Sie sind auf Seite 1von 7

818 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 38, NO.

3, MAY/JUNE 2002

DC Traction Power System Grounding


Dev Paul, Senior Member, IEEE

Abstract—This paper provides a review of the present practice


of dc traction power system grounding methods employed in
North America. An analysis of equipment grounding, system
grounding, and their relationships to achieve optimized equipment
and personal safety is derived. Generic protective relay schemes
commonly used in the dc equipment enclosure grounding are
shown. Rail leakage stray current and personnel safety affected
by the dc system grounding method are discussed. To enhance
personnel/equipment safety, specific recommendations for the
design of the dc traction power system grounding are included.
Index Terms—Equipment grounding, rail-to-ground potential,
rapid transit system, stray current, system grounding, touch po-
tential.

I. INTRODUCTION

R APID TRANSIT systems are expanding at great speed


throughout the world, including North America. However,
there is very little effort toward development of standards for dc
power system design and protection as compared to ac power
systems used for general industry. Each new transit project be- Fig. 1. DC electrification one-line diagram. 1: Rectifier unit; 2: dc switchgear;
gins with its own set of design directive documents and applies 3: negative bus box; 4: equipment grounding protection; 5: system grounding
equipment and system grounding methods that may not be fully protection.
evaluated due to lack of clear understanding of their relation-
ship to stray current and personnel safety. It is the author’s view quirements of minimizing dc stray current and maximizing per-
that there are times when the low-resistance and high-resistance sonnel safety through the design of dc power system grounding
equipment grounding methods used for dc power systems may protection schemes is discussed.
be misunderstood to be the power system grounding in accor-
dance with the definition of ac power systems grounding. At II. DC TRACTION POWER SYSTEM
present, there are no recommended guidelines or industry stan- In a dc traction power system, current from the traction power
dards that cover dc traction power system grounding, unlike the substations is delivered to the moving trains by either the third
color book series [5] that covers ac power system grounding. rail or the overhead contact system (OCS) and is returned to the
This paper attempts to provide the ABCs of dc equipment substations by the track running rails. The installation configu-
enclosure and dc traction power system grounding methods and ration of the traction power substation stations (TPSSs), positive
their relationship. Only the protective relay schemes associated and negative feeder cable runs, and the track running rails is such
with dc equipment enclosure grounding and system grounding that the third rail or the OCS acts as a long positive conductor
are described. The overall dc rapid transit system protective and the cross-bonded running rails as the negative conductor,
relay scheme is beyond the scope of this paper. Interested while each TPSS is in parallel between these two positive and
readers are encouraged to read dc breakers protection duty negative conductors. Sectionalizing of the positive conductor is
requirements indicated in [9]. provided by the dc feeder breakers at each traction power substa-
A typical dc electrification one-line diagram of a rapid transit tion. Sometimes, gap stations are employed in the middle of the
system with grounding protective relay schemes covering the two traction power substations to increase the sectionalization,
equipment and dc power system grounding methods is included especially for a 1500-V dc system when the distance between
in Fig. 1. A way to accommodate two different contradictory re- the traction power substations is relatively large. Under normal
system operation, to minimize dc stray current and its associ-
Paper ICPSD 01–51–5, presented at the 2001 Industry Applications Society ated corrosion effects on underground utilities, the running rails
Annual Meeting, Chicago, IL, September 30–October 5, and approved for and the dc traction power system negative are kept ungrounded.
publication in the IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS by the
Power Systems Protection Committee of the IEEE Industry Applications Present practice when designing the dc traction power system
Society. Manuscript submitted for review October 15, 2001 and released for is to keep rated voltage in the range of 600–1500-V dc with 750-
publication March 18, 2002. V dc the normal choice of many projects [3]. The dc switchgear
The author is with Earth Tech, Oakland, CA 94612-3060 USA (e-mail:
Dev_Paul@earthtech.com). [4] consists of single-polarity (positive) dc circuit breakers of
Publisher Item Identifier S 0093-9994(02)05009-0. either the high-speed or the semihigh-speed type [11] to supply
0093-9994/02$17.00 © 2002 IEEE
PAUL: DC TRACTION POWER SYSTEM GROUNDING 819

dc power to the train propulsion system via third rail or OCS


system. The negative-polarity bus box is physically kept sepa-
rated from the dc switchgear.
Fig. 1 represents various components of the dc electrification
system including the vehicle. It should be noted that the vehicle
touch potential is practically the same as the rail-to-ground po-
tential, especially if there is no other provision for grounding
the vehicle [7].
To properly address the subject of grounding, there should be
a clear understanding of the differences between “equipment”
grounding and “system” grounding. Equipment grounding
refers to grounding of the enclosures of the rectifier unit and
dc switchgear. System grounding refers to grounding of the
current-carrying conductor of the dc negative system. This
negative system is the negative of the rectifier unit at each TPSS
and the track running rails carrying negative return current.
The three basic configurations: 1) ungrounded; 2) impedance Fig. 2. HRGM. 64M: Ground-fault monitoring relay; 64T: enclosure live fault
grounded; and 3) effectively grounded that apply to ac power trip relay.
systems [5] could very well apply to dc traction power systems.
Under normal system operation, there is no direct intentional ommended that they be connected to ground only by pro-
electrical connection between the dc negative and the ground. tecting or indicating devices of relatively high resistance.
However, this ungrounded system establishes reference to The National Electrical Code [6] Article 250–110 (1) states
ground through leakage resistance of the running rails. This that the exposed noncurrent carrying metal parts of fixed equip-
leakage resistance depends upon the track insulation material ment likely to become energized shall be grounded if within 8 ft
and is generally on the order of 200 /1000 ft/rail under normal vertically or 5 ft horizontally from grounded surface and subject
dry weather conditions [5]. This value is subject to change to contact by persons.
depending upon type of track construction, weather conditions, It has been recognized by the transit industry that dc equip-
and age of the tracks due to accumulation of metallic dust. Thus, ment enclosure rectifiers and metal-enclosed dc switchgear
the ungrounded dc traction power system in reality is grounded should be grounded by using an appropriate protective relay
through an equivalent rail-to-ground leakage resistance scheme for safety of personnel and equipment. This protection
value derived by expression (1), assuming all four running rails relay scheme, which employs either high-resistance or low-re-
of the double-track system are cross bonded sistance equipment grounding methods, has been a subject of
many debates and discussions among equipment suppliers,
(1) design engineers, and transit authority representatives. Each
transit property employs one or the other grounding method
where represents the sum of half the distances in miles be-
depending upon their own understanding of the safety and
tween adjacent traction power substations.
design issues [3]. It should be mentioned that the tolerable
These inherent characteristics of the dc traction power system
touch potential for a dc system is relatively higher, on the order
being grounded through its rail leakage resistance will establish
of 3.5 times, than an ac system [14].
the return path for the positive-to-ground fault current.
A. High-Resistance Grounding Method (HRGM)
III. EQUIPMENT GROUNDING
The equipment is completely insulated/isolated from all sur-
Design of the dc equipment enclosure grounding shall as- rounding grounded structures by using insulated floor, insu-
sure maximum safety of personnel and equipment under fault lated conduit bushings, and insulated substation walls facing
conditions. the equipment. A constant voltage on the order of 25-V dc is
Early published literature [1], [2] indicates that danger to per- applied between the enclosure and ground (see Fig. 2). This
sonnel results from high dc short-circuit currents due to associ- voltage produces current high enough to energize relay 64M
ated fire, molten metal, and brilliant flash rather than electric but not relay 64T. Upon loss of this voltage or in case of enclo-
shock risk due to dc voltage present at the equipment enclosure sure-to-ground fault, relay 64M will deenergize to provide en-
under fault conditions. At that time, grounding of one polarity of closure ground-fault alarm indication. In case of a dc-bus short
the dc system was standard practice for the railway and mining to the enclosure, the current will be high enough to energize
industries. As a result of these experiences, the development of relay 64T to trip the substation ac and dc breakers to clear the
high-resistance equipment grounding protective relay schemes enclosure live fault condition. Shorting switch device 57 and
became the norm of the transit industry in the U.S. These prac- overvoltage relay device 59 are components of one of the system
tices lead to the inclusion of the following in ANSI C37.20.1 [4] grounding schemes that follow. It is worth mentioning that the
resistance value of the HRGM scheme will assure that during
Exception: LV switchgear having single polarity dc cir- equipment fault (arcing or bolted), the reasonable setting of de-
cuits, rated above 250 V, shall be ungrounded. It is rec- vice 59 will allow its activation to clear the enclosure live fault.
820 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 38, NO. 3, MAY/JUNE 2002

Fig. 4. Solidly grounded system.

Fig. 3. LRGM. 74: Alarm relay; 64: enclosure live fault detection trip relay.

B. Low-Resistance Grounding Method (LRGM)


The equipment enclosure is kept insulated/isolated from all
surrounding grounded structures. The enclosure is grounded at a
single point by a low-resistance protection relay scheme (Fig. 3).
A low voltage on the order of 1-V dc is applied between the
enclosure and ground to monitor integrity of the low-resistance Fig. 5. Diode-grounded system.
grounding protection. Alarm relay device 74 will provide alarm
when this voltage is interrupted or there is enclosure ground
condition. During enclosure live fault condition, relay device Various methods employed to achieve the system grounding
64 will energize to trip the substation ac and dc breakers due schemes and their limitations are discussed.
to relatively higher magnitude of fault current when switch 57
closes upon energization of relay device 59. Transfer tripping of A. Solidly Grounded System
the dc feeder breakers at adjacent substations is a must to clear The negative of each substation is grounded to the local
the fault on the load side of local dc feeder breakers. Without this ground grid without any intentional impedance in the grounding
transfer tripping, major equipment damage has resulted with a circuit Fig. 4. It should be recognized that the running rails’
low-resistance equipment grounding scheme. negative return circuit effectively becomes in parallel with the
ground and, thus, a considerable part of the negative return
current may seek the path of ground, increasing the threat of
IV. DC POWER SYSTEM GROUNDING
corrosion to underground utilities in vicinity of the tracks.
Design of the dc power system grounding needs to compro- Drainage bonds between underground utilities near the traction
mise two contradictory requirements: 1) minimum dc stray cur- power substation and electrical bonding of underground util-
rent and 2) maximum personnel/equipment safety. To achieve ities in the vicinity of the tracks is mandatory to mitigate the
this objective, system grounding should be designed to satisfy corrosion effect of dc currents. This method may exist only in
the following basic requirements. older transit systems. The modern systems do not employ such
1) Under normal system operation, the grounding system a grounding system.
should minimize dc stray current. This can be achieved by
keeping the system ungrounded, i.e., floating. No inten- B. Diode-Grounded System
tional connection is made between system negative and Paralleled array of diodes with a shorting dc contactor and
ground. protection relays are employed at each traction power substa-
2) Under abnormal system operation with unsafe tion (Fig. 5). Upon detecting a set voltage level, relay device
rail-to-ground potential, the system should be grounded 59 energizes a dc contactor to automatically ground the nega-
by shorting the negative polarity to ground to suppress tive system. Directional overcurrent relay device 32 opens the
the unsafe voltage. The method of shorting the rail or the shorting contactor for low-level “forward” currents and trips the
substation negative bus box to ground shall be achieved traction power system if high-level ground-fault current con-
automatically through protection relays and shorting tinues to flow. It should be noted that, under normal system
devices in the shortest possible time. Upon clearing this operation, for small magnitudes of voltage difference between
abnormal situation, the system will automatically return rail and ground, the diodes are always conductive, thus setting
to the original stage of an ungrounded power system. a stage for relatively higher stray currents.
PAUL: DC TRACTION POWER SYSTEM GROUNDING 821

Fig. 6. Automatic grounding switch. Fig. 8. Thyristor grounding system.

relay device 59X to ground the negative system. This limits


the potentially dangerous rail-to-ground voltage by allowing
current to return to the source. The contacts of instantaneous
current relay device 50 energize time delay auxiliary relays
50X1 and 50X2. After a short delay upon sensing decrease in
the current, device 50X1 provides an alarm as well as provides
gate-turn-off signal to the thyristor to resume its normal
position of an ungrounded system. However, if the current
continues to flow in case of positive-to-ground fault, then after
a preset time delay device 50X2 will trip all dc feeder breakers.
The setting of relay device 59 may be set on the order of 60
V, which is considered safe touch potential. This will allow
Fig. 7. Ungrounded system. the system to operate ungrounded for normal conditions until
ground-to-negative rail potential rises to the set limit of 60 V
under abnormal positive feeder-to-ground fault condition.
C. Automatic Grounding Switch
The dc feeder breakers will automatically close through the
Shorting switch device 57, overvoltage relay device 59, and load-measuring protective relay scheme except for the faulted
overcurrent relay device 50 are employed at each traction power feeder circuit breaker and, thus, provides a positive indication
substation (Fig. 6). Upon detecting a set voltage level, device 59 of the faulted circuit.
activates and closes the shorting switch to automatically ground It should be mentioned that a bidirectional GTO unit may be
the negative system. Upon sensing short-circuit current, device required, depending upon the system configuration and exces-
50 activates to deenergize the traction power substation. In ad- sive train starting currents resulting in dangerous rail voltage
dition, device 50 provides local indication and remote alarm to rise above ground. Such a design if implemented should have
manually reset the shorting switch. It should be mentioned that GTO activation counters, and a voltage and current monitoring
a shorting switch is a mechanical device and takes definite time device scheme to optimize the settings of device 59 to assure
to activate; dangerous voltage could occur during this time. maximum safety and minimum stray current injection.
The advantage of the bidirectional thyristor scheme over the
D. Ungrounded (Floating) System grounding diode scheme is that the thyristor unit will ground the
The system is kept ungrounded under normal and abnormal system only when the set dangerous voltage occurs due to either
conditions (Fig. 7). This system provides the least stray current; train bunching load currents or due to positive-to-ground faults
however, it may prove to be dangerous to the general public and that develop. Under normal system operation below the set neg-
maintenance persons as the vehicle or running rails may be at ative-to-ground overvoltage, the system is kept ungrounded and,
an elevated dc voltage with respect to ground, especially during thus, stray leakage current is minimum.
positive-to-ground fault. This method is not used in present
transit systems for safety reasons, especially under abnormal
V. DC EQUIPMENT ENCLOSURE FAULT
fault conditions.
Bridging of the dc bus to the enclosure may lead to bolted
E. Thyristor-Grounding Method fault or arcing fault inside the dc enclosure. Depending upon the
The various protective relay devices of the thyristor- condition of the power system being ungrounded or grounded,
grounding scheme are shown in Fig. 8. Overvoltage relay fault current will be controlled by the various resistance param-
device 59 continuously checks the negative-to-ground voltage. eters defined below.
When this voltage exceeds a preset value, the relay triggers Running rails leakage resistance. This can be com-
the thyristor gate [gate-turn-off thyristor (GTO)] by auxiliary puted by using expression (1).
822 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 38, NO. 3, MAY/JUNE 2002

Substation ground grid resistance. This value can be TABLE I


on the order of 5 or less by proper design of TPSS HIGH-RESISTANCE AND LOW-RESISTANCE EQUIPMENT GROUNDING METHODS
ground grid.
Equipment grounding protection scheme resistance.
System nominal dc voltage.

A. Ungrounded Power System


Steady-state dc bolted fault current and arcing fault cur-
rent inside the dc equipment enclosure may be computed
by using the following expressions when the power system is
ungrounded:

(2)
(3)

B. Grounded Power System


When any of the system grounding protection schemes
grounds the negative rail, then the value of rail-to-ground
resistance as well as the local ground grid resistance in expres- * Indicates values associated with double track lengths of 5 miles with leakage
sions (2) and (3) will become zeros, thus increasing the fault resistance of 200
/1000 ft/rail, ungrounded system.
current values. The fault current expressions for the grounded ** Indicates corresponding values for track length of 10 miles, ungrounded
system (grounding points of equipment ground circuit and the system.
grounding point of the negative rail or bus connected to same *** Values for the grounded system, when grounded by any of the system
ground grid) will be as follows: grounding methods connecting negative rail to ground by voltage-sensing
relay device 59.
(4)
(5) the case of the HRGM is small compared to the low-resistance
method. This may not be detected by system grounding relay
Expressions (2)–(5) are for comparing grounding configura- device 59.
tions only and not for computing accurate dc short-circuit cur-
rent. It should be noted that the enclosure touch voltage in case
of arcing or bolted fault between the positive dc bus and the VI. FAULTS OUTSIDE THE DC ENCLOSURE
enclosure is practically the voltage drop across the equipment
grounding protection scheme resistance value. Thus, the touch There is a possibility of two types of faults outside the dc
potential in the case of the low-resistance equipment grounding enclosure on the electrified tracks. These faults are arcing fault
method will be lower than the touch potential in the case of the (positive to ground) and bolted short-circuit fault (positive-
HRGM. However, the corresponding short-circuit current in the to- negative). The arcing fault will generally involve high
case of the low-resistance method will be considerably higher impedance at the fault location, whereas the bolted fault will
than the corresponding value in the case of the high-resistance have no intentional fault impedance at the fault location.
method. Both types of fault currents will be controlled by the system
It is important that the settings of relay device 59 associated grounding resistance parameters and/or rail-to-ground leakage
with the system grounding protection relays be such that de- resistance, irrespective of the type of equipment grounding
vice 59 activates to make the ungrounded system as a grounded method.
system to clear enclosure live fault condition as required. If positive touches ground away from the traction power sub-
The calculated values of bolted and arcing fault currents station, it will lead to a high-impedance fault with low current
shown in Table I are based upon system voltage of 750 V and magnitude. However, the ground potential will be elevated with
ground grid resistance of 5 both for the grounded system and respect to the rail with the possibility of activating relay device
ungrounded system. Voltage drop across the arc is assumed to 59 as shown in system grounding methods. This, in turn, will trip
be 200 V as shown in expressions (3) and (5). the substation feeder breakers to clear the fault condition. Unless
Table I indicates that short-circuit current values in the case the negative is shorted to ground by an appropriate protection
of the HRGM as compared to the corresponding short-circuit relay scheme, fault current is controlled by the rail-to-ground
values in the case of the low-resistance method have very leakage resistance and the fault impedance. In many situations,
little effect by the change from an ungrounded to a grounded this fault current will be so low that the dc feeder breaker protec-
system. Using the short-circuit values listed in Table I, it can be tive relays may not be able to detect and clear the fault condition
concluded that the potential rise of local substation ground in in an appropriate time.
PAUL: DC TRACTION POWER SYSTEM GROUNDING 823

TABLE II difference between the rail and ground, and automatically re-
SYSTEM GROUNDING VERSUS TOUCH POTENTIAL AND STRAY CURRENT turn to the normal state of an ungrounded rail when dangerous
voltage is suppressed.

IX. CONCLUSIONS
1) Generic protection schemes of high-resistance and
low-resistance equipment grounding methods were pre-
sented. With the application of modern microprocessor
and digital relays, individual vendors offer their own
brand names for these grounding protection schemes.
There is no industry standard for the resistance values
VII. DC STRAY CURRENT
used in the low- or high-resistance protective relay
The fraction of the dc load current returning to the traction schemes. Some suppliers may promote their low-resis-
power substation via negative rails leaks to ground due to tance protective relay scheme without establishing its
leakage resistance of the insulation pads between running short-circuit current withstand capability. This could
rails and ground. To minimize dc stray current, voltage drop prove to be destructive and dangerous in the case of
across the negative return rails is kept as low as practical heavy short-circuit current established by the system
and the traction power system negative is kept ungrounded grounding protection scheme. Both the protective relay
under normal system operation. The relative magnitude of scheme as well as the shorting device should be capable
the stray current and the vehicle touch potential for various of withstanding the worst case maximum expected dc
system grounding configurations is shown in Table II. Both short-circuit currents.
the stray current and the human safety seem to be balanced by 2) Both the high-resistance and the low-resistance equip-
the thyristor-grounding method as compared to other system ment grounding protective relay schemes in combination
grounding methods. with the preferred GTO system grounding protection
The protective relays shown in Fig. 8 provide complete scheme should be evaluated. The evaluation should be
tripping and isolation of the traction power system in case based upon the short-circuit and rail-to-ground potential
of heavy short-circuit current due to positive-to-ground fault, rise calculations. The results should be reviewed with the
and automatically return to normal configuration once the equipment supplier.
fault is cleared. Reverse GTO may be used at the stations to 3) The substation spacing should be established by per-
suppress dangerous vehicle touch potential; however, it may forming rail-to-ground potential rise and stray current
unnecessarily increase stray current magnitude. analysis under normal and abnormal system operation.
For system grounding purposes, a bidirectional GTO unit
may be needed, depending upon the system parameters
VIII. SAFETY ANALYSIS
and configuration.
The arc associated with dc current has proven to be very 4) When the passenger stations are physically separated
dangerous to personnel and equipment. Thus, the equipment from the traction power substations, a system grounding
grounding and system grounding protection schemes should be protection scheme with reverse GTO similar to one used
optimized to minimize dc fault current if possible. The design at the traction power substation may be employed at the
should also assure that a person in contact with the faulted dc passenger station. This may increase the personnel safety
equipment enclosure or the transit vehicle is not exposed to the from the high vehicle touch potential under rare cases of
danger of electric shock. DC voltage in the range of 60–90 V simultaneous train starting or train bunching conditions.
is considered safe [7], [14] according to the present transit in- 5) The application engineer should carefully evaluate the
dustry practice. Based upon the present trends of more litigation supplier’s equipment and system grounding protective
from such causes as electric shocks and from the nature of some relay schemes. Evaluation should include the overall
humans with pacemakers or metallic components embedded in reliability and factory tests of microprocessor solid-state
human bones by advances in the medical field, it appears that products to assure that their performance is guaranteed.
the safe dc voltage may very well be lower than 60 V.
To reduce the effect of electric shock to passengers, the sta-
X. RECOMMENDATION
tion platform edges should employ high-resistance rubber mats.
Similarly, inside the traction power substation, insulated floors 1) For safe design practices of a dc traction power system,
with very high volume resistivity compound tend to increase the there is a need for the industry standard for clarification of
operator safety from electric shock. high- and low-resistance grounding protection methods
From the safety point of view, running rails should be with recommended resistance values. The standard
grounded, however, from the stray current point of view, they should review and establish the safe touch dc potential
should be kept isolated from ground. To compromise this for the general public and the substation maintenance
requirement, the system grounding protective relay scheme person, especially now when pacemakers and metallic
should ground the rail upon sensing the dangerous voltage bones have become an integral part of the human body.
824 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 38, NO. 3, MAY/JUNE 2002

2) It is recommended that the low-voltage switchgear [10] J. C. Das and R. H. Osman, “Grounding of AC and DC low-voltage and
committee responsible for upgrading ANSI C37.20.1 [4] medium-voltage drive systems,” IEEE Trans. Ind. Applicat., vol. 34, pp.
205–216, Jan./Feb. 1998.
should review the outdated exception, “LV switchgear [11] IEEE Standard for Low-Voltage DC Power Circuit Breakers Used in
having single polarity dc circuits, rated above 250 V, Enclosures, ANSI/IEEE Standard C37.14-1999.
should be ungrounded. It is recommended that they be [12] “A corrosion control manual for rail rapid transit,” U.S. Department of
Transportation, Washington, DC, Rep. by NASA Design Engineering
connected to the ground only by protecting or indicating Directorate/SRI International/NASA, 1982.
devices of relatively high resistance.” This seems to be [13] C. F. Dalziel and W. R. Lee, “Reevaluation of lethal electric current,”
invalid, as the majority of the modern transit systems IEEE Trans. Ind. Gen. Applicat., vol. IGA-4, pp. 467–476, Sept./Oct.
1968.
are operated ungrounded under normal system operation [14] IEEE Guide for Safety in AC Substation Grounding, ANSI/IEEE Std.
compared to the grounded systems of the past. 80, 2000.

ACKNOWLEDGMENT
The author would like to thank R. Belardo of Earth Tech for
his technical review during the preparation of this paper.
Dev Paul (M’73–SM’90) received the B.Sc. degree
REFERENCES with honors in mathematics and the B.E. (Honors)
[1] “IEEE recommended practices for grounding single polarity DC struc- and M.S.E.E. degrees in electrical engineering from
tures ,” AIEE, Committee Rep., p. 784–790, Oct. 1957. Punjab University, Chandigarh, India, in 1965, 1969,
[2] D. C. Hoffman, “Grounding of DC structures and enclosures,” presented and 1971, respectively. He completed further studies
at the AIEE Winter General Meeting, New York, 1961. in power systems at the University of Santa Clara,
[3] P. Forquer, “Equipment grounding in traction power substations,” pre- Santa Clara, CA, in 1975.
sented at the APTA Annu. Conf., Miami, FL, 1993, Paper 67-R93. In 1972, he joined Kaiser Engineers (now Earth
[4] IEEE Standard for Metal-Enclosed Low-Voltage Power Circuit Breaker Tech), Oakland, CA, as a Design Engineer. He has
Switchgear, ANSI/IEEE Std. C37.20.1. worked on a variety of heavy industrial, cogener-
[5] IEEE Recommended Practices for Grounding of Industrial and Com- ation, commercial, DOD, and DOE facilities, and
mercial Power Systems, IEEE Std. 142-1991. rapid transit rail projects. In his present position as a Senior Professional
[6] National Electrical Code, National Fire Protection Assoc., Quincy, MA, XI, he is responsible for the overall design, analysis, studies, specifications,
1999. installation, project management, system startup, and system integration work
[7] D. Paul, “Operational safety and maintenance considerations for people on rapid transit systems. He has authored several papers published in the IEEE
movers’ DC grounding systems,” presented at the APTA Annu. Conf., TRANSACTIONS ON INDUSTRY APPLICATIONS and American Public Transit
Buffalo, NY, 1988, Paper 175-R88. Association conference proceedings. His main fields of interests are power
[8] K. J. Moody, “Stray current characteristics of grounded, ungrounded, system analysis, protection, grounding, and harmonics.
and diode grounded DC transit systems,” presented at the CORRO- Mr. Paul is an active member of several committees of the IEEE Industry
SION/94, Baltimore, MD, Mar. 1994. Applications Society. He has served as a Treasurer and Vice Chairman for the
[9] J. S. Morton, “Circuit breaker and protection requirements for DC local IEEE Chapter. He received the Award of Distinction for his M.S.E.E. thesis
switchgear used in rapid transit systems,” IEEE Trans. Ind. Applicat., work on power system stability. He is a Registered Professional Engineer in the
vol. IA-21, pp. 1268–1273, Sept./Oct. 1985. States of California, Nevada, and Oregon.

Das könnte Ihnen auch gefallen