Introduction
The Power Manager 345 has an internal transformer that powers a Reset Module 420, 421, 422, or 423. A single tN4 bus
input is available to allow Zone Managers and in some cases, Mixing Expansion Modules, to be connected.
Features:
• tN4 Compatible
• Internal 56 VA Transformer
• CSA C US Certified for use in USA and Canada
Aux tN4 C R C R
Pmp 1 24 V (ac)
1 2 3 4 5 6 Limited power available, see wiring brochure
24 V (ac) Fuse: T2.5 A 250 V
Power
Aux Pump
tektra 996-03
7 8 9 10
Input Power Aux Pump Made in Canada
Supply/signal wires 90°C min. H7012A
L N Pmp N
Test
tN4 Thermostat
or
Reset 345 Zone Zone
tN4 Setpoint Control Module Power Expansion Manager
Manager Module
System
Pump
Mix 1 Bus
Mixing
Expansion
Module Zone Expansion Module 325
tN4
Mix 2 Bus
Mixing
Expansion
Module
Mix 3 Bus
Zone Expansion Module 325
tN4
Mixing
Pump Zone Manager
Location 2
Primary
Pump Mixing Zone Manager
Pump Location 3
Mechanical Room
Auxiliary Pump
Zone Group Pump The auxiliary pump can be used in two different ways:
1) In single zone applications, a tN4 Thermostat or tN4
The 345 includes an auxiliary pump input (terminal 1) and
Setpoint Control activates the auxiliary pump output to
a powered auxiliary pump output (terminals 9 and 10).
power the system pump.
When the auxiliary pump input is powered with 24 V (ac),
the auxiliary pump output is energized with 115 V (ac). 2) In applications with Mixing Expansion Modules, the low
voltage system pump output on the Mixing Expansion
Module activates the auxiliary pump output to power the
system pump.
Power LED
Green: Power Manager 345
• Normal operation.
Amber:
• Power is present but the fuse for the internal 24 V (ac)
Power
transformer is blown. Aux Pump
Off:
• No power to the Power Input of the Power Manager.