98 deg

MRes = 46.75 kNm

( φ ) MCap = 91.06 kNm

Capacity Ratio = MRes/ MCap

= 0.513 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 278.92 kN

Luy = 1150 mm

Mnty = 91.02 kNm

Mnby = 91.02 kNm

Vuy1 = 158.29 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 78.92 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:


LL) +(LOAD 1: SX) kN

Nu = 278.92 kN

Muy = 46.72 kNm

Vuy = 26.8082 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 158.29 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 8.44 kNm

Vcy Permissible = 89.57 kN

Vuy > Vcy Permissible

Link For Shear Design Along D are required

Vs = Vu - Vcy

= 68.72 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 29.11

Area of shear reinforcement

required, Asv-D = 824.47 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design for shear along B

Shear from Moment Capacity:

Pu = 278.92 kN

Lux = 1150 mm

Mntx = 91.02 kNm

Mnbx = 91.02 kNm


Vux1 = 158.29 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 72.6114 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 294.14 kN

Mux = 41.19 kNm

Vux = -25.4691 kN

Design Shear = max(Vux, Vux1, Vux2)

= 158.29 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 0.82 kNm

Vcx Permissible = 91.19 kN

Vux > Vcx Permissible

Link For Shear Design Along B are required

Vs = Vu - Vcx

= 67.1 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 29.64

Area of shear reinforcement

required, Asv-B = 805.02 mm^2/m

Diameter of column master links = 10


Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C8

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm


Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 52

Critical Analysis Load Combination : 10

Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 2:

SZ)

Critical Location = Top Joint

Put = 214.26 kN

Muxt = 2.64 kNm

Muyt = 49.55 kNm

Vuxt = 26.18 kN

Vuyt = -0.8 kN

Pub = 226.39 kN

Muxb = -0.17 kNm

Muyb = -42.07 kNm

Vuxb = 26.18 kN

Vuyb = -0.8 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column
Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 4000 x 200 x

350

4000 x 200 x

350 16.373 16.373 3.331

Top 32.746 4000 x 250 x

400

4000 x 250 x

400 30.551 30.551 1.16

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1
(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 4000 x 200 x

350

3000 x 200 x

350 16.373 21.831 2.853

Top 32.746 4000 x 250 x

400

3000 x 250 x

400

30.551 40.734 0.996

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021
0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 30.68

M1 = -0.17 kNm

M2 = 2.64 kNm

34 - 12 x (M1/M2) = 34.75

30.68 < 34.75, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 26.69

M1 = -42.07 kNm

M2 = 49.55 kNm

34 - 12 x (M1/M2) = 44.19

26.69 < 44.19, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 2.64 - 2.64

Major Axis Mux (bottom) -0.17 - -0.17

Minor Axis Muy (top) 49.55 - 49.55

Minor Axis Muy (bottom) -42.07 - -42.07

Where
A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 214.26 kN

Mux = 2.64 kNm

Muy = 49.55 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 86.96 deg

MRes = 49.62 kNm

( φ ) MCap = 83.68 kNm

Capacity Ratio = MRes/ MCap

= 0.593 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 214.26 kN

Luy = 3100 mm

Mnty = 85 kNm

Mnby = 85 kNm

Vuy1 = 54.84 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3


(LOAD 1: SX)

Vuy2 = 72.4 kN

Critical Analysis Load Combination : 5

Critical Load Combination = [1] : 1.4 (LOAD 3: DL) kN

Nu = 253.17 kN

Muy = 0.05 kNm

Vuy = -0.6523 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 71.13 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 34.69 kNm

Vcy Permissible = 177.65 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 214.26 kN

Lux = 3100 mm

Mntx = 85 kNm

Mnbx = 85 kNm

Vux1 = 54.84 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 71.131 kN
Critical Analysis Load Combination : 5

Critical Load Combination = [1] : 1.4 (LOAD 3: DL) kN

Nu = 253.17 kN

Mux = 3.62 kNm

Vux = 3.4853 kN

Design Shear = max(Vux, Vux1, Vux2)

= 72.4 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 31.13 kNm

Vcx Permissible = 177.65 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm


B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C8

Level : 5m To 8m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 2700 mm

Clear Floor Height @ luy = 2700 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 96

Critical Analysis Load Combination : 10

Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 2:

SZ)

Critical Location = Bottom Joint


Put = 52.48 kN

Muxt = -0.65 kNm

Muyt = 20.11 kNm

Vuxt = 14.93 kN

Vuyt = -0.17 kN

Pub = 62.88 kN

Muxb = -1.16 kNm

Muyb = -24.66 kNm

Vuxb = 14.93 kN

Vuyb = -0.17 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x

400

4000 x 250 x

400 30.551 30.551 1.16


Top 38.204 4000 x 200 x

300

4000 x 200 x

300 10.311 10.311 1.853

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x

400

3000 x 250 x

400 30.551 40.734 0.996

Top 38.204 4000 x 200 x

300

3000 x 200 x
300 10.311 13.748 1.588

Sway Condition (as per Stability

Index) = Non Sway

= 0.87

Effective Length Factor along Minor

axis

Check For Stability Index

Along D

Q = 0.013

0.013< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 26.72

M1 = -0.65 kNm

M2 = -1.16 kNm

34 - 12 x (M1/M2) = 27.24

26.72 < 27.24, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm
Klux /r = 23.25

M1 = 20.11 kNm

M2 = -24.66 kNm

34 - 12 x (M1/M2) = 43.79

23.25 < 43.79, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) -0.65 - -0.65

Major Axis Mux (bottom) -1.16 - -1.16

Minor Axis Muy (top) 20.11 - 20.11

Minor Axis Muy (bottom) -24.66 - -24.66

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 62.88 kN

Mux = -1.16 kNm

Muy = -24.66 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 87.31 deg

MRes = 24.69 kNm

( φ ) MCap = 65.22 kNm


Capacity Ratio = MRes/ MCap

= 0.379 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 62.88 kN

Luy = 2700 mm

Mnty = 65.1 kNm

Mnby = 65.1 kNm

Vuy1 = 48.22 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 41.78 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 65.4 kN

Muy = 19.68 kNm

Vuy = 13.8056 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 48.22 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 10.7 kNm

Vcy Permissible = 86.23 kN


Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 62.88 kN

Lux = 2700 mm

Mntx = 65.1 kNm

Mnbx = 65.1 kNm

Vux1 = 48.22 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 36.2966 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 65.4 kN

Mux = 9.55 kNm

Vux = 4.1592 kN

Design Shear = max(Vux, Vux1, Vux2)

= 48.22 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 0.57 kNm

Vcx Permissible = 95.49 kN

Vux < Vcx Permissible


Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C9

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm


Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 9

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 289.74 kN

Muxt = 3.88 kNm

Muyt = 0.75 kNm

Vuxt = 2.08 kN

Vuyt = 29.37 kN

Pub = 294.94 kN

Muxb = 47.93 kNm

Muyb = -2.38 kNm

Vuxb = 2.08 kN

Vuyb = 29.37 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness
Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x

350

4000 x 200 x

350 16.373 16.373 3.331

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2
(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x

350

3000 x 200 x

350 16.373 21.831 2.853

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 101.04 mm

Kluy /r = 9.9
M1 = 3.88 kNm

M2 = 47.93 kNm

34 - 12 x (M1/M2) = 33.03

9.9 < 33.03, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 9.9

M1 = 0.75 kNm

M2 = -2.38 kNm

34 - 12 x (M1/M2) = 37.78

9.9 < 37.78, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 3.88 - 3.88

Major Axis Mux (bottom) 47.93 - 47.93

Minor Axis Muy (top) 0.75 - 0.75

Minor Axis Muy (bottom) -2.38 - -2.38

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 294.94 kN

Mux = 47.93 kNm

Muy = -2.38 kNm


Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 2.84 deg

MRes = 47.99 kNm

( φ ) MCap = 92.59 kNm

Capacity Ratio = MRes/ MCap

= 0.518 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 294.94 kN

Luy = 1150 mm

Mnty = 92.86 kNm

Mnby = 92.86 kNm

Vuy1 = 161.49 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 80.45 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 294.94 kN

Muy = 47.93 kNm

Vuy = 29.374 kN
Design Shear = max(Vuy, Vuy1, Vuy2)

= 161.49 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 7.45 kNm

Vcy Permissible = 89.5 kN

Vuy > Vcy Permissible

Link For Shear Design Along D are required

Vs = Vu - Vcy

= 71.99 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 29.09

Area of shear reinforcement

required, Asv-D = 863.63 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design for shear along B

Shear from Moment Capacity:

Pu = 294.94 kN

Lux = 1150 mm

Mntx = 92.86 kNm

Mnbx = 92.86 kNm

Vux1 = 161.49 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3


(LOAD 2: SZ)

Vux2 = 65.7115 kN

Critical Analysis Load Combination : 10

Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 2: SZ) kN

Nu = 270.08 kN

Mux = 37.83 kNm

Vux = 22.6879 kN

Design Shear = max(Vux, Vux1, Vux2)

= 161.49 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 0.77 kNm

Vcx Permissible = 92.71 kN

Vux > Vcx Permissible

Link For Shear Design Along B are required

Vs = Vu - Vcx

= 68.78 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 30.13

Area of shear reinforcement

required, Asv-B = 825.19 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design Of Links

Links in the zone where special confining links are not required
Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C9

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm
Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 53

Critical Analysis Load Combination : 10

Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 2:

SZ)

Critical Location = Top Joint

Put = 217.65 kN

Muxt = 0.14 kNm

Muyt = 44.22 kNm

Vuxt = 23.97 kN

Vuyt = 0.58 kN

Pub = 229.77 kN

Muxb = 2.16 kNm

Muyb = -39.66 kNm

Vuxb = 23.97 kN

Vuyb = 0.58 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x
Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 4000 x 200 x

350

4000 x 200 x

350 16.373 16.373 3.331

Top 32.746 4000 x 250 x

400

4000 x 250 x

400 30.551 30.551 1.16

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2
(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 4000 x 200 x

350

3000 x 200 x

350 16.373 21.831 2.853

Top 32.746 4000 x 250 x

400

3000 x 250 x

400 30.551 40.734 0.996

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D


K=1

r = 101.04 mm

Kluy /r = 30.68

M1 = 0.14 kNm

M2 = 2.16 kNm

34 - 12 x (M1/M2) = 33.25

30.68 < 33.25, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 26.69

M1 = -39.66 kNm

M2 = 44.22 kNm

34 - 12 x (M1/M2) = 44.76

26.69 < 44.76, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 0.14 - 0.14

Major Axis Mux (bottom) 2.16 - 2.16

Minor Axis Muy (top) 44.22 - 44.22

Minor Axis Muy (bottom) -39.66 - -39.66

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending


Pu = 217.65 kN

Mux = 0.14 kNm

Muy = 44.22 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 89.82 deg

MRes = 44.22 kNm

( φ ) MCap = 84 kNm

Capacity Ratio = MRes/ MCap

= 0.526 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 217.65 kN

Luy = 3100 mm

Mnty = 85.38 kNm

Mnby = 85.38 kNm

Vuy1 = 55.09 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 71.13 kN

Critical Analysis Load Combination : 6

Critical Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4:

LL) kN
Nu = 257.57 kN

Muy = 2.19 kNm

Vuy = 0.5488 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 66.65 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 33.16 kNm

Vcy Permissible = 178.22 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 217.65 kN

Lux = 3100 mm

Mntx = 85.38 kNm

Mnbx = 85.38 kNm

Vux1 = 55.09 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 66.6483 kN

Critical Analysis Load Combination : 6

Critical Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4:

LL) kN

Nu = 257.57 kN
Mux = 3.77 kNm

Vux = 2.9589 kN

Design Shear = max(Vux, Vux1, Vux2)

= 71.13 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 31.58 kNm

Vcx Permissible = 178.22 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm


Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C9

Level : 5m To 8m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 2700 mm

Clear Floor Height @ luy = 2700 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 97

Critical Analysis Load Combination : 10

Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 2:

SZ)

Critical Location = Bottom Joint

Put = 42.21 kN

Muxt = -6.14 kNm

Muyt = 18.48 kNm


Vuxt = 12.72 kN

Vuyt = 3.08 kN

Pub = 52.6 kN

Muxb = 3.11 kNm

Muyb = -19.68 kNm

Vuxb = 12.72 kN

Vuyb = 3.08 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x

400

4000 x 250 x

400 30.551 30.551 1.16

Top 38.204 No Beam 4000 x 200 x

300 - 10.311 3.705

Sway Condition (as per Stability


Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x

400

3000 x 250 x

400 30.551 40.734 0.996

Top 38.204 4000 x 200 x

300

3000 x 200 x

300 10.311 13.748 1.588

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87
Check For Stability Index

Along D

Q = 0.013

0.013< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 26.72

M1 = 3.11 kNm

M2 = -6.14 kNm

34 - 12 x (M1/M2) = 40.07

26.72 < 40.07, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 23.25

M1 = 18.48 kNm

M2 = -19.68 kNm

34 - 12 x (M1/M2) = 45.27

23.25 < 45.27, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) -6.14 - -6.14

Major Axis Mux (bottom) 3.11 - 3.11

Minor Axis Muy (top) 18.48 - 18.48

Minor Axis Muy (bottom) -19.68 - -19.68

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 52.6 kN

Mux = 3.11 kNm

Muy = -19.68 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 81.03 deg

MRes = 19.93 kNm

( φ ) MCap = 64.69 kNm

Capacity Ratio = MRes/ MCap

= 0.308 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 52.6 kN
Luy = 2700 mm

Mnty = 62.52 kNm

Mnby = 62.52 kNm

Vuy1 = 46.31 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 30.35 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 57.77 kN

Muy = 3.75 kNm

Vuy = 3.3327 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 46.31 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 4.18 kNm

Vcy Permissible = 149.77 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 52.6 kN

Lux = 2700 mm
Mntx = 62.52 kNm

Mnbx = 62.52 kNm

Vux1 = 46.31 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 32.0331 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 60.58 kN

Mux = 7.36 kNm

Vux = 3.8399 kN

Design Shear = max(Vux, Vux1, Vux2)

= 46.31 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 0.96 kNm

Vcx Permissible = 150.21 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4


= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C10

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 250 mm

Column D = 250 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm


Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 10

Critical Analysis Load Combination : 8

Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 84.61 kN

Muxt = 1.63 kNm

Muyt = 6.01 kNm

Vuxt = 5.15 kN

Vuyt = -10.19 kN

Pub = 87.27 kN

Muxb = -13.65 kNm

Muyb = -1.71 kNm

Vuxb = 5.15 kN

Vuyb = -10.19 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2
(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 19.89 No Beam No Beam - - 1

Top 19.89 No Beam 4000 x 200 x

350 - 16.373 1.747

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 19.89 No Beam No Beam - - 1

Top 19.89 4000 x 200 x

350 No Beam 16.373 - 1.747


Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 72.17 mm

Kluy /r = 13.86

M1 = 1.63 kNm

M2 = -13.65 kNm

34 - 12 x (M1/M2) = 35.43

13.86 < 35.43, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 72.17 mm

Klux /r = 13.86

M1 = -1.71 kNm
M2 = 6.01 kNm

34 - 12 x (M1/M2) = 37.41

13.86 < 37.41, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 1.63 - 1.63

Major Axis Mux (bottom) -13.65 - -13.65

Minor Axis Muy (top) 6.01 - 6.01

Minor Axis Muy (bottom) -1.71 - -1.71

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 87.27 kN

Mux = -13.65 kNm

Muy = -1.71 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.29

Reinforcement Provided = 4-#16

Load Angle = Tan-1(Muy/Mux)

= 7.14 deg

MRes = 13.76 kNm

( φ ) MCap = 26.87 kNm

Capacity Ratio = MRes/ MCap

= 0.512 < 1
Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 87.27 kN

Luy = 1150 mm

Mnty = 26.41 kNm

Mnby = 26.41 kNm

Vuy1 = 45.93 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 28.25 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 134.13 kN

Muy = 12.69 kNm

Vuy = 7.8777 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 45.93 kN

λ=1

φ = 0.65

deff = 202 mm

ρw = 0.006

mm = 0.69 kNm

Vcy Permissible = 85.48 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required


Design for shear along B

Shear from Moment Capacity:

Pu = 87.27 kN

Lux = 1150 mm

Mntx = 26.46 kNm

Mnbx = 26.46 kNm

Vux1 = 46.02 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 25.258 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 134.13 kN

Mux = 4.53 kNm

Vux = 7.5586 kN

Design Shear = max(Vux, Vux1, Vux2)

= 46.02 kN

λ=1

φ = 0.65

deff = 202 mm

ρw = 0.006

mm = 8.85 kNm

Vcx Permissible = 85.48 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 125 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 125 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 125 --- 125 125 125

General Data

Column No. : C10

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate


Column B = 250 mm

Column D = 250 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 54

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Top Joint

Put = 96.85 kN

Muxt = -28.57 kNm

Muyt = -1.46 kNm

Vuxt = 0.24 kN

Vuyt = 13.88 kN

Pub = 103.04 kN

Muxb = 19.99 kNm

Muyb = -2.29 kNm

Vuxb = 0.24 kN

Vuyb = 13.88 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1
(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 8.524 No Beam 4000 x 200 x

350 - 16.373 1.747

Top 8.524 No Beam 4000 x 250 x

400 - 30.551 0.28

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.78

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)
Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 8.524 4000 x 200 x

350 No Beam 16.373 - 1.747

Top 8.524 4000 x 250 x

400

1500 x 250 x

400 30.551 81.468 0.076

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.72

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.78

r = 72.17 mm

Kluy /r = 33.5

M1 = 19.99 kNm

M2 = -28.57 kNm
34 - 12 x (M1/M2) = 42.4

33.5 < 42.4, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.72

r = 72.17 mm

Klux /r = 30.93

M1 = -1.46 kNm

M2 = -2.29 kNm

34 - 12 x (M1/M2) = 26.37

30.93 > 26.37, Column slender along B

Moment Magnification:

For Non-sway frame:

Along B

βdns = 0.6

Ec = 21538.11 N/sqmm

Ig ( x 10 9

) = 0.326 mm^4

EI ( x 10 6

) = 2023929.91 N-sqmm

M2min = 2.32 kNm

Cm = 1

Pc = 4009.65 kN

δns = 1.04

Mc1 = -2.4 kN

Mc2 = -2.4 kN

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC
Major Axis Mux (top) -28.57 - -28.57

Major Axis Mux (bottom) 19.99 - 19.99

Minor Axis Muy (top) -1.46 -2.4 -2.4

Minor Axis Muy (bottom) -2.29 -2.4 -2.4

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 96.85 kN

Mux = -28.57 kNm

Muy = -2.4 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 2.01

Reinforcement Provided = 4-#20

Load Angle = Tan-1(Muy/Mux)

= 4.8 deg

MRes = 28.67 kNm

( φ ) MCap = 35.76 kNm

Capacity Ratio = MRes/ MCap

= 0.802 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 96.85 kN

Luy = 3100 mm

Mnty = 36.12 kNm


Mnby = 36.12 kNm

Vuy1 = 23.3 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 33.86 kN

Critical Analysis Load Combination : 5

Critical Load Combination = [1] : 1.4 (LOAD 3: DL) kN

Nu = 82.53 kN

Muy = 8.6 kNm

Vuy = 3.6665 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 23.3 kN

λ=1

φ = 0.65

deff = 200 mm

ρw = 0.01

mm = 0.35 kNm

Vcy Permissible = 41.29 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 96.85 kN

Lux = 3100 mm

Mntx = 36.13 kNm

Mnbx = 36.13 kNm

Vux1 = 23.31 kN
Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 19.748 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 103.04 kN

Mux = 2.29 kNm

Vux = 0.2385 kN

Design Shear = max(Vux, Vux1, Vux2)

= 33.86 kN

λ=1

φ = 0.65

deff = 200 mm

ρw = 0.01

mm = 8.01 kNm

Vcx Permissible = 80.78 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 5 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 320 mm


48 x diameter of links = 480 mm

Provided spacing = 125 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 160 mm

24 x diameter of links = 240 mm

B / 2 = 125 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 125 --- 125 125 125

General Data

Column No. : C11

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1
Load Data

Analysis Reference No. = 11

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 123.83 kN

Muxt = 18.91 kNm

Muyt = -1.18 kNm

Vuxt = -3.46 kN

Vuyt = 16.56 kN

Pub = 129.03 kN

Muxb = 43.74 kNm

Muyb = 4.01 kNm

Vuxb = -3.46 kN

Vuyb = 16.56 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x Depth)

Beam 2

(Length x

Width x Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M


Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x

350 No Beam 16.373 - 6.71

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x Depth)

Beam 2

(Length x

Width x Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 No Beam 4000 x 200 x

350

- 16.373 6.71

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D
Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 101.04 mm

Kluy /r = 9.9

M1 = 18.91 kNm

M2 = 43.74 kNm

34 - 12 x (M1/M2) = 28.81

9.9 < 28.81, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 9.9

M1 = -1.18 kNm

M2 = 4.01 kNm

34 - 12 x (M1/M2) = 37.54

9.9 < 37.54, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC
Major Axis Mux (top) 18.91 - 18.91

Major Axis Mux (bottom) 43.74 - 43.74

Minor Axis Muy (top) -1.18 - -1.18

Minor Axis Muy (bottom) 4.01 - 4.01

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 129.03 kN

Mux = 43.74 kNm

Muy = 4.01 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 5.24 deg

MRes = 43.93 kNm

( φ ) MCap = 73.6 kNm

Capacity Ratio = MRes/ MCap

= 0.597 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 129.03 kN

Luy = 1150 mm

Mnty = 73.35 kNm


Mnby = 73.35 kNm

Vuy1 = 127.56 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 62 kN

Critical Analysis Load Combination : 8

Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 190.39 kN

Muy = 45.92 kNm

Vuy = -22.7205 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 127.56 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 19.79 kNm

Vcy Permissible = 87.4 kN

Vuy > Vcy Permissible

Link For Shear Design Along D are required

Vs = Vu - Vcy

= 40.16 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 28.4

Area of shear reinforcement

required, Asv-D = 481.83 mm^2/m


Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design for shear along B

Shear from Moment Capacity:

Pu = 129.03 kN

Lux = 1150 mm

Mntx = 73.35 kNm

Mnbx = 73.35 kNm

Vux1 = 127.56 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 51.9749 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 184.39 kN

Mux = 40.15 kNm

Vux = -18.761 kN

Design Shear = max(Vux, Vux1, Vux2)

= 127.56 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 14.84 kNm

Vcx Permissible = 88.82 kN


Vux > Vcx Permissible

Link For Shear Design Along B are required

Vs = Vu - Vcx

= 38.74 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 28.87

Area of shear reinforcement

required, Asv-B = 464.75 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links


Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C11

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 55

Critical Analysis Load Combination : 8

Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 1:

SX)

Critical Location = Top Joint

Put = 137.92 kN

Muxt = 41.34 kNm

Muyt = -8.55 kNm

Vuxt = -3.63 kN
Vuyt = -23.01 kN

Pub = 150.05 kN

Muxb = -39.18 kNm

Muyb = 4.14 kNm

Vuxb = -3.63 kN

Vuyb = -23.01 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 No Beam 16.373 - 6.71

4000 x 200 x

350

Top 32.746 4000 x 250 x

400 No Beam 30.551 - 2.328

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major


Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 No Beam 4000 x 200 x

350 - 16.373 6.71

Top 32.746 No Beam 4000 x 250 x

400 - 30.551 2.328

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 1

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B
Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 30.68

M1 = -39.18 kNm

M2 = 41.34 kNm

34 - 12 x (M1/M2) = 45.37

30.68 < 45.37, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K=1

r = 101.04 mm

Klux /r = 30.68

M1 = 4.14 kNm

M2 = -8.55 kNm

34 - 12 x (M1/M2) = 39.81

30.68 < 39.81, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 41.34 - 41.34

Major Axis Mux (bottom) -39.18 - -39.18

Minor Axis Muy (top) -8.55 - -8.55

Minor Axis Muy (bottom) 4.14 - 4.14


Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 137.92 kN

Mux = 41.34 kNm

Muy = -8.55 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 11.68 deg

MRes = 42.21 kNm

( φ ) MCap = 75.22 kNm

Capacity Ratio = MRes/ MCap

= 0.561 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 137.92 kN

Luy = 3100 mm

Mnty = 75.97 kNm

Mnby = 75.97 kNm

Vuy1 = 49.01 kN

Shear from Load combinations with

Enhanced Eq factor:
Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 60.49 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 145.18 kN

Muy = 3.16 kNm

Vuy = -3.3139 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 57.34 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 16.77 kNm

Vcy Permissible = 162.83 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 137.92 kN

Lux = 3100 mm

Mntx = 75.97 kNm

Mnbx = 75.97 kNm

Vux1 = 49.01 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3


(LOAD 2: SZ)

Vux2 = 57.3385 kN

Critical Analysis Load Combination : 8

Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 150.05 kN

Mux = 4.14 kNm

Vux = -3.627 kN

Design Shear = max(Vux, Vux1, Vux2)

= 60.49 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 16.45 kNm

Vcx Permissible = 163.53 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile


links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C11

Level : 5m To 8m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 2700 mm

Clear Floor Height @ luy = 2700 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 98

Critical Analysis Load Combination : 8


Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 42.59 kN

Muxt = 16.91 kNm

Muyt = -6.07 kNm

Vuxt = -6.25 kN

Vuyt = -10.93 kN

Pub = 52.98 kN

Muxb = -15.86 kNm

Muyb = 12.69 kNm

Vuxb = -6.25 kN

Vuyb = -10.93 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x


400 No Beam 30.551 - 2.328

Top 38.204 4000 x 200 x

300 No Beam 10.311 - 3.705

Sway Condition (as per Stability

Index)

= Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 No Beam 4000 x 250 x

400 - 30.551 2.328

Top 38.204 No Beam 4000 x 200 x

300 - 10.311 3.705

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor


axis = 1

Check For Stability Index

Along D

Q = 0.013

0.013< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 26.72

M1 = -15.86 kNm

M2 = 16.91 kNm

34 - 12 x (M1/M2) = 45.26

26.72 < 45.26, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K=1

r = 101.04 mm

Klux /r = 26.72

M1 = -6.07 kNm

M2 = 12.69 kNm

34 - 12 x (M1/M2) = 39.74

26.72 < 39.74, Column not slender along B


Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 16.91 - 16.91

Major Axis Mux (bottom) -15.86 - -15.86

Minor Axis Muy (top) -6.07 - -6.07

Minor Axis Muy (bottom) 12.69 - 12.69

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 52.98 kN

Mux = -15.86 kNm

Muy = 12.69 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 38.66 deg

MRes = 20.31 kNm

( φ ) MCap = 67.81 kNm

Capacity Ratio = MRes/ MCap

= 0.3 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:


Pu = 52.98 kN

Luy = 2700 mm

Mnty = 63.86 kNm

Mnby = 63.86 kNm

Vuy1 = 47.31 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 22.54 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 32.2 kN

Muy = 5.58 kNm

Vuy = 0.6855 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 47.31 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 1.16 kNm

Vcy Permissible = 107.71 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 52.98 kN
Lux = 2700 mm

Mntx = 63.86 kNm

Mnbx = 63.86 kNm

Vux1 = 47.31 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 18.1574 kN

Critical Analysis Load Combination : 10

Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 2: SZ) kN

Nu = 44.05 kN

Mux = 10.3 kNm

Vux = -2.7364 kN

Design Shear = max(Vux, Vux1, Vux2)

= 47.31 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 4.25 kNm

Vcx Permissible = 93.87 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm
> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C12

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm
Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 12

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 258.79 kN

Muxt = 7.31 kNm

Muyt = 1.48 kNm

Vuxt = 0.97 kN

Vuyt = 27.86 kN

Pub = 263.98 kN

Muxb = 49.1 kNm

Muyb = 0.03 kNm

Vuxb = 0.97 kN

Vuyb = 27.86 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)
Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x

350

4000 x 200 x

350 16.373 16.373 3.331

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M


Bottom 76.408 No Beam No Beam - - 1

Top 76.408 2000 x 200 x

350

4000 x 200 x

350 32.746 16.373 2.226

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 101.04 mm

Kluy /r = 9.9

M1 = 7.31 kNm

M2 = 49.1 kNm

34 - 12 x (M1/M2) = 32.21

9.9 < 32.21, Column not slender along D

Column Is Braced Along B


Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 9.9

M1 = 0.03 kNm

M2 = 1.48 kNm

34 - 12 x (M1/M2) = 33.74

9.9 < 33.74, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 7.31 - 7.31

Major Axis Mux (bottom) 49.1 - 49.1

Minor Axis Muy (top) 1.48 - 1.48

Minor Axis Muy (bottom) 0.03 - 0.03

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 263.98 kN

Mux = 49.1 kNm

Muy = 0.03 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)


= 0.04 deg

MRes = 49.1 kNm

( φ ) MCap = 89.31 kNm

Capacity Ratio = MRes/ MCap

= 0.55 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 263.98 kN

Luy = 1150 mm

Mnty = 89.31 kNm

Mnby = 89.31 kNm

Vuy1 = 155.32 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 82.59 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 263.98 kN

Muy = 49.1 kNm

Vuy = 27.8634 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 155.32 kN

λ=1

φ = 0.65

deff = 302 mm
ρw = 0.007

mm = 12.86 kNm

Vcy Permissible = 88.77 kN

Vuy > Vcy Permissible

Link For Shear Design Along D are required

Vs = Vu - Vcy

= 66.55 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 28.85

Area of shear reinforcement

required, Asv-D = 798.36 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design for shear along B

Shear from Moment Capacity:

Pu = 263.98 kN

Lux = 1150 mm

Mntx = 89.31 kNm

Mnbx = 89.31 kNm

Vux1 = 155.32 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 82.9063 kN

Critical Analysis Load Combination : 9

Critical Load Combination = kN

[5] : 1.2 (LOAD 3: DL) +(LOAD 4:


LL) +(LOAD 2: SZ)

Nu = 210.67 kN

Mux = 41.24 kNm

Vux = -25.5894 kN

Design Shear = max(Vux, Vux1, Vux2)

= 155.32 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 12.33 kNm

Vcx Permissible = 90.92 kN

Vux > Vcx Permissible

Link For Shear Design Along B are required

Vs = Vu - Vcx

= 64.4 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 29.55

Area of shear reinforcement

required, Asv-B = 772.61 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm
Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C12

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm


No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 56

Critical Analysis Load Combination : 9

Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 2:

SZ)

Critical Location = Top Joint

Put = 179.64 kN

Muxt = 0.38 kNm

Muyt = -53.46 kNm

Vuxt = -28.3 kN

Vuyt = 0.52 kN

Pub = 191.77 kN

Muxb = 2.2 kNm

Muyb = 45.56 kNm

Vuxb = -28.3 kN

Vuyb = 0.52 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x
Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 4000 x 200 x

350

4000 x 200 x

350 16.373 16.373 3.331

Top 32.746 4000 x 250 x

400

4000 x 250 x

400 30.551 30.551 1.16

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2
N-M mm mm N-M N-M

Bottom 32.746 2000 x 200 x

350

4000 x 200 x

350 32.746 16.373 2.226

Top 32.746 2000 x 250 x

400

4000 x 250 x

400 61.101 30.551 0.774

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.85

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 30.68

M1 = 0.38 kNm
M2 = 2.2 kNm

34 - 12 x (M1/M2) = 31.95

30.68 < 31.95, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.85

r = 101.04 mm

Klux /r = 26.08

M1 = 45.56 kNm

M2 = -53.46 kNm

34 - 12 x (M1/M2) = 44.23

26.08 < 44.23, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 0.38 - 0.38

Major Axis Mux (bottom) 2.2 - 2.2

Minor Axis Muy (top) -53.46 - -53.46

Minor Axis Muy (bottom) 45.56 - 45.56

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 179.64 kN

Mux = 0.38 kNm

Muy = -53.46 kNm

Resultant Moment (Combined Action)


Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 89.6 deg

MRes = 53.46 kNm

( φ ) MCap = 79.63 kNm

Capacity Ratio = MRes/ MCap

= 0.671 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 179.64 kN

Luy = 3100 mm

Mnty = 81.03 kNm

Mnby = 81.03 kNm

Vuy1 = 52.28 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 76.12 kN

Critical Analysis Load Combination : 10

Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 2: SZ) kN

Nu = 261.14 kN

Muy = 2.1 kNm

Vuy = -1.9487 kN

Design Shear = max(Vuy, Vuy1, Vuy2)


= 76.25 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 33.74 kNm

Vcy Permissible = 178.69 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 179.64 kN

Lux = 3100 mm

Mntx = 81.03 kNm

Mnbx = 81.03 kNm

Vux1 = 52.28 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 76.2484 kN

Critical Analysis Load Combination : 10

Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 2: SZ) kN

Nu = 249.01 kN

Mux = 32.59 kNm

Vux = 19.6522 kN

Design Shear = max(Vux, Vux1, Vux2)

= 76.12 kN
λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 1.59 kNm

Vcx Permissible = 177.1 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10


Spacing 175 --- 125 175 125

General Data

Column No. : C12

Level : 5m To 8m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 2700 mm

Clear Floor Height @ luy = 2700 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 99

Critical Analysis Load Combination : 9

Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 2:

SZ)

Critical Location = Bottom Joint

Put = 43.15 kN

Muxt = -2.37 kNm

Muyt = -25.64 kNm

Vuxt = -18.82 kN

Vuyt = 1.21 kN

Pub = 53.55 kN

Muxb = 1.27 kNm


Muyb = 30.79 kNm

Vuxb = -18.82 kN

Vuyb = 1.21 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x

400

4000 x 250 x

400 30.551 30.551 1.16

Top 38.204 4000 x 200 x

300

4000 x 200 x

300 10.311 10.311 1.853

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major


Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 2000 x 250 x

400

4000 x 250 x

400 61.101 30.551 0.774

Top 38.204 2000 x 200 x

300

4000 x 200 x

300 20.622 10.311 1.235

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.85

Check For Stability Index

Along D
Q = 0.013

0.013< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 26.72

M1 = 1.27 kNm

M2 = -2.37 kNm

34 - 12 x (M1/M2) = 40.42

26.72 < 40.42, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.85

r = 101.04 mm

Klux /r = 22.71

M1 = -25.64 kNm

M2 = 30.79 kNm

34 - 12 x (M1/M2) = 43.99

22.71 < 43.99, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC
Major Axis Mux (top) -2.37 - -2.37

Major Axis Mux (bottom) 1.27 - 1.27

Minor Axis Muy (top) -25.64 - -25.64

Minor Axis Muy (bottom) 30.79 - 30.79

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 53.55 kN

Mux = 1.27 kNm

Muy = 30.79 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 87.64 deg

MRes = 30.82 kNm

( φ ) MCap = 64 kNm

Capacity Ratio = MRes/ MCap

= 0.482 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 53.55 kN

Luy = 2700 mm

Mnty = 63.93 kNm


Mnby = 63.93 kNm

Vuy1 = 47.36 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 43.45 kN

Critical Analysis Load Combination : 6

Critical Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4:

LL) kN

Nu = 62.07 kN

Muy = 0.77 kNm

Vuy = 0.023 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 47.36 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 7.74 kNm

Vcy Permissible = 150.44 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 53.55 kN

Lux = 2700 mm

Mntx = 63.93 kNm

Mnbx = 63.93 kNm


Vux1 = 47.36 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 43.8068 kN

Critical Analysis Load Combination : 5

Critical Load Combination = [1] : 1.4 (LOAD 3: DL) kN

Nu = 72.96 kN

Mux = 12.63 kNm

Vux = -6.4168 kN

Design Shear = max(Vux, Vux1, Vux2)

= 47.36 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 2.62 kNm

Vcx Permissible = 90.86 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm


48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C13

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1
Load Data

Analysis Reference No. = 13

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 272.94 kN

Muxt = 4.32 kNm

Muyt = -2.56 kNm

Vuxt = -1.14 kN

Vuyt = 30.78 kN

Pub = 278.14 kN

Muxb = 50.48 kNm

Muyb = -0.85 kNm

Vuxb = -1.14 kN

Vuyb = 30.78 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)
Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 4000 x 200 x

350

4000 x 200 x

350 16.373 16.373 3.331

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 76.408 No Beam No Beam - - 1

Top 76.408 2000 x 200 x

350

4000 x 200 x
350 32.746 16.373 2.226

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 101.04 mm

Kluy /r = 9.9

M1 = 4.32 kNm

M2 = 50.48 kNm

34 - 12 x (M1/M2) = 32.97

9.9 < 32.97, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 101.04 mm

Klux /r = 9.9
M1 = -0.85 kNm

M2 = -2.56 kNm

34 - 12 x (M1/M2) = 30.03

9.9 < 30.03, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 4.32 - 4.32

Major Axis Mux (bottom) 50.48 - 50.48

Minor Axis Muy (top) -2.56 - -2.56

Minor Axis Muy (bottom) -0.85 - -0.85

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 278.14 kN

Mux = 50.48 kNm

Muy = -0.85 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 0.96 deg

MRes = 50.48 kNm

( φ ) MCap = 90.95 kNm

Capacity Ratio = MRes/ MCap


= 0.555 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 278.14 kN

Luy = 1150 mm

Mnty = 90.93 kNm

Mnby = 90.93 kNm

Vuy1 = 158.14 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 85.05 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 278.14 kN

Muy = 50.48 kNm

Vuy = 30.7779 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 158.14 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 12.3 kNm

Vcy Permissible = 88.66 kN

Vuy > Vcy Permissible


Link For Shear Design Along D are required

Vs = Vu - Vcy

= 69.48 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 28.81

Area of shear reinforcement

required, Asv-D = 833.54 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design for shear along B

Shear from Moment Capacity:

Pu = 278.14 kN

Lux = 1150 mm

Mntx = 90.93 kNm

Mnbx = 90.93 kNm

Vux1 = 158.14 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 75.9326 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 221.42 kN

Mux = 39.7 kNm

Vux = -26.8427 kN

Design Shear = max(Vux, Vux1, Vux2)


= 158.14 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 9.31 kNm

Vcx Permissible = 91.69 kN

Vux > Vcx Permissible

Link For Shear Design Along B are required

Vs = Vu - Vcx

= 66.45 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 29.8

Area of shear reinforcement

required, Asv-B = 797.18 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 175 mm

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile


links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C13

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 57

Critical Analysis Load Combination : 9


Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 2:

SZ)

Critical Location = Top Joint

Put = 186.61 kN

Muxt = -2.34 kNm

Muyt = -50.04 kNm

Vuxt = -26.76 kN

Vuyt = 1.99 kN

Pub = 198.73 kN

Muxb = 4.63 kNm

Muyb = 43.61 kNm

Vuxb = -26.76 kN

Vuyb = 1.99 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 4000 x 200 x


350

4000 x 200 x

350 16.373 16.373 3.331

Top 32.746 4000 x 250 x

400

4000 x 250 x

400 30.551 30.551 1.16

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 32.746 2000 x 200 x

350

4000 x 200 x

350 32.746 16.373 2.226


Top 32.746 2000 x 250 x

400

4000 x 250 x

400 61.101 30.551 0.774

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.85

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 30.68

M1 = -2.34 kNm

M2 = 4.63 kNm

34 - 12 x (M1/M2) = 40.05

30.68 < 40.05, Column not slender along D

Column Is Braced Along B

Slenderness Check along B


K = 0.85

r = 101.04 mm

Klux /r = 26.08

M1 = 43.61 kNm

M2 = -50.04 kNm

34 - 12 x (M1/M2) = 44.46

26.08 < 44.46, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) -2.34 - -2.34

Major Axis Mux (bottom) 4.63 - 4.63

Minor Axis Muy (top) -50.04 - -50.04

Minor Axis Muy (bottom) 43.61 - 43.61

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 186.61 kN

Mux = -2.34 kNm

Muy = -50.04 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 87.33 deg
MRes = 50.09 kNm

( φ ) MCap = 80.4 kNm

Capacity Ratio = MRes/ MCap

= 0.623 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 186.61 kN

Luy = 3100 mm

Mnty = 81.83 kNm

Mnby = 81.83 kNm

Vuy1 = 52.79 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 74.62 kN

Critical Analysis Load Combination : 10

Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 2: SZ) kN

Nu = 253.93 kN

Muy = 0.6 kNm

Vuy = -0.2692 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 71.97 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007
mm = 34.26 kNm

Vcy Permissible = 177.75 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 186.61 kN

Lux = 3100 mm

Mntx = 81.83 kNm

Mnbx = 81.83 kNm

Vux1 = 52.79 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 71.9692 kN

Critical Analysis Load Combination : 10

Critical Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 2: SZ) kN

Nu = 253.93 kN

Mux = 33.17 kNm

Vux = 18.4456 kN

Design Shear = max(Vux, Vux1, Vux2)

= 74.62 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 1.68 kNm
Vcx Permissible = 177.75 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C13

Level : 5m To 8m

Design Code = ACI 318M - 2011


Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 350 mm

Column D = 350 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 2700 mm

Clear Floor Height @ luy = 2700 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 100

Critical Analysis Load Combination : 9

Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 2:

SZ)

Critical Location = Bottom Joint

Put = 34.33 kN

Muxt = -7.61 kNm

Muyt = -23.42 kNm

Vuxt = -16.79 kN

Vuyt = 4.4 kN

Pub = 44.72 kN

Muxb = 5.6 kNm

Muyb = 26.93 kNm

Vuxb = -16.79 kN

Vuyb = 4.4 kN

Effective Length Calculation

Calculation Along Major Axis Of Column


Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 4000 x 250 x

400

4000 x 250 x

400 30.551 30.551 1.16

Top 38.204 No Beam 4000 x 200 x

300 - 10.311 3.705

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x
Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 38.204 2000 x 250 x

400

4000 x 250 x

400 61.101 30.551 0.774

Top 38.204 2000 x 200 x

300

4000 x 200 x

300 20.622 10.311 1.235

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.85

Check For Stability Index

Along D

Q = 0.013

0.013< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)
Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 101.04 mm

Kluy /r = 26.72

M1 = 5.6 kNm

M2 = -7.61 kNm

34 - 12 x (M1/M2) = 42.83

26.72 < 42.83, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.85

r = 101.04 mm

Klux /r = 22.71

M1 = -23.42 kNm

M2 = 26.93 kNm

34 - 12 x (M1/M2) = 44.44

22.71 < 44.44, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) -7.61 - -7.61

Major Axis Mux (bottom) 5.6 - 5.6

Minor Axis Muy (top) -23.42 - -23.42

Minor Axis Muy (bottom) 26.93 - 26.93

Where

A = Moments from analysis

B = Moment due to slenderness effect


C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 44.72 kN

Mux = 5.6 kNm

Muy = 26.93 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.31

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 78.25 deg

MRes = 27.51 kNm

( φ ) MCap = 64.05 kNm

Capacity Ratio = MRes/ MCap

= 0.429 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 44.72 kN

Luy = 2700 mm

Mnty = 62.83 kNm

Mnby = 62.83 kNm

Vuy1 = 46.54 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 31.7 kN
Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 34.33 kN

Muy = 7.61 kNm

Vuy = 4.4039 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 46.54 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 2.9 kNm

Vcy Permissible = 99.3 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 44.72 kN

Lux = 2700 mm

Mntx = 62.83 kNm

Mnbx = 62.83 kNm

Vux1 = 46.54 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 39.9591 kN

Critical Analysis Load Combination : 6


Critical Load Combination = [2] : 1.2 (LOAD 3: DL) +1.6 (LOAD 4:

LL) kN

Nu = 53.08 kN

Mux = 11.53 kNm

Vux = -5.591 kN

Design Shear = max(Vux, Vux1, Vux2)

= 46.54 kN

λ=1

φ = 0.65

deff = 302 mm

ρw = 0.007

mm = 4.24 kNm

Vcx Permissible = 91.88 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 175 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm


B / 2 = 175 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 175 --- 125 175 125

General Data

Column No. : C14

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 250 mm

Column D = 250 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 14

Critical Analysis Load Combination : 8

Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 1:

SX)

Critical Location = Bottom Joint


Put = 111.2 kN

Muxt = 2.35 kNm

Muyt = -1.19 kNm

Vuxt = -1.96 kN

Vuyt = -11.35 kN

Pub = 113.85 kN

Muxb = -14.68 kNm

Muyb = 1.75 kNm

Vuxb = -1.96 kN

Vuyb = -11.35 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 19.89 No Beam No Beam - - 1

Top 19.89 No Beam 4000 x 200 x

350 - 16.373 1.747

Sway Condition (as per Stability


Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 19.89 No Beam No Beam - - 1

Top 19.89 4000 x 200 x

350

4000 x 200 x

350 16.373 16.373 0.867

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.76

Check For Stability Index

Along D

Q = 0.011
0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 72.17 mm

Kluy /r = 13.86

M1 = 2.35 kNm

M2 = -14.68 kNm

34 - 12 x (M1/M2) = 35.92

13.86 < 35.92, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.76

r = 72.17 mm

Klux /r = 12.11

M1 = -1.19 kNm

M2 = 1.75 kNm

34 - 12 x (M1/M2) = 42.17

12.11 < 42.17, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 2.35 - 2.35


Major Axis Mux (bottom) -14.68 - -14.68

Minor Axis Muy (top) -1.19 - -1.19

Minor Axis Muy (bottom) 1.75 - 1.75

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 113.85 kN

Mux = -14.68 kNm

Muy = 1.75 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.29

Reinforcement Provided = 4-#16

Load Angle = Tan-1(Muy/Mux)

= 6.79 deg

MRes = 14.78 kNm

( φ ) MCap = 28.93 kNm

Capacity Ratio = MRes/ MCap

= 0.511 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 113.85 kN

Luy = 1150 mm

Mnty = 28.69 kNm

Mnby = 28.69 kNm


Vuy1 = 49.89 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 31.08 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 152.04 kN

Muy = 13.42 kNm

Vuy = 8.3717 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 49.89 kN

λ=1

φ = 0.65

deff = 202 mm

ρw = 0.006

mm = 1.75 kNm

Vcy Permissible = 87.64 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 113.85 kN

Lux = 1150 mm

Mntx = 28.72 kNm

Mnbx = 28.72 kNm

Vux1 = 49.95 kN
Shear from Load combinations with

Enhanced Eq factor:

Load Combination =

1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 34.0295 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 152.04 kN

Mux = 1.21 kNm

Vux = 0.7298 kN

Design Shear = max(Vux, Vux1, Vux2)

= 49.95 kN

λ=1

φ = 0.65

deff = 202 mm

ρw = 0.006

mm = 13.96 kNm

Vcx Permissible = 87.64 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links


Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 125 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 125 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 125 --- 125 125 125

General Data

Column No. : C14

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 250 mm

Column D = 250 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm

No Of Floors = 1
No Of Columns In Group = 1

Load Data

Analysis Reference No. = 58

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Top Joint

Put = 96 kN

Muxt = -29.73 kNm

Muyt = 3.94 kNm

Vuxt = 1.89 kN

Vuyt = 14.5 kN

Pub = 102.19 kN

Muxb = 20.99 kNm

Muyb = -2.67 kNm

Vuxb = 1.89 kN

Vuyb = 14.5 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Beam Sizes Beam Stiffness Beta

Column

Stiffness

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x
Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 8.524 No Beam 4000 x 200 x

350 - 16.373 1.747

Top 8.524 No Beam 4000 x 250 x

400 - 30.551 0.28

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.78

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 8.524 4000 x 200 x

350

4000 x 200 x

350 16.373 16.373 0.867


Top 8.524 4000 x 250 x

400

4000 x 250 x

400 30.551 30.551 0.139

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.65

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.78

r = 72.17 mm

Kluy /r = 33.5

M1 = 20.99 kNm

M2 = -29.73 kNm

34 - 12 x (M1/M2) = 42.47

33.5 < 42.47, Column not slender along D

Column Is Braced Along B

Slenderness Check along B


K = 0.65

r = 72.17 mm

Klux /r = 27.92

M1 = -2.67 kNm

M2 = 3.94 kNm

34 - 12 x (M1/M2) = 42.12

27.92 < 42.12, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) -29.73 - -29.73

Major Axis Mux (bottom) 20.99 - 20.99

Minor Axis Muy (top) 3.94 - 3.94

Minor Axis Muy (bottom) -2.67 - -2.67

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 96 kN

Mux = -29.73 kNm

Muy = 3.94 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 2.01

Reinforcement Provided = 4-#20

Load Angle = Tan-1(Muy/Mux)

= 7.55 deg
MRes = 29.99 kNm

( φ ) MCap = 35.82 kNm

Capacity Ratio = MRes/ MCap

= 0.837 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 96 kN

Luy = 3100 mm

Mnty = 36.05 kNm

Mnby = 36.05 kNm

Vuy1 = 23.26 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 34.7 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 92.2 kN

Muy = 5.77 kNm

Vuy = 4.9136 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 25.98 kN

λ=1

φ = 0.65

deff = 200 mm

ρw = 0.01
mm = 3.45 kNm

Vcy Permissible = 79.4 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 96 kN

Lux = 3100 mm

Mntx = 36.06 kNm

Mnbx = 36.06 kNm

Vux1 = 23.27 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 25.9834 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX)

kN

Nu = 102.19 kN

Mux = 2.67 kNm

Vux = 1.8893 kN

Design Shear = max(Vux, Vux1, Vux2)

= 34.7 kN

λ=1

φ = 0.65

deff = 200 mm

ρw = 0.01
mm = 7.55 kNm

Vcx Permissible = 80.68 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 5 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 320 mm

48 x diameter of links = 480 mm

Provided spacing = 125 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 160 mm

24 x diameter of links = 240 mm

B / 2 = 125 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 125 --- 125 125 125

General Data

Column No. : C15

Level : 0m To 1.5m
Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 300 mm

Column D = 300 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 15

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 66.64 kN

Muxt = 4.65 kNm

Muyt = -0.75 kNm

Vuxt = -0.99 kN

Vuyt = 14.95 kN

Pub = 70.46 kN

Muxb = 27.07 kNm

Muyb = 0.74 kNm

Vuxb = -0.99 kN

Vuyb = 14.95 kN

Effective Length Calculation


Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 41.243 No Beam No Beam - - 1

Top 41.243 4000 x 200 x

350 No Beam 16.373 - 3.622

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)
Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 41.243 No Beam No Beam - - 1

Top 41.243 No Beam 2000 x 200 x

350 - 32.746 1.798

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87

Check For Stability Index

Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 86.6 mm

Kluy /r = 11.55

M1 = 4.65 kNm
M2 = 27.07 kNm

34 - 12 x (M1/M2) = 31.94

11.55 < 31.94, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 86.6 mm

Klux /r = 11.55

M1 = 0.74 kNm

M2 = -0.75 kNm

34 - 12 x (M1/M2) = 45.92

11.55 < 45.92, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 4.65 - 4.65

Major Axis Mux (bottom) 27.07 - 27.07

Minor Axis Muy (top) -0.75 - -0.75

Minor Axis Muy (bottom) 0.74 - 0.74

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 70.46 kN

Mux = 27.07 kNm

Muy = 0.74 kNm

Resultant Moment (Combined Action)


Moment Capacity Check

Pt Calculated = 1.79

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 1.57 deg

MRes = 27.08 kNm

( φ ) MCap = 53.38 kNm

Capacity Ratio = MRes/ MCap

= 0.507 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 70.46 kN

Luy = 1150 mm

Mnty = 53.37 kNm

Mnby = 53.37 kNm

Vuy1 = 92.81 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 44.47 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 70.46 kN

Muy = 27.07 kNm

Vuy = 14.9537 kN

Design Shear = max(Vuy, Vuy1, Vuy2)


= 92.81 kN

λ=1

φ = 0.65

deff = 252 mm

ρw = 0.009

mm = 18.72 kNm

Vcy Permissible = 65.35 kN

Vuy > Vcy Permissible

Link For Shear Design Along D are required

Vs = Vu - Vcy

= 27.46 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 21.24

Area of shear reinforcement

required, Asv-D = 394.76 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 150 mm

Design for shear along B

Shear from Moment Capacity:

Pu = 70.46 kN

Lux = 1150 mm

Mntx = 53.37 kNm

Mnbx = 53.37 kNm

Vux1 = 92.81 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)
Vux2 = 52.0713 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 169.3 kN

Mux = 2.36 kNm

Vux = -17.7389 kN

Design Shear = max(Vux, Vux1, Vux2)

= 92.81 kN

λ=1

φ = 0.65

deff = 252 mm

ρw = 0.009

mm = 17.71 kNm

Vcx Permissible = 124.9 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 150 mm

Criterion for spacing of Ductile

links:
Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 150 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 150 --- 125 150 125

General Data

Column No. : C15

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 300 mm

Column D = 300 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 59

Critical Analysis Load Combination : 8

Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 1:


SX)

Critical Location = Top Joint

Put = 101 kN

Muxt = 30.07 kNm

Muyt = -0.04 kNm

Vuxt = -0.04 kN

Vuyt = -15.98 kN

Pub = 109.91 kN

Muxb = -25.83 kNm

Muyb = 0.09 kNm

Vuxb = -0.04 kN

Vuyb = -15.98 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Beam Sizes Beam Stiffness Beta

Column

Stiffness

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 17.676 4000 x 200 x

350 No Beam 16.373 - 3.622


Top 17.676 4000 x 250 x

400 No Beam 30.551 - 1.257

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 17.676 No Beam 2000 x 200 x

350 - 32.746 1.798

Top 17.676 No Beam 2000 x 250 x

400 - 61.101 0.626

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.83

Check For Stability Index


Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 86.6 mm

Kluy /r = 35.8

M1 = -25.83 kNm

M2 = 30.07 kNm

34 - 12 x (M1/M2) = 44.31

35.8 < 44.31, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.83

r = 86.6 mm

Klux /r = 29.71

M1 = -0.04 kNm

M2 = 0.09 kNm

34 - 12 x (M1/M2) = 39.36

29.71 < 39.36, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final


ABC

Major Axis Mux (top) 30.07 - 30.07

Major Axis Mux (bottom) -25.83 - -25.83

Minor Axis Muy (top) -0.04 - -0.04

Minor Axis Muy (bottom) 0.09 - 0.09

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 101 kN

Mux = 30.07 kNm

Muy = -0.04 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.79

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 0.07 deg

MRes = 30.07 kNm

( φ ) MCap = 56.33 kNm

Capacity Ratio = MRes/ MCap

= 0.534 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 101 kN

Luy = 3100 mm
Mnty = 57.19 kNm

Mnby = 57.19 kNm

Vuy1 = 36.9 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 42.77 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 137.87 kN

Muy = 0.71 kNm

Vuy = -1.5648 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 43.5 kN

λ=1

φ = 0.65

deff = 252 mm

ρw = 0.009

mm = 15.62 kNm

Vcy Permissible = 120.74 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 101 kN

Lux = 3100 mm

Mntx = 57.19 kNm


Mnbx = 57.19 kNm

Vux1 = 36.9 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 43.5003 kN

Critical Analysis Load Combination : 8

Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX)

kN

Nu = 109.91 kN

Mux = 0.09 kNm

Vux = -0.0363 kN

Design Shear = max(Vux, Vux1, Vux2)

= 42.77 kN

λ=1

φ = 0.65

deff = 252 mm

ρw = 0.009

mm = 12.94 kNm

Vcx Permissible = 116.91 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4


= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 150 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 150 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 150 --- 125 150 125

General Data

Column No. : C15

Level : 5m To 8m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 300 mm

Column D = 300 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 2700 mm


Clear Floor Height @ luy = 2700 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 101

Critical Analysis Load Combination : 8

Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 38.39 kN

Muxt = 16.29 kNm

Muyt = -1.77 kNm

Vuxt = -1.03 kN

Vuyt = -11.45 kN

Pub = 46.02 kN

Muxb = -18.04 kNm

Muyb = 1.31 kNm

Vuxb = -1.03 kN

Vuyb = -11.45 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2
(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 20.622 No Beam 30.551 - 1.257

4000 x 250 x

400

Top 20.622 4000 x 200 x

300 No Beam 10.311 - 2

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 20.622 No Beam 2000 x 250 x


400 - 61.101 0.626

Top 20.622 No Beam 2000 x 200 x

300 - 20.622 1

User Defined Effective Length Factor = 0.74

Check For Stability Index

Along D

Q = 0.013

0.013< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 86.6 mm

Kluy /r = 31.18

M1 = 16.29 kNm

M2 = -18.04 kNm

34 - 12 x (M1/M2) = 44.83

31.18 < 44.83, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.74

r = 86.6 mm

Klux /r = 23.07

M1 = 1.31 kNm
M2 = -1.77 kNm

34 - 12 x (M1/M2) = 42.92

23.07 < 42.92, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 16.29 - 16.29

Major Axis Mux (bottom) -18.04 - -18.04

Minor Axis Muy (top) -1.77 - -1.77

Minor Axis Muy (bottom) 1.31 - 1.31

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 46.02 kN

Mux = -18.04 kNm

Muy = 1.31 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.79

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 4.16 deg

MRes = 18.09 kNm

( φ ) MCap = 51 kNm

Capacity Ratio = MRes/ MCap

= 0.355 < 1
Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 46.02 kN

Luy = 2700 mm

Mnty = 50.99 kNm

Mnby = 50.99 kNm

Vuy1 = 37.77 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 25.89 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 52.71 kN

Muy = 6.04 kNm

Vuy = -3.2753 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 37.77 kN

λ=1

φ = 0.65

deff = 252 mm

ρw = 0.009

mm = 0.2 kNm

Vcy Permissible = 108.67 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required


Design for shear along B

Shear from Moment Capacity:

Pu = 46.02 kN

Lux = 2700 mm

Mntx = 50.99 kNm

Mnbx = 50.99 kNm

Vux1 = 37.77 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 26.2849 kN

Critical Analysis Load Combination : 5

Critical Load Combination = [1] : 1.4 (LOAD 3: DL) kN

Nu = 47.45 kN

Mux = 1.99 kNm

Vux = -1.4498 kN

Design Shear = max(Vux, Vux1, Vux2)

= 37.77 kN

λ=1

φ = 0.65

deff = 252 mm

ρw = 0.009

mm = 3.63 kNm

Vcx Permissible = 107.88 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required
Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 150 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 150 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 150 --- 125 150 125

General Data

Column No. : C16

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 300 mm
Column D = 300 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 16

Critical Analysis Load Combination : 8

Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 102.23 kN

Muxt = -4.76 kNm

Muyt = -0.73 kNm

Vuxt = -1.4 kN

Vuyt = -14.42 kN

Pub = 106.05 kN

Muxb = -26.38 kNm

Muyb = 1.37 kNm

Vuxb = -1.4 kN

Vuyb = -14.42 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x
Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 41.243 No Beam No Beam - - 1

Top 41.243 No Beam 4000 x 200 x

350 - 16.373 3.622

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M


Bottom 41.243 No Beam No Beam - - 1

Top 41.243 2000 x 200 x

350

2000 x 200 x

350 32.746 32.746 0.899

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.76

Check For Stability Index

Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 86.6 mm

Kluy /r = 11.55

M1 = -4.76 kNm

M2 = -26.38 kNm

34 - 12 x (M1/M2) = 31.83

11.55 < 31.83, Column not slender along D

Column Is Braced Along B


Slenderness Check along B

K = 0.76

r = 86.6 mm

Klux /r = 10.09

M1 = -0.73 kNm

M2 = 1.37 kNm

34 - 12 x (M1/M2) = 40.43

10.09 < 40.43, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) -4.76 - -4.76

Major Axis Mux (bottom) -26.38 - -26.38

Minor Axis Muy (top) -0.73 - -0.73

Minor Axis Muy (bottom) 1.37 - 1.37

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 106.05 kN

Mux = -26.38 kNm

Muy = 1.37 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.79

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)


= 2.97 deg

MRes = 26.42 kNm

( φ ) MCap = 56.95 kNm

Capacity Ratio = MRes/ MCap

= 0.464 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 106.05 kN

Luy = 1150 mm

Mnty = 56.82 kNm

Mnby = 56.82 kNm

Vuy1 = 98.81 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 44.41 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 162.28 kN

Muy = 27.09 kNm

Vuy = 14.9989 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 98.81 kN

λ=1

φ = 0.65

deff = 252 mm
ρw = 0.009

mm = 7.86 kNm

Vcy Permissible = 65.99 kN

Vuy > Vcy Permissible

Link For Shear Design Along D are required

Vs = Vu - Vcy

= 32.82 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 21.45

Area of shear reinforcement

required, Asv-D = 471.99 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 150 mm

Design for shear along B

Shear from Moment Capacity:

Pu = 106.05 kN

Lux = 1150 mm

Mntx = 56.82 kNm

Mnbx = 56.82 kNm

Vux1 = 98.81 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 72.5128 kN

Critical Analysis Load Combination : 9

Critical Load Combination = kN

[5] : 1.2 (LOAD 3: DL) +(LOAD 4:


LL) +(LOAD 2: SZ)

Nu = 162.94 kN

Mux = 26.26 kNm

Vux = -24.3329 kN

Design Shear = max(Vux, Vux1, Vux2)

= 98.81 kN

λ=1

φ = 0.65

deff = 252 mm

ρw = 0.009

mm = 6.95 kNm

Vcx Permissible = 66.32 kN

Vux > Vcx Permissible

Link For Shear Design Along B are required

Vs = Vu - Vcx

= 32.49 kN

Vcx Permissible = 0.5 x Vcx x 0.65

= 21.55

Area of shear reinforcement

required, Asv-B = 467.18 mm^2/m

Diameter of column master links = 10

Number of legs provided = 4

Spacing of links prvd, Sv = 150 mm

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm
Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 150 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 150 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 150 --- 125 150 125

General Data

Column No. : C16

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 300 mm

Column D = 300 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm


No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 60

Critical Analysis Load Combination : 10

Load Combination = [6] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 2:

SZ)

Critical Location = Top Joint

Put = 88.39 kN

Muxt = -2.5 kNm

Muyt = 31.38 kNm

Vuxt = 17.28 kN

Vuyt = 1.05 kN

Pub = 97.3 kN

Muxb = 1.16 kNm

Muyb = -29.07 kNm

Vuxb = 17.28 kN

Vuyb = 1.05 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x
Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 17.676 No Beam 4000 x 200 x

350 - 16.373 3.622

Top 17.676 No Beam 4000 x 250 x

400 - 30.551 1.257

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 17.676 2000 x 200 x

350

2000 x 200 x
350 32.746 32.746 0.899

Top 17.676 2000 x 250 x

400

2000 x 250 x

400 61.101 61.101 0.314

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.69

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 86.6 mm

Kluy /r = 35.8

M1 = 1.16 kNm

M2 = -2.5 kNm

34 - 12 x (M1/M2) = 39.6

35.8 < 39.6, Column not slender along D

Column Is Braced Along B


Slenderness Check along B

K = 0.69

r = 86.6 mm

Klux /r = 24.7

M1 = -29.07 kNm

M2 = 31.38 kNm

34 - 12 x (M1/M2) = 45.12

24.7 < 45.12, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) -2.5 - -2.5

Major Axis Mux (bottom) 1.16 - 1.16

Minor Axis Muy (top) 31.38 - 31.38

Minor Axis Muy (bottom) -29.07 - -29.07

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 88.39 kN

Mux = -2.5 kNm

Muy = 31.38 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.79

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)


= 85.45 deg

MRes = 31.48 kNm

( φ ) MCap = 55.26 kNm

Capacity Ratio = MRes/ MCap

= 0.57 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 88.39 kN

Luy = 3100 mm

Mnty = 55.97 kNm

Mnby = 55.97 kNm

Vuy1 = 36.11 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 43.87 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 148.01 kN

Muy = 4.7 kNm

Vuy = 3.1094 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 51.5 kN

λ=1

φ = 0.65

deff = 252 mm
ρw = 0.009

mm = 12.84 kNm

Vcy Permissible = 122.1 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 88.39 kN

Lux = 3100 mm

Mntx = 55.97 kNm

Mnbx = 55.97 kNm

Vux1 = 36.11 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 2: SZ)

Vux2 = 51.5008 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 142.03 kN

Mux = 1.7 kNm

Vux = 1.0324 kN

Design Shear = max(Vux, Vux1, Vux2)

= 43.87 kN

λ=1

φ = 0.65

deff = 252 mm

ρw = 0.009
mm = 15.13 kNm

Vcx Permissible = 121.3 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 150 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 150 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 150 --- 125 150 125

General Data

Column No. : C16

Level : 5m To 8m
Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 300 mm

Column D = 300 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 2700 mm

Clear Floor Height @ luy = 2700 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 102

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 37.72 kN

Muxt = -17.52 kNm

Muyt = -0.46 kNm

Vuxt = 0.04 kN

Vuyt = 12.25 kN

Pub = 45.36 kN

Muxb = 19.22 kNm

Muyb = -0.59 kNm

Vuxb = 0.04 kN

Vuyb = 12.25 kN

Effective Length Calculation


Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 20.622 No Beam 4000 x 250 x

400 - 30.551 1.257

Top 20.622 No Beam 4000 x 200 x

300 - 10.311 2

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 1

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x
Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 20.622 2000 x 250 x

400

2000 x 250 x

400 61.101 61.101 0.314

Top 20.622 No Beam 2000 x 200 x

300 - 20.622 1

User Defined Effective Length Factor = 0.7

Check For Stability Index

Along D

Q = 0.013

0.013< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K=1

r = 86.6 mm

Kluy /r = 31.18
M1 = -17.52 kNm

M2 = 19.22 kNm

34 - 12 x (M1/M2) = 44.94

31.18 < 44.94, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.7

r = 86.6 mm

Klux /r = 21.82

M1 = -0.46 kNm

M2 = -0.59 kNm

34 - 12 x (M1/M2) = 24.73

21.82 < 24.73, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) -17.52 - -17.52

Major Axis Mux (bottom) 19.22 - 19.22

Minor Axis Muy (top) -0.46 - -0.46

Minor Axis Muy (bottom) -0.59 - -0.59

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 45.36 kN

Mux = 19.22 kNm

Muy = -0.59 kNm


Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.79

Reinforcement Provided = 8-#16

Load Angle = Tan-1(Muy/Mux)

= 1.76 deg

MRes = 19.23 kNm

( φ ) MCap = 50.9 kNm

Capacity Ratio = MRes/ MCap

= 0.378 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 45.36 kN

Luy = 2700 mm

Mnty = 50.92 kNm

Mnby = 50.92 kNm

Vuy1 = 37.72 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 27 kN

Critical Analysis Load Combination : 8

Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 36.02 kN

Muy = 3.53 kNm

Vuy = -2.4957 kN
Design Shear = max(Vuy, Vuy1, Vuy2)

= 37.72 kN

λ=1

φ = 0.65

deff = 252 mm

ρw = 0.009

mm = 0.74 kNm

Vcy Permissible = 106.14 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 45.36 kN

Lux = 2700 mm

Mntx = 50.92 kNm

Mnbx = 50.92 kNm

Vux1 = 37.72 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 28.7683 kN

Critical Analysis Load Combination : 5

Critical Load Combination = [1] : 1.4 (LOAD 3: DL) kN

Nu = 47.19 kN

Mux = 0.62 kNm

Vux = -0.7123 kN

Design Shear = max(Vux, Vux1, Vux2)

= 37.72 kN
λ=1

φ = 0.65

deff = 252 mm

ρw = 0.009

mm = 4.98 kNm

Vcx Permissible = 107.84 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 150 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 150 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10


Spacing 150 --- 125 150 125

General Data

Column No. : C17

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 250 mm

Column D = 250 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 17

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 29.28 kN

Muxt = -1.45 kNm

Muyt = -0.14 kNm

Vuxt = 0.22 kN

Vuyt = 11.14 kN

Pub = 31.93 kN

Muxb = 15.25 kNm


Muyb = -0.47 kNm

Vuxb = 0.22 kN

Vuyb = 11.14 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 19.89 No Beam No Beam - - 1

Top 19.89 No Beam 16.373 - 1.747

4000 x 200 x

350

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Column

Stiffness
Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 19.89 No Beam No Beam - - 1

Top 19.89 No Beam 2000 x 200 x

350 - 32.746 0.867

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.76

Check For Stability Index

Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D


Slenderness Check along D

K = 0.87

r = 72.17 mm

Kluy /r = 13.86

M1 = -1.45 kNm

M2 = 15.25 kNm

34 - 12 x (M1/M2) = 35.14

13.86 < 35.14, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.76

r = 72.17 mm

Klux /r = 12.11

M1 = -0.14 kNm

M2 = -0.47 kNm

34 - 12 x (M1/M2) = 30.41

12.11 < 30.41, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) -1.45 - -1.45

Major Axis Mux (bottom) 15.25 - 15.25

Minor Axis Muy (top) -0.14 - -0.14

Minor Axis Muy (bottom) -0.47 - -0.47

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending

Pu = 31.93 kN

Mux = 15.25 kNm

Muy = -0.47 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.29

Reinforcement Provided = 4-#16

Load Angle = Tan-1(Muy/Mux)

= 1.76 deg

MRes = 15.26 kNm

( φ ) MCap = 22.24 kNm

Capacity Ratio = MRes/ MCap

= 0.686 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 31.93 kN

Luy = 1150 mm

Mnty = 22.16 kNm

Mnby = 22.16 kNm

Vuy1 = 38.54 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 32.5 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:


LL) +(LOAD 2: SZ) kN

Nu = 87.75 kN

Muy = 2.09 kNm

Vuy = 1.8426 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 38.54 kN

λ=1

φ = 0.65

deff = 202 mm

ρw = 0.006

mm = 6.66 kNm

Vcy Permissible = 79.61 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 31.93 kN

Lux = 1150 mm

Mntx = 22.17 kNm

Mnbx = 22.17 kNm

Vux1 = 38.56 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 33.8665 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN


Nu = 85.1 kN

Mux = 4.53 kNm

Vux = -11.4087 kN

Design Shear = max(Vux, Vux1, Vux2)

= 38.56 kN

λ=1

φ = 0.65

deff = 202 mm

ρw = 0.006

mm = 3.95 kNm

Vcx Permissible = 79.26 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 125 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 125 mm

Spacing = 300 mm
Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 125 --- 125 125 125

General Data

Column No. : C17

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 250 mm

Column D = 250 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm

Clear Floor Height @ luy = 3100 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 61

Critical Analysis Load Combination : 8

Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 1:

SX)

Critical Location = Top Joint

Put = 46.99 kN

Muxt = 23.43 kNm


Muyt = -2.47 kNm

Vuxt = -1.14 kN

Vuyt = -11.84 kN

Pub = 53.17 kN

Muxb = -18 kNm

Muyb = 1.53 kNm

Vuxb = -1.14 kN

Vuyb = -11.84 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 8.524 4000 x 200 x

350 No Beam 16.373 - 1.747

Top 8.524 4000 x 250 x

400 No Beam 30.551 - 0.28

Sway Condition (as per Stability

Index) = Non Sway


= 0.78

Effective Length Factor along Major

Axis

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 8.524 No Beam 2000 x 200 x

350 - 32.746 0.867

Top 8.524 No Beam 2000 x 250 x

400 - 61.101 0.139

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.65

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame


(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.78

r = 72.17 mm

Kluy /r = 33.5

M1 = -18 kNm

M2 = 23.43 kNm

34 - 12 x (M1/M2) = 43.22

33.5 < 43.22, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.65

r = 72.17 mm

Klux /r = 27.92

M1 = 1.53 kNm

M2 = -2.47 kNm

34 - 12 x (M1/M2) = 41.45

27.92 < 41.45, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 23.43 - 23.43

Major Axis Mux (bottom) -18 - -18


Minor Axis Muy (top) -2.47 - -2.47

Minor Axis Muy (bottom) 1.53 - 1.53

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 46.99 kN

Mux = 23.43 kNm

Muy = -2.47 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 2.01

Reinforcement Provided = 4-#20

Load Angle = Tan-1(Muy/Mux)

= 6.01 deg

MRes = 23.56 kNm

( φ ) MCap = 32.12 kNm

Capacity Ratio = MRes/ MCap

= 0.734 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 46.99 kN

Luy = 3100 mm

Mnty = 32.3 kNm

Mnby = 32.3 kNm

Vuy1 = 20.84 kN
Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 30.2 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 61.19 kN

Muy = 1.15 kNm

Vuy = -1.6827 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 27.53 kN

λ=1

φ = 0.65

deff = 200 mm

ρw = 0.01

mm = 4.97 kNm

Vcy Permissible = 75.29 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 46.99 kN

Lux = 3100 mm

Mntx = 32.34 kNm

Mnbx = 32.34 kNm

Vux1 = 20.87 kN

Shear from Load combinations with


Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 27.5265 kN

Critical Analysis Load Combination : 8

Critical Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) -(LOAD 1: SX) kN

Nu = 53.17 kN

Mux = 1.53 kNm

Vux = -1.1423 kN

Design Shear = max(Vux, Vux1, Vux2)

= 30.2 kN

λ=1

φ = 0.65

deff = 200 mm

ρw = 0.01

mm = 3.79 kNm

Vcx Permissible = 74.19 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 5 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 320 mm

48 x diameter of links = 480 mm


Provided spacing = 125 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 160 mm

24 x diameter of links = 240 mm

B / 2 = 125 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 125 --- 125 125 125

General Data

Column No. : C18

Level : 0m To 1.5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 250 mm

Column D = 250 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 1150 mm

Clear Floor Height @ luy = 1150 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data
Analysis Reference No. = 18

Critical Analysis Load Combination : 8

Load Combination = [4] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) -(LOAD 1:

SX)

Critical Location = Bottom Joint

Put = 58.92 kN

Muxt = 2.38 kNm

Muyt = -4 kNm

Vuxt = -4.74 kN

Vuyt = -11.84 kN

Pub = 61.57 kN

Muxb = -15.37 kNm

Muyb = 3.1 kNm

Vuxb = -4.74 kN

Vuyb = -11.84 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2
N-M mm mm N-M N-M

Bottom 19.89 No Beam No Beam - - 1

Top 19.89 No Beam 4000 x 200 x

350 - 16.373 1.747

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.87

Calculation Along Minor Axis Of Column

Joint Beam Sizes Beam Stiffness Beta

Column

Stiffness

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 19.89 No Beam No Beam - - 1

Top 19.89 No Beam 4000 x 200 x

350 - 16.373 1.747

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.87
Check For Stability Index

Along D

Q = 0.011

0.011< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.009

0.009< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.87

r = 72.17 mm

Kluy /r = 13.86

M1 = 2.38 kNm

M2 = -15.37 kNm

34 - 12 x (M1/M2) = 35.86

13.86 < 35.86, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.87

r = 72.17 mm

Klux /r = 13.86

M1 = 3.1 kNm

M2 = -4 kNm

34 - 12 x (M1/M2) = 43.29

13.86 < 43.29, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) 2.38 - 2.38

Major Axis Mux (bottom) -15.37 - -15.37

Minor Axis Muy (top) -4 - -4

Minor Axis Muy (bottom) 3.1 - 3.1

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 61.57 kN

Mux = -15.37 kNm

Muy = 3.1 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 1.29

Reinforcement Provided = 4-#16

Load Angle = Tan-1(Muy/Mux)

= 11.4 deg

MRes = 15.68 kNm

( φ ) MCap = 25.14 kNm

Capacity Ratio = MRes/ MCap

= 0.624 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 61.57 kN
Luy = 1150 mm

Mnty = 24.37 kNm

Mnby = 24.37 kNm

Vuy1 = 42.38 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) -3

(LOAD 1: SX)

Vuy2 = 32.63 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 93.05 kN

Muy = 0.76 kNm

Vuy = 8.9555 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 42.38 kN

λ=1

φ = 0.65

deff = 202 mm

ρw = 0.006

mm = 8.52 kNm

Vcy Permissible = 80.3 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 61.57 kN

Lux = 1150 mm
Mntx = 24.38 kNm

Mnbx = 24.38 kNm

Vux1 = 42.41 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 23.6572 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 95.7 kN

Mux = 0.58 kNm

Vux = -2.9413 kN

Design Shear = max(Vux, Vux1, Vux2)

= 42.41 kN

λ=1

φ = 0.65

deff = 202 mm

ρw = 0.006

mm = 8.97 kNm

Vcx Permissible = 80.65 kN

Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4


= 4 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 256 mm

48 x diameter of links = 480 mm

Provided spacing = 125 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 128 mm

24 x diameter of links = 240 mm

B / 2 = 125 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 125 --- 125 125 125

General Data

Column No. : C18

Level : 1.5m To 5m

Design Code = ACI 318M - 2011

Grade Of Concrete = C21 N/sqmm

Grade Of Steel = Fy276 N/sqmm

Consider Ductile = Yes

Type of Frame = Intermediate

Column B = 250 mm

Column D = 250 mm

Clear Cover = 40 mm

Clear Floor Height @ lux = 3100 mm


Clear Floor Height @ luy = 3100 mm

No Of Floors = 1

No Of Columns In Group = 1

Load Data

Analysis Reference No. = 62

Critical Analysis Load Combination : 7

Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4: LL) +(LOAD 1:

SX)

Critical Location = Top Joint

Put = 59.05 kN

Muxt = -29.37 kNm

Muyt = -5.99 kNm

Vuxt = -2.71 kN

Vuyt = 14.47 kN

Pub = 65.24 kN

Muxb = 21.26 kNm

Muyb = 3.5 kNm

Vuxb = -2.71 kN

Vuyb = 14.47 kN

Effective Length Calculation

Calculation Along Major Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2
(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 8.524 No Beam 4000 x 200 x

350 - 16.373 1.747

Top 8.524 No Beam 4000 x 250 x

400 - 30.551 0.28

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Major

Axis = 0.78

Calculation Along Minor Axis Of Column

Joint Column

Stiffness

Beam Sizes Beam Stiffness Beta

Beam 1

(Length x

Width x

Depth)

Beam 2

(Length x

Width x

Depth)

Beam 1 Beam 2

N-M mm mm N-M N-M

Bottom 8.524 No Beam 4000 x 200 x

350
- 16.373 1.747

Top 8.524 No Beam 4000 x 250 x

400 - 30.551 0.28

Sway Condition (as per Stability

Index) = Non Sway

Effective Length Factor along Minor

axis = 0.78

Check For Stability Index

Along D

Q = 0.025

0.025< 0.05, Column shall be designed as non-sway frame

(Braced)

Along B

Q = 0.021

0.021< 0.05, Column shall be designed as non-sway frame

(Braced)

Slenderness Check

Column Is Braced Along D

Slenderness Check along D

K = 0.78

r = 72.17 mm

Kluy /r = 33.5

M1 = 21.26 kNm

M2 = -29.37 kNm

34 - 12 x (M1/M2) = 42.69

33.5 < 42.69, Column not slender along D

Column Is Braced Along B

Slenderness Check along B

K = 0.78
r = 72.17 mm

Klux /r = 33.5

M1 = 3.5 kNm

M2 = -5.99 kNm

34 - 12 x (M1/M2) = 41.02

33.5 < 41.02, Column not slender along B

Calculation of Design Moment

Direction Manalysis Msldr or Mc Mdesign-final

ABC

Major Axis Mux (top) -29.37 - -29.37

Major Axis Mux (bottom) 21.26 - 21.26

Minor Axis Muy (top) -5.99 - -5.99

Minor Axis Muy (bottom) 3.5 - 3.5

Where

A = Moments from analysis

B = Moment due to slenderness effect

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

Critical Case - Axial Load & BiAxial Bending

Pu = 59.05 kN

Mux = -29.37 kNm

Muy = -5.99 kNm

Resultant Moment (Combined Action)

Moment Capacity Check

Pt Calculated = 2.01

Reinforcement Provided = 4-#20

Load Angle = Tan-1(Muy/Mux)

= 11.52 deg

MRes = 29.98 kNm


( φ ) MCap = 33.4 kNm

Capacity Ratio = MRes/ MCap

= 0.898 < 1

Design Of Shear

Design for shear along D

Shear from Moment Capacity:

Pu = 59.05 kN

Luy = 3100 mm

Mnty = 33.22 kNm

Mnby = 33.22 kNm

Vuy1 = 21.43 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 1: SX)

Vuy2 = 34.76 kN

Critical Analysis Load Combination : 9

Critical Load Combination = [5] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 2: SZ) kN

Nu = 62.09 kN

Muy = 6.62 kNm

Vuy = 5.3855 kN

Design Shear = max(Vuy, Vuy1, Vuy2)

= 23.33 kN

λ=1

φ = 0.65

deff = 200 mm

ρw = 0.01

mm = 0.41 kNm
Vcy Permissible = 42.68 kN

Vuy < Vcy Permissible

Link For Shear Design Along D are not required

Design for shear along B

Shear from Moment Capacity:

Pu = 59.05 kN

Lux = 3100 mm

Mntx = 33.26 kNm

Mnbx = 33.26 kNm

Vux1 = 21.46 kN

Shear from Load combinations with

Enhanced Eq factor:

Load Combination = 1.2 (LOAD 3: DL) +(LOAD 4: LL) +3

(LOAD 2: SZ)

Vux2 = 23.3266 kN

Critical Analysis Load Combination : 7

Critical Load Combination = [3] : 1.2 (LOAD 3: DL) +(LOAD 4:

LL) +(LOAD 1: SX) kN

Nu = 65.24 kN

Mux = 3.5 kNm

Vux = -2.7116 kN

Design Shear = max(Vux, Vux1, Vux2)

= 34.76 kN

λ=1

φ = 0.65

deff = 200 mm

ρw = 0.01

mm = 3.02 kNm

Vcx Permissible = 75.84 kN


Vux < Vcx Permissible

Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

> Max. longitudinal bar dia / 4

= 5 mm

Criterion for spacing of normal links

Min. Longitudinal Bar dia X 16 = 320 mm

48 x diameter of links = 480 mm

Provided spacing = 125 mm

Criterion for spacing of Ductile

links:

Min. Longitudinal Bar dia x 8 = 160 mm

24 x diameter of links = 240 mm

B / 2 = 125 mm

Spacing = 300 mm

Provided Spacing = 125 mm

Table For Links

Required Provided

Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

Link Dia. 10 --- 10 10 10

Spacing 125 --- 125 125 125