DeltaV Whitepaper

September 2010 – Page 1 DeltaV Grounding Options

DeltaV Grounding Options


This document discusses the Power and Grounding changes that will be in an upcoming
release of the Site Preparation and Design for DeltaV Digital Automation Systems manual (the
Site Preparation manual). This information supplements the Site Preparation manual and
provides additional options for design and installation of the control system ground.

Table of Contents

Introduction ....................................................................................................... 2

Typical DeltaV AC Power and Grounding ........................................................ 2


AC Ground ...................................................................................................... 3

DC Ground ...................................................................................................... 5

System Power Isolation ................................................................................. 5

Floating AC Ground........................................................................................ 6

Summary ............................................................................................................ 6

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
September 2010 – Page 2 DeltaV Grounding Options
Introduction
The Site Preparation manual provides recommendations for the installation of AC power
distribution and system grounding that exceed those dictated by the NEC. The Site
Preparation manual also provides recommendations of the installation of Isolation
Transformers how they should be connected to the AC Ground.

The AC power distribution and system grounding guidelines have raised questions because
they exceed NEC guidelines and common installation practices and because they may result
in additional installation costs. This paper discusses upcoming changes to the DeltaV Site
Preparation manual intended to clarify these recommendations and to recognize an alternative
solution for the grounding of signal shields. This paper should be used in conjunction with the
current Site Preparation manual to help in the design of your control system’s power and
grounding.

Typical DeltaV AC Power and Grounding


DeltaV installation guidelines as documented in the Site Preparation Guide are based on a
solidly grounded AC power distribution system. The recommended practices in the guide are
based on years of proven solutions that provide excellent protection from electrical surges and
transients, often found in industrial installations. The key feature of the recommended
installation practice is that DeltaV connects the AC Ground to the dedicated Instrumentation
Ground and as a result, recommends connecting signal shields to the AC Ground bars.

This is often viewed as an unnecessary expense that conflicts with code. The following note
from the manual should always be considered:

Important Guidelines
“This manual provides most of the information you need to prepare your site. It is
believed that the guidelines and recommendations in this manual meet or exceed
applicable government electrical codes and regulations. If differences occur between
this manual and codes and regulations, codes and regulations take precedence.

The guidelines and recommendations cover most situations. At some sites, specific
peculiarities may require alternate approaches. If your site requires a different
approach, contact your Emerson Process Management local business partner or field
sales office (LBP/FSO).”

It can be argued that the Site Preparation manual does not conflict with the electrical code, but
it certainly goes beyond the code when it comes to handling EM noise and the grounding of
signal shields. As a result, Emerson has re-evaluated the recommended installation practices
to help customers and engineering consultants optimize the installation costs by aligning these
practices with accepted industry practice.
DeltaV Whitepaper
September 2010 – Page 3 DeltaV Grounding Options

AC Ground
The intent of the AC ground bar as defined in the NEC Handbook (NFPA 70) in particular with
respect to article 250, is generally to provide a connection for equipment grounding
conductor(s) when AC power is brought into a metal enclosure. A bonded connector must be
provided between the metal enclosure and the AC ground Bar. The AC ground bar must be
connected back to the equipment grounding terminal bar located at the power distribution
source. All metal equipment casings, panels, DIN rails and so on in a cabinet must be
grounded appropriately in order to mitigate a short circuit of any AC feed and ensure a good
ground path back to the source.

Some grounding diagrams shown in the Site Preparation manual show the AC ground bar
connected to the DeltaV instrumentation grid, and also connected back to the equipment
grounding terminal bar. The purpose of this additional connection to the DeltaV instrumentation
ground is to improve the noise dissipation capability of the AC ground by providing a low
impedance, unique direct path to ground (true earth) for the higher frequency noise. This
makes the DeltaV AC ground suitable for shield noise dissipation, isolating this noise from the
DC ground reference. However, this additional connection adds cost to the site installation
and is not required for purposes of proper AC grounding. According to the ISA grounding
scheme and customer accepted practice, the AC ground should not be connected to the
instrument ground.

Figure 1 - ISA recommended ground scheme


DeltaV Whitepaper
September 2010 – Page 4 DeltaV Grounding Options

Without this additional connection to the dedicated low-Z instrument ground, the AC ground is
no longer a suitable location for connection signal shields. As shown in the ISA grounding
scheme, signal shields are therefore connected to the DC Ground for a low impedance direct
path to ground. The following diagram shows a typical Site Preparation manual diagram with
the AC ground connection to the DeltaV instrumentation ground removed.

Figure 2 - Modified DeltaV Grounding scheme

Notice that in figure 2, the shield bars are connected to the DC Gnd Bus bars, along with the
DC Common of the 24 VDC Bulk power supplies. The Site Preperation manual and DeltaV
installation manuals will provide more details on the DeltaV equipment installation. The point
here is that the DC ground system is completely isolated from the AC ground and used
isolated bus bars all the way to the DeltaV instrumentation ground.
DeltaV Whitepaper
September 2010 – Page 5 DeltaV Grounding Options

To avoid further confusion on this topic and to help customers manage the cost of their
installations, the Site Preperation manual will be updated to remove the specific instructions to
connect the AC ground bars to the DeltaV instrumentation ground. To support this, the manual
will instruct users to connect DeltaV shield bars and all control signal shields to the DC ground
reference. The update will effectively remove specific DeltaV requirements to the AC power
and grounding system, allowing this installation to be governed solely by the appropriate local
electrical code.

DC Ground
With respect to the DeltaV instrument ground and DC ground reference bars, there is little
change to be made to the Site Preparation manual other than to indicate that shield bars and
signal shields should be connected directly to the DC ground reference. It is always important
to note that the quality of the DC ground reference has direct impact on the availability of any
control system, not just DeltaV systems.

System Power Isolation


Isolation transformers are frequently referred to in the Site Preparation manual. Are they really
needed? After all, the control system components are powered by AC/DC bulk power supplies
that provide 1500 VDC of isolation from the AC power.

When connecting the AC ground to the dedicated instrument ground, it is extremely important
to isolate the AC ground system from undue noise and transients eminating from other process
equipment, such as variable speed drives, welders, commutated motors, and other major
noise culprits. The isolation tranformer protects the quality of the instrument ground and is
highly recommended. But if the AC ground is not connected to the instrument ground, is the
isolation tranformer still needed? There are other AC powered devices in the control system
such as workstation computers, servers and network communication gear, which are sensitive
to dirty AC power and grounding. It is important to protect these devices from transient noise
eminating from heavy process equipment. The isolation transformer is an effective solution to
dirty AC power and can help ensure reliable operation of these devices. It is much less
expensive to install an isolation transformer during site preparation than to add it during plant
start up or after a period of troubled operation. The decision to install the transformer must be
made after careful consideration of the the site-specific conditions. It is considered by many to
be a sound investment.

The need for an Isolation transformer is a site-specific issue and is dependent on many
factors. It is likely more difficult to justify not installing this device, since it is a good insurance
measure to achieving stable operation of electronic devices. Ultimately, it is a decision for the
electrical engineering team and not a requirement for the system,
DeltaV Whitepaper
September 2010 – Page 6 DeltaV Grounding Options

Floating AC Ground
Removing the connection of AC ground to the dedicated DeltaV instrument ground also
changes the way in which the AC power distribution system must be grounded. The AC power
and grounding system can now be designed with floating or high-resistive grounds, in
accordance with applicable electrical code. The DeltaV DC power must remain solidly
grounded as detailed in the Site Preparation manual. The controller and I/O components are
certified based on the prescribed grounding of the equipment. Note that DeltaV AC discrete
I/O products are tested and certified for use with solidly grounded AC systems and should not
be used on a floating or high-resistive ground. Isolated AC channels are permitted. The Bulk
Power supplies are able to provide up to 1500 VDC isolation from the AC power, and they
must be installed per the manufacturers’ instructions. The end result is that the AC Power and
Grouding is entirely governed by the applicable codes and regulations and is independent of
the DeltaV DC power requirements.

Summary
The primary change coming to the Site Preparation manual is the location of signal shield
connection. By shifting the shields to the DeltaV DC ground reference and removing the
connection for the AC ground bar to the DeltaV instrumentation ground, the conflict with
accepted industry practice is eliminated and AC power and grounding systems can be
designed strictly per applicable code. These changes have the potential to reduce the cost of
the power and grounding installation by simplifying the AC ground requirements. The new
version of the guide will make this much clearer.

To locate a sales office near you, visit our website at: For large power, water, and wastewater applications
www.EmersonProcess.com/DeltaV contact Power and Water Solutions at:
Or call us at: www.EmersonProcess-powerwater.com
Asia Pacific: 65.777.8211 Or call us at:
Europe, Middle East: 41.41.768.6111 Asia Pacific: 65.777.8211
North America, Latin America: +1 800.833.8314 or Europe, Middle East, Africa: 48.22.630.2443
+1 512.832.3774 North America, Latin America: +1 412.963.4000

© Emerson Process Management 1996-2010. All rights reserved. For Emerson Process Management trademarks and service marks, go to:
http://www.emersonprocess.com/home/news/resources/marks.pdf.

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be
construed as warrantees or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed
by our terms and conditions, which are available on request. We reserve the right to modify or improve the design or specification of such products at any time
without notice.