INSTRUMENT CABLES
Single triad shielded signal cables shall be used between RTD head and junction
boxes / transmitters / local control panel mounted instruments.
For fieldbus compatible instrument single pair shielded cable shall be used
between instrument to junction box/ local panel and to control room.
Foundation Field bus shall be Type-A cable. Construction of same shall be as Per
IEC 61158-2. Trunk cable shall be used of 1 Pair, 5 Pair, 12 Pair.
Single pair shielded signal / alarm cables shall be used between field instruments
/ switches and junction boxes / local control panels.
Separate Multipair/ multitriad cables shall be used between junction boxes/ local
control panel and control room as per following applications. • 4-20 mA signals
(for conventional HART Transmitters) • Foundation Field signals •
Thermocouple signals • Resistance Temperature Detectors (RTD) signals •
Switch contacts / Proximity switch contacts • Gas detectors
1 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
For solenoid valve signals and power supply to instruments, junction boxes shall
be used
The cable design shall generally follow BS 5308 Part-1 for various cables above.
Thermocouple cables design shall comply with ANSI MC 96.1. The power and
control cables shall be generally as per BS 6346. For these cables, equivalent
IEC/IS specifications are also acceptable
All cables shall be armoured and suitable for operation when installed as follows:
– Directly buried in the ground – Fastened to cable ladder rack or tray in the
open air – In underground ducts – In overhead closed cable ducts
Running length of the cable shall be printed at least at every 5 meter interval. For
multipair/ multi-triad cables, pair identification shall be provided with numbers
at interval of not more than 250 mm as per standard.
2 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
insulation.
3 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
4 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
5 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
6 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
CABLE CONSTRUCTION
The various mechanical / electrical parameters indicated here are indicative and
shall be select / design the cables as per applicable standards.
7 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
8 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
RTD cables:
9 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
10 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
Thermocouple Cables:
11 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
12 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
Note : All thermocouple extension cable shall be matched and calibrated in ac-
cordance with IEC-60584-2 / ANSI MC 96.1
Control cables:
13 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
Power cables :
14 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
Ethernet cables
EIA/TIA 568 A Category 5, 4 pair 0.5 mm2 (24 AWG) solid conductors, with
plastic foil wrapping. Overall screen to consist of aluminium bonded polyester
tape and tinned copper wire. Overall sheath shall be light grey PVC.
62.5 / 125 micron multimode, graded index, glass silica fibre core, mechanical
protection provided by round galvanized steel armour with polyester laminated
15 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
tape layered over inner sheath. Outer sheath shall be orange.HDPE conduit shall
be orange colour.
Cable Testing:-
Type Test:-
Certificate from independent test house for the following tests shall be furnished
for the FRLS low halogen sheathed cable.
16 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
CABLE DRUMS
Drum identification shall be painted black on both sides of drum with permanent
oil paint. The following information shall be given on the drums as a minimum:
Signal Cables:
17 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
Thermocouple Cables:
18 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...
CABLE GLANDS
Cable glands shall be of SS 316 and double compression type suitable for
armoured cables.
For all field items and junction box end, NPT threaded cable glands shall be used
and for control room / control panel end, cable glands shall be ET threaded
types.
JUNCTION BOXES
Junction boxes shall be of die-cast aluminium alloy (LM-6) epoxy painted body.
All junction boxes shall be weatherproof to IP 66 as a minimum. Flame proof
junction boxes wherever required shall be supplied with Ex (d) certification. All
flame proof JB’s shall be provided with labels for isolating power supply before
opening cover. All JB’s for intrinsic safe signals shall be identified on name plate
accordingly.
Each JB shall be provided with 2 multi-cable entries with one plugged with
weather proof, explosion proof plugs as required.
19 of 20 7/22/2019, 1:51 PM
STANDARD SPECIFICATION FOR INSTRUMENTATION CABLES ... https://instrumentationsuyog.wordpress.com/2019/07/10/standard-specifi...