Sie sind auf Seite 1von 2

ES-127

For Institutional, Industrial, and Commercial Applications


Job Name

Contractor

Job Location

Approval

Engineer

Contractors P.O. No.

Approval

Representative

Series 127SS
Process Steam Pressure
Regulators
Sizes: 12" 4" (15 100mm)
Series 127 Process Steam Pressure Regulators are single
seated, direct acting, diaphragm type regulators ideal for
institutional, industrial, and commercial applications. They
are engineered and recommended for mainline and high
capacity process service heating applications. Watts engineers gave particular attention to the convenience of maintenance and the need to quickly restore regulator service when
maintenance is required. The springs and diaphragm chamber assemblies of Series 127 are easily changed and the
valve is simple to adjust.

127SS

Features

Bronze body, threaded connection (127SS)


Iron body, Flanged connection (F127SS)
Single seated, direct acting
Standardly furnished with stainless steel valve disc

Models
127SS Bronze body, threaded connections, and
stainless steel disc 12" 3" (15 80mm)
F127SS Iron body, flanged connections, and stainless
steel disc 3" and 4" (80 100mm)

Pressures
Maximum Working Pressure: 127SS initial pressures up to
250psi (17.2 bar)
Maximum Working Pressure: F127S initial pressures up to
125psi (8.6 bar)

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

F127SS

Materials
Body 127SS: Bronze
Body F127SS: Iron
Diaphragm: Buna-N on Nylon
Seat/Trim: Stainless Steel and Nickel Alloy
Disc 127SS/F127SS: Stainless steel

Dimensions
MODEL

SIZE (DN)

DIMENSIONS (APPROX.)
B

A
mm

in.
12

127

15
34
127
20
127
1
25
127
114
32
127
112
40
127
2
50
127
212
65
127
3
80
F127*
3
80
F127*
4
100
*Iron body, flanged connections

in

mm

in

mm

in

mm

in

mm

4
4
414
412
514
6
714
8
8
1218

102
102
108
114
133
152
184
203
203
308

16
16
1618
1638
1634
1718
1778
1812
2012
2114

406
406
410
416
425
435
454
470
521
540

15
15
15
1518
1514
1538
1534
1618
1634
1634

381
381
381
384
387
391
400
410
425
425

1
1
118
114
112
134
218
238
334
412

25
25
29
32
38
44
54
60
95
114

D
A

Capacities
Quick Reference Capacity Chart
MAXIMUM CAPACITIES In Pounds or Kilograms (lbs. or kgs.) per Hour of Steam
INITIAL
PRESSURE

FROM 50PSI
(3.4 BAR)

FROM 100PSI
(6.9 BAR)

FROM 150PSI
(10.3 BAR)

FROM 200PSI
(13.8 BAR)

FROM 250PSI
(17.2 BAR)

REDUCED
PRESSURE

UP TO 20PSI
(1.4 BAR)

UP TO 50PSI
(3.4 BAR)

UP TO 70PSI
(4.8 BAR)

UP TO 90PSI
(6.2 BAR)

UP TO 125PSI
(8.6 BAR)

MODEL

127
127
127
127
127
127
127
127
F127
F127

SIZE (DN)
in.

mm

lbs./hr.

kgs./hr.

lbs./hr.

kgs./hr.

lbs./hr.

kgs./hr.

lbs./hr.

12

15
20
25
32
40
50
65
80
80
100

218
492
878
1370
1973
3518
5494
7906
7906
8301

99
223
398
621
895
1596
2492
3586
3586
3765

387
875
1560
2436
3508
6253
9766
14054
14054
14756

175
397
708
1105
1591
2836
4430
6375
6375
6693

555
1255
2237
3493
5030
8967
14006
20154
20154
21161

252
569
1015
1584
2282
4067
6353
9142
9142
9598

731
1653
2943
4599
6623
11807
18442
26538

1
114
112
2
212
3
3
4
34

kgs./hr.

332
750
1131
2086
3004
5356
8365
12037

lbs./hr.

900
2037
3631
5668
8163
14553
22730
32709

kgs./hr.

408
924
1647
2570
3703
6601
10310
14837

EXAMPLE: Initial Pressure is 100psi (6.9 bar), Reduced Pressure is 50psi (3.4 bar) and Capacity required is 1500 lbs. (680 kgs.) of
steam per hour. By referring to the proper initial reduced pressure column From 100psi/Up to 50psi (6.9 3.4 bar), you will find the capacity of 1560 lbs./hr. (708 kgs./hr.) for the 1" (25mm) Model 127 valve corresponds most closely to the required capacity of 1500 lbs./hr.
NOTE: For reduced pressures greater than those shown for each Initial Pressure column above, refer to the Detailed Capacity Table in the
Watts brochure F-127. Be sure to determine both Initial Pressure and Reduced Pressure setting, or the range required.

A Watts Water Technologies Company

ES-127 1128

USA: No. Andover, MA Tel: (978) 688-1811 Fax: (978) 794-1848 www.watts.com
Canada: Burlington, ON Tel: (905) 332-4090 Fax: (905) 332-7068 www.wattscanada.ca

2011 Watts