Specific Gravity of Battery Cells Electrolyte in a battery has dried off Transfer electrolyte to balance
is not same charge.
Cell uses excessive water Caused by overcharging, high Remove the cause
operating temperatures, or leaking
cell
Cell uses very little water Caused by insufficient charging Ensure battery is charged fully
Antimony deposit dark-slate Caused by charging at too high a Connect / Replace charger
patches on negative plates rate or an aged cell nearing the end Caused due to wrong charger.
(usually near the terminal) of its service life. Replace the charger.
Problem
Battery discharging very quickly
Check
When batteries become old, their charge holding capacity reduces.
To test if your battery is good or dead, you can perform Load Test.
Troubleshoot
• Batteries must be fully charged-up for doing load test. If not, then first
• recharge the batteries to full voltage level.
• Disconnect batteries from being charged
• Take a battery and connect Voltmeter across it terminals.
• Connect a heavy 12 Volt DC load (like a 12 Volt Fan) directly to the battery
and observe change in the voltage across it. Battery should maintain
voltage of 10.5 Volts or higher while on load. If it falls below that voltage,
there is problem with the battery, and it needs to be replaced.
System Diagnostics
Battery Load Test
Outcome
With this test you will be able to test if your
battery is good or dead
Load Test
• Batteries must be fully charged-up for doing
load test. If not, then first recharge the
batteries to full voltage level.
• Disconnect Solar Panels from Charge
Controller. Remove Solar Panels first, because
if you disconnect the batteries first, power
from Solar Panels can damage the batteries
• Switch OFF Load from Charge Controller
System Diagnostics
Wash the top of the battery with hot water until all the corrosion
is gone
Clean the positive post with a battery cleaning brush, then the
battery cable
The corrosion is gone when the post and cable are shiny
Eliminating Corrosion
+ -
Battery 1 Battery 2
- +
Short Circuit Risks in Batteries
+ -
Battery 1 Battery 2
+
outgoing
-
-
incoming
batteries batteries
+
-
-
-
-
Charge Equalization
Balancing voltage of batteries connected in series
Observe different terminal voltage of two batteries connected in CHARGE
series CONTROLLER
+ Batt. -
Vbatt1 = 12.3 V Vbatt2 = 11.6 V
Veq. = 23.9 Volts Vdiff. = 0.7 Volts
Now lets understand what happens when this charge controller
starts charging the battery 12.3
Ideally maximum charging voltage of a battery should be 14.2 V, and V
-
for two batteries connected in series is 28.4 V.
Here CC will disconnect at voltage Vbatt1 = 14.55 V, Vbatt2 = 13.85 V
Here we can see Battery 1 is overcharged (which reduces its life), and
battery 2 is undercharged (its full capacity is not utilized) 11.6
V
-
To overcome this problem we use charge equalizers to balance
voltage of batteries connected in series.
Charge Equalization
+
-
-
imbalance in between batteries at a stable
charging/discharging rate.
Charge Equalization
Battery Battery
• Allow batteries to equalize for around 15-20 1 2
+
minutes, now batteries are equalized and ready
-
for commissioning
Charge Equalization
+
-
-
• When equalizer is working, the equalizer light
blinks at a very fast pace. And when charge
equalization is completed blink rate of Charge
controller slows down.
Deep Discharging
Correct Method
Connect Deep Discharged battery in series with
a fully charged battery
Ah capacity of Charged Battery should higher
then that of Deep Discharged battery
Voltage of Charged battery might drop to
below its nominal range while charging of
Deep Discharged battery, thereby Good
battery can also be damaged while reviving a Deep Discharged
Battery (75 Ah)
Correct Method
• Negative terminals of all
batteries are connected to
each other
• Similarly Positive terminals of
all batteries are connected to
each other Normal Battery
180 Ah
• Note: Charge Capacity of Live initially at 12.5 volts
batteries should be higher
then that of Deep Discharged
batteries Deep Discharged
Battery (75 Ah)
Initially at 6 volts
Battery Problem