1. Study the site plan and elevation of the installation. Determine the lighting needs in
consultation with standard and the end user.
2. Select the light sources and luminaire, appropriate to the installation to the installation
geometry, nature of visual task and energy criteria.
3. Calculate the room index(RI) using the formula:
Length∗Breadth
Room index(RI) =
( Lenght +Breadth )∗Mounting Height
4. Base on this coefficient of utilization of the value can be obtained from the C.O.U table
for the selected luminaire. This value is generally 70% of the light colored, 50% for
average, 30% for dark walls and 50%, 30% and 10% for corresponding ceilings.
5. Select the light loss factor (LLF), Third factor was previously referred to as maintenance
factor (MF) generally accepted value is:
Area∗Illumination
No. of Luminaires =
CU ∗LLF∗LumenOutput of Luminaire
7. Arrange the luminaire symmetrically giving due consideration spacing criterion to
achieve uniformity of illumination
Room Area
Area per Luminaire (Fixture)=
No . of fixture
RECEIVING AREA
Area = 5 m*15 m = 75
Mounting Height = 2.5 m
5. Select the Light Loss Factor (LLF) : A/C rooms, Clean Rooms, etc. 0.8
75∗150
6. Number of luminaires: =17.36
0.6∗0.8∗2700
18 luminaires used.
75
7. Area per luminaire: =4.17 m2 /luminaire
18
8. Fixture Spacing: √ 4.17=2.04 m
5. Select the Light Loss Factor (LLF) : A/C rooms, Clean Rooms, etc. 0.8
31.25∗150
6. Number of luminaires: =2.71
0.8∗0.8∗2700
3 luminaires used.
31.25 2
7. Area per luminaire: =10.416 m /luminaire
3
8. Fixture Spacing: √ 10.416=3.227 m
HOSTEL HALLWAY
Area = 20.0 m*2.5 m = 50.0
Mounting Height = 3.0 m
5. Select the Light Loss Factor (LLF) : A/C rooms, Clean Rooms, etc. 0.8
50.0∗150
6. Number of luminaires: =4.3402
0.8∗0.8∗2700
5 luminaires used.
50.0
7. Area per luminaire: =10 m2 /luminaire
5
8. Fixture Spacing: √ 10=3.16 m
HOSTEL HALLWAY
Area = 10.75 m*5.0 m = 53.75
Mounting Height = 3.0 m
5. Select the Light Loss Factor (LLF) : A/C rooms, Clean Rooms, etc. 0.8
53.75∗150
6. Number of luminaires: =4.665
0.8∗0.8∗2700
5 luminaires used.
53.75 2
7. Area per luminaire: =10.75 m /luminaire
5
8. Fixture Spacing: √ 10.75=3.279 m